CONTRACTOR TO FIELD VERIFY EXISTING HVAC EQUIPMENT LOCATIONS AND PENETRATIONS AND TO COORDINATE WITH <br />DESIGN PROPOSED DUCTWORK LAYOUT. AS WELL AS THE REQUIRED MINIMUM 10 FEET SEPARATION BETWEEN FRESH <br />AIR INTAKE AND EXHAUST DEVICES, REQUIRED BY FBC MECHANICAL. <br />ALL EXHAUST, SUPPLY AND RETURN AIR DUCT SHALL BE INSULATED WITH MINIMUM R-6. PROVIDE INTERIOR LINING <br />FOR THE FIRST 15 FEET OF DUCTWORK FROM MECHANICAL EQUIPMENT. IF LINING R-VALUE DOES NOT COMPLY WITH <br />THE MINIMUM REQUIRED BY CODER-6), EXTERNAL INSULATION OF DUCTWORK SHALL BE ALSO INSTALLED. <br />6"0 WALL CAP. PROVIDE <br />WITH INSECT SCREEN AN <br />BACKDRAFT DAMPER. MOUNT <br />CAP AS HIGH AS POSSIBLE --\ <br />6" 0 WALL CAP. PROVIDE <br />WITH INSECT SCREEN AN <br />BACKDRAFT DAMPER. MOUNT <br />CAP AS HIGH AS POSSIBLE — <br />EXIST. RTU-11 ON ROOF <br />MODEL: THC072A, 6 TONS BY TRANE. <br />2400 CFM OF SUPPLY AIR. EXIST. SMOKE DUCT <br />DETECTOR. EXIST. O.A DAMPER IS CURRENTLY <br />ADJUSTED TO DELIVER 430 CFM OF FRESH AIR <br />REFRIGERANT LINES <br />UP TO LIEBERT <br />CONDENSING UNIT ON <br />THE ROOF ABOVE <br />1-1/2"0 CONDENSATE DRAIN LINE. <br />INSULATE WITH MIN. OF 3/4" PLENUM <br />RATED FLEXIBLE FOAM INSULATION. <br />SLOPE AT A MINIMUM RATE OF 1 /2" PER <br />LF. PIPE TO GO DOWN AFTER EXTERIOR <br />WALL PENETRATION. CONNECT TO <br />CONDENSATE DRYWELL. SEE DETAIL <br />1/4"0 CW HUMIDIFIER SUPPLY <br />LINE WITH BACKFLOW PREVENTOR <br />ASSEMBLY, TYPICAL OF WATTS 009QT. <br />SEE PLUMBING DRAWINGS FOR CONT.- <br />UST UP TO ROOF <br />VIDE WITH INSECT <br />,N BACKDRAFT <br />ROOF <br />5 TONS BY TRANE. <br />'LY AIR. EXIST. SMOKE DUCT <br />I.A DAMPER IS CURRENTLY <br />JER 430 CFM OF FRESH AIR. <br />Project <br />HUMANA- ZEPHYRHILLS, <br />FLORIDA - GUIDANCE <br />CENTER <br />7920 GALL BLVD. <br />ZEPHYRHILLS, FLORIDA 33541 <br />Prepared for <br />HUMANA INC. <br />Contract No: 12.01622.00 <br />HOK <br />One Tampa City Center, Suite 1800 <br />Tampa, FL 33602 USA <br />t +1 813 229 0300 f +1 813 223 7116 <br />FL Reg: AAC001139 <br />All reproduction & intellectual property rights reserved © 2012 <br />In Association with <br />SDM Consulting Engineers <br />MEP Engineer <br />135 Almeria Ave. <br />Coral Gables, FL 33134 <br />305.446.2788 <br />www.sdmcorp.com <br />Key Plan <br />3 <br />Professional Seals <br />ERNESTO ALOMA <br />P.E. 53823 <br />JOSE I. MARTINEZ <br />P. E. 53779 <br />No. <br />Issue Description <br />YYYY-MM-DD <br />01 <br />50% CONSTRUCTION DOCUMENTS <br />06.15.2012 <br />02 <br />BID SET <br />06.29.2012 <br />03 <br />ISSUE FOR PERMIT <br />07.27.2012 <br />No. <br />Revision Description <br />YYYY-MM-DD <br />1 <br />ADDENDUM 1 <br />2012-07-09 <br />2 <br />ADDENDUM 2 <br />2012-07-19 <br />Drawn by SDM Reviewed by SDM <br />Project No 12.01622.00 <br />Sheet Title: <br />FLOOR PLAN - LEVEL 1 <br />Original drawing is 36 x 24 Do not scale contents of this drawing <br />A M11 _ 41 n11 <br />Sheet Number <br />M201 <br />