<br />MECHANICAL NOTES:
<br />I. CONTRACTOR TO VERIFY ALL CONDITIONS ON SITE PRIOR TO BIDDING
<br />AND BEGINNING WORK AND NOTIFY OF ANY DISCREPANCIES.
<br />2. CONTRACTOR SHALL COMPLY WITH 2O04 FLORIDA BUILDING CODE.
<br />3. CONTRACTOR TO OBTAIN AND PAY FOR ALL PERMITS, FEES,
<br />LICENSES AND INSPECTIONS.
<br />4. CONTRACTOR SHALL OBSERVE OSHA SAFETY STANDARDS AND
<br />MAINTAIN AREA CLEAN DAILY.
<br />S. ALL FINAL CONNECTIONS BY THIS CONTRACTOR TO ALL EQUIPMENT.
<br />6. ALL INTERIOR RECTANGULAR DUCTWORK TO BE GALVANIZED
<br />SHEET METAL IN ACCORD. WITH SMACNA DUCT CONSTRUCTION
<br />STANDARDS, 1/2" W.G.. DISHWASHER EXH. DUCT TO BE ST.STL.
<br />7. DUCTWORK SHALL BE FABRICATED AND BRACED IN
<br />ACCORDANCE WITH ASHRAE AND SMACNA STANDARDS.
<br />8. ALL DUCTWORK SHALL COMPLY WITH NFPA 90A.
<br />9. ALL KITCHEN HOOD DUCTWORK SHALL COMPLY WITH NFPA 96, BLACK STEEL.
<br />10. FLEXIBLE DUCTWORK SHALL BE INSULATED WITH 1" THICK
<br />VAPOR BARRIER, FLEXMASTER TYPE 3 OR EQUAL. NO FLEXIBLE
<br />DUCTWORK SHALL BE INSTALLED ABOVE INACCESSIBLE
<br />CEILINGS.
<br />11. SUPPLY DUCTWORK SHALL BE INSULATED 1" THICK FIBERGLASS
<br />WITH VAPOR BARRIER, 25/50 FIRE HAZARD RATING, SEALED SEAMS.
<br />12. FURNISH AND INSTALL ALL CONTROL WIRING FOR OPERATION
<br />OF EQUIPMENT.
<br />13. PROVIDE FOR FLEXIBLE CONNECTIONS AT EQUIPMENT.
<br />14. INSTALL ALL DUCTWORK AS HIGH AS POSSIBLE.
<br />15. PROVIDE SHOP DRAWINGS OF ALL EQUIPMENT FOR REVIEW
<br />PRIOR TO ORDERING.
<br />16. DUCTWORK SHOP DRAWINGS TO BE SUBMITTED FOR REVIEW PRIOR
<br />TO FABRICATION, THE CONTRACTOR SHALL PREPARE DETAILED
<br />CONSTRUCTION SHOP DRAWINGS OF THE ENTIRE EXTENT OF
<br />THE SHEET METAL DUCT INSTALLATION. LOCATIONS OF ALL
<br />DUCTS TO BE FIELD VERIFIED TO ELIMINATE INTERFERENCE
<br />WITH BUILDING CONSTRUCTION AND WORK OF OTHER TRADES.
<br />17. PROPER FIRE PROTECTION MEASURES SHALL BE ENFORCED
<br />AT ALL TIMES.
<br />18. CONTRACTOR TO COORDINATE DUCTWORK WITH CEILING HEIGHT
<br />AND EXISTING STRUCTURAL STEEL.
<br />19. ALL WALL AND ROOF PENETRATIONS BY THIS CONTRACTOR.
<br />OPENINGS SHALL BE FLASHED, COUNTERFLASHED AND SEALED
<br />WEATHERTIGHT AND WATERPROOF.
<br />20. CONTRACTOR SHALL PROVIDE, IN WRITING, A ONE (1) YEAR
<br />GUARANTEE AND WARRANTY ON ALL MATERIAL, EQUIPMENT
<br />AND WORKMANSHIP. ANY DEFECTS WILL BE REPAIRED OR
<br />REPLACED AT NO COST TO THE OWNER.
<br />21. ALL MECHANICAL EQUIPMENT AND APPLIANCES SHALL BEAR THE
<br />LABEL OF AN APPROVED TESTING AGENCY. ALL EQUIPMENT SHALL
<br />BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.
<br />22. ALL EQUIPMENT SHALL BE IN STRICT ACCORDANCE WITH ASHRAE
<br />STANDARD 62.1.2004 AS PER INDOOR AIR QUALITY CONSTRUCTION OF
<br />EQUIPMENT STANDARDS.
<br />23. ALL LOCAL AND EXHAUST FANS MUST BE A MINIMUM OF 10'-O" AWAY
<br />FROM OUT DOOR AIR INTAKES PER FLORIDA 2004 BUILDING CODE.
<br />24. EQUIPMENT MANUFACTURES NAMES & MODEL NUMBERS ARE SHOWN
<br />FOR BASIS OF DESIGN.
<br />25. DUCT MOUNTED SMOKE DETECTORS, PROVIDED BY THE ELECTRICAL
<br />CONTRACTOR, SHALL BE MOUNTED BY THIS CONTRACTOR.
<br />26. PROVIDE RETURN AIR DUCT WITH 1/2" ACOUSTICAL LINING.
<br />27. HOOD EXHAUST DUCTWORK TO HAVE 2 HOUR FIREPROOF INSULATION.
<br />28. PROVIDE DUCT SMOKE DETECTORS FOR ALL AC EQUIPMENT
<br />2000 CFM OR GREATER.
<br />29. PROVIDE FIRE STOPPING AT ALL FIRE WALL PENETRATIONS.
<br />SEE ARCHITECTURAL DRAWINGS FOR FIRE WALL LOCATIONS.
<br />30. PROVIDE FIRE DAMPERS AT ALL FIRE WALL. SEE ARCHITECTURAL
<br />DRAWINGS FOR LOCATIONS.
<br />31. CONTRACTOR SHALL BALANCE ALL AIR SYSTEMS PER NEBB.
<br />32. ALL DUCTWORK ASSOCIATED WITH POOL AREA TO BE ALUMINUM WITH
<br />WATERTIGHT JOINTS AND SEAMS.
<br />33. ALL APPURTENANCES REQUIRED FOR A COMPLETE AND OPERATING
<br />SYSTEM ARE NOT SHOWN. CONTRACTOR TO PROVIDE ALL APPURTENANCES
<br />NECESSARY FOR A COMPLETE OPERATING SYSTEM. CONTRACTOR TO
<br />CONTACT ARCHITECT/ENGINEER IN WRITING, PRIOR TO BIDDING FOR
<br />CLARIFICATION OF DISCREPANCIES OR OMISSIONS IN DESIGN
<br />DOCUMENTS.
<br />HVAC ABBREVIATIONS:
<br />AFF ABOVE FINISHED FLOOR
<br />AHU AIR HANDLING UNIT
<br />AP ACCESS PANEL
<br />ATC AUTOMATIC TEMPERATURE CONTROL
<br />BDD BACKDRAFT DAMPER
<br />BHP BRAKE HORSEPOWER
<br />BTU BRITISH THERMAL UNIT
<br />CD CEILING DIFFUSER
<br />CFM CUBIC FEET PER MINUTE
<br />DB DRY BULB
<br />DEG DEGREES (FAHRENHEIT)
<br />DIA/0 DIAMETER
<br />DN DOWN
<br />DX DIRECT EXPANSION
<br />EA EXHAUST AIR
<br />EF EXHAUSTFAN
<br />EG EXHAUST GRILLE
<br />ER EXHAUST REGISTER
<br />ESP EXTERNAL STATIC PRESSURE
<br />EXH EXHAUST
<br />OF DEGREE(S) FAHRENHEIT
<br />FD FIRE DAMPER
<br />FLA FULL LOAD AMPS
<br />HOA HAND-OFF AUTOMATIC SELECTOR SWITCH
<br />HP HORSEPOWER
<br />HVAC HEATING, VENTILATING, AIR CONDITIONING
<br />HAV HEATING & VENTILATING
<br />IN/WG INCHES WATER GAUGE
<br />KW KILOWATT
<br />LAT LEAVING AIR TEMPERATURE
<br />LD LINEAR DIFFUSER
<br />LVR LOUVER
<br />MBH
<br />1000 BTU PER HOUR
<br />NTS
<br />NOT TO SCALE
<br />OA
<br />OUTSIDE AIR
<br />OAD
<br />OUTSIDE AIR DAMPER
<br />OAI
<br />OUTSIDE AIR INTAKE
<br />RG
<br />RETURN AIR GRILLE
<br />RH
<br />RELATIVE HUMIDITY
<br />RHC
<br />REHEAT COIL
<br />RPM
<br />REVOLUTIONS PER MINUTE
<br />RR
<br />RETURN AIR REGISTER
<br />RS
<br />REFRIGERANT SUCTION
<br />SEF
<br />SMOKE EXHAUST FAN
<br />SF
<br />SUPPLY AIR FAN
<br />SH
<br />SENSIBLE HEAT
<br />SP
<br />STATIC PRESSURE
<br />T
<br />THERMOSTAT
<br />DUCT SYMBOLS:
<br />VOLUME
<br />DAMPER
<br />10" 18"
<br />VOLUME
<br />DAMPERS
<br />VOLUME
<br />DAMPER
<br />TURNING VANES
<br />EXHAUST FAN SCHEDULE
<br />STATIC
<br />UNIT NO.
<br />AREA SERVED
<br />DUTY
<br />CFM
<br />RE
<br />PN
<br />HP
<br />RPM
<br />TIP
<br />REMARKS*
<br />DRIVE
<br />BASIS OF DESIGN
<br />ELEC.
<br />H2�
<br />SPEED
<br />77
<br />eE
<br />LIVING UNITS
<br />EXH
<br />93
<br />.25"
<br />WATTS
<br />640
<br />1
<br />DIRECT
<br />CARNES VCDD010C
<br />120/1/60
<br />e102
<br />ELEV. RM C125
<br />EXH
<br />141
<br />.125"
<br />WATTS
<br />710
<br />1
<br />DIRECT
<br />CARNES VCDD015C
<br />120/1/60
<br />eJAN.C12013102
<br />EXH
<br />141
<br />.125"
<br />WATTS
<br />710
<br />1
<br />DIRECT
<br />CARNES VCDD015C
<br />120/1/60
<br />77
<br />eTOILET
<br />C120A
<br />EXH
<br />93
<br />.25"
<br />WATTS
<br />640
<br />1
<br />DIRECT
<br />CARNES VCDDOIOC
<br />120/1/60
<br />eDISHWASHER300
<br />EXH
<br />500
<br />.5"
<br />WATTS
<br />960
<br />DIRECT
<br />CARNES VCDD070C
<br />120/1/60
<br />120
<br />GREENHECK
<br />e/EF\
<br />ELEC. RM
<br />EXH
<br />240
<br />.25"
<br />WATTS
<br />2600
<br />2,5
<br />DIRECT
<br />CBF-205-QD
<br />120/1/60
<br />300
<br />eBEAUTY
<br />C113
<br />EXH
<br />534
<br />.75��WATTS
<br />980
<br />1
<br />DIRECT
<br />CARNES VCDD070C
<br />120/1/60
<br />EF
<br />131
<br />8
<br />TOILET C106
<br />EXH
<br />196
<br />.25"
<br />WATTS
<br />740
<br />1
<br />DIRECT
<br />CARNES VCDD020C
<br />120/1/60
<br />77
<br />eTOILET
<br />C107
<br />EXH
<br />93
<br />.25"
<br />WATTS
<br />640
<br />1
<br />DIRECT
<br />CARNES VCDD010C
<br />120/1/60
<br />EF
<br />102
<br />10
<br />ELEV. RM C132
<br />EXH
<br />141
<br />.125"
<br />WATTS
<br />710
<br />1
<br />DIRECT
<br />CARNES VCDD015C
<br />120/1/60
<br />EF
<br />77
<br />11
<br />TOILET C135A
<br />EXH
<br />93
<br />.25"
<br />WATTS
<br />640
<br />1
<br />DIRECT
<br />CARNES VCDD010C
<br />120/1/60
<br />EF
<br />77
<br />12
<br />TOILET C204
<br />EXH
<br />93
<br />.25"
<br />WATTS
<br />640
<br />1
<br />DIRECT
<br />CARNES VCDD010C
<br />120/1/60
<br />EF
<br />77
<br />13
<br />TOILET C304
<br />EXH
<br />93
<br />.25"
<br />WATTS
<br />640
<br />1
<br />DIRECT
<br />CARNES VCDD010C
<br />120/1/60
<br />EF
<br />77
<br />14
<br />JANITOR C133
<br />EXH
<br />93
<br />.25"
<br />WATTS
<br />640
<br />1
<br />DIRECT
<br />CARNES VCDD010C
<br />120/1/60
<br />EF
<br />77
<br />15
<br />JANITOR C233
<br />EXH
<br />93
<br />.25"
<br />WATTS
<br />640
<br />i
<br />DIRECT
<br />CARNES VCDD010C
<br />120/1/60
<br />EF
<br />77
<br />16
<br />JANITOR C333
<br />EXH
<br />93
<br />.25"
<br />WATTS
<br />640
<br />1
<br />DIRECT
<br />CARNES VCDD010C
<br />120/1/60
<br />EF
<br />RESIDENTIAL
<br />DRYER
<br />EXH
<br />120
<br />2.00"
<br />83
<br />WATTS
<br />800
<br />7,8
<br />DIRECT
<br />FANTECH DBF4XLT
<br />120/1/60
<br />17
<br />BOOSTER
<br />REMARKS:
<br />1. RADIATION DAMPER 3. SHUTTER DAMPER 5. FAN THERMOSTAT 7. FURNISH WITH PRESSURE SWITCH
<br />2. WALL SLEEVE 4. MOTOR GUARD 6. EQUAL PRODUCTS BY GREENHECK ARE APPROVED 8. FURNISH WITH DBLT4 LINT TRAP
<br />TURNING VANES
<br />RETURN OR
<br />EXHAUST
<br />SUPPLY
<br />TURNING
<br />VANES
<br />45° EL.
<br />90° EL:'-W
<br />WIDTH "W" = INS. RADIUS
<br />TURNING
<br />VANES
<br />�x
<br />RETURN OR
<br />EXHAUST
<br />kLNJ I;i
<br />SUPPLY
<br />TURNING
<br />VANES
<br />AIR DISTRIBUTION, GENERAL SYMBOLS &
<br />NOMENCLATURE:
<br />NOTE:
<br />VOLUME DAMPER 1. FOR EQUIPMENT SCHEDULES FOR CONDENSING UNITS (CU),
<br />UNIT AIR HANDLING UNITS (FSO) AND CEILING CASSETTE
<br />UNITS (FXF), SEE MECHANICAL SPECIFICATIONS.
<br />DAMPER
<br />(type as indicated; BBD,
<br />�- MOD, FD, SD/FD, VD, etc.)
<br />- DAMPER
<br />ODUCT MOUNTED SMOKE DETECTOR
<br />D
<br />c FLEXIBLE CONNECTION
<br />FLEXIBLE DUCTWORK
<br />FLEXIBLE DUCTWORK
<br />TO THERMOSTAT
<br />TURNING VANES
<br />��- FULLY LOUVERED DOOR (LIVING UNITS)
<br />DIFFUSER, REGISTER & GRILLE SCHEDULE
<br />DUTY
<br />SYMBOL
<br />AREA SERVED
<br />MODEL
<br />FINISH
<br />REMARKS
<br />BAKED WHITE
<br />SUPPLY
<br />CD
<br />AS NOTED
<br />CARNES SETS
<br />ENAMEL
<br />W/ OPPOSED BLADE DAMPER
<br />BAKED WHITE
<br />SUPPLY
<br />SR
<br />AS NOTED
<br />CARNES RTDB
<br />ENAMEL
<br />W/ OPPOSED BLADE DAMPER
<br />BAKED WHITE
<br />RETURN
<br />RR
<br />AS NOTED
<br />CARNES RSAB
<br />ENAMEL
<br />BAKED WHITE
<br />EXHAUST
<br />ER
<br />AS NOTED
<br />CARNES RSAB
<br />ENAMEL
<br />BAKED WHITE
<br />TRANSFER
<br />GR
<br />AS NOTED
<br />CARNES RSAB
<br />ENAMEL
<br />WITH FIRE DAMPER
<br />BAKED WHITE
<br />SUPPLY
<br />SG
<br />AS NOTED
<br />CARNES RSAB
<br />ENAMEL
<br />BAKED WHITE
<br />SUPPLY
<br />FRD
<br />AS NOTED
<br />TITUS TMSA-FR
<br />ENAMEL
<br />BAKED WHITE
<br />RETURN
<br />FRG
<br />AS NOTED
<br />TITUS PAS-FR
<br />ENAMEL
<br />FAN SCHEDULE
<br />STATIC
<br />UNIT NO.
<br />AREA SERVED
<br />CFM
<br />PRESSURE
<br />HP
<br />RPM
<br />TIP
<br />REMARKS*
<br />DRIVE
<br />BASIS OF DESIGN
<br />ELEC
<br />IN. H2O
<br />SPEED
<br />eATRIUM
<br />1
<br />14,000
<br />0.5"
<br />5
<br />884
<br />5,909
<br />1, 2, 3, 4, 5
<br />BELT
<br />COOK 330CPS
<br />208/3/60
<br />eAE
<br />ATRIUM
<br />14,000
<br />0.5"
<br />5
<br />884
<br />5,909
<br />1,2,3,4,5
<br />BELT
<br />COOK 330CPS
<br />208/3/60
<br />REMARKS:
<br />1. EXPDXY COATING 4. BIRSCREEN
<br />2. WEATHER OVER 5. UL LISTED FOR SMOKE CONTROL
<br />3. RAIN HOOD
<br />KITCHEN MAKE-UP / EXHAUST UNIT
<br />UNIT No.
<br />CFM
<br />SUPPLY
<br />CFM
<br />EXHAUST
<br />SUPPLY
<br />ESP
<br />SUPPLY
<br />HP
<br />EXHAUST
<br />ESP
<br />SUPPLY
<br />HP
<br />MBH HEATING
<br />MOH
<br />GAS
<br />CF/H
<br />ELECTRIC
<br />FUSING
<br />REMARKS
<br />BASIS OF DESIGN
<br />MUA
<br />1,958
<br />3,375
<br />1"
<br />1.1/2
<br />2"
<br />3
<br />NONE
<br />NONE
<br />208/3/60
<br />30 HACR
<br />12" HIGH GALV. PREFAB ROOF CURB,
<br />SUPPLY EXTENSION
<br />GREENHECK KSF
<br />1
<br />VENT SCHEDULE
<br />UNIT NO.
<br />CFM
<br />SQ. FT.
<br />REMARKS
<br />BASIS OF DESIGN
<br />RV
<br />1
<br />534
<br />.96
<br />PREFAB CURB, BIRDSCREEN
<br />CARNES GSAA12
<br />LOUVER SCHEDULE
<br />UNIT NO. WIDTH HEIGHT FREE AREA (SQFT) BASIS OF DESIGN REMARKS
<br />FURNISH WITH ES-30 (45x8) BACKDRAFT DAMPER
<br />L 45 IN. 8 IN. 0.55 GREENHECK EHH-501X FURNISH WITH TITUS 23RL RETURN GRILLE (45x8 FACE W/ WHITE BORDER)
<br />1 FURNISH LOUVER WIT BAKED ENAMEL FINISH. COLOR TO BE CHOSEN BY OWNER.
<br />ROOFTOP AIR CONDITIONING UNIT SCHEDULE
<br />UNIT
<br />NO.
<br />SUPPLY
<br />AIR
<br />CFM
<br />OUTSIDE
<br />AIR
<br />CFM
<br />COOLING
<br />ELECTRIC HEATING
<br />RE -HEAT
<br />ELECTRICAL
<br />REMARKS
<br />BASIS OF DESIGN
<br />EXT
<br />S.P.
<br />EAT
<br />SENS
<br />BTU/HR
<br />TOTAL
<br />BTU/HR
<br />COIL LAT
<br />BTU/HR
<br />OUTPUT
<br />BTU/HR
<br />INPUT
<br />ELECTRIC
<br />FLA
<br />EAT
<br />LAT
<br />BTU/HR
<br />OUTPUT
<br />LAT
<br />LAT
<br />VOLTAGE
<br />MCA
<br />MOCP
<br />SA FAN
<br />HP
<br />CU FAN
<br />HP
<br />DB
<br />WB
<br />DB
<br />WB
<br />OAU
<br />4550
<br />4550
<br />2"
<br />94
<br />79
<br />188,500
<br />377,510
<br />56
<br />55
<br />205,100
<br />4x15KW
<br />166.8
<br />37
<br />79
<br />104,000
<br />75 i 61.7
<br />75161.7
<br />230/3/60
<br />188
<br />225
<br />5.0
<br />0.75
<br />1 2 3 4 5 6 7 8 9
<br />AAON RM-025.8-0-BB02.344
<br />Nam
<br />be advised thisA
<br />of .
<br />hractor in � .
<br />review is not intemw
<br />bmitted n1ans it it. -
<br />40ta
<br />to be 2
<br />u* safety codes.
<br />� val of the
<br />REMARKS:
<br />1. 2" PLEATED FILTER
<br />2. THROUGH BASE ELECTRICAL & GAS
<br />3. UNIT MOUNTED DISCONNECT
<br />4. POWERED CONVENIENCE OUTLET
<br />S. SMOKE DETECTOR
<br />6. PROVIDE WITH 12" TALL GALVANIZED ROOF CURB
<br />7. PROVIDE WITH 2-POSITION MOTORIZED OUTSIDE AIR DAMPER
<br />8. FACTORY HINGED PANELS
<br />9. DUAL SETPOINT AUTOCHANGEOVER SENSOR WITHOUT STATUS INDICATOR LIGHTS
<br />DAIKEN SYSTEM COORDINATION
<br />GENERAL CONTRACTOR SHALL REFER TO MECHANICAL
<br />SPECIFICATIONS FOR DAIKEN SYSTEM AIR HANDLING
<br />UNIT CAPACITIES, CONDENSING UNIT CAPACITIES,
<br />REFRIGERANT PIPE SIZES, AND ASSOCIATED
<br />ACCESORIES. CONTACT ROB TEETSEL AT PRO -TECH AIR
<br />CONDITIONING AND HEATING, INC. 407.291.1642
<br />ALL FORK SHALL COMPLY WITHALL
<br />PREVAILING CODES,
<br />CITY FLORIDABUILDRIG
<br />CODE, NATIONAL ELECTRIC CODE ANIi
<br />OF ZEPHYRHILLS ORDINANCES
<br />llWDA-r
<br />PLANS EXANNER
<br />,"u"lry to ensure that the plans are .
<br />+ance *rich all applicable NFPA codes ano
<br />e In a event that further examination or
<br />h ®n reveals areas of no'
<br />�e ttr 's n-c°mP►iar,Ce, it shall be
<br />bft responsibility, at their sere expense to
<br />those areas in compliance. The City assumes no
<br />bitity for the contractors failure to be in compli
<br />anM
<br />"ka* NFPA Codes and local ordin
<br />.
<br />FREDERICK MUSCATELLO, PE
<br />FL. PE # 62451
<br />PO Box 941168
<br />MAITLAND, FL 32794-1168
<br />EMAIL: fredOfcmengineering.com
<br />v
<br />t
<br />U
<br />z
<br />O
<br />U
<br />�
<br />O
<br />w
<br />p�
<br />U
<br />0
<br />o
<br />O
<br />O
<br />w
<br />600
<br />aD
<br />_0
<br />N
<br />r
<br />0
<br />0
<br />w
<br />U
<br />.. N
<br />M
<br />m
<br />]C
<br />W
<br />o
<br />UJ
<br />(n
<br />project no.
<br />drawn by:
<br />2006-068.00
<br />date:
<br />checked by:
<br />NOV , 2006
<br />scale:
<br />approved by:
<br />sheet no.
<br />ml A 00
<br />a
<br />L
<br />c
<br />ca @
<br />0L
<br />C N
<br />0)_C
<br />N
<br />m o
<br />N 3
<br />0 0r
<br />>'N
<br />t c
<br />+1 0
<br />� C
<br />0 0
<br />C
<br />�+ C
<br />0 N
<br />30
<br />
|