7.2.1.6.2 ACCESS -CONTROLLED EGRESS DOOR ASSEMBLIES <br />WHERE PERMITTED IN CHAPTER 11 THROUGH 43, DOOR ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS <br />CONTROL SYSTEM, PROVIDED THAT ALL THE FOLLOWING CRITERIA ARE MET. <br />1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, ARRANGED TO DETECT AN OCCUPANT APPROACHING DOOR LEAVES THAT ARE ARRANGED TO UNLOCK IN THE DIRECTION OF AN <br />APPROACHING OCCUPANT OR LOSS OF POWER TOP THE SENSOR <br />2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS <br />3. DOOR LEAVES SHALL BE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE LOCATED 40 IN. TO 48 IN. ()1015 MM TO 1220 MM) VERTICALLY ABOVE THE <br />FLOOR WITHIN 60 IN. (1525 MM) OF THE SECURED DOOR OPENING <br />4. THE MANUAL RELEASE DEVICE SPECIFIED IN 7.2.1.6.2 (3) SHALL BE READILY ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS:PUSH TO EXIT. <br />5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS - AND THE <br />DOOR LEAVES SHALL REMAIN UNLOCKED FOR NOT LESS THAN 30 SECONDS. <br />6. ACTIVATION OF THE BUILDING FIRE -PROTECTIVE SIGNALING SYSTEM, OF PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THEY SHALL REMAIN <br />UNLOCKED UNTIL THE FIRE -PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY RESET. <br />7. THE ACTIVATION OF MANUAL FORE ALARM BOXES THAT ACTIVATE THE BUILDING FIRE -PROTECTIVE SIGNALING SYSTEM SPECIFIED IN 7.2.1.6.2 (6) SHALL NOT BE REQUIRED TO UNLOCK THE <br />DOOR LEAVES. <br />8. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THEY <br />SHALL REMAIN UNLOCKED UNTIL THE FORE -PROTECTIVE SYSTEM HAS BEEN MANUALLY RESET. <br />TRANSFORMER: 120 AC 60 Hz <br />120V AC,6OHz PRIMARY <br />24V AC, 60 Hz SECONDARY L120V AC GND <br />CLASS II, UL LISTED <br />48 V.A. (MIN.) rr� <br />24V AC <br />ELECTRONIC <br />SENSOR <br />BLACK <br />RED <br />WHITE COIL WIRE <br />!7'Tl <br />ELECTRONIC <br />SENSOR <br />BLACK <br />RED <br />WHITE COIL WIRE • <br />lTf7 <br />BOX <br />24V AC <br />COIL ON <br />FLUSHOMETER UNIT #1 <br />GROUND WIRE <br />ON NIPPLE <br />ASSEMBLY <br />24V AC <br />COIL ON <br />UNIT #2 <br />FLUSHOMEfER <br />THROUGH <br />GROUND WIRE <br />UNIT #3 <br />ON NIPPLE <br />ASSEMBLY <br />EL-150 <br />SENSOR <br />CONNECTION TO FIRE <br />ALARM FOR DOOR <br />RELEASE UNDER FIRE <br />ALARM CONDITIONS <br />—4 CONDUCTOR STRANDED UNSHIELDED #18 AWG WPW 244 <br />OR EQUAL, AND (1) BELDEN 9116 COAXIAL CABLE <br />3/4" CONDUIT TO EACH TERMINAL CONTROLLER. <br />REQUEST TO EXIT DEVICE WITH PIR DETECTOR AND WRAP <br />AROUND COVERAGE MTD ABOVE. <br />EMERGENCY MANUAL PUSHBUTTON <br />RELEASE ON THE INSIDE OF DOOR <br />AT 48"AFF (NOT MORE THAN 12" <br />DOOR JAM) <br />ELECTRIC DOOR STRIKE <br />F ELECTROMAGNETIC LOCK (1200 LEIS MIN) <br />�—MOUNTED ON TOP OF DOOR FRAME OPPOSITE <br />REX I HINGESIDE OF DOOR. TYPICAL <br />J :D]S--FLL] <br />TC I-- THESE DEVICES ARE TO BE PROVIDED <br />J PCR I IN EACH DOOR WITH CARD READER REQUIREMENTS. <br />J (SHOWN IN PLAN WITH A CR ON ENTRANCE DOOR) CR <br />I I REFER TO SHEET E201 FOR ALL LOCATIONS <br />L — — — — PROVIDED WITH CARD READERS <br />VENDOR IT ROOM PROXIMITY TYPE CARD -READING SENSOR <br />TERMINAL SHALL BE RECESSED MOUNTED IN <br />PROXIMITY CONTROLLER WALL AT 48" AFF. FIELD COORDINATE EXACT <br />CARD ACCESS CEILING MTD LOCATION (TYPICAL FOR ALL). <br />PANEL <br />LENEL OR PROVIDE ALL REQUIRED 120 VOLT EMERGENCY <br />EQUAL SUPPLIES AND TRANSFORMERS REQUIRED <br />AT EACH DOOR LOCATION. <br />#10 AWG COPPER <br />TO ELECTRICAL SYSTEM <br />GROUND, TYPICAL. <br />PROXIMITY CARD READER RISER DIAGRAM <br />NTS <br />7.2.1.6.2 ACCESS CONTROLLED EGRESS DOOR ASSEMBLIES <br />4"SQ. BOX DEVICE <br />COVER (PLASTER RING) <br />;" HIGH - APPLETON <br />ELECT #8470 OR EQUAL <br />FINISHED <br />(BY CONTRACTOR) <br />TI LE <br />VALL OPENING WALL <br />TABS OF YOKE <br />SENSOR TO <br />BE MOUNTED <br />ON TOP OF <br />FINISHED <br />PLASTER OR <br />TILE WALL <br />NOTE: <br />INSTALL PLASTER RING SO THAT SCREW HOLES <br />ARE ON THE LEFT AND RIGHT SIDE OF BOX. <br />(VIEW WITH COVER REMOVED) <br />EL-154 <br />SENSOR <br />� RANGE <br />ADJUSTMENTS <br />BLACK <br />RED kt WHITE <br />FINISHED <br />PLASTER <br />WALL <br />ELECTRONIC SENSOR VALVE WIRING DIAGRAM <br />NO SCALE <br />TELCOM NOTES: <br />• TELCOM CODES ARE IN THE NEC <br />(NATIONAL ELECTRICAL CODE), EIA/TIA <br />(ELECTRONICS INDUSTRIES <br />ALLIANCE/TELECOMMUNICATION INDUSTRY <br />ASSOCIATION) <br />• PROVIDE NEW IT ROOM WITH A 3/4" <br />PLYWOOD BACKBOARD WITH FIRE <br />RETARDANT PAINT. <br />• PROVIDE THE LATEST REQUIRED DATA AND <br />TELCOM WIRING FOR SERVICE FROM EACH <br />DATA LOCATION TO SERVER ROOM. <br />PROVIDE ALL REQUIRED CONNECTIONS FROM <br />SERVER ROOM TO EXISTING <br />COMMUNICATIONS SERVICE ENTRANCE <br />EQUIPMENT. <br />• HORIZONTAL WIRING IS THE RUN BETWEEN <br />JACK AND CLOSET. <br />• PROVIDE ALL REQUIRED APPURTENANCES, <br />REQUIRED FOR A FULLY FUNCTIONING <br />TELCOM/DATA SYSTEM INSIDE THESE NEW <br />OFFICES. <br />• RUN TELCOM LINES AWAY FROM EMI <br />(ELECTROMAGNETIC INTERFERENCE) e,g., <br />MOTORS AND TRANSFORMERS. EMI <br />SHIELD CAN BE USED TO PROTECT <br />TELCOM LINES. GROUNDING ALSO HELPS <br />PROTECT THE TELCOM LINES <br />• BACKBONE WIRING IS TO PROVIDE <br />INTERCONNECTION BETWEEN <br />TELECOMMUNICATIONS CLOSETS, <br />EQUIPMENT ROOM AND ENTRANCE <br />FACILITIES. <br />• EIA/TIA-568 5.2.1 THERE SHALL BE NO <br />MORE THAN TWO HIERARCHICAL LEVELS <br />OF CROSS -CONNECTS. ALL NEW JACKS <br />TO BE A MINIMUM OF CATEGORY 6a <br />(ANSI/TIA/EIA 568-B). <br />• CATEGORY 6a CABLING WILL BE <br />TERMINATED ON A SERVER RACK IN THE <br />IT ROOM <br />ALL NEW JACKS TO BE A MINIMUM OF <br />CATEGORY 6a (ANSI/TIA/EIA 568-8). <br />CATEGORY 6a CABLING WILL BE <br />TERMINATED BETWEEN A CATEGORY 6A <br />JACK LOCATED IN THE NEW SPACE AND <br />ON A RACK IN THE EXISTING IT ROOM. <br />3/4"C WITH CAT 6a <br />TO EXISTING IT <br />ROOM DATA SERVER <br />RACK IN ADJACENT <br />SPACE. <br />TYPICAL COMBO VOICE/DATA JACK <br />TELCOM RECEPTACLE <br />DATA TELCOM JACK <br />- A \ VVOICE JACK <br />B m`[ 2 GANG STEEL BACKBOX <br />1 GANG RING <br />TELECOM FACEPLATE <br />a <br />TYPICAL VOICE/DATA JACK <br />DENOTED BY THE SYMBOL <br />A TWO OR FOUR PORT <br />ANGLED FACEPLATE, <br />COLOR WHITE, CONNECT <br />CAT 6a <br />PROVIDE WITH TWO (2) <br />TIA CAT 6a JACKS UNLESS <br />OTHERWISE NOTED ON <br />PLANS (SHOWN WITH A <br />(4) ADJACENT TO JACK). <br />B LASER PRINTED LABEL <br />INDICATING OUTLET <br />IDENTIFIER. COORDINATE <br />WITH HUMANA IT DEPT. <br />FOR ADDITIONAL <br />INFORMATION. <br />FURNITURE FACEPLATE <br />INFORMATION <br />USE QUAD FACEPLATE AVAYA <br />M14CE-262 PART No. <br />108216128 <br />REFER TO IT AND VENDOR IT <br />ROOMS ENLARGED DETAILS ON <br />DATA <br />SHEET E401 FOR ADDITIONAL <br />EXISTING <br />SERVER <br />i <br />EQUIPMENT TO BE PROVIDED <br />TELEPHONE <br />RACK <br />BACKBOARDAND <br />(30A RECEIPT, DATA JACKS, <br />EQUIPMENTTO <br />ETC.) REMAIN 4 4 4 4 <br />REFER TO SHEET E201 FOR <br />QUANTITIES AND EXACT LOCATION OF <br />#6 TO BUILDING IT ROOM 109 I ALL DATA/TELEPHONE JACKS <br />ELEC GROUND. <br />CONTRACTOR MUST COORDINATE ALL DATA WORK <br />WITH HUMANA CAC IT DEPARTMENT FOR <br />ADDITIONAL REQUIREMENTS PRIOR TO ROUGH -IN. <br />TELEPHONE/DATA SYSTEMS RISER DIAGRAM <br />NTS <br />i <br />Project <br />HUMANA- ZEPHYRHILLS, <br />FLORIDA - GUIDANCE <br />CENTER <br />7920 GALL BLVD. <br />ZEPHYRHILLS, FLORIDA 33541 <br />Prepared for <br />HUMANA INC. <br />Contract No: 12.01622.00 <br />HOK <br />One Tampa City Center, Suite 1800 <br />Tampa, FL 33602 USA <br />t +1 813 229 0300 f +1 813 223 7116 <br />FL Reg: AAC001139 <br />All reproduction & intellectual property rights reserved © 2012 <br />In Association with <br />SDM Consulting Engineers <br />MEP Engineer <br />135 Almeria Ave. <br />Coral Gables, FL 33134 <br />305.446.2788 <br />www.sdmcorp.com <br />Key Plan <br />C' <br />Professional Seals <br />4"SQ x 2%" DEEP OUTLET GB GB GB D <br />BOX - APPLETON <br />ELECT #4SD1 OR EQUAL <br />(BY CONTRACTOR) <br />DC DC DC D C 63/4"C w <br />GC TO INSTALL TENANT PROVIDED PWB-100 SECURITY WIRING PER ` J� <br />PLASMA/FLAT PANEL DISPLAY WALL BOX AND TV SEE FLOOR PLANS FOR D SYSTEM , MANUFACTURER'S Ax <br />WALL MOUNT BRACKET AND BLOCKING AS DEVICE LOCATIONS KP CABINET RECOMMENDATIONS <br />REQUIRED. BOX TO RECEIVE DUPLEX OUTLET AND "LENEL" <br />PULLSTRINGS FOR ALL AUDIO/VISUAL CABLING (TYP KP OR ERNESTO ALOMA JOSE I. MARTINEZ <br />" . P.E. 53823 P.E. 53779 <br />AS SHOWN) PROVIDE 2 CONDUIT TO LOCATIONS KP EQUAL <br />INDICATED FOR A/V CABLING AS NEEDED. 10 AWG COPPER No. Issue Description ' YYYY-MM-DD <br />VENDOR IT 0 ELEC ROOM <br />ROOM GROUND 01 50% CONSTRUCTION DOCUMENTS 06.15.2012 <br />02 BID SET 06.29.2012 <br />SEE PLAN SEE PLAN <br />03 ISSUE FOR PERMIT 07.27.2012 <br />INTRUSION DETECTION SYSTEM RISER DIAGRAM <br />r-- ----� NTS <br />ALL SECURITY SERVICES SHALL .BE COORDINATED WITH <br />I F —I I HUMANA GLOBAL SECURITY <br />502-476-4444 <br />globalsecurity®humana.com <br />GC TO PROVIDE SOLID WOOD No. Revision Description YYYY-MM-DD <br />1 ADDENDUM 1 2012-07-09 <br />CENTERED ON SCREEN <br />FOR BLOCKING; REE2" CEILING - C-1 J ALL 2 ADDENDUM 2 2012-07-19 <br />N MOUNTED <br />TENANT PROVIDED WALL CAMERAS C-2 J CAMERAS <br />MOUNT AND TV (TYP AT ALL TO BE <br />LOCATIONS) FIXED <br />Ln in <br />I 3 4"C <br />3 4 C <br />WIRING PER WIRING PER <br />AV9 MANUFACTURER'S CCTV MANUFACTURER'S <br />RECOMMENDATIONS RACK RECOMMENDATIONS <br />19"X19" DVR <br />UPS <br />II Drawn by SDM Reviewed by SDM <br />ONE UPS PER MULTIPLEXER VENDOR IT #10 AWG COPPER <br />INSTALL DUPLEX OUTLET AND SINGLE GANG BOX TO ELEC SYSTEM Project No 12.01622.00 <br />FOR DATA CONNECTION. ALSO INSTALL SINGLE (16 CAMERAS PER ROOM GROUND <br />GANG WITH PULL STRING AND 2" CONDUIT TO TV MULTIPLEXER) SYSTEM TO BE Sheet Title: <br />LOCATION FOR A/V CABLING. SEE PLAN FOR CAMERAS TO BE "AXIS" COMPATIBLE WITH ACTUAL LOCATION. MODEL M3014, M7001 HUMANA CESS. SYSTEMS RISER <br />TYPICAL WALL MOUNT TV ELEVATION OR EQUAL. COORDINATE WITH DIAGRAMS AND <br />HUMANA GLOBAL <br />NTS CCTV SYSTEM RISER DIAGRAM SECURITY. DETAILS <br />NTS <br />ALL SECURITY SERVICES SHALL BE COORDINATED WITH Original drawing is 36 x 24 Do not scale contents of this drawing <br />HUMANA GLOBAL SECURITY <br />502-476-4444 Sheet Number <br />globalsecurity@humana.com E601 <br />