FABRICATED WIRING DEVICES
<br />A. PROVIDE FACTORY FABRICATED WIRING DEVICES, IN TYPES,
<br />COLORS, AND ELECTRICAL RATINGS FOR APPLICATIONS
<br />INDICATED AND WHICH COMPLY WITH NEMA STANDARDS
<br />PUBUCATION NO. WD1. PROVIDE IVORY COLOR DEVICES AND
<br />WALL PLATES EXCEPT AS OTHERWISE INDICATED: COLOR
<br />SELECTION TO BE VERIFIED BY CONTRACTOR WITH
<br />ARCHITECT/ENGINEER.
<br />B. PROVIDE 20 AMPERE DUPLEX SPECIFICATION GRADE
<br />RECEPTACLES INCORPORATING NYLON THERMOPLASTIC FACE,
<br />REINFORCED THERMOPLASTIC HEAT RESISTANT BASE, ASSURED
<br />GROUNDING FEATURES AND A PLATED STEEL MOUNTING
<br />STRAP. RECEPTACLES SHALL CONFORM TO NEMA STANDARDS,
<br />BE UL LISTED AND MEET NEMA WD1 TESTS. WIRING
<br />TERMINATIONS SHALL BE THE CLAMP TERMINAL SCREW 13ACK
<br />AND SIDE WIRE TYPE. (HUBBELL 5352 SERIES)
<br />C. POWER RECEPTACLES FOR 30 TO 50 AMPERE CIRCUITS SHALL
<br />BE PREMIUM SPECIFICATION GRADE, WITH HEAVY GAUGE
<br />DOUBLE WIPE CONTACTS. TERMINALS SHALL ACCEPT UP TO #4
<br />AWG CONDUCTOR AND SHALL BE OF THREE POINT PRESSURE
<br />CLAMP TYPE DESIGN ON FLUSH MOUNT UNITS AND LAY —IN
<br />WIRING DESIGN ON SURFACE MOUNT DEVICES. VERIFY
<br />RECEPTACLE RATING AND NEMA CONFIGURATION WITH OWNER
<br />PRIOR TO INSTALLATION.
<br />D. GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLES SHALL BE
<br />HEAVY DUTY SPECIFICATION GRADE 'FEED—THRU" TYPE ON A
<br />SINGLE CIRCUIT, INSTALLED IN A 2-3/4' DEEP OUTLET BOX
<br />WITHOUT ADAPTER, GROUNDING TYPE UL—RATED CLASS A.
<br />GROUP 1. RATED 20 AMPERES, 120 VOLT. 60 HZ: WITH SOLID
<br />STATE GROUND FAULT SENSING AND SIGNALING, WITH 5
<br />MIUAMPERS GROUND FAULT TRIP LEVEL, NEMA CONFIGURATION
<br />5-20R. (HUBBELL GF5352)
<br />E. ISOLATED GROUND RECEPTACLES SHALL BE SPECIFICATION
<br />GRADE RATED 20 AMPERES, U.L LISTED 'ISOLATED GROUND'
<br />WITH MOUNTING STRAPS FULLY INSULATED FROM THE
<br />GROUNDING PATH CREATED THROUGH METAL WALL BOXES.
<br />RECEPTACLES SHALL_ BE IDENTIFIED BY ORANGE —COLORED FACE
<br />OR OTHER INDUSTRY STANDARD MARKINGS, AND SHWA BE
<br />GROUNDED ONLY ONLY THROUGH THEIR GROUNDING TERMINAL
<br />SCREWS, WITH NO SELF —GROUNDING FEATURE. (HUBBELL
<br />IG5352)
<br />F. TOGGLE SWITCHES SHWA BE SPECIFICATION GRADE AC QUIET
<br />TYPE, COMPLYING WITH TESTS OF CURRENT FEDERAL
<br />SPECIFICATION W—S-896, NEMA WD-1 AND U.L TESTS 20.
<br />CIRCUIT CONTROL CONTACTS SHALL BE SILVER —CADMIUM OXIDE;
<br />TERMINAL. SCREWS SHALL ACCEPT UP TO SIZE #10 AWG WIRE.
<br />CONTROL SHALL BE SINGLE POLE. DOUBLE POLE, THREE—WAY
<br />OR FOUR—WAY, STANDARD OR ILLUMINATED ROCKER ON
<br />SINGLE —POLE, RATED AT 20 AMPERES, 120/277 VOLTS.
<br />(HUBBELL 1221 SERIES)
<br />G. COMBINATION DEVICES SHALL BE UL LISTED PREMIUM
<br />SPECIFICATION GRADE WITH AC QUIET SWITCHES HAVING
<br />SWITCHES SILVER —CADMIUM OXIDE CONTACTS, RECEPTACLES
<br />WITH BRONZE DOUBLE —WIPE CONTACTS. AND NEON OR
<br />INCANDESCENT PILOT LAMPS. EACH SWITCH ON TWO —SWITCH
<br />UNITS SHALL BE RATED 20A. 120/277V AC; SWITCHES ON
<br />OTHER COMBINATIONS SHALL BE RATED 15A. 120V AC;
<br />RECEPTACLES SHALL BE RATED 20A. 125V, NEON PILOT UGHTS
<br />SHALL BE RATED 1/25W, 125V, INCANDESCENT PILOT LAMP
<br />HOLDERS (CANDELABRA BASE) SHALL BE RATED 75W, 125V.
<br />H. MOMENTARY CONTACT SWITCHES SHALL BE SINGLE POLE
<br />3—POSITION SPRING RETURN TO CENTER 'OFF', RATED 20
<br />AMPERES, 120/277 VOLTS AC.
<br />(PASS & SEYMOUR 1251 SERIES)
<br />WALL PLATES
<br />A. PROVIDE WALL PLATES FOR SINGLE AND COMBINATION WIRING
<br />DEVICES, OF TYPES, SIZES, AND WITH GANGING AND CUTOUTS
<br />AS INDICATED. SELECT PLATES WHICH MATE AND MATCH/WIRING
<br />DEVICES TO WHICH ATTACHED. CONSTRUCT WITH METAL SCREWS
<br />FOR SECURING PLATES TO DEVICES. SCREW HEAD COLOR
<br />SHALL MATCH FINISH OF PLATES. WALL PLATE COLOR SHALL
<br />MATCH WIRING DEVICES.
<br />MULTI —OUTLET SYSTEM
<br />A. SURFACE MOUNTED TWO—PIECE MULTI —OUTLET SYSTEM
<br />CONSISTING OF GALVANIZED STEEL BASE AND COVER WITH
<br />BAKED ENAMEL IVORY FINISH.
<br />B. SYSTEM SHALL BE COMPLETE WITH WALL BOX CONNECTOR AND
<br />ALL NECESSARY FITTINGS AND APPURTENANCES FOR A
<br />COMPLETE INSTALLATION.
<br />C. LENGTHS, FITTINGS AND DEVICES SHALL BE AS SHOWN ON
<br />PAWS AND REQUIRED BY COUNTER AND WALL DIMENSIONS.
<br />D. PROVIDE 20A, 120V, 3—POLE SINGLE RECEPTACLES ON 6 INCH
<br />CETIT[, , WIRED ON TWO ALTERNATE CIRCUITS WITH 4#12 AWG
<br />COPPER CONDUCTORS (2 HOT, 1 NEUTRAL. 1 GROUND) WITH
<br />THHN—THWN INSULATION.
<br />E. THE SYSTEM SHALL BE WIREMOLD PLUGMOLD V-2400 SERIES.
<br />EXECUTION
<br />A. INSTALL WIRING DEVICES AS INDICATED, IN ACCORDANCE WITH
<br />MANUFACTURER'S WRITTEN INSTRUCTIONS, APPUCABLE
<br />REQUIREMENTS OF NEC AND NDWS "STANDARD OF
<br />INSTALLATION' AND IN ACCORDANCE WITH RECOGNIZED
<br />INDUSTRY PRACTICES TO FULFILL PROJECT REQUIREMENTS.
<br />B. COORDINATE WITH OTHER WORK, INCLUDING PAINTING,
<br />ELECTRICAL BOXES AND WIRING WORK, AS NECESSARY TO
<br />INTERFACE INSTALLATION OF WIRING DEVICES WITH OTHER
<br />WORK.
<br />C. INSTALL WIRING DEVICES ONLY IN ELECTRICAL BOXES WHICH
<br />ARE CLEAN; FREE FROM EXCESS BUILDING MATERIALS, DIRT,
<br />AND DEBRIS.
<br />D. TIGHTEN CONNECTORS AND TERMINALS, INCLUDING SCREWS
<br />AND BOLTS, IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'S
<br />PUBUSHED TORQUE TIGHTENING VALUES FOR WIRING DEVICES.
<br />WHERE MANUFACTURER'S TORQUING REQUIREMENTS ARE NOT
<br />INDICATED, TIGHTEN CONNECTORS AND TERMINALS TO COMPLY
<br />WITH TIGHTENING TORQUES SPECIFIED IN U.L STANDARDS 486A
<br />AND 486B. USE PROPERLY SCALED TORQUE INDICATING TOOL
<br />E. PROVIDE GROUNDING CONNECTIONS FOR WIRING DEVICES,
<br />UNLESS OTHERWISE INDICATED. TIGHTEN CONNECTIONS TO
<br />COMPLY WITH TIGHTENING TORQUES SPECIFIED IN UL STANDARD
<br />468A TO ASSURE PERMANENT AND EFFECTIVE GROUNDS.
<br />F. PRIOR TO ENERGIZING CIRCUITRY, TEST WIRING FOR ELECTRICAL
<br />CONTINUITY, FOR SHORT—CIRCUITS. ENSURE PROPER POLARITY
<br />OF CONNECTIONS IS MAINTAINED. SUBSEQUENT TO
<br />ENERGIZATION, TEST WIRING DEVICES TO DEMONSTRATE
<br />COMPLIANCE WITH REQUIREMENTS.
<br />F1616O]l CABINETS AND ENCLOSURES
<br />SUBMITTALS
<br />A PRODUCT DATA: SUBMIT MANUFACTURER'S DATA ON CABINETS
<br />AND ENCLOSURES INCLUDING CATALOG CUTS, SPECIFICATIONS
<br />AND INSTALLATION INSTRUCTIONS FOR EACH TYPE OF SUPPORT,
<br />ANCHOR, SLEEVE AND SEAL
<br />GENERAL
<br />A. CABINETS AND ENCLOSURES NECESSARY FOR HOUSING VARIOUS
<br />ELECTRICAL EQUIPMENT SHALL BE FURNISHED AS SHOWN AND
<br />AS REQUIRED. THESE SHALL INCLUDE ALL CABINETS NOT
<br />SPECIFICALLY SPECIFIED. CABINETS AND ENCLOSURES SHALL BE
<br />CONSTRUCTED IN ACCORDANCE WITH NEMA, U.L. IEC AND ANSI
<br />STANDARDS APPUCABLE FOR THE ENVIRONMENTAL CONDITIONS
<br />OF THEIR INSTALLATION.
<br />ENCLOSURE TYPES
<br />A. TYPE 1 — GENERAL PURPOSE INDOOR: ENCLOSURES ARE
<br />INTENDED FOR USE INDOORS, PRIMARILY TO PREVENT
<br />ACCIDENTAL CONTACT OF PERSONNEL WITH THE ENCLOSED
<br />EQUIPMENT, IN AREA WHERE UNUSUAL SERVICE CONDITIONS DO
<br />NOT EXIST.
<br />B. TYPE 3R — RAINPROOF AND SLEET —(ICE) RESISTANT:
<br />ENCLOSURES ARE INTENDED FOR USE OUTDOORS TO PROTECT
<br />THE ENCLOSED EQUIPMENT AGAINST RAIN AND MEET THE
<br />REQUIREMENTS OF U.L PUBUC•ATION NO. UL 508, APPLYING
<br />TO 'RAINPROOF ENCLOSURES'. THEY SHALL HAVE A CONDUIT
<br />HUB OR EQUIVALENT PROVISION FOR WATERTIGHT CONNECTION
<br />AT THE CONDUIT ENTRANCE WHEN THE CONDUIT ENTERS AT A
<br />LEVEL HIGHER THAN THE LOWEST LIVE PART, PROVISION FOR
<br />LOCKING AND A PROVISION FOR DRAINAGE. THE PROVISION FOR
<br />LOCKING DOES APPLY TO ENCLOSURES FOR PUSHBUTTON
<br />STATIONS.
<br />C. TYPE 4 — WATERTIGHT AND DUSTTTGHT—INDOOR/OUTDOOR:
<br />ENCLOSURES ARE INTENDED FOR USE INDOORS OR OUTDOORS
<br />TO PROTECT THE ENCLOSED EQUIPMENT AGAINST SPLASHING
<br />WATER, SEEPAGE OF WATER, FALUNG OR HOSE DRIPPED
<br />WATER, AND SEVERE EXTERNAL CONDENSATION.
<br />D. TYPE 12 — INDUSTRIAL DUSTTIGHT AND DRIPTIGHIT:
<br />ENCLOSURES AR INTENDED FOR USE INDOORS TO PROTECT
<br />THE ENCLOSED EQUIPMENT AGAINST FIBERS, FLYINGS, LINT,
<br />DUST AND DIRT, AND UGHR SPLASHING, SEEPAGE, DRIPPING
<br />AND EXTERNAL CONDENSATION OF NONCORROSIVE UQUIDS.
<br />ENCLOSURES FOR COMBINATION CONTROLLERS SHALL HAVE
<br />HINGED DOORS WHICH SWING HORIZONTALLY AND REQUIRE A
<br />TOOL TO OPEN.
<br />MANUFACTURERS
<br />A. SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
<br />MANUFACTURES OF CABINETS AND ENCLOSURES SHALL BE AS
<br />FOLLOWS:
<br />CUTLER HAMMER
<br />HOFFMAN
<br />SQUARE D
<br />WIEGMANN
<br />EXECUTION
<br />A. INSTALL CABINETS AND ENCLOSURES AS RECOMMENDED BY
<br />MANUFACTURER.
<br />16190 SUPPORTING DEVICES
<br />SUBMITTALS
<br />A. SUBMIT MANUFACTURER'S DATA AND SHOP DRAWINGS ON
<br />SUPPORTING DEVICES INCLUDING CATALOG CUTS,
<br />SPECIFICATIONS. AND INSTALLATION INSTRUCTIONS FOR EACH
<br />TYPE OF SUPPORT, ANCHOR, SLEEVE AND SEAL
<br />SUPPORTS
<br />A. CLEAVIS HUNGERS: FOR SUPPORTING 2' RIGID METAL CONDUIT;
<br />GALVANIZED STEEL; WITH 1/2' DIAMETER HOLE FOR ROUND
<br />STEEL. ROD; APPROXIMATELY 54 POUNDS PER 100 UNITS.
<br />B. RISER CLAMPS: FOR SUPPORTING 5' RIGID METAL CONDUIT;
<br />BLACK STEEL; WITH 2 BOLTS AND NUTS, AND 4" EARS;
<br />APPROXIMATELY 510 POUNDS PER 100 UNITS.
<br />C. REDUCING COUPUNGS: STEEL ROD REDUCING COUPUNG, 1/2"
<br />X 5/8', BLACK STEEL;; APPROXIMATELY 16 POUNDS PER 100
<br />UNITS.
<br />D. C—CLAMPS: BLACK MALLEABLE IRON: 1/2' ROD SIZE;
<br />APPROXIMATELY 70 POUNDS PER 100 UNITS.
<br />E. I —BEAM CLAMPS: BLACK STEEL, 1 1/2" X 3/16" STOCK; 3/8'
<br />CROSS BOLT, FLANGE WIDTH 2"; APPROXIMATELY 7 POUNDS
<br />PER 100 UNITS.
<br />F. ONE —HOLE CONDUIT STRAPS: FOR SUPPORTING 3/4' RIGID
<br />METAL CONDUIT; GALVANIZED STEEL; 3/4' STRAP WIDTH, AND 2
<br />1/8' BETWEEN CENTER OF SCREW HOLES.
<br />G. TWO —HOLE CONDUIT STRAPS: FOR SUPPORTING 3/4" RIGID
<br />METAL CONDUIT, GALVANIZED STEEL; 3/4' STRAP WIDTH, AND 2
<br />1/8" BETWEEN CENTER OF SCREW HOLES.
<br />H. HEXAGON NUTS: FOR 1/2" ROD SIZE; GALVANIZED STEEL;
<br />APPROXIMATELY 4 POUNDS PER 100 UNITS.
<br />I. ROUND STEEL ROD: BLACK STEEL; 1/2" DIAMETER;
<br />APPROXIMATELY 67 POUNDS PER 100 FEET.
<br />J. OFFSET CONDUIT CLAMPS: FOR SUPPORTING 2" RIGID METAL
<br />CONDUIT; BLACK STEEL; APPROXIMATELY 200 POUNDS PER 100
<br />UNITS.
<br />ANCHORS
<br />A. LEAD EXPANSION ANCHORS: 1/2'; APPROXIMATELY 38 POUNDS
<br />PER 100 UNITS.
<br />B. TOGGLE BOLTS: SPRINGHEAD; 3/16" X 4, APPROXIMATELY 5
<br />POUNDS PER 100 UNITS.
<br />C. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE
<br />ANCHORS OF ONE OF THE FOLLOWING:
<br />ACKERMAN JOHNSON FASTENING SYSTEMS, INC.
<br />ELCEN METAL PRODUCTS COMPANY
<br />IDEAL INDUSTRIES, INC.
<br />RAWPLUG COMPANY, INC.
<br />STAR EXPANSION COMPANY
<br />U.S. EXPANSION BOLT COMPANY
<br />WALL AND FLOOR SEALS
<br />A. PROVIDE FACTORY ASSEMBLED WATERTIGHT WALL AND FLOOR
<br />SEALS, OF TYPES AND SIZES INDICATED; SUITABLE FOR
<br />SEALING AROUND CONDUIT, PIPE, OR TUBING PASSING
<br />THROUGH CONCRETE FLOORS AND WALLS. CONSTRUCT SEALS
<br />WITH STEEL SLEEVES, MALLEABLE IRON BODY, NEOPRENE
<br />SEALING GROMMETS AND RINGS, METAL PRESSURE RINGS,
<br />PRESSURE CLAMPS, AND CAP SCREWS.
<br />U—CHANNEL STRUT SYSTEMS
<br />A. PROVIDE U—CHANNEL STRUT SYSTEM FOR SUPPORTING
<br />ELECTRICAL EQUIPMENT, 12—GUAGE HOT —DIP GALVANIZED
<br />STEEL, OF TYPES AND SIZES INDICATED: CONSTRUCT WITH
<br />9/16' DIAMETER HOLES, 8' O.C. ON TOP SURFACE, WITH
<br />STANDARD GREEN FINISH, AND WITH STANDARD FITTINGS WHICH
<br />MATE AND MATCH WITH U—CHANNEL
<br />B. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE
<br />CHANNEL SYSTEMS OF ONE OF THE FOLLOWING:
<br />B—UNE SYSTEMS, INC.
<br />MIDLAND—ROSS CORPORATION
<br />POWER —STRUT DIVISION: VAN HUFFEL TUBE CORPORATION
<br />UNISTRUT DIVISION; GTE PRODUCTS CORPORATION
<br />PIPE SLEEVES
<br />A. FABRICATE FROM SCHEDULE 40 GALVANIZED STEEL PIPE;
<br />REMOVE BURRS.
<br />B. PROVIDE SLEEVES FOR PIPING WHICH PENETRATE
<br />FOUNDATION WALLS BELOW GRADE, OR EXTERIOR WALLS.
<br />CAULK BETWEEN SLEEVE AND PIPE WITH NON —TOXIC,
<br />UL—CLASSIFIED CAULKING MATERIAL TO ENSURE WATERTIGHT
<br />SEAL
<br />EXECUTION
<br />A. INSTALL HANGERS, ANCHORS, SLEEVES AND SEALS AS
<br />INDICATED, IN ACCORDANCE WITH MANUFACTURER'S WRITTEN
<br />INSTRUCTIONS AND WITH RECOGNIZED INDUSTRY PRACTICES TO
<br />INSURE SUPPORTING DEVICES COMPLY WITH REQUIREMENTS.
<br />B. COORDINATE WITH OTHER ELECTRICAL WORK, INCLUDING
<br />RACEWAY AND WIRING WORK, AS NECESSARY TO INTERFACE
<br />INSTALLATION OF SUPPORTING DEVICES WITH OTHER WORK.
<br />C. INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS TO
<br />SUPPORT PIPING PROPERLY FROM BUILDING STRUCTURE.
<br />ARRANGE FOR GROUPING OF PARALLEL RUNS OF HORIZONTAL
<br />CONDUITS TO BE SUPPORTED TOGETHER ON TRAPEZE TYPE
<br />HANGERS WHERE POSSIBLE.
<br />D. TORQUE SLEEVE NUTS, COMPLYING WITH MANUFACTURER'S
<br />RECOMMENDED VALUES. ENSURE THE SEAUNG GROMMETS
<br />EXPAND TO FORM WATERTIGHT SEAL
<br />E. PROVIDE LATERAL SUPPORT MEMBERS TO PREVENT SWAY
<br />MOVEMENT IN ANY DIRECTION FOR PENDANT OR TRAPEZE
<br />STYLE HANGERS.
<br />16195 I ELECTRICAL IDENTIFICATION
<br />ENGRAVED PLASTIC —LAMINATE NAMEPLATES
<br />A. PROVIDE ENGRAVING STOCK MELAMINE PLASTIC LAMINATE,
<br />COMPLYING WITH FS L—P-387, IN SIZES AND THICKNESS
<br />INDICATED, ENGRAVED WITH ENGRAVER'S STANDARD LETTER
<br />STYLE OF SIZES AND WORDING INDICATED, BLACK FACE AND
<br />WHITE CORE PILES (LETTER COLOR) EXCEPT AS OTHERWISE
<br />INDICATED, PUNCHED FOR MECHANICAL FASTENING EXCEPT
<br />WHERE ADHESIVE MOUNTING IS NECESSARY BECAUSE OF
<br />SUBSTRATE.
<br />B. THICKNESS: 1/16", FOR UNITS UP TO 20 SQUARE INCHES OR
<br />8' LENGTH; 1/8" FOR LARGER UNITS.
<br />C. FASTENERS: SELF —TAPPING STAINLESS STEEL SCREWS, EXCEPT
<br />CONTACT —TYPE PERMANENT ADHESIVE WHERE SCREWS CANNOT
<br />OR SHOULD NOT PENETRATE SUBSTRATE.
<br />LETTERING AND GRAPHICS
<br />A. COORDINATE NAMES, ABBREVIATIONS AND OTHER DESIGNATIONS
<br />USED IN ELECTRICAL IDENTIFICATION WORK, WITH
<br />CORRESPONDING DESIGNATIONS SHOWN, SPECIFIED OR
<br />SCHEDULED. PROVIDE NUMBERS, LETTERING AND WORDING AS
<br />INDICATED OR, IF NOT OTHERWISE INDICATED, AS
<br />RECOMMENDED BY MANUFACTURER OR AS REQUIRED FOR
<br />PROPER IDENTIFICATION AND OPERATION/MAINTENANCE OF
<br />ELECTRICAL SYSTEMS AND EQUIPMENT. COMPLY WITH ANSI
<br />A13.1 PERTAINING TO MINIMUM SIZES FOR LETTERS AND
<br />NUMBERS.
<br />EXECUTION
<br />A. PROVIDE PERMANENT IDENTIFICATION MARKINGS AND
<br />NAMEPLATES FOR WIRING AND EACH ITEM OF ELECTRICAL
<br />APPARATUS AND ASSOCIATED CONTROLLED EQUIPMENT, WITH
<br />THE SAME INSCRIPTIONS AS SHOWN ON THE DRAWING OR AS
<br />DIRECTED, CLEARLY AND NEATLY APPUED.
<br />B. APPLY ENGRAVED PLASTIC LAMINATE NAMEPLATES WITH
<br />NON —CORRODING TYPE SCREW FASTENERS OR RIVETS TO ALL
<br />MOTOR STARTERS, DISCONNECT SWITCHES, RELAYS, REMOTE
<br />CONTROL PANELS, PUSHBUTTON STATIONS, PANELBOARDS,
<br />SWITCHGEAR, TRANSFORMERS, AND OTHER ELECTRICAL
<br />APPARATUS. THE NAMEPLATE SHWA IDENTIFY EQUIPMENT NAME
<br />AND WHERE IT IS FEED FROM.
<br />C. PROVIDE A TYPEWRITTEN DIRECTORY OF CIRCUITS IN
<br />UGHTING AND POWER PANELS.
<br />D. WHENEVER REASONABLY REQUIRED TO ENSURE SAFE AND
<br />EFFICIENT OPERATION AND MAINTENANCE OF ELECTRICAL
<br />SYSTEMS, AND ELECTRICALLY CONNECTED MECHANICAL SYSTEMS
<br />AND GENERAL SYSTEMS AND EQUIPMENT, INCLUDING
<br />PREVENTION OF MISUSE OF ELECTRICAL FACILITIES BY
<br />UNAUTHORIZED PERSONNEL, INSTALL SELF—ADHESIVE PLASTIC
<br />SIGNS OR SIMILAR EQUIVALENT IDENTIFICATION, INSTRUCTION OR
<br />WARNINGS ON SWITCHES, OUTLETS AND OTHER CONTROLS,
<br />DEVICES AND COVERS OF ELECTRICAL ENCLOSURES. WHERE
<br />DETAILED INSTRUCTIONS OR EXPLANATIONS ARE NEEDED,
<br />PROVIDE PLASTICIZED TAGS WITH CLEARLY WRITTEN MESSAGES
<br />ADEQUATE FOR INTENDED PURPOSES.
<br />16440I DISCONNECT SWITCHES
<br />SUBMITTALS
<br />A. SUBMIT MANUFACTURER'S DATA AND SHOP DRAWINGS ON
<br />ELECTRICAL DISCONNECT SWITCHES.
<br />DISCONNECT SWITCHES
<br />A. PROVIDE ALL DISCONNECT SWITCHES INDICATED ON THE
<br />DRAWINGS.
<br />B. SWITCHES SHALL BE NEMA TYPE HD (HEAVY DUTY) AND SHALL
<br />BE UNDERWRITERS LABORATORIES LISTED. PROVIDE RATINGS
<br />AND MODIFICATIONS SHOWN ON THE DRAWINGS.
<br />C. ALL SWITCHES SHALL HAVE: NEMA 1 GENERAL PURPOSE
<br />ENCLOSURES UNLESS OTHERWISE NOTED: METAL NAMEPLATES,
<br />FRONT COVER MOUNTED, THAT CONTAIN A PERMANENT RECORD
<br />ON SWITCH TYPE. CATALOG NUMBER AND HP RATINGS (WITH
<br />BOTH STANDARD AND TIME DEWY FUSES): HANDLE WHOSE
<br />POSITION IS EASILY RECOGNIZABLE AND PADLOCKABLE IN THE
<br />'OFF' POSITION; VISIBLE BLADES; REINFORCED FUSE CUPS;
<br />NONTEASIBLE, POSITIVE, QUICK MAKE —QUICK BREAK
<br />MECHANISMS; AND SWITCH ASSEMBLY PLUS OPERATING HANDLE
<br />AS AN INTEGRAL PART OF THE ENCLOSURE AREA,
<br />D. ALL SWITCHES SHALL BE UNDERWRITERS LABORATORIES INC.,
<br />LISTED, HP RATED, MEET FEDERAL SPECIFICATION WS-865C,
<br />AND NEMA SPECIFICATIONS KS1-1975. SWITCHES SHALL HAVE
<br />DEFEATABLE DOOR INTERLOCKS THAT PREVENT THE DOOR FROM
<br />OPENING WHEN THE OPERATING HANDLE IS IN THE 'ON'
<br />POSITION. HEAVY DUTY SWITCHES SHALL HAVE UNE TERMINAL
<br />SHIELDS.
<br />E. SWITCHES SHALL BE HORSEPOWER RATED FOR AC AND/OR DC
<br />AS INDICATED BY THE PLANS. ALL FUSIBLE SWITCHES RATED
<br />100 THRU 600 AMPERES AT 240 VOLTS AND 30 THRU 600
<br />AMPERES AT 600 VOLTS SHALL HAVE A UL USTTED METHOD OF
<br />FIELD CONVERSION FROM STANDARD CLASS H FUSE SPACING
<br />TO CLASS J FUSE SPACING. THE SWITCH ALSO MUST ACCEPT
<br />CLASS R FUSES AND HAVE PROVISIONS FOR FIELD
<br />INSTALLATION OF A UL USTED REJECTION FEATURE TO REJECT
<br />ALL FUSES EXCEPT CLASS R. THE UL LISTED SHORT CIRCUIT
<br />RATING OF THE SWITCHES SHALL BE 200,000 RMS
<br />SYMMETRICAL AMPERES WHEN CLASS R OR CLASS J FUSES
<br />ARE USED WITH THE APPROPRIATE REJECTION SCHEME. 800
<br />AND 1200 AMPERE SWITCHES SHALL HAVE PROVISIONS FOR
<br />CLASS L FUSE AND SHALL HAVE A UL LISTED SHORT
<br />CIRCUIT RATING OF 200.000 RMS SYMMETRICAL AMPERES.
<br />F. THE USE OF TOGGLE TYPE MOTOR RATED DISCONNECT
<br />SWITCHES ARE NOT ACCEPTABLE.
<br />MANUFACTURERS
<br />A. SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
<br />MANUFACTURERS OF DISCONNECT SWITCHES SHALL BE AS
<br />FOLLOWS:
<br />CUTLER HAMMER
<br />SQUARE D
<br />SIEMENS
<br />EXECUTION
<br />A. INSTALL DISCONNECT SWITCHES AND PROVIDE SUPPORTS.
<br />B. TERMINATE RACEWAYS AND CONDUCTORS FOR DISCONNECT
<br />SWITCHES.
<br />16450I GROUNDING
<br />MANUFACTURERS
<br />A. SUBJECT TO COMPLIANCE WITH REQUIREMENTS,
<br />MANUFACTURERS OF GROUNDING EQUIPMENT SHALL BE AS
<br />FOLLOWS:
<br />BURNDY CORPORATION
<br />CADWELD DIV.; ERICO PRODUCTS, INC.
<br />CROUSE—HINDS DIV.; COOPER INDUSTRIES
<br />IDEAL INDUSTRIES, INC.
<br />OZ GEDNEY DIV, GENERAL SIGNAL CORP.
<br />THOMAS AND BETTS CORPORATION
<br />MATERIALS
<br />A. PROVIDE A GROUNDING SYSTEM THAT INCLUDES ALL
<br />CONNECTIONS AND TESTING OF GROUND RODS, GROUND
<br />CABLES, GROUND BUSSES, CONDUITS, FITTINGS, ANCHORS,
<br />SUPPORTS, CADWELD MATERIAL AND EQUIPMENT, AND OTHER
<br />MATERIALS REQUIRED FOR A COMPLETE INSTALLATION.
<br />B. ALL COPPER TO COPPER AND COPPER TO STEEL CONNECTIONS
<br />OF J6 AWG AND LARGER SHALL BE MADE WITH CADWELD
<br />PROCESS EXCEPT AS NOTED IN ITEM C. BELOW.
<br />C. PROVIDE BURNDY CORP., TYPE NE, THOMAS do BETTS CO., INC.
<br />CATALOG NO. 3951, OR APPROVED EQUAL, GROUND FITTINGS
<br />FOR BONDING GROUND CABLE TO ENCASING METAL CONDUIT.
<br />1. BONDING JUMPER: COPPER BRAIDED TAPE, CONSTRUCTED
<br />OF 30—GAUGE BARE COPPER WIRES AND PROPERLY SIZED
<br />FOR INDICATED APPUCATIONS.
<br />2. FLEXIBLE JUMPER STRAP: FLEXIBLE FLAT CONDUCTOR, 480
<br />STRANDS OF 30—GAUGE BARE COPPER WIRE; 3/4' WIDE, 9
<br />1/2' LONG; 48,250 CM. SELECT BRAID WITH HOLES SIZED
<br />FOR 3/8" DIAMETER BOLTS, AND PROTECT BRAID WITH
<br />COPPER BOLT HOLE ENDS.
<br />D. PROVIDE ELECTRICAL BONDING CONNECTORS, TERMINALS, LUGS
<br />AND CLAMPS AS RECOMMENDED BY MANUFACTURERS FOR
<br />INDICATED APPLICATIONS.
<br />E. GROUNDING BUSHINGS SHALL BE MALLEABLE IRON, THREADED,
<br />WITH INSULATED LINER AND SOLDERLESS LUG.
<br />GROUNDING CONNECTIONS
<br />A. CADWELD CONNECTIONS TO BE USED OUTDOORS SHALL BE
<br />SUITABLE FOR EXPOSURE TO THE ELEMENTS OR DIRECT BURIAL
<br />ELEMENTS OR DIRECT BURIAL WITHOUT DEGRADATION OVER THE
<br />UFETIME OF THE GROUNDING SYSTEM.
<br />B. CADWELD CONNECTIONS TO BE MADE IN FINISHED BUILDINGS
<br />OR CONFINED SPACES SHALL USE THE LOW SMOKE, LOW
<br />EMISSION CADWELD EXOLON PROCESS WHICH IS
<br />METALLURGICALLY EQUALLY TO THE ABOVE CONNECTION.
<br />C• THE INSTALLER IS PROHIBITED FROM USING A MOLD FROM ONE
<br />MANUFACTURER'S WELDING MIXTURE. THIS PRACTICE CAN
<br />PROVIDE AN UNACCEPTABLE PRODUCT.
<br />SYSTEM GROUNDING
<br />A. WHERE GROUND CONDUCTORS ARE RUN IN CONDUIT OR OTHER
<br />RACEWAY, THE GROUND CONDUCTOR SHALL BE BONDED AT
<br />EACH END.
<br />B. FLEXIBLE CONDUIT CONNECTIONS TO ELECTRICAL EQUIPMENT
<br />SHALL HAVE A THWN/THHN GROUND CONDUCTOR IN THE
<br />FLEXIBLE CONDUIT WITH THE CIRCUIT CONDUCTORS. GROUND
<br />CONDUCTORS SHALL BE TERMINATED AT EACH END IN
<br />ACCORDANCE WITH CODE REQUIREMENTS.
<br />COMMUNICATION GROUNDING
<br />A. PROVIDE A NO. 4 AWG COPPER CONDUCTOR WITH TYPE THW
<br />INSULATION TO GROUND BUS IN EACH TELEPHONE EQUIPMENT
<br />ROOM. LEAVE 12' PIGTAIL AT TELEPHONE BOARD.
<br />INSTALLATION
<br />A. THE SYSTEM GROUND SHALL INCLUDE THE INCOMING SERVICE
<br />AND ALL TRANSFORMER NEUTRALS.
<br />THE EQUIPMENT GROUND SHALL INCLUDE ALL SWITCHGEAR,
<br />TRANSFORMERS, CABLE SHEATHS, CABLE RACKS, CONDUIT
<br />SYSTEM, MOTOR FRAMES, AND EQUIPMENT ENCLOSURES.
<br />B. ALL GROUND CONDUCTORS SHALL BE IN CONDUIT EXCEPT
<br />WHERE OTHERWISE INDICATED ON THE DRAWINGS.
<br />C. THE CONDUIT SYSTEM OR SPRINKLER SYSTEM PIPING SHALL IN
<br />NO CASE BE USED FOR ESTABUSHING A TRANSFORMER
<br />NEUTRAL GROUNDING ELECTRODE.
<br />D. MAKE ALL ELECTRICAL POWER GROUNDING AND CONTROL
<br />CONNECTIONS TO EQUIPMENT FURNISHED BY OTHER TRADES
<br />AND FURNISH WIRING, CONDUIT, OUTLET BOXES, DISCONNECT
<br />SWITCHES, ETC., AS REQUIRED FOR SAME.
<br />E. INSTALL GROUND CONDUCTORS CONTINUOUS BETWEEN
<br />CONNECTIONS. SPUCES WILL NOT BE ALLOWED EXCEPT
<br />INDICATED ON THE DRAWINGS. WHERE GROUND CABLES PASS
<br />THROUGH FLOOR SLABS, BUILDING WALLS, ETC., AND ARE NOT
<br />IN METALUC ENCLOSURES, PROVIDE THE SLEEVES OF
<br />APPROVED NONMETALUC MATERIAL
<br />F. USE RIGID METAL CONDUIT AND ELECTRICAL METALLIC TUBING
<br />AS EQUIPMENT GROUNDING CONDUCTORS UNLESS NOTED
<br />OTHERWISE. MAKE—UP COUPUNGS WRENCH TIGHT. INSTALL
<br />GROUNDING CONDUCTOR IN NONMETALLIC RACEWAYS AND
<br />UNDERFLOOR DUCTS.
<br />G. INSTALL EQUIPMENT GROUNDING CONDUCTORS IN ALL
<br />NONMETALLIC RACEWAYS.
<br />H. GROUND INTERIOR UGHTING FIXTURES WITH GROUNDING
<br />CONDUCTOR TO RIGID METAL RACEWAYS SERVING THEM.
<br />FLEXIBLE METAL CONDUIT IN LENGTHS LESS THAN 6'-0"
<br />INCHES MAY BE USED AS GROUNDING CONDUCTORS WHEN
<br />TERMINATED WITH APPROVED FITTINGS ON CIRCUITS OF 20
<br />AMPERES OR LESS.
<br />I. WHERE CONNECTIONS ARE MADE TO MOTORS OR EQUIPMENT
<br />WITH FLEXIBLE METAL CONDUIT, GROUNDING CONDUCTOR SHALL
<br />BE STRANDING COPPER CONDUCTOR WITHIN THE CONDUIT,
<br />BONDED TO THE EQUIPMENT AND TO THE RIGID METAL
<br />RACEWAY SYSTEM.
<br />J. AT EACH CONVENIENCE OUTLET, INSTALL A GROUNDING CUP
<br />ATTACHED TO THE OUTLET BOX AND LEAVE A SUFFICIENT
<br />LENGTH OF J12 WIRE WITH GREEN COLORED INSULATION TO
<br />CONNECT TO THE GROUNDING TERMINAL OF THE RECEPTACLE.
<br />GROUNDING CUP SHALL BE EQUAL TO STEEL CITY TYPE G.
<br />F164-6011 TRANSFORMERS
<br />SUBMITTALS
<br />A. SUBMIT SHOP DRAWINGS INDICATING PRODUCT DATA INCLUDING
<br />RATED KVA, FREQUENCY, PRIMARY AND SECONDARY VOLTAGES,
<br />PERCENT TAPS, POLARITY, IMPEDANCE AND CERTIFICATION OF
<br />TRANSFORMER PERFORMANCE EFFICIENCY AT INDICATED LOADS,
<br />PERCENTAGE REGULATION AT 10OX AND 80% POWER FACTOR,
<br />NO—LOAD AND FULL —LOAD LOSSES IN WATTS, X IMPEDANCE AT
<br />75 DEG. CELSIUS,
<br />HOT —SPOT AND AVERAGE TEMPERATURE RISE ABOVE 40 DEG.
<br />CELSIUS AMBIENT TEMPERATURE, SOUND LEVEL IN DECIBELS,
<br />AND STANDARD PUBUSHED DATA.
<br />IWIn:111IY_I0119:1:1
<br />CUTLER HAMMER
<br />SIEMENS, INC.
<br />SORGEL ELECTRICAL DIV.; SQUARE D CO.
<br />HEAVY —DUN ELECTRIC DIV.; GENERAL SIGNAL CORP.
<br />DRY —TYPE TRANSFORMERS (45 KVA OR LESS
<br />A. PROVIDE FACTORY —ASSEMBLED, GENERAL PURPOSE,
<br />AIR—COOLED, DRY —TYPE DISTRIBUTION TRANSFORMERS WHERE
<br />SHOWN; OF SIZES, CHARACTERISTICS AND RATED CAPACITIES
<br />INDICATED; SINGLE—PHASE; 60—HERTZ, 30 KV BIL, 4.OX
<br />IMPEDANCE, WITH 480—VOLTS PRIMARY AND 240/120 VOLTS
<br />SECONDARY OR THREE—PHASE: 60—HERTZ, 30 KV BIL, 4.OX
<br />IMPEDANCE WITH 480—VOLTS DELTA CONNECTED PRIMARY AND
<br />208/120 3 PHASE, 4 WIRE SECONDARY WYE CONNECTED, WITH
<br />GROUNDED NEUTRAL PROVIDE PRIMARY WINDING WITH 2 TAPS;
<br />BOTH 5X INCREMENTS BELOW FULL —RATED VOLTAGE FOR
<br />DE —ENERGIZED TAP —CHANGING OPERATION. INSULATE WITH
<br />CLASS H INSULATION BASED ON 150 DEG. CELSIUS RISE
<br />ABOVE 40 DEG. AMBIENT. RATE TRANSFORMER FOR
<br />CONTINUOUS OPERATION AT RATED KVA. UMIT TRANSFORMER
<br />SURFACE TEMPERATURE RISE TO MAXIMUM OF 65 DEG.
<br />CELSIUS PROVIDE TERMINAL ENCLOSURE, WITH COVER, TO
<br />ACCOMMODATE PRIMARY AND SECONDARY COIL WIRING
<br />CONNECTIONS AND ELECTRICAL SUPPLY RACEWAY TERMINAL
<br />CONNECTOR. EQUIP TERMINAL LEADS WITH CONNECTORS
<br />INSTALLED. LIMIT TERMINAL COMPARTMENT TEMPERATURE TO 75
<br />DEG. CELSIUS WHEN TRANSFORMER IS OPERATING
<br />CONTINUOUSLY AT RATED LOAD WITH AMBIENT TEMPERATURE OF
<br />40 DEG. CELSIUS PROVIDE WIRING CONNECTORS SUITABLE FOR
<br />COPPER OR ALUMINUM WIRING. CUSHION —MOUNT
<br />TRANSFORMERS WITH EXTERNAL VIBRATION ISOLATION
<br />SUPPORTS; SOUND —LEVEL RATINGS NOT TO EXCEED 45 DB AS
<br />DETERMINED IN ACCORDANCE WITH ANSI/NEMA STANDARDS.
<br />ELECTRICALLY GROUND CORE AND COILS TO TRANSFORMER
<br />ENCLOSURE BY MEANS OF FLEXIBLE METAL GROUNDING STRAP.
<br />PROVIDE TRANSFORMERS WITH FULL —ENCLOSED SHEET STEEL
<br />ENCLOSURES. APPLY MANUFACTURER'S STANDARD GRAY INDOOR
<br />ENAMEL OVER CLEANED AND PHOSPHATED STEEL ENCLOSURE.
<br />PROVIDE TRANSFORMERS SUITABLE FOR WALL MOUNTING.
<br />B. TRANSFORMERS SERVING NON—UNEAR LOADS SHALL HAVE A
<br />NEUTRAL CAPABLE OF CARRYING 200 PERCENT OF THE UNE
<br />CURRENT CONTINUOUSLY.
<br />INSTALLATION
<br />A. INSTALL TRANSFORMERS AS INDICATED, COMPLYING WITH
<br />MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLICABLE
<br />REQUIREMENTS OF NEC, NESC, NEMA. ANSI AND IEEE
<br />STANDARDS, AND IN ACCORDANCE WITH RECOGNIZED
<br />INDUSTRY PRACTICES TO ENSURE THAT PRODUCTS FULFILL
<br />REQUIREMENTS.
<br />B. COORDINATE TRANSFORMER INSTALLATION WORK WITH
<br />ELECTRICAL RACEWAY AND WIRE/CABLE WORK, AS
<br />NECESSARY FOR PROPER INTERFACE.
<br />C. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS, INCLUDING
<br />SCREWS AND BOLTS, IN ACCORDANCE WITH EQUIPMENT
<br />MANUFACTURER'S PUBUSHED TORQUE TIGHTENING VALUES FOR
<br />EQUIPMENT CONNECTORS. WHERE MANUFACTURER'S TORQUING
<br />REQUIREMENTS ARE NOT INDICATED, TIGHTEN CONNECTORS AND
<br />TERMINALS TO COMPLY WITH TIGHTENING TORQUES SPECIFIED
<br />IN UL STANDARD 486A AND 486B.
<br />D. INSTALL WALL MOUNTED TRANSFORMERS ON PREFABRICATED
<br />BRACKETS DESIGNED FOR THAT PURPOSE.
<br />E. PROVIDE 4 INCH CONCRETE PAD WITH BEVELED EDGE FOR
<br />FLOOR MOUNTED TRANSFORMERS.
<br />GROUNDING
<br />A. PROVIDE EQUIPMENT GROUNDING CONNECTIONS FOR POWER
<br />/DISTRIBUTION TRANSFORMERS AS INDICATED. TIGHTEN
<br />CONNECTIONS TO COMPLY WITH TIGHTENING TORQUES
<br />SPECIFIED IN UL STANDARD 486A TO ASSURE PERMANENT AND
<br />EFFECTIVE GROUNDING.
<br />B. TRANSFORMER SECONDARY SHALL BE GROUNDED TO BUILDING
<br />STEEL OR GROUND ELECTRODE SYSTEM.
<br />TESTING
<br />A. RATIO TESTS AT THE RATED VOLTAGE CONNECTION AND AT ALL
<br />TAP CONNECTIONS.
<br />B. POLARITY AND PHASE —RELATION TESTS ON THE RATED VOLTAGE
<br />CONNECTION.
<br />C. APPUED POTENTIAL TESTS.
<br />D. INDUCED POTENTIAL TESTS.
<br />E. NO—LOAD AND EXCITATION CURRENT AT RATED VOLTAGE ON
<br />THE RATED VOLTAGE CONNECTION. ON RATINGS ABOVE 500
<br />KVA, THE FOLLOWING TEST IN ITEM 'F' SHALL ALSO BE
<br />PERFORMED ON EACH TRANSFORMER.
<br />F. RESISTANCE MEASUREMENTS OF ALL WINDINGS AT THE RATED
<br />VOLTAGE CONNECTION OF EACH UNIT AND AT THE TAP
<br />EXTREMES OF THE FIRST UNIT MADE OF A NEW DESIGN.
<br />G. PRIOR TO ENERGIZATION OF TRANSFORMERS, CHECK ALL
<br />ACCESSIBLE CONNECTIONS FOR COMPLIANCE WITH
<br />MANUFACTURER'S TORQUE TIGHTENING SPECIFICATIONS.
<br />H. PRIOR TO ENERGIZATION, CHECK CIRCUITRY FOR ELECTRICAL
<br />CONTINUITY, AND FOR SHORT—CIRCUITS.
<br />I. UPON COMPLETION OF INSTALLATION OF TRANSFORMERS,
<br />ENERGIZE PRIMARY CIRCUITRY AT RATED VOLTAGE AND
<br />FREQUENCY FROM NORMAL POWER SOURCE, AND TEST
<br />TRANSFORMERS, INCLUDING, BUT NOT UMITED TO, AUDIBLE
<br />SOUND LEVELS, TO DEMONSTRATE CAPABIUTY AND COMPUANCE
<br />WITH REQUIREMENTS. WHERE POSSIBLE, CORRECT
<br />MALFUNCTIONING UNITS AT SITE, THEN RETEST TO
<br />DEMONSTRATE COMPUANCE; OTHERWISE, REMOVE AND
<br />REPLACE WITH NEW UNITS OR COMPONENTS, AND PROCEED
<br />WITH RETESTING.
<br />16470 SWITCHBOARDS AND PANELBOARDS
<br />SUBMITTALS
<br />A. SUBMIT MANUFACTURER'S DATA AND SHOP DRAWINGS ON
<br />SWITCHBOARDS, PANELBOARDS AND ENCLOSURES INCLUDING
<br />VOLTAGES. CURRENT RATINGS, INTERRUPTING RATINGS AND
<br />ELECTRICAL CHARACTERISTICS. IN ADDITION SUBMIT FULL POWER
<br />STUDIES INCLUDING BUT NOT UMITED TO ARC FLASH STUDIES,
<br />COORDINATION STUDIES AND SHORT CIRCUIT STUDIES.
<br />MANUFACTURERS
<br />A. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE
<br />PANELBOARD PRODUCTS OF ONE OF THE FOLLOWING (FOR
<br />EACH TYPE AND RATING OF PANELBOARD AND ENCLOSURE):
<br />CUTLER HAMMER
<br />SIEMENS, INC.
<br />SQUARE D COMPANY
<br />MEP / FP Engineer
<br />EPSTEIN
<br />600 West Fulton
<br />Chicago, IL 60661
<br />312.454.9100
<br />Design Architect
<br />EPSTEIN
<br />600 West Fulton
<br />Chicago, IL 60661
<br />312.454.9100
<br />Nestle Waters North America
<br />Nestle Waters North America
<br />4330 20th Street
<br />Zephyrhills, Florida 33542-6703
<br />972.462.3663
<br />F7jtIe1\
<br />ers
<br />Expires
<br />FEB ;� 0 Z015
<br />�•
<br />�G`�,� G E N
<br />7520
<br />• STATE OF
<br />0'• ,
<br />0 R 4 Q Q �`�k'
<br />1-� r- 109-
<br />4
<br />09.18.2013
<br />ISSUE FOR PERMIT
<br />3
<br />09.11.2013
<br />ISSUE FOR BIDS
<br />2
<br />09.03.2013
<br />CD REVIEW PACKAGE
<br />1
<br />08.16.2013
<br />DD REVIEW PACKAGE
<br />NO.
<br />DATE
<br />REVISIONS/ISSUANCES
<br />�PSTEIN
<br />Architecture
<br />Chicago
<br />Interiors
<br />New York
<br />Engineering
<br />Bucharest
<br />Construction
<br />Warsaw
<br />600 W. Fulton Street
<br />Chicago, IL 60661-1259
<br />T 312.454.9100
<br />www.epsteinglobal.com
<br />PROJECT NUMBER: 12386
<br />PROJECT MANAGER: JK
<br />ARCH/ENG: DD
<br />SCALE: NOT TO SCALE
<br />DRAWN BY: DD
<br />CHECKED BY: MS
<br />ELECTRICAL
<br />SPECIFICATIONS