<br />Classified by
<br />underwriters Laboratories, Inc.
<br />to UL 1479 and CAN/ULCS115
<br />System No. C-AJ-1184
<br />ANSI/UL1479 (ASTM E814)
<br />CAN/ULC S115
<br />F Rating — 3 Hr
<br />F Rating — 3 Hr
<br />T Rating — 0 Hr
<br />FT Rating — 0 Hr
<br />FH Rating — 3 Hr
<br />FTH Rating — 0 Hr
<br />1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m') concrete. Wall
<br />may also be constructed of any UL Classified Concrete Blocks*. Floor may also be constructed of any min 7-1/2 in. (190 mm) thick UL Classified
<br />hollow core Precast Concrete Units*. Max diam of opening is 14 in. (356 mm) when concrete floor or wall is used and max 7 in. (178 mm) when
<br />precast concrete units are used.
<br />See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers.
<br />2. Through -Penetrants — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The
<br />annular space between pipe, conduit or tubing and periphery of opening shall be min 0 in. (point contact) to max 3-1/4 in. (83 mm). Pipe, conduit
<br />or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may
<br />be used:
<br />A. Steel Pipe — Nom 10 in. (254 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
<br />B. Iron Pipe — Nom 10 in. (254 mm) diam (or smaller) cast or ductile iron pipe.
<br />C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or steel conduit.
<br />D. Copper Tubing — Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tubing.
<br />E. Copper Pipe — Nom 4 in. (102 mm) diam (or smaller) regular (or heavier) copper pipe.
<br />3. Forms — (Not Shown, Optional) — Used as a form to prevent leakage of fill material during installation. Forms to be rigid sheet material, cut to fit
<br />the contour of the penetrating item and positioned as required to accommodate the required thickness of fill material. Forms to be removed after
<br />fill material has cured. Additional forming material may be used concrete block wall is penetrated. A min 1/2 in. (13 mm) thickness of min 4 pcf
<br />(64 kg/m') mineral wool batt insulation is firmly packed into the annulus as a permanent form and recessed from both surfaces of the wall as
<br />required to accommodate the required thickness of fill material.
<br />4. Fill, Void or Cavity Material* — Sealant — Min 1 in. (25 mm) thickness of fill material applied within the annulus. At the point contact location
<br />between through penetrant and concrete, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the concrete through penetrant
<br />interface. When precast concrete units are used, the fill material shall be installed within annular space, flush with lower surface of floor. When
<br />concrete block wall is penetrated, a min 1 in. (25 mm) thickness of fill material shall be applied within the annulus flush with both surfaces of wall.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS605, FS-ONE Sealant or FS-ONE MAX Intumescent Sealant
<br />* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
<br />respectively.
<br />Reproduced by HILTI, Inc. Courtesy of
<br />Underwriters Laboratories, Inc.
<br />Hilti Firestop Systems January07,2015
<br />FLOOR OR WALL PENETRATIONS
<br />IFj
<br />c V� us
<br />Classified by
<br />Underwriters Laboratories, Inc.
<br />to UL 1479 and CAN/ULC-S115
<br />System No. W-L-1054
<br />ANSI/UL1479 (ASTM E814)
<br />CAN/ULC S115
<br />F Ratings —1 and 2 Hr (See Items 1 and
<br />F Ratings —1 and 2 Hr (See Items 1 and
<br />3)
<br />3)
<br />T Rating — 0 Hr
<br />FT Rating — 0 Hr
<br />L Rating at Ambient — Less Than 1
<br />FH Ratings —1 and 2 Hr (See Items 1
<br />CFM/sq ft
<br />and 3)
<br />L Rating at 400 F — Less Than 1 CFM/sq
<br />FTH Rating — 0 Hr
<br />ft
<br />FTH Rating — 0 Hr
<br />L Rating at Ambient — Less Than 1
<br />CFM/sq ft L Rating at 400 F — Less Than
<br />1 CFM/sq ft
<br />1. Wall Assembly — The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified
<br />in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction
<br />features:
<br />A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm)
<br />lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. When steel studs are
<br />used and the diam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed
<br />between the vertical studs and screw -attached to the steel studs at each end. The framed opening in the wall shall be 4 to 6 in. (102 to 152
<br />mm) wider and 4 to 6 in. (102 to 152 mm) higher than the diam of the penetrating item such that, when the penetrating item is installed in the
<br />opening, a 2 to 3 in. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides.
<br />B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 It (122 cm) wide with square or tapered edges. The gypsum board type, thickness, number of
<br />layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance
<br />Directory. Max diam of opening is 32-1/4 in. (819 mm) for steel stud walls. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls.
<br />The F and FH Ratings of the firestop system are equal to the fire rating of the wall assembly.
<br />2. Through -Penetrants — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The
<br />annular space shall be min 0 in. to max 2-1/4 in. (57 mm). Pipe may be installed with continuous point contact. Pipe, conduit or tubing may be
<br />installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides of wall
<br />assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
<br />A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
<br />B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.
<br />C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or 6 in. (152 mm) . diam steel conduit.
<br />D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
<br />E. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) regular (or heavier) copper pipe.
<br />3. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of
<br />wall. At the point or continuous contact locations between pipe and wall, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the
<br />pipe wall interface on both surfaces of wall.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant
<br />* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
<br />respectively.
<br />Reproduced by HILTI, Inc. Courtesy of
<br />Underwriters Laboratories, Inc.
<br />Hifd Firestop Systierins
<br />January 23, 2015
<br />WALL PENETRATIONS
<br />CV
<br />c V� us
<br />Classified by
<br />Underwriters Laboratories, Inc.
<br />to UL 1479 and CAN/ULC•S115
<br />System No. C-AJ-1421
<br />ANSI/UL1479 (ASTM E814)
<br />CAN/ULC S115
<br />F Ratings — 2 or 3 Hr
<br />F Ratings — 2 or 3 Hr
<br />T Rating — 0 Hr
<br />FT Rating — 0 Hr
<br />L Rating at Ambient — Less Than 1
<br />FH Ratings — 2 or 3 Hr
<br />CFM/sq ft
<br />L Rating at 400 F — Less Than 1
<br />FTH Rating — 0 Hr
<br />CFM/sq ft
<br />L Rating at Ambient — Less Than 1
<br />CFM/sq ft
<br />L Rating at 400 F — Less Than 1
<br />CFM/sq ft
<br />SECTION A -A
<br />1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m') concrete. Wall
<br />may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 6 in. (152 mm).
<br />See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
<br />2. Metallic Sleeve — (Optional) Nom 6 in. (152 mm) diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted into floor or wall assembly,
<br />flush with floor or wall surfaces.
<br />3. Through -Penetrant — One metallic pipe or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space
<br />between pipe, tube or conduit and periphery of opening shall be min 0 in. (pant contact) to max 5-318 in. (137 mm). Pipe or conduit to be rigidly
<br />supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes or conduits may be used:
<br />A. Steel Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
<br />B. Iron Pipe — Nom 4 in. (102 mm) diam (or smaller) cast or ductile iron pipe.
<br />C. Copper Pipe — Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.
<br />D. Copper Tubing — Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tubing.
<br />E. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel conduit.
<br />F. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT).
<br />4. Firestop System — The firestop system shall consist of the following:
<br />A. Packing Material — Min 4 in. (102 mm) thickness of min 4 pcf (64 kg/m') mineral wool batt insulation firmly packed into opening as a permanent
<br />form. Packing material to be recessed from top surface of floor or from both surfaces of wall to accommodate the required thickness of fill
<br />material.
<br />B. Fill, Void or Cavity Material* - Sealant — Min 1/4 in. (6 mm) thickness of fill material applied within the annulus, flush with top surface of floor or
<br />with both surfaces of wall. For 3 Hr rated assemblies, a min 1/4 in. (6 mm) diam bead of fill material shall be applied at the concrete/pipe
<br />interface at the point contact location on the top surface of floor and on both surfaces of wall.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-S SIL GG, CFS-S SIL SL, FS-ONE Sealant, FS-ONE MAX Intumescent
<br />Sealant or CP604 Self -Leveling Firestop Sealant. CP604 and CFS-S SIL SL shall be used in floor applications only.
<br />When CP604, CFS-S SIL GG or CFS-S SIL SL (floors only) is used, F Rating is 2 Hr.
<br />* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
<br />respectively.
<br />Reproduced by HILTI, Inc. Courtesy of
<br />Underwriters Laboratories, Inc.
<br />Hilti Firestop Systems January 28, 2015
<br />FLOOR OR WALL PENETRATIONS
<br />NOT TO SCALE I NOT TO SCALE I �`�� NOT TO SCALE
<br />(A
<br />tki
<br />r-
<br />Lr)
<br />r-
<br />0
<br />Z
<br />C
<br />0
<br />0)
<br />•4)
<br />0
<br />5
<br />5
<br />Ln
<br />ZU
<br />E-MM(>
<br />_
<br />Z
<br />Ln
<br />Ln
<br />N
<br />N
<br />�ti
<br />n
<br />n
<br />LU`°
<br />W
<br />C
<br />U_
<br />W�
<br />~
<br />3
<br />�
<br />Z
<br />Z
<br />O
<br />(5
<br />b
<br />O
<br />Z
<br />IL
<br />IL
<br />WUJI
<br />IX
<br />LL
<br />l7
<br />Z
<br />m
<br />N
<br />J
<br />a
<br />N
<br />00
<br />—
<br />m
<br />t
<br />a
<br />on
<br />W
<br />Z
<br />can
<br />M
<br />LUN
<br />W
<br />CCU
<br />—
<br />>
<br />_O
<br />J
<br />CU
<br />Q
<br />Ll
<br />u
<br />QU
<br />L
<br />L
<br />o
<br />q
<br />-J
<br />=
<br />3
<br />LU
<br />Ln
<br />U
<br />W
<br />a
<br />N
<br />cv
<br />(11
<br />Q
<br />dam'
<br />V
<br />a
<br />W
<br />IV
<br />W
<br />O
<br />O
<br />Q
<br />Iflc
<br />Z
<br />O
<br />LU
<br />Z
<br />-p
<br />Ln
<br />M
<br />M
<br />LU
<br />V
<br />C
<br />a
<br />'%
<br />o
<br />W
<br />>%�
<br />4 1
<br />�^
<br />LU
<br />L.
<br />a
<br />M
<br />L
<br />L
<br />.c
<br />z
<br />00
<br />M
<br />a
<br />N
<br />\\Xj%IIIIII////
<br />o�GIP-\-EWIS JOy�
<br />\\CENSF. SO
<br />* ,No 38680
<br />0 TATE OF
<br />George Johnson, P.E.
<br />PE38680
<br />ISSUE DATE: 10/19/2018
<br />PROJECT NUMBER: 2847
<br />REVISIONS:
<br />NO. DATE DESCRIPTION
<br />ELECTRICAL DETAILS
<br />TO THE BEST OF THE ENGINEERS KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE -SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTER 553.79 AND CHAPTER 633, FLORIDA STATUTES.
<br />0 2018 APG ENGINEERING
<br />E302
<br />
|