F1 i5i0j I BASIC ELECTRICAL MATERIALS AND METHODS <br />SCOPE OF WORK <br />A. FURNISH ALL LABOR, EQUIPMENT, MATERIALS. TOOLS <br />TRANSPORTATION, PERMITS, ETC., NECESSARY FOR, OR <br />INCIDENTAL TO, THE INSTALLATION OF COMPLETE SYSTEMS OF <br />ELECTRIC WIRING FOR LIGHTING, POWER AND MISCELLANEOUS <br />SYSTEMS IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. <br />B. FURNISH, ERECT, INSTALL, CONNECT, CLEAN, ADJUST, TEST AND <br />CONDITION ALL MANUFACTURED ARTICLES, MATERWS, AND <br />EQUIPMENT, AND PLACE IN SERVICE IN ACCORDANCE WITH THE <br />MANUFACTURER'S DIRECTIONS AND RECOMMENDATIONS, EXCEPT <br />AS OTHERWISE NOTED. <br />C. <br />CAREFULLY EXAMINE THE CONTRACT DOCUMENTS, VISIT THE <br />SITE AND THOROUGHLY BECOME FAMILIAR WITH THE LOCAL <br />CONDITIONS RELATING TO THE WORK. FAILURE TO DO SO WILL <br />NOT RELIEVE THE CONTRACTOR OF THE OBUGA71ONS OF THE <br />CONTRACT. <br />CODES <br />A. INSTALLATION SHALL BE MADE IN ACCORDANCE WITH THE <br />FLORIDA CODE AND ALL AHJ CODES. INSTALLATION SHALL ALSO <br />BE MADE IN ACCORDANCE WITH THE REQUIREMENTS OF THE <br />PUBLIC UTILITY COMPANY WHICH WILL SERVE THE PROPERTY. <br />STANDARDS AND REGULATIONS <br />A THE WORK AND MATERIALS SHALL COMPLY WITH THE LATEST <br />EDITION OF ALL APPLICABLE SAFETY AND PERFORMANCE <br />STANDARDS AND CODES. <br />B. IN EVERY INSTALLATION WHERE REGULATIONS OF ELECTRIC <br />UTILITY COMPANY APPLY, CONFORMANCE WITH THEIR <br />REGULATIONS IS MANDATORY AND ANY COSTS INVOLVED SHALL <br />BE INCLUDED IN THE CONTRACT. <br />C. SHOULD WORK BE PERFORMED WHICH DOES NOT COMPLY WITH <br />THE REQUIREMENTS OF APPLICABLE BUILDING CODES, STATE <br />AND FEDERAL LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS <br />AND UTILITY COMPANY REGULATIONS, CHANGES FOR <br />COMPLIANCE SHALL BE DONE AT NO ADDITIONAL COST TO THE <br />OWNER. <br />D. <br />SECURE AND PAY FOR ALL PERMITS, GOVERNMENTAL FEES, <br />TAXES, AND LICENSES NECESSARY FOR THE PROPER <br />EXECUTION AND COMPLETION OF THE WORK REQUIRED. <br />DEFINITIONS <br />A. FURNISH: EXCEPT AS OTHERWISE DEFINED IN GREATER DETAIL. <br />TERM "FURNISH' IS USED TO MEAN SUPPLY AND DELIVER TO <br />PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY, <br />INSTALLATION, ETC., AS APPLICABLE IN EACH INSTANCE <br />B. INSTALL EXCEPT AS OTHERWISE DEFINED IN GREATER DETAIL. <br />TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT <br />PROJECT SITE INCLUDING UNLOADING, UNPACKING, ASSEMBLY, <br />ERECTION, PLACING, ANCHORING, APPLYING, WORKING TO <br />DIMENSION, FINISHING, CURING, PROTECTING, CLEANING, <br />CONNECTIONS, WIRING, ADJUSTING, TESTING (IF REQUIRED) AND <br />SIMILAR OPERATIONS, AS APPLICABLE IN EACH INSTANCE <br />C. PROVIDE: EXCEPT AS OTHERWISE DEFINED IN GREATER DETAIL, <br />TERM "PROVIDE' MEAN FURNISH AND INSTALL, COMPLETE AND <br />READY FOR INTENDED USE, AS APPLICABLE IN EACH <br />INSTANCE. <br />PRODUCT DATA <br />A. ALL EQUIPMENT, MATERIAL AND FIXTURES SHALL BE REVIEWED <br />BY THE ENGINEER BEFORE ORDERS ARE PLACED. THE <br />ENGINEER RESERVES THE RIGHT TO REJECT ANY MATERIAL <br />WHICH, IN THE OPINION OF THE ENGINEER, IS NOT IN <br />ACCORDANCE WITH SPECIFICATIONS EITHER BEFORE OR AFTER <br />INSTALLATION. <br />B. <br />ALL EQUIPMENT, MATERIAL AND FIXTURES SHALL BE TESTED <br />AND LISTED BY UNDERWRITERS LABORATORIES INC. AND <br />OFFICIAL LISTS OF ALL GOVERNMENT AND INSURANCE BOARDS <br />WAVING JURISDICTION. <br />GOVERNMENTAL SUBMITTALS <br />A. PREPARE SHOP DRAWINGS REQUIRED FOR THE SUBMITTAL OF <br />EXIT AND EMERGENCY LIGHTING, LIFE SAFETY AND FIRE ALARM <br />SYSTEMS TO THE GOVERNMENTAL AGENCIES. <br />B. SUBMIT TO GOVERNMENTAL AGENCIES AND UTILITY COMPANIES <br />SHOP DRAWINGS, WHICH ARE REQUIRED BY THESE AGENCIES, <br />FOR THEIR APPROVAL <br />COORDINATION <br />A EXACT LOCATION OF EQUIPMENT FURNISHED BY THE OTHER <br />TRADES AND WIRED BY THE ELECTRICAL TRADE SHALL BE <br />OBTAINED FROM THE DRAWINGS OF THE OTHER TRADES. <br />B. INSTALL ELECTRICAL EQUIPMENT TO FACILITATE MAINTENANCE <br />AND REPAIR OR REPLACEMENT OF EQUIPMENT COMPONENTS. <br />RECORD DRAWINGS <br />A. PROVIDE RECORD "AS -BUILT' DRAWINGS AND SUBMIT TO <br />ENGINEER. <br />B. <br />DRAWINGS SHALL INDICATE ACTUAL BRANCH CIRCUIT NUMBERS <br />USED AND EXACT LOCATIONS OF ALL EQUIPMENT, DEVICES, <br />AND LIGHTING FIXTURES. <br />QUALITY CONTROL SUBMITTALS <br />A. AFTER ALL EQUIPMENT, DEVICES AND RACEWAYS ARE INSTALLED <br />AND WIRES AND CABLES ARE IN PLACE AND CONNECTED TO <br />DEVICES AND EQUIPMENT, TEST THE SYSTEM FOR CONTINUITY, <br />PROPER PHASE ROTATION, SHORT CIRCUIT, IMPROPER <br />GROUNDS, AND OTHER DEFECTS. IF DEFECTIVE CONDITION IS <br />PRESENT, MAKE ALL NECESSARY CORRECTIONS AND RETEST <br />FOR COMPLIANCE. <br />WARRANTY <br />A. ELECTRICAL WORK SHALL BE GUARANTEED FOR BOTH MATERIALS <br />AND LABOR FOR A PERIOD OF ONE (1) YEAR. <br />B. NOTE THAT GUARANTEES SHALL RUN FROM DATE OF <br />SUBSTANTIAL COMPLETION OF THE WORK, NOT FROM THE DATE <br />OF INSTALLATION OF THE REM OR DEVICE. <br />TEMPORARY LIGHT AND POWER <br />A. PROVIDE ELECTRIC SERVICE OF SUFFICIENT CAPACITY TO <br />SUPPLY THE ELECTRIC UGHTING AND POWER REQUIREMENTS <br />OF THE CONSTRUCTION SITE <br />B. ALL NECESSARY TRANSFORMERS, METERS, CABLES, <br />PANELBOARDS. LAMPS, SWITCHES, RECEPTACLES AND <br />ASSOCIATED EQUIPMENT SHALL BE PROVIDED. <br />C. TEMPORARY LIGHTS SHALL BE BASED ON A MINIMUM OF 1 <br />WATT/SQ. FT., EXCEPT WHERE HIGHER LIGHTING INTENSITIES <br />ARE REQUIRED BY CODES OR STANDARDS OR SPECIFIED, IN <br />WHICH CASE THE WATTAGE SHALL BE INCREASED TO PROVIDE <br />THE HIGHER INTENSITIES. SUFFICIENT WIRING, OUTLETS AND <br />LAMPS SHALL BE INSTALLED TO ENSURE PROPER LIGHTING IN <br />ROOMS, SPACES, STAIRS, EGRESS, AND PASSAGE AREAS. <br />MINIMUM SIZE LAMP USED SHALL BE 100 WATTS. <br />D. THE CONTRACTOR SHALL PAY FOR COST OF ENERGY AND <br />POWER CONSUMED BY ALL TRADES. <br />E. TEMPORARY WIRING OF A SPECIAL NATURE FOR UGHTING, <br />SAFETY AND POWER OTHER THAN MENTIONED ABOVE. SHALL <br />BE PAID FOR BY THOSE USING SAME <br />F. TEMPORARY WORK SHALL BE REMOVED AFTER IT HAS SERVED <br />ITS PURPOSE <br />G. LAMPS INSTALLED IN PERMANENT LIGHTING FIXTURES AND USED <br />FOR LIGHTING DURING CONSTRUCTION SHALL BE REPLACED <br />JUST PRIOR TO THE DATE OF SUBSTANTIAL COMPLETION. <br />MATERIALS AND EQUIPMENT <br />A. MATERIALS AND EQUIPMENT SHALL BE NEW, UL OR CSA <br />LABELED AND SHALL BEAR THE MANUFACTURER'S NAME, MODEL <br />NUMBER AND OTHER IDENTIFICATION MARKINGS. <br />B. MATERIALS AND EQUIPMENT SHALL BE THE STANDARD PRODUCT <br />OF A MANUFACTURER REGULARLY ENGAGED IN THE <br />PRODUCTION OF THE REQUIRED TYPE OF MATERIAL OR <br />EQUIPMENT FOR AT LEAST FIVE (5) YEARS (UNLESS <br />SPECIFICALLY EXEMPTED BY THE ENGINEER) AND SHALL BE <br />THE MANUFACTURER'S LATEST DESIGN WITH PUBLISHED <br />PROPERTIES. <br />C. <br />EQUIPMENT AND MATERIALS OF THE SAME GENERAL TYPE <br />SHALL BE OF THE SAME MANUFACTURER THROUGHOUT THE <br />PROJECT TO PROVIDE UNIFORM APPEARANCE, OPERATION AND <br />D. MAINTENANCE <br />REFER TO MATERIAL LISTS AND SCHEDULES ON THE DRAWINGS <br />FOR MATERIAL NOT DESCRIBED IN THE SPECIFICATION. <br />INSTALLATION <br />A. THE DRAWINGS FOR WORK ARE DIAGRAMMATIC AND ARE <br />INTENDED TO CONVEY THE SCOPE OF WORK AND INDICATED <br />THE GENERAL ARRANGEMENT OF CONDUIT, BOXES, EQUIPMENT, <br />FIXTURES AND OTHER WORK INCLUDED IN THE CONTRACT. <br />B. LOCATION OF ITEMS REQUIRED BY THE DRAWINGS OR <br />SPECIFICATIONS NOT DEFINITELY FIXED BY DIMENSIONS ARE <br />APPROXIMATE ONLY. EXACT LOCATIONS NECESSARY TO SECURE <br />THE BEST CONDITIONS AND RESULTS SHALL BE DETERMINED AT <br />THE SITE, AND SHALL BE SUBJECT TO THE APPROVAL OF THE <br />ENGINEER. <br />C. <br />WITH THE APPROVAL OF THE ENGINEER AND WITHOUT <br />ADDITIONAL COST TO THE OWNER, MAKE MINOR <br />MODIFICATIONS IN THE WORK AS REQUIRED BY STRUCTURAL <br />INTERFERENCE, BY INTERFERENCE WITH WORK OF OTHER <br />D. TRADES OR FOR PROPER EXECUTION OF WORK. <br />WORK INSTALLED BEFORE COORDINATED WITH OTHER TRADES <br />SO AS TO CAUSE INTERFERENCE WITH THE WORK OF SUCH <br />OTHER TRADES SHALL BE CHANGED TO CORRECT SUCH <br />E CONDITION WITHOUT ADDITIONAL COST TO THE OWNER AS <br />DIRECTED BY THE ENGINEER. <br />ELECTRICAL CONTRACTOR SHALL REFER TO CONTRACT <br />DOCUMENTS FOR DETAILS, REFLECTED CEILING PLANS, AND <br />LARGE SCALE DRAWINGS. <br />AIR PLENUM CEILINGS <br />A. EQUIPMENT AND WIRING INSTALLED IN CEILINGS USED AS AIR <br />PLENUMS SHALL BE APPROVED FOR THAT USE. <br />1. ALL EQUIPMENT AND WIRING SHALL CONFORM TO ALL LOCAL <br />GOVERNING CODES. <br />2. EQUIPMENT SPECIFIED OR SHOWN ON THE DRAWINGS <br />SHALL ALSO INCLUDE ANY MODIFICATIONS REQUIRED TO <br />CONFORM TO ALL APPLICABLE CODES. <br />B. ELECTRICAL CONTRACTOR SHALL REFER TO ARCHITECTURAL AND <br />MECHANICAL DRAWINGS TO VERIFY AREAS DESIGNATED FOR USE <br />AS AIR PLENUMS. <br />CUTTING AND PATCHING <br />A. DO CORE DRILLING, CUTTING, FITTING AND PATCHING <br />NECESSARY FOR INSTALLATION OF CONDUITS, WIREWAYS, AND <br />OTHER ELECTRICAL EQUIPMENT. PROVIDE SUPPORTS NECESSARY <br />FOR THE SAME AND FOR BRACING AND ANCHORAGE OF WORK. <br />NO CUTTING OF STRUCTURAL WORK OR OF FIREPROOFING <br />SHALL BE DONE WITHOUT THE CONSENT OF THE ENGINEER. <br />B. CONDUITS PASSING THROUGH ROOFS OR OTHER SURFACES <br />EXPOSED TO WEATHER SHALL BE PROPERLY FLASHED. <br />C. ALL PENETRATIONS SHALL BE PROPERLY FIREPROOFED. <br />D. INTERIOR PARTITIONS OF THE PERIMETER WALLS ARE FINISHED <br />WITH DRYWALL UP TO DECKING. ELECTRICAL CONTRACTOR <br />SHALL BE RESPONSIBLE FOR CUTTING AND PATCHING AS <br />REQUIRED TO INSTALL RECESSED CONDUIT AND OUTLET BOXES <br />IN THESE WALLS. <br />EQUIPMENT NOISE LIMITATION <br />A. NOISE LEVELS OF ELECTRIC DEVICES AND EQUIPMENT SHALL <br />BE WITHIN ACCEPTABLE LIMITS AS ESTABLISHED BY NEMA OR <br />OTHER VAUD NOISE RATING AGENCIES. <br />MOUNTING HEIGHTS <br />A MOUNTING HEIGHTS OF ELECTRICAL. ITEMS SHALL BE AS LISTED <br />BELOW, UNLESS OTHERWISE INDICATED ON THE CONTRACT <br />DOCUMENTS. DIMENSIONS ARE ABOVE FINISHED FLOOR TO <br />CENTERLINE OF DEVICE. IN AREAS WHERE APPLICABLE CODE <br />REQUIRES DIFFERENT MOUNTING HEIGHTS, AS IN HAZARDOUS <br />AREAS, COMPLY WITH CODE REQUIREMENTS. <br />B. INDOOR RECEPTACLE OUTLETS IN WALLS OR PARTITIONS: <br />(1'-6" TO CENTERUNE. MOUNT HORIZONTALLY) <br />C. TELEPHONE/DATA SYSTEM OUTLETS: <br />(LINE UP WITH RECEPTACLES, MOUNT HORIZONTALLY) <br />D. TOGGLE SWITCH OUTLETS: <br />(4'-0" TO CENTERLINE) <br />E INDIVIDUAL MOTOR STARTERS: <br />(6'-0" TO TOP) <br />F. INDIVIDUAL DISCONNECT SWITCHES: <br />(6'-0" ON TOP) <br />G. GROUP MOUNTED MOTOR STARTERS OR DISC. SWITCHES: <br />(6'-0" TO CENTERUNE OF HIGHEST HANDLE, V-6" MINIMUM <br />TO LOWEST, OR PER CODE) <br />H. PANELBOARDS: <br />(6'-0" TO TOP, OR 6'-0" TO CENTERLINE OF HIGHEST <br />HANDLE, V-6" MINIMUM TO LOWEST FOR LARGE <br />I. DISTRIBUTION PANELS) <br />BRACKET LIGHTS: <br />(7'-O" TO CENTERLINE OR AS REQUIRED FOR DEVICE TO <br />J. CLEAR CEILING BY V-6' <br />WALL MOUNTED EXIT SIGNS: <br />(7'-0" TO CENTERLINE OR AS REQUIRED FOR DEVICE TO <br />K. CLEAR CEILING BY 0'-6") <br />FIRE ALARM PULL STATIONS: <br />L (4'-0" TO CENTERLINE) <br />OUTLETS FOR SIGNALS, SOUNDING DEVICES, OR CLOCKS: <br />(AS REQUIRED FOR DEVICE TO CLEAR CEILING BY O'-6") <br />MISCELLANEOUS STEEL WORK AND EQUIP. SUPPORTS <br />A. FURNISH AND INSTALL ALL MISCELLANEOUS STRUCTURAL <br />MEMBERS AS REQUIRED TO INSTALL ALL ELECTRICAL <br />EQUIPMENT INCLUDING TRANSFORMERS, PANELS, CONDUITS, <br />BUS DUCTS, CABINETS, CONTROLS AND LIGHTING FIXTURES. <br />NONE OF THESE ITEMS WILL BE PERMITTED TO BE ATTACHED <br />TO OR SUPPORTED FROM OTHER TRADES SUPPORT SYSTEMS <br />OR CONVEYORS. ELECTRICAL SUPPORT SHALL BE A <br />COMPLETELY INDEPENDENT SYSTEM. <br />FEEDERS <br />A. INSTALL ALL FEEDERS OVERHEAD, UNLESS OTHERWISE <br />INDICATED ON THE DRAWINGS. PROVIDE CABLE SUPPORTS FOR <br />RISERS AT INTERVALS REQUIRED BY CODE. PROVIDE PULL <br />AND/OR SPLICE BOXES WHERE REQUIRED. <br />WIRING <br />A. NO MORE THAN EIGHT (8) WIRES PLUS GROUND WIRE SHALL <br />BE PERMITTED IN HOMERUN CONDUITS TO UGHTING PANELS. <br />NO MORE THAN NINE (9) WIRES PLUS GROUND WIRE SHALL <br />BE PERMITTED IN HOMERUN CONDUITS TO POWER PANELS. <br />B. 120 VOLT LIGHTING CIRCUITS SHALL BE LIMITED TO 1600 <br />WATTS FOR 20 AMPERE CIRCUIT BREAKERS UNLESS INDICATED <br />OTHERWISE ON THE DRAWINGS. <br />C. 277 VOLT UGHTING CIRCUITS SHALL BE LIMITED TO 3000 <br />WATTS FOR 20 AMPERE CIRCUIT BREAKERS UNLESS INDICATED <br />OTHERWISE ON THE DRAWINGS. <br />D. ONLY ONE 277 VOLT CIRCUIT SHALL BE INSTALLED IN A WALL <br />SWITCH OUTLET BOX. WHERE MORE THAN ONE 277 VOLT <br />CIRCUIT (ON DIFFERENT PHASES) IS INDICATED ON DRAWINGS <br />AS BEING RUN TO MULTI -WALL SWITCH UNITS FROM A BRANCH <br />CIRCUIT OUTLET BOX, PROVIDE INDIVIDUAL CONDUITS <br />SEPARATING PHASES AND SEPARATE SWITCH OUTLET BOXES OR <br />A BOX WITH METAL BARRIERS TO SEPARATE EACH PHASE. <br />E. CONVENIENCE OUTLETS SHALL BE PLACED ON SEPARATE <br />CIRCUITS FROM LIGHTING OUTLETS, UNLESS OTHERWISE <br />INDICATED ON THE DRAWINGS. CONNECT A MAXIMUM OF EIGHT <br />(8) GENERAL PURPOSE CONVENIENCE OUTLETS OR FOUR (4) <br />DATA PROCESSING EQUIPMENT OUTLETS PER CIRCUIT UNLESS <br />INDICATED OTHERWISE ON THE DRAWINGS. <br />F. MOTORS SHALL BE ON SEPARATE CIRCUITS FROM LIGHTING <br />OUTLETS UNLESS INDICATED OTHERWISE ON THE DRAWINGS. <br />G. BEFORE CONNECTING EQUIPMENT, CHECK NAMEPLATE DATA <br />AGAINST THE INFORMATION SHOWN ON THE DRAWINGS. CALL <br />ANY DISCREPANCIES TO THE ATTENTION OF THE ENGINEER. <br />H. BALANCE BRANCH CIRCUIT LOADS AMONG FEEDER CONDUCTORS <br />AT EACH SWITCHBOARD AND PANELBOARD, AND RECONNECT <br />LOADS AS MAY BE NECESSARY TO OBTAIN REASONABLE LOAD <br />BALANCE ON EACH PHASE ELECTRICAL UNBALANCE SHALL BE <br />NOT EXCEED 7-1/2X. <br />1. ALL 2-CIRCUIT AND 3-CIRCUIT WIRING NETWORKS TO <br />COMPUTER EQUIPMENT, PRINTERS AND OTHER NON-UNEAR <br />LOADS SHALL CONSIST OF #12 AWG PHASE WIRES, #10 AWG <br />NEUTRAL WIRE AND #12 AWG GROUND WIRE. <br />CONCRETE PADS <br />A. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A 4 INCH HIGH <br />CONCRETE HOUSEKEEPING PAD UNDER EACH PIECE OF FLOOR <br />MOUNTED OR GROUND MOUNTED EQUIPMENT, UNLESS LARGER <br />SIZES ARE OTHERWISE SPECIFIED. <br />B. PAD DIMENSION SHALL BE 2 INCHES (MINIMUM) GREATER ON <br />EACH SIDE OF THE FLOOR DIMENSION OF THE ELECTRICAL <br />EQUIPMENT. THE EDGE OF THE PAD SHALL HAVE A 1 INCH <br />CHAMFER ON EACH SIDE. <br />TOUCH-UP PAINTING <br />A. ALL EQUIPMENT AND SYSTEMS SHALL BE THOROUGHLY <br />CLEANED OF RUST, SPLATTERS AND OTHER FOREIGN MATTER <br />OR DISCOLORATION LEAVING EVERY PART OF ALL SYSTEMS IN <br />AN ACCEPTABLE PRIME CONDITION. THE CONTRACTOR FOR THE <br />WORK UNDER HIS CONTRACT SHALL REFINISH AND RESTORE TO <br />THE ORIGINAL CONDITION ALL EQUIPMENT WHICH HAS <br />SUSTAINED DAMAGE TO THE MANUFACTURER'S PRIME AND <br />FINISH COATS OF PAINT AND/OR ENAMEL <br />CLEAN UP <br />A. AFTER THE COMPLETION OF THE ELECTRICAL INSTALLATION, THE <br />ENTIRE SYSTEM SHALL BE THOROUGHLY CLEANED. CLEAN AND <br />VACUUM FOREIGN MATTER FROM ALL ENCLOSURES, LIGHTING <br />FIXTURES, EQUIPMENT AND CONDUITS. <br />DEFECTIVE WORK AND MATERIALS <br />A. ALL MATERIALS OR WORK FOUND TO BE DEFECTIVE OR NOT IN <br />STRICT CONFORMITY WITH THE DRAWINGS, DIFFERENT FROM <br />REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS, <br />DEFACED OR DAMAGED THROUGH ACTION OF FIRE, WEATHER OR <br />ANY OTHER CAUSE, WILL BE REJECTED AND SHALL BE <br />IMMEDIATELY REMOVED FROM THE PREMISES BY THE <br />CONTRACTOR AND SATISFACTORY MATERIAL AND WORK <br />SUBSTITUTED THEREFORE WITHOUT DELAY OR ADDITIONAL COST <br />TO OWNER. <br />B. ANY DEFECTIVE OR IMPERFECT WORK WHICH MAY BE <br />DISCOVERED SHALL BE CORRECTED IMMEDIATELY UPON NOTICE. <br />NO PREVIOUS INSPECTION OR CERTIFICATES ON ACCOUNT <br />SHALL BE HELD TO RELIEVE THE CONTRACTOR FROM THE <br />OBUGA71ON TO FURNISH SOUND MATERIAL AND TO PERFORM <br />SATISFACTORY WORK. <br />FINAL INSPECTION <br />A. WHEN ALL ELECTRICAL WORK ON THE PROJECT HAS BEEN <br />COMPLETED AS INDICATED ON THE DRAWINGS AND SPECIFIED <br />HEREIN AND IS READY FOR FINAL INSPECTION, SUCH AN <br />INSPECTION SHALL BE MADE. AT THIS TIME, THE ELECTRICAL <br />CONTRACTOR FOR THE WORK UNDER THIS CONTRACT SHALL <br />DEMONSTRATE THAT THE REQUIREMENTS OF THESE <br />SPECIFICATIONS HAVE BEEN MET TO THE ENGINEERS <br />SATISFACTION. <br />16110 RACEWAYS <br />SUBMITTALS <br />A. PRODUCT DATA: SUBMIT MANUFACTURER'S DATA, <br />SPECIFICATIONS AND INSTALLATION RECOMMENDATIONS FOR ALL <br />EQUIPMENT USED AS RACEWAY. <br />B. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS FOR ALL EQUIPMENT <br />USED AS RACEWAY. <br />GENERAL <br />A. CONDUIT SHALL BE SECURELY FASTENED IN PLACE AT <br />INTERVALS AS SPECIFIED BY THE CODE USING SUITABLE <br />STRAPS, HANGERS AND OTHER SUPPORTING ASSEMBLIES AS <br />INDICATED ON PLANS. ALL STRAP HANGERS AND SUPPORTING <br />ASSEMBLIES SHALL BE OF RUGGED CONSTRUCTION CAPABLE <br />SUPPORTING WEIGHT WITH A REASONABLE FACTOR OF SAFETY. <br />RIGID HEAVYWALL STEEL CONDUIT <br />A. RIGID HEAVY WALL STEEL CONDUIT (RHWS) SHALL BE <br />HOT -DIPPED GALVANIZED, STANDARD WEIGHT, RIGID MILD <br />STEEL WITH THREADED CONNECTIONS AS MANUFACTURED 13Y <br />AWED, WHEATLAND, OR EQUAL FITTINGS SHALL BE APPLETON, <br />CROUSE-HINDS OR EQUAL <br />RIGID HEAVYWALL ALUMINUM CONDUIT <br />A RIGID HEAVY WALL ALUMINUM CONDUIT (RHWA) SHALL NOT BE <br />USED. <br />INTERMEDIATE METAL CONDUIT <br />A. INTERMEDIATE METAL CONDUIT (IMC) SHALL BE HOT -DIPPED <br />GALVANIZED OR ELECTRO-GALVANIZED, UNIFORM THICKNESS <br />MILD STEEL WITH THREADED CONNECTIONS AS MANUFACTURED <br />BY AWED, TRIANGLE OR WHEATLAND. FITTINGS SHALL BE <br />KILLARK, APPLETON OR CROUSE-HINDS. <br />ELECTRICAL METALLIC TUBING <br />A. ELECTRICAL METALLIC TUBING (EMT) SHALL BE ZINC COATED, <br />ENAMEL LINED, THREADLESS STEEL TUBING, U/L LABELED AS <br />MANUFACTURED BY AWED, WHEATLAND OR YOUNGSTOWN. <br />FITTINGS SHALL BE MANUFACTURED BY THOMAS & BEATS, <br />APPLETON, OR EFCOR. <br />ELECTRICAL PLASTIC CONDUIT <br />A. PLASTIC CONDUIT SHALL BE SCHEDULE (40). (80). U.L RATED <br />90 DEGREES CELSIUS POLYVINYL CHLORIDE AND SHALL <br />CONFORM TO NEMA STANDARDS. PLASTIC CONDUIT SHALL BE <br />U.L LISTED IN CONFORMITY WITH ARTICLE 347 OF THE <br />NATIONAL ELECTRIC CODE <br />B. <br />PLASTIC CONDUIT WILL NOT BE ALLOWED WITHIN THE MAIN <br />WALLS OF THE BUILDING. <br />LIQUIDTIGHT FLEXIBLE METAL CONDUIT <br />A. LIQUIDTIGHT FLEXIBLE METAL CONDUIT SHALL BE <br />MOISTUREPROOF AND OILPROOF, TYPE "UA", FLEXIBLE METAL <br />CONDUIT WITH PVC OUTER JACKET AND INTEGRAL GROUNDING <br />CONDUCTOR AS MANUFACTURED BY ANACONDA AMERICAN <br />BRASS COMPANY OR ELECTI-FLEX COMPANY. <br />FLEXIBLE METAL CONDUIT <br />A. FLEXIBLE METAL CONDUIT SHALL BE SINGLE STRAP, HOLICALLY <br />WOUND, GALVANIZED STEEL WITH SMOOTH INTERIOR SURFACE <br />AS MANUFACTURED BY ALFLEX CORP. OR ELCTRI-FLEX CO. <br />FLEXIBLE METALLIC TUBING <br />A. FLEXIBLE METALLIC TUBING (FMT) SHALL BE SEAMLESS, <br />UQUIDTIGHT, APPROVED FOR USE AS AN ELECTRICAL RACEWAY. <br />IT SHALL BE USED FOR WIRING IN RETURN AIR PLENUM <br />SPACES TO COMPLY WITH CODE REQUIREMENTS WHERE <br />FLEXIBLE CONNECTIONS ARE REQUIRED. <br />FITTINGS <br />A. COUPLINGS, CONNECTORS AND FITTINGS FOR RIGID STEEL <br />CONDUIT AND IMC SHALL BE THREADED GALVANIZED STEEL OR <br />GALVANIZED MALLEABLE IRON SPECIFICALLY DESIGNED AND <br />MANUFACTURED FOR THE PURPOSE. FITTINGS SHALL CONFORM <br />TO ANSI C80.4. <br />B. EMT FITTINGS SHALL BE OF THE STEEL COMPRESSION TYPE, <br />RAIN AND CONCRETE TIGHT, WITH STEEL COMPRESSION NUTS. <br />CONNECTORS SHALL BE INSULATED THROAT WITH CASE <br />HARDENED LOCKNUTS. FITTINGS SHALL CONFORM TO ANSI <br />C80.4. <br />C. LIQUIDTIGHT FLEXIBLE METAL CONDUIT CONNECTORS SHALL BE <br />GALVANIZED MALLEABLE IRON OR STEEL WITH INSULATED <br />THROAT. <br />D. FLEXIBLE METAL CONDUIT CONNECTORS SHALL BE GALVANIZED <br />MALLEABLE IRON OR STEEL WITH TWO SCREWS AT EACH <br />TERMINATION AND INSULATED THROAT. <br />BUSHINGS <br />A. BUSHINGS FOR CONDUITS 1 INCH AND SMALLER SHALL BE <br />SELF -EXTINGUISHING THERMOPLASTIC TYPE, 150 DEG. CELSIUS <br />TEMPERATURE RATING. MANUFACTURERS SHALL BE APPLETON <br />SERIES BBU50H. THOMAS & BELTS SERIES 510 OR <br />OZ/GEDNEY. <br />B. <br />BUSHINGS FOR CONDUITS 1 1/4 INCH AND LARGER SHALL BE <br />MALLEABLE IRON BODY WITH 150 DEG. CELSIUS INSULATING <br />RING. INSULATING MATERIAL SHALL BE LOCKED IN PLACE AND <br />NON -REMOVABLE MANUFACTURERS SHALL BE APPLETON <br />SERIES BU1251, THOMAS & BETTS SERIES 1222 OR <br />OZ/GEDNEY. <br />SLEEVES <br />A. SLEEVES IN FLOORS SHALL EXTEND ONE (1) INCH ABOVE <br />FINISHED FLOOR LEVEL THE SPACE BETWEEN THE CONDUIT <br />AND THE SLEEVE SHALL BE SEALED WITH A FIRE RESISTANT <br />MATERIAL AND MADE WATERTIGHT. <br />BUILDING EXPANSION JOINTS <br />A. DEFLECTION/EXPANSION FITTINGS ARE NOT SHOWN ON THE <br />DRAWINGS. REFER TO ARCHITECTURAL DRAWINGS FOR <br />EXPANSION JOINT LOCATIONS. PROVIDE DEFLECTION/ <br />EXPANSION FITTINGS WITH BONDING JUMPERS IN ALL CONDUIT, <br />BUS DUCT AND CABLE RUNS CROSSING BLDG. EXPANSION <br />JOINTS. DEFU- CTION/EXPANSION FITTINGS SHALL BE <br />0-Z/GEDNEY TYPE "DX". <br />MOISTURE SEALS <br />A. WALL ENTRANCE 0-Z/GEDNEY TYPE FSK OR FSC THRU-WALL <br />FITTING. <br />B. <br />ROOF PENETRATIONS: SEAL WITH FLASHINGS COMPATIBLE <br />WITH ROOF DESIGN AND APPROVED BY ROOFING SYSTEM <br />MANUFACTURER AND ARCHTTECT/ENGINEER. <br />C. <br />CONDUITS: JOHN MANVILLE "DUXSEAL" NON -SETTING <br />ELECTRICAL MASTIC. <br />FIRE STOPPING <br />A. ALL CONDUITS. DUCTS, TROUGHS AND SIMILAR ITEMS WHICH <br />PENETRATE FIRE -RATED OR TIME -RATED WALLS, PARTITIONS OR <br />FLOORS SHALL BE SEALED WITH A FIRE RESISTANT MATERIAL <br />WHICH COMPLIES WITH ASTM E 814 AND UL 1479 <br />REQUIREMENTS. <br />SPARE CONDUITS <br />A. FROM EACH FLUSH CABINET OR PANEL, INSTALL THREE (3) <br />SPARE (1) INCH EMPTY CONDUITS TO AN ACCESSIBLE POINT <br />ABOVE THE CEILING LINE AND CAP FOR FUTURE USE. <br />INSTALLATION <br />A. ALL WIRING, UNLESS OTHERWISE NOTED, SHALL BE <br />INSTALLED IN CONDUIT. MINIMUM SIZE SHALL BE 3/4" <br />UNLESS NOTED OTHERWISE <br />1. LIGHTING SWITCH WIRING AND WIRING TO LAST DEVICE OF A <br />2-WIRE BRANCH CIRCUIT MAY BE INSTALLED IN 1/2" <br />CONDUIT. <br />B. ALL CONDUIT 2 INCHES AND SMALLER MAY BE ELECTRIC <br />METALLIC TUBING (EMT) UNLESS OTHERWISE SPECIFIED IN THIS <br />SPECIFICATION OR OTHERWISE CALLED FOR ON THE DRAWINGS. <br />C. INTERMEDIATE METAL CONDUIT SHALL BE USED AS FOLLOWS: <br />1. CONDUIT SIZES GREATER THAN 2 INCHES. <br />2. ON VERTICAL RUNS WHERE THE SPACING OF SUPPORTS <br />ARE SPACED GREATER THAN 7 FEET ON CENTER. <br />3. VERTICAL DROPS TO EQUIPMENT IN OPEN SPACES. <br />4. EMBEDDED IN SLABS ON GRADE. <br />5. EXPOSED OUTSIDE OF THE BUILDING. <br />6. WHERE EXPOSED TO MOISTURE. <br />7. IN MECHANICAL EQUIPMENT ROOMS BELOW 10'-O" A.F.F. <br />D. PROVIDE RIGID HEAVYWALL STEEL CONDUIT WHERE EMBEDDED <br />IN CONCRETE, MASONRY, EARTH, OR WHERE INDICATED ON <br />DRAWINGS. <br />E. RIGID NONMETALLIC CONDUIT (PVC) OR PVC -COATED RIGID <br />STEEL CONDUIT MAY BE USED SUBJECT TO THE FOLLOWING <br />CONDITIONS OR WHERE INDICATED ON THE DRAWINGS: <br />1. OUTSIDE THE MAIN BUILDING WALLS. <br />2. SUBJECT TO SEVERE CORROSIVE ATMOSPHERE <br />F. FEEDER CONDUITS SHALL NOT BE INSTALLED IN FLOOR SLABS. <br />G. CONDUITS RUN IN SLABS OR BELOW SLABS ON GRADE SHALL <br />BE ENTIRELY ENCASED IN CONCRETE. IN NO CASE SHALL THEY <br />BE INSTALLED IN FILL BELOW SLABS. PROVIDE ANY CONCRETE <br />REQUIRED TO ENCASE CONDUITS PLACED BELOW SLABS. <br />H. INSTALL UNDERGROUND CONDUITS A MINIMUM OF 30" BELOW <br />FINISHED GRADE, OR BELOW THE FROST LINE <br />I. FINAL CONNECTIONS TO MOTORS, TRANSFORMERS AND SIMILAR <br />EQUIPMENT SUBJECT TO VIBRATION OR ADJUSTMENT SHALL BE <br />MADE WITH SECTIONS OF FLEXIBLE METAL CONDUIT, MINIMUM <br />18 INCHES LONG AND MAXIMUM 36 INCHES LONG. MINIMUM <br />SIZE SHALL BE 3/4 INCH. IN WET OR DAMP LOCATIONS, <br />LIQUID TIGHT FLEXIBLE METAL CONDUIT SHALL BE USED. <br />J. IN SUSPENDED CEILING CAVITIES WHERE RECESSED LIGHTING <br />FIXTURES ARE INSTALLED. PROVIDE JUNCTION BOXES NEAR <br />FIXTURES FOR EXTENDING BRANCH CIRCUIT CONDUCTORS TO <br />FIXTURE THROUGH FLEXIBLE METAL CONDUIT. FLEXIBLE METAL <br />CONDUIT SHALL BE 3/8 INCH MINIMUM SIZE, IN LENGTHS NOT <br />IN EXCESS OF SIX FEET. IN RETURN AIR PLENUM CEILINGS, <br />CHICAGO ELECTRICAL CODE APPROVED FLEXIBLE METAL TUBING <br />SHALL BE USED. <br />K. INSTALL CONDUIT, TUBING, RACEWAY AND CABLE TRAY <br />PRODUCTS AS INDICATED, AS SPECIFIED ELSEWHERE, AND IN <br />ACCORDANCE WITH THE MANUFACTURER'S WRITTEN <br />INSTRUCTIONS, THE APPLICABLE REQUIREMENTS OF NEC, THE <br />NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION'S 'STANDARD <br />OF INSTALLATION", AND IN ACCORDANCE WITH RECOGNIZED <br />INDUSTRY PRACTICES TO ENSURE THAT PRODUCTS SERVE THE <br />INTENDED FUNCTION. <br />L, MECHANICALLY FASTEN TOGETHER METAL CONDUITS, <br />ENCLOSURES, AND RACEWAYS FOR CONDUCTORS TO FORM <br />CONTINUOUS ELECTRICAL CONDUCTOR. CONNECT TO ELECTRICAL <br />BOXES, FITTINGS AND CABINETS TO PROVIDE ELECTRICAL <br />CONTINUITY AND FIRM MECHANICAL ASSEMBLY. <br />M. ALL CONDUIT SHALL BE CONCEALED IN THE BUILDING <br />CONSTRUCTION IF AT ALL POSSIBLE UNDER NO <br />CIRCUMSTANCES WILL CONDUIT BE PERMITTED TO BE <br />CONCEALED IN THE INSULATION OF INSULATED WALLS OR <br />CEILINGS. WHERE INSULATED WALLS OCCUR, CONDUIT SHALL BE <br />CONCEALED WITHIN MASONRY CONSTRUCTION. <br />N. WHERE CONDUIT MUST BE RUN EXPOSED, IT SHALL BE <br />INSTALLED PARALLEL WITH OR AT RIGHT ANGLES TO THE <br />BUILDING WAILS. HANGERS SHALL BE FABRICATED TYPE <br />CONDUITS SHALL NOT CROSS PIPE SHAFTS, OR VENTILATING <br />DUCT OPENINGS. <br />0. KEEP CONDUITS A MINIMUM DISTANCE OF 6" FROM PARALLEL <br />RUNS OF LOUVERS, HOT WATER PIPES OR OTHER SOURCES OF <br />HEAT. WHENEVER POSSIBLE INSTALL HORIZONTAL RACEWAY <br />RUNS ABOVE WATER AND STEAM PIPING. <br />P. SUPPORT RISER CONDUITS AT EACH FLOOR LEVEL WITH CLAMP <br />HANGERS. <br />CONDUITS IN CONCRETE SLABS <br />A. PLACE CONDUITS BETWEEN BOTTOM REINFORCING STEEL AND <br />TOP REINFORCING STEEL <br />B. PLACE CONDUITS EITHER PARALLEL, OR AT 90 DEGREES, TO <br />MAIN REINFORCING STEEL <br />C. SEPARATE CONDUITS BY NOT LESS THAN 3 DIAMETERS OF <br />ADJACENT CONDUITS TO ENSURE PROPER CONCRETE BOND. <br />D. EMBEDDED CONDUIT DIAMETER IS NOT TO EXCEED 1/3 OF <br />SLAB THICKNESS. <br />E. INSTALL CONDUITS AS NOT TO DAMAGE OR RUN THROUGH <br />STRUCTURAL MEMBERS. AVOID HORIZONTAL OR CROSS RUNS IN <br />BUILDING PARTITIONS OR SIDE WALLS. <br />18120 <br />SUBMITTALS <br />A. PRODUCT DATA: SUBMIT MANUFACTURER'S DATA ON ELECTRICAL <br />WIRES, CABLES AND CONNECTORS. <br />ACCEPTABLE WIRE MANUFACTURERS <br />A. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, <br />MANUFACTURERS OFFERING PRODUCTS WHICH MAY BE <br />INCORPORATED IN THE WORK INCLUDE, BUT ARE NOT <br />LIMITED TO THE FOLLOWING: <br />AMERICAN WIRE AND CABLE COMPANY <br />BELDEN WIRE AND CABLE <br />GENERAL CABLE CORPORATION <br />OKONITE COMPANY <br />PIREW CABLE CORPORATION SOUTHWIRE COMPANY <br />ACCEPTABLE CONNECTOR MANUFACTURERS <br />A. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, <br />MANUFACTURERS OFFERING PRODUCTS WHICH MAY BE <br />INCORPORATED IN THE WORK INCLUDE, BUT ARE NOT <br />LIMITED TO THE FOLLOWING: <br />AMP, INC. <br />BURNDY CORPORATION ELECTRICAL PRODUCTS DIVISION, <br />MIDLAND-ROSS CORP. <br />IDEAL INDUSTRIES, INC. <br />3M COMPANY <br />0-Z/GEDNEY COMPANY <br />THOMAS AND BETTS CORPORATION <br />WIRE AND CABLE - 600 VOLT <br />A. MINIMUM SIZE WIRE SHALL BE NO. 12 AWG EXCEPT NO. 14 <br />AWG MAY BE USED FOR 120 VOLT CONTROL WIRING. FOR LOW <br />VOLTAGE CONTROL WIRING NO. 16 AWG WIRE MAY BE USED. <br />B. ALL WIRE AND CABLE SHALL BE COPPER CONDUCTOR. <br />C. SIZES #12 AND #10 AWG FOR LIGHTING AND RECEPTACLE <br />WIRING SHALL BE 600 VOLT CLASS INDIVIDUAL CONDUCTORS <br />SOLID COPPER IN ACCORDANCE WITH ASrM B-8, CLASS 3. <br />D. SIZES #8 AWG AND LARGER FOR ALL WIRING AND SIZES <br />#14.#12 AND #10 AWG USED FOR POWER AND CONTROL <br />WIRING SHALL BE 600 VOLT CLASS INDIVIDUAL CONDUCTOR <br />STRANDED COPPER IN ACCORDANCE WITH ASTMB-8, CLASS 3. <br />E FOR 120 VOLT, 15A AND 20A BRANCH CIRCUIT RUNS <br />EXCEEDING 100'-0" IN LENGTH FROM THE PANELBOARD TO <br />THE CENTER OF THE LOAD, THE ENTIRE BRANCH CIRCUIT RUN <br />SHALL BE #10 AWG OR LARGER. FOR RUNS EXCEEDING <br />175'-O" TO THE CENTER OF THE LOAD, USE #8 AWG OR <br />LARGER FOR THE ENTIRE LENGTH OF THE BRANCH CIRCUIT <br />RUN. <br />F. COLOR CODE CONDUCTOR INSULATION FOR #8 AWG OR <br />SMALLER. PROVIDE COLOR MARKING TAPE FOR #6 AWG AND <br />LARGER. MATCH EXISTING COLOR CODES WHERE APPLICABLE. <br />WHERE NO COLOR CODE IS PRESENT, THE FOLLOWING SHALL <br />BE UTILIZED. <br />1. FOR 208/12OV. 3-PHASE CIRCUITS COLORS SHALL <br />PHASE A. BLACK, PHASE B: RED, PHASE C: BLUE, <br />NEUTRAL WHITE, GROUND: GREEN, ISOLATED GROUND: <br />GREEN/YELLOW <br />2. FOR 480/277V, 3-PHASE CIRCUITS COLORS SHALL BE <br />PHASE A. BROWN, PHASE B: ORANGE, PHASE C: YELLOW. <br />NEUTRAL GRAY, GROUND: GREEN, ISOLATED GROUND: <br />GREEN/YELLOW <br />G. TYPE THWN/THHN: FOR LIGHTING, POWER, CONTROL AND <br />OTHER WIRING IN DRY LOCATIONS NOT SPECIFICALLY DEFINED, <br />FOR ALL SIZES UP TO NO. 6, 600 VOLT COPPER, FLAME <br />RETARDANT, HEAT RESISTANT, THERMOPLASTIC INSULATED WITH <br />NYLON JACKET, HEAT, MOISTURE, OIL AND GASOLINE RESISTANT, <br />CODE GRADE, 90 DEGREES CELSIUS RATED. IN WET LOCATIONS <br />RATED 75 DEGREES CELSIUS. <br />H. TYPE THWN/THHN: FOR LIGHTING, POWER AND OTHER WIRING <br />NOT SPECIFICALLY DEFINED, FOR ALL SIZES NO. 6 AND <br />LARGER, 600 VOLT COPPER, FLAME RETARDANT, HEAT <br />RESISTANT, THERMOPLASTIC INSULATED WITH NYLON JACKET, <br />HEAT, MOISTURE, OIL AND GASOLINE RESISTANT, CODE GRADE, <br />90 DEGREES CELSIUS RATED IN DRY LOCATIONS. IN WET <br />LOCATIONS RATED 75 DEGREES CELSIUS. <br />1. TYPE XHHW: FOR WIRING IN TEMPERATURE SPACES OF 50 <br />DEGREES FAHRENHEIT AND BELOW FOR ALL WIRE GAUGE SIZES <br />CROSS INKED POLYETHYLENE HIGH HEAT AND MOISTURE 600 <br />VOLT COPPER RESISTANT UTILIZE ALSO FOR WIRING OF SMOKE <br />EXHAUST AND SMOKE REMOVAL FANS. 90 DEGREES CELSIUS IN <br />DRY LOCATIONS, AND 75 DEGREES CELSIUS IN WET LOCATIONS. <br />J. ALL LUGS FOR FEEDER CONDUCTORS AND CONNECTORS FOR <br />BRANCH CIRCUIT JOINTS SHALL BE OF THE SOLDERLESS TYPE <br />SUITABLE FOR COPPER WIRE, RATED 75 DEGREES CELSIUS. <br />CONNECTORS <br />A• PROVIDE UL-LISTED FACTORY FABRICATED, METAL CONNECTORS <br />OF SIZES, AMPACITY RATINGS, MATERIALS, TYPES AND CLASSES <br />FOR APPLICATIONS AND FOR SERVICES INDICATED. WHERE NOT <br />INDICATED, PROVIDE PROPER SELECTION AS DETERMINED BY <br />INSTALLER TO COMPLY WITH PROJECT'S INSTALLATION <br />REQUIREMENTS, NEC AND NEMA STANDARDS. <br />INSTALLATION <br />A. COORDINATE CABLE AND WIRE INSTALLATION WORK WITH <br />ELECTRICAL RACEWAY AND EQUIPMENT INSTALLATION WORK. <br />B. PULL CONDUCTORS TOGETHER WHERE MORE THAN ONE IS <br />BEING INSTALLED IN A RACEWAY. <br />C. USE PULLING COMPOUND OR LUBRICANT, WHEN NECESSARY' <br />COMPOUND MUST NOT DETERIORATE CONDUCTOR OR <br />INSULATION. <br />D. DO NOT USE A PULLING MEANS, INCLUDING FISH TAPE, CABLE <br />OR ROPE WHICH CAN DAMAGE THE RACEWAY. <br />E. KEEP CONDUCTOR SPUCES TO A MINIMUM. <br />F. INSTALL SPLICES AND TAPS WHICH HAVE <br />EQUIVALENT -OR -BETTER MECHANICAL STRENGTH AND <br />INSULATION PROPERTIES THAN THE CONDUCTOR. <br />G. USE SPLICE AND TAP CONNECTORS WHICH ARE COMPATIBLE <br />WITH THE CONDUCTOR MATERIAL <br />H. SUPPORT CONDUCTORS IN VERTICAL RACEWAYS USING SUITABLE <br />CABLE SUPPORTS. LOCATE SUPPORTS AT TOP OF VERTICAL <br />RACEWAY AND SO EACH 25'-0"MAXIMUM LENGTH OF <br />CONDUCTOR IN VERTICAL RACEWAY WILL BE COMPLETE WITH <br />SUPPORT. PROVIDE CABLE SUPPORT PULL BOXES AS <br />REQUIRED TO INSTALL CABLE SUPPORTS. <br />FIELD QUALITY CONTROL <br />A. PRIOR TO ENERGIZATION, CHECK CABLE CONDUIT, RACEWAYS, <br />OUTLET BOXES, AND WIRE FOR CONTINUITY OF CIRCUITRY, AND <br />FOR SHORT CIRCUITS. CORRECT MALFUNCTION IF DETECTED. <br />B. SUBSEQUENT TO WIRE AND CABLE HOOKUPS, ENERGIZE <br />CIRCUITRY AND DEMONSTRATE FUNCTIONING IN ACCORDANCE <br />WITH REQUIREMENTS. <br />MEP / FP Engineer Design Architect <br />EPSTEIN <br />EPSTEIN <br />600 West Fulton <br />600 West Fulton <br />Chicago, IL 60661 <br />Chicago, IL 60661 <br />312.454.9100 <br />312.454.9100 <br />EE01 ELECTRICAL BOXES <br />SUBMITTALS <br />A. PRODUCT DATA: SUBMIT MANUFACTURER'S DATA ON ELECTRICAL <br />BOXES AND FITTINGS. <br />OUTLET BOXES <br />A OUTLET BOXES: PROVIDE GALVANIZED COATED FLAT ROLLED <br />SHEET -STEEL OUTLET WIRING BOXES, OF SHAPES, CUBIC INCH <br />CAPACITIES, AND SIZES INCLUDING BOX DEPTHS AS INDICATED, <br />SUITABLE FOR INSTALLATION AT RESPECTIVE LOCATIONS. <br />CONSTRUCT OUTLET BOXES WITH MOUNTING HOLES, AND WITH <br />CABLE AND CONDUIT -SIZE KNOCKOUT OPENINGS IN BOTTOM <br />AND SIDES. PROVIDE BOXES WITH THREADED SCREW HOLES, <br />WITH CORROSION -RESISTANT COVER AND GROUNDING SCREWS <br />FOR FASTENING SURFACE AND DEVICE TYPE BOX COVERS. AND <br />FOR EQUIPMENT TYPE GROUNDING. OUTLET BOXES INSTALLED <br />IN RETURN AIR PLENUM CEILING SHALL BE IN ACCORDANCE <br />WITH APPLICABLE CODES. <br />B. OUTLET BOXES -FLUSH MOUNTED <br />1. WALL OUTLETS IN MASONRY' SQUARE CORNER, GALVANIZED <br />MASONRY TYPE WITH INTERNALLY MOUNTED EARS OR 4 <br />INCH SQUARE, 2 1/2 INCH DEEP (MINIMUM). WITH RAISED <br />PLASTER RING HAVING SQUARE CORNERS AND <br />INTERNALLY MOUNTED EARS OR MULTI -GANG AS REQUIRED <br />WITH RAISED COVER TO SUIT MASONRY WALL THICKNESS. <br />2. WALL OUTLETS IN METAL STUD WALLS: UNLESS OTHERWISE <br />NOTED, 4 INCH SQUARE. 1 1/2 INCH DEEP (MINIMUM) OR <br />4-11/16 INCH SQUARE. 2-1/8 INCH DEEP (MINIMUM) <br />FOR SINGLE GANG DEVICES, OR MULTI -GANG AS REQUIRED, <br />RAISED PLASTER RING FOR THICKNESS OF PLASTERBOARD <br />AND FINAL FINISH, COMPLETE WITH BRACKET OR CONDUIT <br />SUPPORT STRAP. <br />3. SURFACE MOUNTED LIGHTING FIXTURE OUTLET BOXES: 4 <br />INCH SQUARE OR OCTAGON, 2-1/8 INCH DEEP <br />GALVANIZED BOX WITH RAISED PLASTER RING SET FLUSH <br />WITH FINISHED SURFACE, COMPLETE WITH 3/8 INCH <br />FIXTURE STUD IF REQUIRED. <br />4. PROVIDE BLANK FLAT COVERS WHERE REQUIRED. <br />C. OUTLET BOXES -SURFACE MOUNTED <br />1. GENERAL USE: 4 INCH SQUARE WITH RAISED DEVICE COVER. <br />2. WEATHERPROOF: CAST GALVANIZED BOX WITH THREADED <br />HUBS, TYPE FS OR FD. <br />3. PROVIDE BLANK FLAT COVERS WHERE REQUIRED, GASKETED <br />FOR WEATHERPROOF USE. <br />D. OUTLET BOX ACCESSORIES: PROVIDE OUTLET BOX ACCESSORIES <br />AS REQUIRED FOR EACH INSTALLATION, INCLUDING BOX <br />SUPPORTS, MOUNTING EARS AND BRACKETS, WALLBOARD <br />HANGERS, BOX EXTENSION RINGS, FIXTURE STUDS, CABLE <br />CLAMPS AND METAL STRAPS FOR SUPPORTING BOXES, WHICH <br />ARE COMPATIBLE WITH OUTLET BOXES BEING USED TO FULFILL <br />INSTALLATION REQUIREMENTS FOR INDIVIDUAL WIRING <br />SITUATIONS. CHOICE OF ACCESSORIES IS INSTALLERS <br />CODE -COMPLIANCE OPTION. <br />SUBJECT TO COMPLIANCE WITH REQUIREMENTS, <br />MANUFACTURERS OFFERING PRODUCTS WHICH MAY BE <br />INCORPORATED IN THE WORK INCLUDE, BUT ARE NOT <br />LIMITED TO THE FOLLOWING: <br />E. APPLETON ELECTRIC: EMERSON ELECTRIC CO. <br />MIDLAND-ROSS CORPORATION <br />OZ/GEDNEY. GENERAL SIGNAL COMPANY RACO DIVISION: <br />HARVEY HUBBELL, INC. <br />THOMAS & BETTS COMPANY <br />JUNCTION AND PULL BOXES <br />A. PROVIDE JUNCTION BOXES, PULL BOXES, CABLE SUPPORT <br />BOXES AND WIREWAYS AS REQUIRED FOR PROPER <br />INSTALLATION OF THE ELECTRICAL WORK. COVERS SHALL BE <br />ACCESSIBLE. SMALL JUNCTION BOXES SHALL BE SIMILAR TO <br />OUTLET BOXES. <br />B. PULL BOXES, CABLE SUPPORT BOXES AND LARGE JUNCTION <br />BOXES FOR INDOOR USE SHALL BE MADE OF CODE GAUGE <br />STEEL COVERS SHALL BE HELD IN PLACE WITH STAINLESS <br />STEEL SCREWS. PAINT INTERIOR AND EXTERIOR SURFACES WITH <br />RUST -INHIBITIVE PAINT. (PULL BOXES AND COVERS SHALL BE <br />HOT DIPPED GALVANIZED.) <br />C. FLANGED TYPE BOXES SHALL BE USED WHERE INSTALLED <br />FLUSH IN FINISHED AREAS. <br />D. BOXES LOCATED OUTDOORS SHALL BE CAST METAL OR ALLOY, <br />FITTED WITH SCREW -FASTENED COVERS AND GASKETS, AND <br />WITH STAINLESS STEEL OR BRASS SCREWS. <br />E. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />JUNCTION AND PULL BOXES OF ONE OF THE FOLLOWING: <br />APPLETON ELECTRIC: EMERSON ELECTRIC CO. <br />ARROW -HART DIVISION: <br />GROUSE -HINDS CO. <br />OZ/GEDNEY: <br />GENERAL SIGNAL COMPANY KEYSTONE COLUMBI& INC. <br />SPRING CITY ELECTRICAL MANUFACTURING CO. <br />HOFFMAN <br />WIEGMANN <br />EXECUTION <br />A. COORDINATE INSTALLATION OF ELECTRICAL BOXES WITH <br />WIRE/CABLE, WIRING DEVICES, AND RACEWAY INSTALLATION <br />WORK. <br />B. OUTLET BOXES FOR LIGHTING FIXTURES, SWITCHES, <br />RECEPTACLES, TELEPHONE/DATA SYSTEM, FIRE ALARM, ETC., <br />AND ASSOCIATED CONDUIT RUNS SHALL BE CONCEALED IN <br />WALLS OR CEILING SPACE WHEREVER POSSIBLE. <br />C. PROVIDE WEATHERTIGHT OUTLETS FOR INTERIOR AND EXTERIOR <br />LOCATIONS EXPOSED TO WEATHER OR MOISTURE. <br />D. PROVIDE KNOCKOUT CLOSURES TO CAP UNUSED KNOCKOUT <br />HOLES WHERE BLANKS HAVE BEEN REMOVED. <br />E. INSTALL ELECTRICAL BOXES IN THOSE LOCATIONS WHICH <br />ENSURE READY ACCESSIBILITY TO ENCLOSED ELECTRICAL <br />WIRING. <br />F. DO NOT INSTALL BOXES BACK-TO-BACK IN WALLS. <br />G. POSITION RECESSED OUTLET BOXES ACCURATELY TO ALLOW <br />FOR SURFACE FINISH THICKNESS. UTILIZE PLASTER RINGS TO <br />ALLOW FOR PLASTER AND/OR ORIGINAL THICKNESS AS <br />REQUIRED. CONFIGURATION OF PLASTER RING IS DEPENDENT <br />ON WIRING DEVICE SPECIFIED ELSEWHERE. <br />H DO NOT USE ROUND BOXES WHERE CONDUIT MUST ENTER BO) <br />THROUGH SIDE OF BOX, WHICH WOULD RESULT IN DIFFICULT <br />AND INSECURE CONNECTIONS WHEN FASTENED WITH A <br />LOCKNUT OR BUSHING ON ROUNDED SURFACES. <br />I. <br />FASTEN ELECTRICAL BOXES FIRMLY AND RIGIDLY TO <br />SUBSTRATES, OR STRUCTURAL SURFACES TO WHICH ATTACHED, <br />OR SOLIDLY EMBED ELECTRICAL BOXES IN CONCRETE OR <br />MASONRY. <br />J. PROPERLY GROUND ELECTRICAL BOXES AND DEMONSTRATE <br />COMPLIANCE WITH REQUIREMENTS UPON COMPLETION OF THE <br />INSTALLATION. <br />11614011 WIRING DEVICES <br />SUBMITTALS <br />A. SUBMIT MANUFACTURER'S DATA AND SHOP DRAWINGS ON <br />ELECTRICAL WIRING DEVICES. <br />MANUFACTURERS <br />A. CATALOG NUMBERS SPECIFIED HEREIN ARE BASED ON <br />HUBBELL <br />B. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE WIRING <br />DEVICES OF ONE OF THE FOLLOWING (FOR EACH TYPE AND <br />RATING OF WIRING DEVICE): <br />ARROW -HART BRYANT ELECTRIC CO. <br />EAGLE ELECTRIC MFG. CO. <br />GENERAL ELECTRIC CO. <br />HUBBELL. INC. <br />LEVITON MFG. 00. <br />PASS AND SEYMOUR, INC. <br />Nestle Waters North America <br />Nestle Waters North America <br />4330 20th Street <br />Zephyrhills, Florida 33542-6703 <br />972.462.3663 <br />Expires <br />FEB 2 8 2015 <br />." <br />4 <br />09.18.2013 <br />ISSUE FOR PERMIT <br />3 <br />09.11.2013 <br />ISSUE FOR BIDS <br />2 <br />09.03.2013 <br />CD REVIEW PACKAGE <br />1 <br />08.16.2013 <br />DD REVIEW PACKAGE <br />NO. <br />DATE <br />REVISIONS/ISSUANCES <br />� PSTEIN <br />Architecture <br />Chicago <br />Interiors <br />New York <br />Engineering <br />Bucharest <br />Construction <br />Warsaw <br />600 W. Fulton Street <br />Chicago, IL 60661-1259 <br />T 312.454.9100 <br />www.epsteinglobal.com <br />PROJECT NUMBER: 12386 <br />PROJECT MANAGER: JK <br />ARCH/ENG: DD <br />SCALE: NOT TO SCALE <br />DRAWN BY: DD <br />CHECKED BY: MS <br />ELECTRICAL <br />SPECIFICATIONS <br />E-003 <br />A. Epstein and Sons International, Inc. All rights reserved. <br />