MOUNTNG FEMITS FOR ELECTRICAL DEVICES <br />DEVICE <br />MOUNTING HEIGHTS <br />LIGHT SWITCHES, WALL MOUNTED OCCUPANCY SENSORS <br />48" TO CENTERUNE OF BOX. <br />EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS <br />WHICH ARE 20"-25"D. <br />DISCONNECT SWITCHES, MOTOR STARTERS, MOTOR PUSH <br />60" TO CENTERLINE. <br />BUTTON STATIONS <br />WALL MOUNTED DOT SIGNS <br />90" TO CENTERLINE OF SIGN OR CENTERED IN WALL AREA <br />BETWEEN TOP OF DOOR AND CEIUNG. <br />CEUNG MOUNTED EXIT SIGNS <br />80' TO BOTTOM FD(TURE. <br />RECEPTACLES <br />16" TO BOTTOM OF BOX. <br />E)(CEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS <br />WHICH ARE 20'-25"D. <br />SPECIAL OUTLETS OR RECEPTACLES <br />16" TO BOTTOM OF BOX OR AS NOTED ON DRAWINGS. <br />EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS <br />WHICH ARE 20"-25'D. <br />DATA/COMMUNICATION OR TELEPHONE OUTLETS <br />16" TO BOTTOM OF BOX. <br />TELEPHONE OUTLETS - WALL TYPE <br />54" TO DIAL CENTER (NON -ACCESSIBLE). <br />48" TO HIGHEST OPERABLE PART (ACCESSIBLE). <br />FIRE ALARM MANUAL PULL STATIONS <br />48" TO CENTERUNE OF BOX - NOT MORE THAN <br />5'-0' FROM EXIT. <br />FIRE ALARM AUDIBLE ONLY DEVICE <br />NOT LESS THAN 90" TO TOP OR 6" BELOW CLUNG, <br />WHICH EVER IS HIGHER. <br />FIRE ALARM VISUAL ONLY DEVICE OR A COMBINATION <br />80" TO BOTTOM OF DEVICE OR NOT MORE THAN 96" <br />AUDIBLE AND VISUAL DEVICE <br />TO TOP. <br />WALL MOUNTED REMOTE INDICATOR UGHT <br />80" TO CENTERUNE OF DEVICE OR 6" BELOW COUNG, <br />WHICHEVER IS LOWER. <br />CARD READER <br />48" TO HIGHEST OPERABLE PART (SIDE OR FORWARD <br />ACCESS). <br />THERMOSTATS <br />54" TO HIGHEST OPERABLE PART (SIDE ACCESS). <br />48" HIGHEST OPERABLE PART (FORWARD ACCESS). <br />TEMPERATURE/HUMIDITY SENSORS <br />60" TO CENTER UNE OF BOX. <br />OTES: <br />1. ALL DIMENSIONS ARE CONSIDERED FROM FINISHED FLOOR AND, UNLESS NOTED OTHERWISE, SHALL NOT <br />VARY. RAISED FLOORS SHALL BE CONSIDERED FINISHED FLOOR. <br />. ALL DIMENSIONS SHALL BE COORDINATED WITH ARCHITECTURAL DETAILS AND MAY BE ADJUSTED TO <br />CONFORM WITH ARCHITECTURAL REQUIREMENTS AS LONG AS NO CODE RESTRICTION IS VIOLATED. <br />5. OUTLETS INSTALLED LOWER THAN 15" AFF (FORWARD REACH) AND 9" AFF (SIDE REACH) ARE IN <br />VIOLATION OF ADA. <br />PECIAL NOTES: <br />1. EXIT SIGNS SHALL NOT BE INSTALLED IN A MANNER THAT THE SIGN WILL BLOCK FIRE ALARM VISUAL DEVICES. <br />Z. FOR LIGHTING FIXTURES MOUNTING HEIGHTS SEE SCHEDULE AND DRAWINGS. <br />WEIE SMIM TABLE <br />FOR 12OV-20A BRANCH CIRCUITS ONLY (UNLESS NOTED OTHERWISE) <br />IF DISTANCE (A+B) IN FEET IS <br />USE COPPER WIRE IN METALLIC <br />PANEIBQARD <br />(SEE DIAGRAM AT Rl;lil) <br />CONDUIT, AWG SIZE AS FOLLOWS <br />ON ENTIRE CIRCUIT AND SIZE <br />CONDUIT ACCORDINGLY. <br />"A" FT. <br />0' TO 100' <br />112 AWG (MIN.) <br />FIRST ON LAST ON <br />CIRCUIT • CIRCUIT. <br />100' TO 175' <br />#10 AWG <br />175' TO 300' <br />#8 AWG <br />I.-T FT. 4__ 1/2 WIRE LENGTH FROM <br />300' TO 450' <br />16 AWG (MAX.) <br />FIRST TO LAST RECEPTACLE <br />OR LIGHTING FIXTURE <br />ON CIRCUIT. <br />FOR 277V-20A BRANCH CIRCUITS ONLY (MLESS NOTED OTHERWISE) <br />IF DISTANCE (A+B) IN FEET IS: <br />USE COPPER WIRE IN METALLIC <br />PANELBOARD <br />(SEE DIAGRAM AT RIGIM <br />CONDUIT, AWG SIZE AS FOLLOWS <br />ON ENTIRE CIRCUIT AND SIZE <br />CONDUIT ACCORDINGLY. <br />'A' FT. <br />0' TO 250' <br />#12 AN (MIN.) <br />FIRST ON LAST ON <br />2W' TO 400' <br />#10 AWG <br />CIRCUIT. CIRCUIT. <br />400' TO 700' <br />18 AWG <br />2 WIRE LENGTH FROM <br />��' � 4-FIRST <br />700' M 1000, <br />#6 AWG (MAX.) <br />TO LAST LIGHTING <br />FIXTURE ON CIRCUIT. <br />!>♦l2IES: <br />1. TABLES ARE BASED ON EVENLY DISTRIBUTED LOAD ALLOWING A 3% VOLTAGE DROP AT LAST OUTLET. <br />2. 480V MOTOR BRANCH CIRCUIT CONDUCTORS SHALL BE #12 AWG IN 3/4" C UNLESS OTHERWISE NOTED. <br />3. SIZE OF CONDUCTORS ARE BASED UPON EACH MOTOR BEING FED WITH SEPARATE CONDUIT. IF CONDUCTORS <br />FOR TWO MOTORS (MAX.) ARE TO BE COMBINED IN ONE CONDUIT, INCREASE THE SIZE OF CONDUCTORS AND <br />CONDUITS PER NATIONAL ELECTRICAL CODE (NEC), TO COMPENSATE FOR CONDUCTOR DE -RATING. <br />4• PROVIDE DEDICATED NEUTRAL FOR EACH CIRCUIT. <br />ELECTRICAL TESTNQ REOMEMENT <br />NOTE - THE ELECTRICAL CONTRACTOR SHALL BE REQUIRED TO INCLUDE IN HIS SCOPE AND <br />COST OF WORK HIRING A QUAUFIED INDEPENDENT (THIRD PARTY) TESTING AGENCY TO <br />PERFORM ELECTRICAL INSPECTION AND TESTING PER NETA ACCEPTANCE TESTING <br />SPECIFICATIONS. <br />INSPECTION AND TESTS SHALL BE PERFORMED ON NEW EQUIPMENT AND SUB -COMPONENTS <br />INCLUDING: <br />1) PANELBOARDS <br />2) MOTOR CONTROLLERS <br />3) TRANSFORMERS <br />4) LOW VOLTAGE CABLES USED ON FEEDERS 400 AMPS AND LARGER <br />5) GROUNDING SYSTEMS <br />TESTING AGENCY SHALL BE CERTIFIED BY AND A MEMBER COMPANY OF THE INTERNATIONAL <br />ELECTRICAL TESTING ASSOCIATION (NEA). CONTRACTOR SHUT BE RESPONSIBLE FOR <br />CORRECTING DEFICIENCIES IDENTIFIED DURING TESTING AND SUBMITTING TEST RESULTS TO <br />ENGINEER FOR APPROVAL SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. <br />0�� <br />THE WORK SHALL COMPLY WITH ALL APPLICABLE LOCAL, MUNICIPAL, <br />AND NATIONAL CODES. WHERE THE CONSTRUCTION DOCUMENTS <br />INDICATE MORE RESTRICTIVE REQUIREMENT'S THE CONSTRUCTION <br />DOCUMENTS SHALL GOVERN. HOWEVER, THE CONSTRUCTION DOCUMENTS <br />SHALL NOT BE INTERPRETED AS AUTHORITY TO VIOLATE ANY CODE OR <br />REGULATION. <br />2. DRAWINGS AND SPECIFICATIONS <br />THE CONTRACTOR SWILL BE RESPONSIBLE FOR READING AND <br />COMPLYING WITH BOTH THE DRAWINGS AND SPECIFICATIONS. IN THE <br />EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN THE DRAWINGS, <br />NOTES, SPECIFICATIONS, OR CODES, THE REFERENCE WHICH PROVIDES <br />THE MORE COMPLETE OR HIGHER STANDARD SHALL PREVAIL <br />3. INTERPRETATION OF THE DOCUMENTS <br />CAREFULLY COMPARE THE DRAWINGS AND SPECIFICATIONS, CHECKING <br />MEASUREMENTS AND CONDITIONS UNDER WHICH THIS INSTALLATION IS <br />TO BE MADE. FOR CLARIFICATION BETWEEN VARIOUS DRAWINGS, <br />BETWEEN DRAWINGS OR SPECIFICATION, OR BETWEEN SECTIONS OF THE <br />SPECIFICATION, THE MATTER SHALL BE REFERRED TO THE ENGINEER <br />BEFORE ANY WORK IS EXECUTED. THE CONTRACTOR SHALL STATE IN <br />THEIR PROPOSAL ANY EXCEPTIONS NECESSARY TO MAKE THIS A <br />COMPLETE, READY TO USE INSTALLATION. IF NOT STATED IN THE <br />PROPOSAL, IT WILL NOT BE CONSIDERED EXTW4. <br />4. ELECTRICAL DRAWINGS <br />THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SWILL NOT BE <br />SCALED. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF <br />ALL DOORS, WALLS, FURNITURE, EQUIPMENT, ETC.. THE LOCATION OF <br />RACEWAY SYSTEM COMPONENTS IS SCHEMATIC. THE EXACT LOCATION <br />OF RACEWAY SYSTEM COMPONENTS SHALL BE DETERMINED BY THE <br />CONTRACTOR IN THE FIELD. THE CONTRACTOR SHALL CONFIRM THE <br />DIMENSIONS OF THE ACTUAL EQUIPMENT TO BE SUPPUED FOR THIS <br />PROJECT, AND VERIFY CLEARANCES AND ROUGH -INS PRIOR TO <br />STARTING WORK. <br />5. SITE EXAMINATION <br />BEFORE SUBMITTING A BID, THE CONTRACTOR SWILL VISIT THE SITE, <br />EXAMINE THE PREMISES, AND MAKE A THOROUGH SURVEY OF THE <br />EXISTING CONDITIONS. THIS VISIT SHALL ONLY BE ALLOWED AS PER <br />THE VA SCHEDULED WALKTHROUGH AND THE SUBMISSION OF A <br />PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH AN VISIT <br />HAS BEEN MADE. NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED <br />FOR FAILURE TO VISIT THE SITE OR FOR LATER CLAIMS FOR LABOR, <br />EQUIPMENT, MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED <br />WHICH COULD HAVE BEEN FORESEEN HAD SUCH AN VISIT <br />BEEN MADE <br />6. COORDINATION WITH OTHER TRADES <br />THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COMPLETE SET OF <br />ARCHITECTURAL AND ENGINEERING DOCUMENTS AND COORDINATE WITH <br />MECHANICAL, PLUMBING, ARCHITECTURAL, AND OTHER TRADES FOR <br />EXACT DIMENSIONS, CLEARANCES, ROUGH -IN LOCATIONS, AND OTHER <br />ADDITIONAL SCOPES OF WORK THAT MAY NOT BE SHOWN ON THE <br />ELECTRICAL PLANS. THE ELECTRICAL CONTRACTOR SHALL BE <br />RESPONSIBLE FOR ALL 120 VOLT (AND HIGHER) AC POWER TO OTHER <br />TRADES EQUIPMENT AND HARDWARE. THIS SHALL INCLUDE, BUT NOT BE <br />LIMITED T0, CONTROLS, FIRE AND SECURITY SYSTEMS, MOTORIZED <br />DOORS, DAMPERS, UFTS, AND OTHER SYSTEMS. UNLESS SPECIFICALLY <br />NOTED OTHERWISE ON THE ELECTRICAL PLANS, THE ELECTRICAL <br />CONTRACTOR SHALL FURNISH ALL SAFETY DISCONNECT SWITCHES TO <br />MECHANICAL EQUIPMENT. <br />7. PERMITS, APPLICATIONS AND RELEASES <br />THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS <br />INSPECTIONS, APPLICATIONS, RELEASES AND FEES REQUIRED BY LOCAL, <br />STATE AND FEDERAL AGENCIES FOR THE EXECUTION OF THIS WORK. <br />SCHEDUUNG OF ALL REQUIRED INSPECTIONS SHALL BE THE <br />RESPONSIBILITY OF THE CONTRACTOR. <br />8. FIRE STOPPING <br />ALL PENETRATIONS IN WALL, FLOOR OR CEIUNGS SWILL BE SUITABLY <br />CLOSED UP AND SEALED WITH AN INTUMESCENT FIRE STOPPING <br />COMPOUND LISTED IN THE MOST RECENT FACTORY MUTUAL RESEARCH <br />CORPORATION (FMRC) APPROVAL GUIDE FIRE STOPPING PRODUCTS <br />SHALL BE MANUFACTURED BY 3M CO. <br />9. PAINTING <br />ALL NEWLY INSTALLED EXPOSED PIPING SHALL BE PAINTED TO MATCH <br />THE EXISTING ADJACENT WALL OR CEUNG SURFACE. <br />10. OWNER FURNISHED EQUIPMENT <br />EQUIPMENT THAT WILL BE FURNISHED BY THE OWNER WILL BE <br />INDICATED ON A SEPARATE SCHEDULE THE CONTRACTOR SHALL <br />COORDINATE WITH THE OWNER FOR DELIVERY SCHEDULES. THE <br />CONTRACTOR IS TO ASSUME THAT ON SITE STORAGE MAY NOT BE <br />AVAILABLE WHEN COORDINATING DELIVERY OF EQUIPMENT. THE <br />CONTRACTOR, IN COORDINATION WITH THE OWNER'S REPRESENTATIVE, <br />WILL INSPECT THE DELIVERY FOR ACCURACY AND SHIPMENT DAMAGE <br />AND ACCEPTING THE EQUIPMENT. THE CONTRACTOR SHALL BE <br />RESPONSIBLE TO STORE, PROTECT, AND ULTIMATELY INSTALL THE <br />EQUIPMENT. <br />MEP / FP Engineer <br />EPSTEIN <br />600 West Fulton <br />Chicago, IL 60661 <br />312.454.9100 <br />11. ELECTRICAL SERVICE DISRUPTIONS <br />ANY WORK INVOLVING A TASK WHICH EXPOSES ACTIVE BUS SHALL BE <br />PERFORMED AFTER HOURS (11:OOPM TO 5:00AM). THIS RESTRICTION <br />INCLUDES REMOVING THE COVER FROM ANY PANEL BOARD, SWITCHBOARD, <br />M.C.C. ETC.. ALL WORK WHICH EXPOSES ACTIVE BUS REQUIRES A <br />WRITTEN NOTIFICATION TO THE OWNER WHICH WILL OUTLINE THE METHOD OF <br />PROCEDURE FOR THE WORK. THE CONTRACTOR SHALL PROVIDE A <br />MINIMUM OF 2 WEEKS NOTICE TO THE OWNER BEFORE WORKING ON ANY <br />ENERGIZED ELECTRICAL SYSTEM. ALL POWER DISRUPTION SHALL OCCUR AT <br />TIMES AND OF DURATIONS ACCEPTABLE TO THE OWNER. <br />12. EQUIPMENT <br />ALL MATERIALS AND EQUIPMENT USED IN THIS INSTALLATION SHALL BE NEW, <br />AND HAVE THE APPROPRIATE UL LISTING AND LABEL <br />13. MISCELLANEOUS SUPPORTING MEMBERS <br />ALL ANGLES CHANNELS, AND OTHER MISCELLANEOUS STEEL, BOLTS, RODS, <br />ETC.. REQUIRED TO SUPPORT UGHT FIXTURE, CONDUIT, RACEWAY, LADDER <br />TRAY, OR OTHER ELECTRICAL EQUIPMENT OR DEVICES SHALL. BE FURNISHED <br />AND INSTALLED BY THE CONTRACTOR. <br />14. DISTRIBUTION PANELS AND PANELS BOARDS <br />ALL DISTRIBUTION PANELS AND PANEL BOARDS SHALL BE PROVIDED WITH <br />TYPEWRITTEN DIRECTORIES. SEE PANEL SCHEDULES ON THE DRAWINGS AND <br />SPECIFICATION FOR COMPLETE IDENTIFICATION AND LABELING REQUIREMENTS. <br />ALL DISTRIBUTION PANELS AND PANEL BOARDS SHALL BE LABELED ON THE <br />PANEL CABINET WITH THE PANEL NAME AND THE POWER SOURCE FEEDING <br />THE PANEL AS PER THE ELECTRICAL ONE UNE. <br />15. SAFETY <br />THE CONTRACTOR SHALL TAKE ALL STEPS NECESSARY TO ENSURE THE <br />SAFETY OF THE OWNERS EMPLOYEES, BUILDING EMPLOYEES AND GUESTS, <br />AS WELL AS THEIR OWN FORCES, BY ADEQUATELY PROTECTING ANY <br />EXPOSED LIVE CONDUCTORS, OR DEVICES THROUGHOUT THE COURSE OF <br />THIS WORK. <br />16. EQUIPMENT CONNECTIONS <br />PROVIDE FINAL CONNECTIONS FOR ALL EQUIPMENT FURNISHED UNDER <br />OTHER DIVISIONS AND FOR ALL OWNER FURNISHED EQUIPMENT. PROVIDE A <br />FLEXIBLE UQUID TIGHT CONNECTION TO ALL VIBRATION PRODUCING <br />EQUIPMENT. <br />17. TEMPORARY UGHTING, POWER, FIRE, AND SAFETY <br />PROVIDE TEMPORARY LIGHTING AND POWER AS REQUIRED IN AREAS <br />UNDERGOING WORK DURING CONSTRUCTION. FURNISH AND INSTALL ONE <br />OSHA APPROVED PIGTAIL SOCKET WITH 150-WATT LAMP FOR EVERY 500 <br />SQUARE FEET OF FLOOR SPACE AND A MINIMUM 1 PER ROOM. THE <br />TEMPORARY LIGHTING SHALL BE LEFT IN PLACE UNTIL PERMANENT LIGHTING <br />IS COMPLETELY OPERATIONAL <br />FURNISH AND INSTALL POWER OUTLETS TO A TOTAL ONE FOR EVERY 2000 <br />SQUARE FEET OR PART THEREOF OF FLOOR AREA AND THESE SHALL BE 15 <br />AMP, SINGLE PHASE RECEPTACLES FOR EITHER 110 OR 220 VOLTS AS <br />DIRECTED BY THE GENERAL CONTRACTOR. COORDINATE FOR ADDITIONAL <br />TEMPORARY POWER REQUIREMENTS WITH OTHER TRADES AND PROVIDE AN <br />ADEQUATE INSTALLATION. <br />COMPLY WITH NFPA 241 FOR SAFEGUARDING DURING CONSTRUCTION AND <br />ALTERATION OPERATIONS. IN ADDITION, ANY OPENINGS IN FIRE RATED <br />SEPARATIONS BETWEEN OCCUPIED AND UNOCCUPIED (OR OPERATIONAL AND <br />NON -OPERATIONAL) AREAS SHALL BE SEALED AT THE END OF EACH WORK <br />DAY WITH AN APPROPRIATE FIRE RATED ENCLOSURE OR SEALANT. DO NOT <br />COMPROMISE EXISTING SECURITY OR FIRE ALARM SYSTEMS SERVING THE <br />OCCUPIED OR OPERATIONAL AREAS. <br />18. POWER COORDINATION <br />THE CONTRACTOR SHALL PERFORM ALL COORDINATION AND SCHEDUUNG OF <br />LOCAL POWER OUTAGES REQUIRED WITH THE OWNER. ALL NEEDED POWER <br />OUTAGES TO BE SCHEDULED WITH THE OWNER TWO WEEKS IN ADVANCE. <br />19. CABUNG <br />BRANCH CIRCUITS TO RECEPTACLES, UGHTING AND MISC. SMALL LOADS <br />(15 OR 20 AMP CIRCUITS), UNLESS SPECIFICALLY NOTED OTHERWISE, <br />SHALL. BE 2 - #12, 1 - #12 GIRD., 3/4" C. A SEPARATE NEUTRAL SHALL <br />BE RUN FOR EACH CIRCUIT. SEE WIRE SIZING TABLE ON THIS SHEET. <br />EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE <br />CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN <br />INSULATED EQUIPMENT GROUNDING CONDUCTOR. <br />20. CABUNG SIZES <br />BRANCH CIRCUIT CABLE SIZING SHALL BE ADJUSTED BASED ON THE <br />VALUES INDICATED IN THE WIRE SIZING TABLE PER THIS SHEET. <br />21. SPECIAL LUG REQUIREMENTS <br />ANY CABLE WHICH TERMINATES DIRECTLY ON TO A BUS BAR SHALL BE 2 <br />BOLT LONG BARREL TYPE WITH INSPECTION HOLES PRODUCED WITH NON <br />FLASHING TYPE DYES AS MANUFACTURED BY THOMAS AND BETTS, MINIMUM <br />10 TONS OF COMPRESSION, HEX CRIMP. THE USE OF HEAT SHRINK <br />TUBING IS EXPUCITLY FORBIDDEN. THERE SHALL BE NO 'SHINERS" AT THE <br />LUGS. <br />22.RACEWAYS <br />ALL ELECTRICAL CONDUITS TO A MINIMUM OF 3/4". MULTI -GANG BACKBOXES <br />FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH <br />WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES. <br />23. UGHTING <br />ALL FINAL LOCATIONS AND ARRANGEMENTS OF UGHTING FIXTURES SHALL BE <br />OBTAINED FROM THE ARCHITECTURAL REFLECTED CEIUNG PLAN. <br />Design Architect <br />EPSTEIN <br />600 West Fulton <br />Chicago, IL 60661 <br />312.454.9100 <br />Nestle Waters North America <br />Nestle Waters North America <br />4330 20th Street <br />Zephyrhills, Florida 33542-6703 <br />972.462.3663 <br />1. EXAMINATION <br />A THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE AREAS UNDER <br />WHICH THE WORK IS TO BE PERFORMED AND NOTIFY THE OWNER IN <br />WRITING OF ANY CONDITIONS DETRIMENTAL TO THE PROPER AND <br />TIMELY COMPLETION OF THE WORK. CONTRACTOR SHALL NOT <br />PROCEED WITH WORK UNTIL SATISFACTORY CONDITIONS HAVE BEEN <br />CORRECTED. <br />B. VERIFY FIELD MEASUREMENTS AND CIRCUITING ARRANGEMENTS FOR <br />DEVICES SHOWN ON DRAWINGS. <br />C. DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION <br />AND EXISTING RECORD DRAWINGS. REPORT DISCREPANCIES TO <br />OWNER BEFORE DISTURBING EXISTING INSTALLATION. <br />D. COMMENCEMENT OF DEMOLITION MEANS ACCEPTANCE OF EXISTING <br />CONDITIONS. <br />E. REVIEW MECHANICAL AND ARCHITECTURAL DEMOLITION DRAWINGS <br />FOR FOR ANY OTHER ELECTRICAL REQUIREMENTS. <br />2. PREPARATION <br />A. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEIUNGS <br />SCHEDULED FOR REMOVAL. <br />3. DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK. <br />A REMOVE, RELOCATE, AND EXTEND EXISTING ELECTRICAL WORK AS <br />INDICATED ON THE DRAWINGS AND AS NOTED HEREIN. <br />B. REMOVE ABANDONED WIRING AND CONDUIT BACK TO SOURCE OF SUPPLY, <br />FOR ALL EQUIPMENT SHOWN TO BE REMOVED. <br />C. WHERE SOURCE OF SUPPLY IS A PANELBOARD, RE -LABEL <br />PROTECTIVE DEVICE AS 'SPARE". AFTER DEMOLITION IS COMPLETE, <br />SUBMIT REVISED PANELBOARD SCHEDULES INDICATING "SPARES" TO <br />OWNER AND ENGINEER. <br />D. REMOVE EXPOSED ABANDONED CONDUIT ABOVE ACCESSIBLE CEIUNG <br />FINISHES. CUT CONDUIT FLUSH WITH WALLS AND FLOORS, AND <br />PATCH SURFACES. CONDUIT MAY BE ABANDONED IN WALLS TO REMAIN BUT <br />EXISTING WIRING WITHIN THESE CONDUITS TO BE REMOVED COMPLETELY. <br />E. REMOVE AND DISCONNECT ABANDONED OUTLETS AND ASSOCIATED <br />DEVICES. <br />F. DISCONNECT AND REMOVE ABANDONED PANELBOARDS AND <br />DISTRIBUTION EQUIPMENT. <br />G. DISCONNECT AND REMOVE ELECTRICAL DEVICES AND EQUIPMENT THAT <br />IS NO LONGER IN USE. <br />H. DISCONNECT AND REMOVE ABANDONED LUMINARIES. REMOVE <br />BRACKETS, STEMS, HANGERS, AND OTHER ACCESSORIES. <br />I. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF <br />ALL TYPES, OR CAP AND LIBEL IN JUNCTION BOX <br />FOR RE -USE, IN COMPLIANCE WITH THE NATIONAL <br />ELECTRIC CODE <br />J. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING <br />DEMOUTION AND EXTENSION OF WORK. <br />K. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS <br />AND CONDUCTORS PASSING THROUGH RENOVATED AREAS <br />AND SERVICING UNDISTURBED AREAS. <br />4. CLEANING, REPAIR, AND REPLACEMENT <br />A GENERAL: CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT <br />THAT WILL REMAIN OR ARE TO BE REUSED. <br />B. PANELBOARDS: CLEAN EXPOSED SURFACES AND TIGHTEN ALL <br />ELECTRICAL CONNECTIONS. REPLACE DAMMED CIRCUIT BREAKERS <br />AND PROVIDE CLOSURE PLATES FOR VACANT POSITIONS. PROVIDE <br />TYPED SCHEDULES SHOWING REVISED CIRCUITING INFORMATION. <br />C. LUMINARIES: REMOVE EXISTING LUMINARIES AS NOTED. <br />5. DISPOSAL <br />A OWNER SHALL HAVE RIGHT TO RETAIN ANY EQUIPMENT OR MATERIALS <br />THAT HAVE BEEN DEMOLISHED PRIOR TO DISPOSAL OR REMOVAL <br />FROM SITE. <br />B. ANY EQUIPMENT OR MATERIALS NOT WANTED BY THE OWNER SHALL <br />BECOME THE PROPERTY OF THE CONTRACTOR AND REMOVED FROM <br />SITE. <br />C. CONTRACTOR SHALL COMPLY WITH ENVIRONMENTAL LAWS AND <br />REGULATIONS FOR DISPOSAL OF DEMOUSHED MATERIALS AND <br />EQUIPMENT. <br />waters <br />ers <br />NORTH AMERICA <br />Expires <br />FEB 28 Z015 <br />N. <br />�'.• STATE OF <br />117 <br />' G <br />jr <br />4 <br />09.18.2013 <br />ISSUE FOR PERMIT <br />3 <br />09.11.2013 <br />ISSUE FOR BIDS <br />2 <br />09.03.2013 <br />CD REVIEW PACKAGE <br />1 <br />08.16.2013 <br />DD REVIEW PACKAGE <br />NO. <br />DATE <br />REVISIONS/ISSUANCES <br />i PSTEIN <br />Architecture <br />Chicago <br />Interiors <br />New York <br />Engineering <br />Bucharest <br />Construction <br />Warsaw <br />600 W. Fulton Street <br />Chicago, IL 60661-1259 <br />T 312.454.9100 <br />www.epsteinglobal.com <br />PROJECT NUMBER: 12386 <br />PROJECT MANAGER: JK <br />ARCH/ENG: DD <br />SCALE: NOT TO SCALE <br />DRAWN BY: DD <br />CHECKED BY: MS <br />ELECTRICAL NOTES <br />AND TABLES <br />E-002 <br />A. Epstein and Sons International, Inc. All rights reserved. <br />