FABRICATED WIRING DEVICES <br />A. PROVIDE FACTORY FABRICATED WIRING DEVICES, IN TYPES, <br />COLORS, AND ELECTRICAL RATINGS FOR APPLICATIONS <br />INDICATED AND WHICH COMPLY WITH NEMA STANDARDS <br />PUBUCATION NO. WD1. PROVIDE IVORY COLOR DEVICES AND <br />WALL PLATES EXCEPT AS OTHERWISE INDICATED: COLOR <br />SELECTION TO BE VERIFIED BY CONTRACTOR WITH <br />ARCHITECT/ENGINEER. <br />B. PROVIDE 20 AMPERE DUPLEX SPECIFICATION GRADE <br />RECEPTACLES INCORPORATING NYLON THERMOPLASTIC FACE, <br />REINFORCED THERMOPLASTIC HEAT RESISTANT BASE, ASSURED <br />GROUNDING FEATURES AND A PLATED STEEL MOUNTING <br />STRAP. RECEPTACLES SHALL CONFORM TO NEMA STANDARDS, <br />BE UL LISTED AND MEET NEMA WD1 TESTS. WIRING <br />TERMINATIONS SHALL BE THE CLAMP TERMINAL SCREW 13ACK <br />AND SIDE WIRE TYPE. (HUBBELL 5352 SERIES) <br />C. POWER RECEPTACLES FOR 30 TO 50 AMPERE CIRCUITS SHALL <br />BE PREMIUM SPECIFICATION GRADE, WITH HEAVY GAUGE <br />DOUBLE WIPE CONTACTS. TERMINALS SHALL ACCEPT UP TO #4 <br />AWG CONDUCTOR AND SHALL BE OF THREE POINT PRESSURE <br />CLAMP TYPE DESIGN ON FLUSH MOUNT UNITS AND LAY —IN <br />WIRING DESIGN ON SURFACE MOUNT DEVICES. VERIFY <br />RECEPTACLE RATING AND NEMA CONFIGURATION WITH OWNER <br />PRIOR TO INSTALLATION. <br />D. GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLES SHALL BE <br />HEAVY DUTY SPECIFICATION GRADE 'FEED—THRU" TYPE ON A <br />SINGLE CIRCUIT, INSTALLED IN A 2-3/4' DEEP OUTLET BOX <br />WITHOUT ADAPTER, GROUNDING TYPE UL—RATED CLASS A. <br />GROUP 1. RATED 20 AMPERES, 120 VOLT. 60 HZ: WITH SOLID <br />STATE GROUND FAULT SENSING AND SIGNALING, WITH 5 <br />MIUAMPERS GROUND FAULT TRIP LEVEL, NEMA CONFIGURATION <br />5-20R. (HUBBELL GF5352) <br />E. ISOLATED GROUND RECEPTACLES SHALL BE SPECIFICATION <br />GRADE RATED 20 AMPERES, U.L LISTED 'ISOLATED GROUND' <br />WITH MOUNTING STRAPS FULLY INSULATED FROM THE <br />GROUNDING PATH CREATED THROUGH METAL WALL BOXES. <br />RECEPTACLES SHALL_ BE IDENTIFIED BY ORANGE —COLORED FACE <br />OR OTHER INDUSTRY STANDARD MARKINGS, AND SHWA BE <br />GROUNDED ONLY ONLY THROUGH THEIR GROUNDING TERMINAL <br />SCREWS, WITH NO SELF —GROUNDING FEATURE. (HUBBELL <br />IG5352) <br />F. TOGGLE SWITCHES SHWA BE SPECIFICATION GRADE AC QUIET <br />TYPE, COMPLYING WITH TESTS OF CURRENT FEDERAL <br />SPECIFICATION W—S-896, NEMA WD-1 AND U.L TESTS 20. <br />CIRCUIT CONTROL CONTACTS SHALL BE SILVER —CADMIUM OXIDE; <br />TERMINAL. SCREWS SHALL ACCEPT UP TO SIZE #10 AWG WIRE. <br />CONTROL SHALL BE SINGLE POLE. DOUBLE POLE, THREE—WAY <br />OR FOUR—WAY, STANDARD OR ILLUMINATED ROCKER ON <br />SINGLE —POLE, RATED AT 20 AMPERES, 120/277 VOLTS. <br />(HUBBELL 1221 SERIES) <br />G. COMBINATION DEVICES SHALL BE UL LISTED PREMIUM <br />SPECIFICATION GRADE WITH AC QUIET SWITCHES HAVING <br />SWITCHES SILVER —CADMIUM OXIDE CONTACTS, RECEPTACLES <br />WITH BRONZE DOUBLE —WIPE CONTACTS. AND NEON OR <br />INCANDESCENT PILOT LAMPS. EACH SWITCH ON TWO —SWITCH <br />UNITS SHALL BE RATED 20A. 120/277V AC; SWITCHES ON <br />OTHER COMBINATIONS SHALL BE RATED 15A. 120V AC; <br />RECEPTACLES SHALL BE RATED 20A. 125V, NEON PILOT UGHTS <br />SHALL BE RATED 1/25W, 125V, INCANDESCENT PILOT LAMP <br />HOLDERS (CANDELABRA BASE) SHALL BE RATED 75W, 125V. <br />H. MOMENTARY CONTACT SWITCHES SHALL BE SINGLE POLE <br />3—POSITION SPRING RETURN TO CENTER 'OFF', RATED 20 <br />AMPERES, 120/277 VOLTS AC. <br />(PASS & SEYMOUR 1251 SERIES) <br />WALL PLATES <br />A. PROVIDE WALL PLATES FOR SINGLE AND COMBINATION WIRING <br />DEVICES, OF TYPES, SIZES, AND WITH GANGING AND CUTOUTS <br />AS INDICATED. SELECT PLATES WHICH MATE AND MATCH/WIRING <br />DEVICES TO WHICH ATTACHED. CONSTRUCT WITH METAL SCREWS <br />FOR SECURING PLATES TO DEVICES. SCREW HEAD COLOR <br />SHALL MATCH FINISH OF PLATES. WALL PLATE COLOR SHALL <br />MATCH WIRING DEVICES. <br />MULTI —OUTLET SYSTEM <br />A. SURFACE MOUNTED TWO—PIECE MULTI —OUTLET SYSTEM <br />CONSISTING OF GALVANIZED STEEL BASE AND COVER WITH <br />BAKED ENAMEL IVORY FINISH. <br />B. SYSTEM SHALL BE COMPLETE WITH WALL BOX CONNECTOR AND <br />ALL NECESSARY FITTINGS AND APPURTENANCES FOR A <br />COMPLETE INSTALLATION. <br />C. LENGTHS, FITTINGS AND DEVICES SHALL BE AS SHOWN ON <br />PAWS AND REQUIRED BY COUNTER AND WALL DIMENSIONS. <br />D. PROVIDE 20A, 120V, 3—POLE SINGLE RECEPTACLES ON 6 INCH <br />CETIT[, , WIRED ON TWO ALTERNATE CIRCUITS WITH 4#12 AWG <br />COPPER CONDUCTORS (2 HOT, 1 NEUTRAL. 1 GROUND) WITH <br />THHN—THWN INSULATION. <br />E. THE SYSTEM SHALL BE WIREMOLD PLUGMOLD V-2400 SERIES. <br />EXECUTION <br />A. INSTALL WIRING DEVICES AS INDICATED, IN ACCORDANCE WITH <br />MANUFACTURER'S WRITTEN INSTRUCTIONS, APPUCABLE <br />REQUIREMENTS OF NEC AND NDWS "STANDARD OF <br />INSTALLATION' AND IN ACCORDANCE WITH RECOGNIZED <br />INDUSTRY PRACTICES TO FULFILL PROJECT REQUIREMENTS. <br />B. COORDINATE WITH OTHER WORK, INCLUDING PAINTING, <br />ELECTRICAL BOXES AND WIRING WORK, AS NECESSARY TO <br />INTERFACE INSTALLATION OF WIRING DEVICES WITH OTHER <br />WORK. <br />C. INSTALL WIRING DEVICES ONLY IN ELECTRICAL BOXES WHICH <br />ARE CLEAN; FREE FROM EXCESS BUILDING MATERIALS, DIRT, <br />AND DEBRIS. <br />D. TIGHTEN CONNECTORS AND TERMINALS, INCLUDING SCREWS <br />AND BOLTS, IN ACCORDANCE WITH EQUIPMENT MANUFACTURER'S <br />PUBUSHED TORQUE TIGHTENING VALUES FOR WIRING DEVICES. <br />WHERE MANUFACTURER'S TORQUING REQUIREMENTS ARE NOT <br />INDICATED, TIGHTEN CONNECTORS AND TERMINALS TO COMPLY <br />WITH TIGHTENING TORQUES SPECIFIED IN U.L STANDARDS 486A <br />AND 486B. USE PROPERLY SCALED TORQUE INDICATING TOOL <br />E. PROVIDE GROUNDING CONNECTIONS FOR WIRING DEVICES, <br />UNLESS OTHERWISE INDICATED. TIGHTEN CONNECTIONS TO <br />COMPLY WITH TIGHTENING TORQUES SPECIFIED IN UL STANDARD <br />468A TO ASSURE PERMANENT AND EFFECTIVE GROUNDS. <br />F. PRIOR TO ENERGIZING CIRCUITRY, TEST WIRING FOR ELECTRICAL <br />CONTINUITY, FOR SHORT—CIRCUITS. ENSURE PROPER POLARITY <br />OF CONNECTIONS IS MAINTAINED. SUBSEQUENT TO <br />ENERGIZATION, TEST WIRING DEVICES TO DEMONSTRATE <br />COMPLIANCE WITH REQUIREMENTS. <br />F1616O]l CABINETS AND ENCLOSURES <br />SUBMITTALS <br />A PRODUCT DATA: SUBMIT MANUFACTURER'S DATA ON CABINETS <br />AND ENCLOSURES INCLUDING CATALOG CUTS, SPECIFICATIONS <br />AND INSTALLATION INSTRUCTIONS FOR EACH TYPE OF SUPPORT, <br />ANCHOR, SLEEVE AND SEAL <br />GENERAL <br />A. CABINETS AND ENCLOSURES NECESSARY FOR HOUSING VARIOUS <br />ELECTRICAL EQUIPMENT SHALL BE FURNISHED AS SHOWN AND <br />AS REQUIRED. THESE SHALL INCLUDE ALL CABINETS NOT <br />SPECIFICALLY SPECIFIED. CABINETS AND ENCLOSURES SHALL BE <br />CONSTRUCTED IN ACCORDANCE WITH NEMA, U.L. IEC AND ANSI <br />STANDARDS APPUCABLE FOR THE ENVIRONMENTAL CONDITIONS <br />OF THEIR INSTALLATION. <br />ENCLOSURE TYPES <br />A. TYPE 1 — GENERAL PURPOSE INDOOR: ENCLOSURES ARE <br />INTENDED FOR USE INDOORS, PRIMARILY TO PREVENT <br />ACCIDENTAL CONTACT OF PERSONNEL WITH THE ENCLOSED <br />EQUIPMENT, IN AREA WHERE UNUSUAL SERVICE CONDITIONS DO <br />NOT EXIST. <br />B. TYPE 3R — RAINPROOF AND SLEET —(ICE) RESISTANT: <br />ENCLOSURES ARE INTENDED FOR USE OUTDOORS TO PROTECT <br />THE ENCLOSED EQUIPMENT AGAINST RAIN AND MEET THE <br />REQUIREMENTS OF U.L PUBUC•ATION NO. UL 508, APPLYING <br />TO 'RAINPROOF ENCLOSURES'. THEY SHALL HAVE A CONDUIT <br />HUB OR EQUIVALENT PROVISION FOR WATERTIGHT CONNECTION <br />AT THE CONDUIT ENTRANCE WHEN THE CONDUIT ENTERS AT A <br />LEVEL HIGHER THAN THE LOWEST LIVE PART, PROVISION FOR <br />LOCKING AND A PROVISION FOR DRAINAGE. THE PROVISION FOR <br />LOCKING DOES APPLY TO ENCLOSURES FOR PUSHBUTTON <br />STATIONS. <br />C. TYPE 4 — WATERTIGHT AND DUSTTTGHT—INDOOR/OUTDOOR: <br />ENCLOSURES ARE INTENDED FOR USE INDOORS OR OUTDOORS <br />TO PROTECT THE ENCLOSED EQUIPMENT AGAINST SPLASHING <br />WATER, SEEPAGE OF WATER, FALUNG OR HOSE DRIPPED <br />WATER, AND SEVERE EXTERNAL CONDENSATION. <br />D. TYPE 12 — INDUSTRIAL DUSTTIGHT AND DRIPTIGHIT: <br />ENCLOSURES AR INTENDED FOR USE INDOORS TO PROTECT <br />THE ENCLOSED EQUIPMENT AGAINST FIBERS, FLYINGS, LINT, <br />DUST AND DIRT, AND UGHR SPLASHING, SEEPAGE, DRIPPING <br />AND EXTERNAL CONDENSATION OF NONCORROSIVE UQUIDS. <br />ENCLOSURES FOR COMBINATION CONTROLLERS SHALL HAVE <br />HINGED DOORS WHICH SWING HORIZONTALLY AND REQUIRE A <br />TOOL TO OPEN. <br />MANUFACTURERS <br />A. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, <br />MANUFACTURES OF CABINETS AND ENCLOSURES SHALL BE AS <br />FOLLOWS: <br />CUTLER HAMMER <br />HOFFMAN <br />SQUARE D <br />WIEGMANN <br />EXECUTION <br />A. INSTALL CABINETS AND ENCLOSURES AS RECOMMENDED BY <br />MANUFACTURER. <br />16190 SUPPORTING DEVICES <br />SUBMITTALS <br />A. SUBMIT MANUFACTURER'S DATA AND SHOP DRAWINGS ON <br />SUPPORTING DEVICES INCLUDING CATALOG CUTS, <br />SPECIFICATIONS. AND INSTALLATION INSTRUCTIONS FOR EACH <br />TYPE OF SUPPORT, ANCHOR, SLEEVE AND SEAL <br />SUPPORTS <br />A. CLEAVIS HUNGERS: FOR SUPPORTING 2' RIGID METAL CONDUIT; <br />GALVANIZED STEEL; WITH 1/2' DIAMETER HOLE FOR ROUND <br />STEEL. ROD; APPROXIMATELY 54 POUNDS PER 100 UNITS. <br />B. RISER CLAMPS: FOR SUPPORTING 5' RIGID METAL CONDUIT; <br />BLACK STEEL; WITH 2 BOLTS AND NUTS, AND 4" EARS; <br />APPROXIMATELY 510 POUNDS PER 100 UNITS. <br />C. REDUCING COUPUNGS: STEEL ROD REDUCING COUPUNG, 1/2" <br />X 5/8', BLACK STEEL;; APPROXIMATELY 16 POUNDS PER 100 <br />UNITS. <br />D. C—CLAMPS: BLACK MALLEABLE IRON: 1/2' ROD SIZE; <br />APPROXIMATELY 70 POUNDS PER 100 UNITS. <br />E. I —BEAM CLAMPS: BLACK STEEL, 1 1/2" X 3/16" STOCK; 3/8' <br />CROSS BOLT, FLANGE WIDTH 2"; APPROXIMATELY 7 POUNDS <br />PER 100 UNITS. <br />F. ONE —HOLE CONDUIT STRAPS: FOR SUPPORTING 3/4' RIGID <br />METAL CONDUIT; GALVANIZED STEEL; 3/4' STRAP WIDTH, AND 2 <br />1/8' BETWEEN CENTER OF SCREW HOLES. <br />G. TWO —HOLE CONDUIT STRAPS: FOR SUPPORTING 3/4" RIGID <br />METAL CONDUIT, GALVANIZED STEEL; 3/4' STRAP WIDTH, AND 2 <br />1/8" BETWEEN CENTER OF SCREW HOLES. <br />H. HEXAGON NUTS: FOR 1/2" ROD SIZE; GALVANIZED STEEL; <br />APPROXIMATELY 4 POUNDS PER 100 UNITS. <br />I. ROUND STEEL ROD: BLACK STEEL; 1/2" DIAMETER; <br />APPROXIMATELY 67 POUNDS PER 100 FEET. <br />J. OFFSET CONDUIT CLAMPS: FOR SUPPORTING 2" RIGID METAL <br />CONDUIT; BLACK STEEL; APPROXIMATELY 200 POUNDS PER 100 <br />UNITS. <br />ANCHORS <br />A. LEAD EXPANSION ANCHORS: 1/2'; APPROXIMATELY 38 POUNDS <br />PER 100 UNITS. <br />B. TOGGLE BOLTS: SPRINGHEAD; 3/16" X 4, APPROXIMATELY 5 <br />POUNDS PER 100 UNITS. <br />C. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />ANCHORS OF ONE OF THE FOLLOWING: <br />ACKERMAN JOHNSON FASTENING SYSTEMS, INC. <br />ELCEN METAL PRODUCTS COMPANY <br />IDEAL INDUSTRIES, INC. <br />RAWPLUG COMPANY, INC. <br />STAR EXPANSION COMPANY <br />U.S. EXPANSION BOLT COMPANY <br />WALL AND FLOOR SEALS <br />A. PROVIDE FACTORY ASSEMBLED WATERTIGHT WALL AND FLOOR <br />SEALS, OF TYPES AND SIZES INDICATED; SUITABLE FOR <br />SEALING AROUND CONDUIT, PIPE, OR TUBING PASSING <br />THROUGH CONCRETE FLOORS AND WALLS. CONSTRUCT SEALS <br />WITH STEEL SLEEVES, MALLEABLE IRON BODY, NEOPRENE <br />SEALING GROMMETS AND RINGS, METAL PRESSURE RINGS, <br />PRESSURE CLAMPS, AND CAP SCREWS. <br />U—CHANNEL STRUT SYSTEMS <br />A. PROVIDE U—CHANNEL STRUT SYSTEM FOR SUPPORTING <br />ELECTRICAL EQUIPMENT, 12—GUAGE HOT —DIP GALVANIZED <br />STEEL, OF TYPES AND SIZES INDICATED: CONSTRUCT WITH <br />9/16' DIAMETER HOLES, 8' O.C. ON TOP SURFACE, WITH <br />STANDARD GREEN FINISH, AND WITH STANDARD FITTINGS WHICH <br />MATE AND MATCH WITH U—CHANNEL <br />B. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />CHANNEL SYSTEMS OF ONE OF THE FOLLOWING: <br />B—UNE SYSTEMS, INC. <br />MIDLAND—ROSS CORPORATION <br />POWER —STRUT DIVISION: VAN HUFFEL TUBE CORPORATION <br />UNISTRUT DIVISION; GTE PRODUCTS CORPORATION <br />PIPE SLEEVES <br />A. FABRICATE FROM SCHEDULE 40 GALVANIZED STEEL PIPE; <br />REMOVE BURRS. <br />B. PROVIDE SLEEVES FOR PIPING WHICH PENETRATE <br />FOUNDATION WALLS BELOW GRADE, OR EXTERIOR WALLS. <br />CAULK BETWEEN SLEEVE AND PIPE WITH NON —TOXIC, <br />UL—CLASSIFIED CAULKING MATERIAL TO ENSURE WATERTIGHT <br />SEAL <br />EXECUTION <br />A. INSTALL HANGERS, ANCHORS, SLEEVES AND SEALS AS <br />INDICATED, IN ACCORDANCE WITH MANUFACTURER'S WRITTEN <br />INSTRUCTIONS AND WITH RECOGNIZED INDUSTRY PRACTICES TO <br />INSURE SUPPORTING DEVICES COMPLY WITH REQUIREMENTS. <br />B. COORDINATE WITH OTHER ELECTRICAL WORK, INCLUDING <br />RACEWAY AND WIRING WORK, AS NECESSARY TO INTERFACE <br />INSTALLATION OF SUPPORTING DEVICES WITH OTHER WORK. <br />C. INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS TO <br />SUPPORT PIPING PROPERLY FROM BUILDING STRUCTURE. <br />ARRANGE FOR GROUPING OF PARALLEL RUNS OF HORIZONTAL <br />CONDUITS TO BE SUPPORTED TOGETHER ON TRAPEZE TYPE <br />HANGERS WHERE POSSIBLE. <br />D. TORQUE SLEEVE NUTS, COMPLYING WITH MANUFACTURER'S <br />RECOMMENDED VALUES. ENSURE THE SEAUNG GROMMETS <br />EXPAND TO FORM WATERTIGHT SEAL <br />E. PROVIDE LATERAL SUPPORT MEMBERS TO PREVENT SWAY <br />MOVEMENT IN ANY DIRECTION FOR PENDANT OR TRAPEZE <br />STYLE HANGERS. <br />16195 I ELECTRICAL IDENTIFICATION <br />ENGRAVED PLASTIC —LAMINATE NAMEPLATES <br />A. PROVIDE ENGRAVING STOCK MELAMINE PLASTIC LAMINATE, <br />COMPLYING WITH FS L—P-387, IN SIZES AND THICKNESS <br />INDICATED, ENGRAVED WITH ENGRAVER'S STANDARD LETTER <br />STYLE OF SIZES AND WORDING INDICATED, BLACK FACE AND <br />WHITE CORE PILES (LETTER COLOR) EXCEPT AS OTHERWISE <br />INDICATED, PUNCHED FOR MECHANICAL FASTENING EXCEPT <br />WHERE ADHESIVE MOUNTING IS NECESSARY BECAUSE OF <br />SUBSTRATE. <br />B. THICKNESS: 1/16", FOR UNITS UP TO 20 SQUARE INCHES OR <br />8' LENGTH; 1/8" FOR LARGER UNITS. <br />C. FASTENERS: SELF —TAPPING STAINLESS STEEL SCREWS, EXCEPT <br />CONTACT —TYPE PERMANENT ADHESIVE WHERE SCREWS CANNOT <br />OR SHOULD NOT PENETRATE SUBSTRATE. <br />LETTERING AND GRAPHICS <br />A. COORDINATE NAMES, ABBREVIATIONS AND OTHER DESIGNATIONS <br />USED IN ELECTRICAL IDENTIFICATION WORK, WITH <br />CORRESPONDING DESIGNATIONS SHOWN, SPECIFIED OR <br />SCHEDULED. PROVIDE NUMBERS, LETTERING AND WORDING AS <br />INDICATED OR, IF NOT OTHERWISE INDICATED, AS <br />RECOMMENDED BY MANUFACTURER OR AS REQUIRED FOR <br />PROPER IDENTIFICATION AND OPERATION/MAINTENANCE OF <br />ELECTRICAL SYSTEMS AND EQUIPMENT. COMPLY WITH ANSI <br />A13.1 PERTAINING TO MINIMUM SIZES FOR LETTERS AND <br />NUMBERS. <br />EXECUTION <br />A. PROVIDE PERMANENT IDENTIFICATION MARKINGS AND <br />NAMEPLATES FOR WIRING AND EACH ITEM OF ELECTRICAL <br />APPARATUS AND ASSOCIATED CONTROLLED EQUIPMENT, WITH <br />THE SAME INSCRIPTIONS AS SHOWN ON THE DRAWING OR AS <br />DIRECTED, CLEARLY AND NEATLY APPUED. <br />B. APPLY ENGRAVED PLASTIC LAMINATE NAMEPLATES WITH <br />NON —CORRODING TYPE SCREW FASTENERS OR RIVETS TO ALL <br />MOTOR STARTERS, DISCONNECT SWITCHES, RELAYS, REMOTE <br />CONTROL PANELS, PUSHBUTTON STATIONS, PANELBOARDS, <br />SWITCHGEAR, TRANSFORMERS, AND OTHER ELECTRICAL <br />APPARATUS. THE NAMEPLATE SHWA IDENTIFY EQUIPMENT NAME <br />AND WHERE IT IS FEED FROM. <br />C. PROVIDE A TYPEWRITTEN DIRECTORY OF CIRCUITS IN <br />UGHTING AND POWER PANELS. <br />D. WHENEVER REASONABLY REQUIRED TO ENSURE SAFE AND <br />EFFICIENT OPERATION AND MAINTENANCE OF ELECTRICAL <br />SYSTEMS, AND ELECTRICALLY CONNECTED MECHANICAL SYSTEMS <br />AND GENERAL SYSTEMS AND EQUIPMENT, INCLUDING <br />PREVENTION OF MISUSE OF ELECTRICAL FACILITIES BY <br />UNAUTHORIZED PERSONNEL, INSTALL SELF—ADHESIVE PLASTIC <br />SIGNS OR SIMILAR EQUIVALENT IDENTIFICATION, INSTRUCTION OR <br />WARNINGS ON SWITCHES, OUTLETS AND OTHER CONTROLS, <br />DEVICES AND COVERS OF ELECTRICAL ENCLOSURES. WHERE <br />DETAILED INSTRUCTIONS OR EXPLANATIONS ARE NEEDED, <br />PROVIDE PLASTICIZED TAGS WITH CLEARLY WRITTEN MESSAGES <br />ADEQUATE FOR INTENDED PURPOSES. <br />16440I DISCONNECT SWITCHES <br />SUBMITTALS <br />A. SUBMIT MANUFACTURER'S DATA AND SHOP DRAWINGS ON <br />ELECTRICAL DISCONNECT SWITCHES. <br />DISCONNECT SWITCHES <br />A. PROVIDE ALL DISCONNECT SWITCHES INDICATED ON THE <br />DRAWINGS. <br />B. SWITCHES SHALL BE NEMA TYPE HD (HEAVY DUTY) AND SHALL <br />BE UNDERWRITERS LABORATORIES LISTED. PROVIDE RATINGS <br />AND MODIFICATIONS SHOWN ON THE DRAWINGS. <br />C. ALL SWITCHES SHALL HAVE: NEMA 1 GENERAL PURPOSE <br />ENCLOSURES UNLESS OTHERWISE NOTED: METAL NAMEPLATES, <br />FRONT COVER MOUNTED, THAT CONTAIN A PERMANENT RECORD <br />ON SWITCH TYPE. CATALOG NUMBER AND HP RATINGS (WITH <br />BOTH STANDARD AND TIME DEWY FUSES): HANDLE WHOSE <br />POSITION IS EASILY RECOGNIZABLE AND PADLOCKABLE IN THE <br />'OFF' POSITION; VISIBLE BLADES; REINFORCED FUSE CUPS; <br />NONTEASIBLE, POSITIVE, QUICK MAKE —QUICK BREAK <br />MECHANISMS; AND SWITCH ASSEMBLY PLUS OPERATING HANDLE <br />AS AN INTEGRAL PART OF THE ENCLOSURE AREA, <br />D. ALL SWITCHES SHALL BE UNDERWRITERS LABORATORIES INC., <br />LISTED, HP RATED, MEET FEDERAL SPECIFICATION WS-865C, <br />AND NEMA SPECIFICATIONS KS1-1975. SWITCHES SHALL HAVE <br />DEFEATABLE DOOR INTERLOCKS THAT PREVENT THE DOOR FROM <br />OPENING WHEN THE OPERATING HANDLE IS IN THE 'ON' <br />POSITION. HEAVY DUTY SWITCHES SHALL HAVE UNE TERMINAL <br />SHIELDS. <br />E. SWITCHES SHALL BE HORSEPOWER RATED FOR AC AND/OR DC <br />AS INDICATED BY THE PLANS. ALL FUSIBLE SWITCHES RATED <br />100 THRU 600 AMPERES AT 240 VOLTS AND 30 THRU 600 <br />AMPERES AT 600 VOLTS SHALL HAVE A UL USTTED METHOD OF <br />FIELD CONVERSION FROM STANDARD CLASS H FUSE SPACING <br />TO CLASS J FUSE SPACING. THE SWITCH ALSO MUST ACCEPT <br />CLASS R FUSES AND HAVE PROVISIONS FOR FIELD <br />INSTALLATION OF A UL USTED REJECTION FEATURE TO REJECT <br />ALL FUSES EXCEPT CLASS R. THE UL LISTED SHORT CIRCUIT <br />RATING OF THE SWITCHES SHALL BE 200,000 RMS <br />SYMMETRICAL AMPERES WHEN CLASS R OR CLASS J FUSES <br />ARE USED WITH THE APPROPRIATE REJECTION SCHEME. 800 <br />AND 1200 AMPERE SWITCHES SHALL HAVE PROVISIONS FOR <br />CLASS L FUSE AND SHALL HAVE A UL LISTED SHORT <br />CIRCUIT RATING OF 200.000 RMS SYMMETRICAL AMPERES. <br />F. THE USE OF TOGGLE TYPE MOTOR RATED DISCONNECT <br />SWITCHES ARE NOT ACCEPTABLE. <br />MANUFACTURERS <br />A. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, <br />MANUFACTURERS OF DISCONNECT SWITCHES SHALL BE AS <br />FOLLOWS: <br />CUTLER HAMMER <br />SQUARE D <br />SIEMENS <br />EXECUTION <br />A. INSTALL DISCONNECT SWITCHES AND PROVIDE SUPPORTS. <br />B. TERMINATE RACEWAYS AND CONDUCTORS FOR DISCONNECT <br />SWITCHES. <br />16450I GROUNDING <br />MANUFACTURERS <br />A. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, <br />MANUFACTURERS OF GROUNDING EQUIPMENT SHALL BE AS <br />FOLLOWS: <br />BURNDY CORPORATION <br />CADWELD DIV.; ERICO PRODUCTS, INC. <br />CROUSE—HINDS DIV.; COOPER INDUSTRIES <br />IDEAL INDUSTRIES, INC. <br />OZ GEDNEY DIV, GENERAL SIGNAL CORP. <br />THOMAS AND BETTS CORPORATION <br />MATERIALS <br />A. PROVIDE A GROUNDING SYSTEM THAT INCLUDES ALL <br />CONNECTIONS AND TESTING OF GROUND RODS, GROUND <br />CABLES, GROUND BUSSES, CONDUITS, FITTINGS, ANCHORS, <br />SUPPORTS, CADWELD MATERIAL AND EQUIPMENT, AND OTHER <br />MATERIALS REQUIRED FOR A COMPLETE INSTALLATION. <br />B. ALL COPPER TO COPPER AND COPPER TO STEEL CONNECTIONS <br />OF J6 AWG AND LARGER SHALL BE MADE WITH CADWELD <br />PROCESS EXCEPT AS NOTED IN ITEM C. BELOW. <br />C. PROVIDE BURNDY CORP., TYPE NE, THOMAS do BETTS CO., INC. <br />CATALOG NO. 3951, OR APPROVED EQUAL, GROUND FITTINGS <br />FOR BONDING GROUND CABLE TO ENCASING METAL CONDUIT. <br />1. BONDING JUMPER: COPPER BRAIDED TAPE, CONSTRUCTED <br />OF 30—GAUGE BARE COPPER WIRES AND PROPERLY SIZED <br />FOR INDICATED APPUCATIONS. <br />2. FLEXIBLE JUMPER STRAP: FLEXIBLE FLAT CONDUCTOR, 480 <br />STRANDS OF 30—GAUGE BARE COPPER WIRE; 3/4' WIDE, 9 <br />1/2' LONG; 48,250 CM. SELECT BRAID WITH HOLES SIZED <br />FOR 3/8" DIAMETER BOLTS, AND PROTECT BRAID WITH <br />COPPER BOLT HOLE ENDS. <br />D. PROVIDE ELECTRICAL BONDING CONNECTORS, TERMINALS, LUGS <br />AND CLAMPS AS RECOMMENDED BY MANUFACTURERS FOR <br />INDICATED APPLICATIONS. <br />E. GROUNDING BUSHINGS SHALL BE MALLEABLE IRON, THREADED, <br />WITH INSULATED LINER AND SOLDERLESS LUG. <br />GROUNDING CONNECTIONS <br />A. CADWELD CONNECTIONS TO BE USED OUTDOORS SHALL BE <br />SUITABLE FOR EXPOSURE TO THE ELEMENTS OR DIRECT BURIAL <br />ELEMENTS OR DIRECT BURIAL WITHOUT DEGRADATION OVER THE <br />UFETIME OF THE GROUNDING SYSTEM. <br />B. CADWELD CONNECTIONS TO BE MADE IN FINISHED BUILDINGS <br />OR CONFINED SPACES SHALL USE THE LOW SMOKE, LOW <br />EMISSION CADWELD EXOLON PROCESS WHICH IS <br />METALLURGICALLY EQUALLY TO THE ABOVE CONNECTION. <br />C• THE INSTALLER IS PROHIBITED FROM USING A MOLD FROM ONE <br />MANUFACTURER'S WELDING MIXTURE. THIS PRACTICE CAN <br />PROVIDE AN UNACCEPTABLE PRODUCT. <br />SYSTEM GROUNDING <br />A. WHERE GROUND CONDUCTORS ARE RUN IN CONDUIT OR OTHER <br />RACEWAY, THE GROUND CONDUCTOR SHALL BE BONDED AT <br />EACH END. <br />B. FLEXIBLE CONDUIT CONNECTIONS TO ELECTRICAL EQUIPMENT <br />SHALL HAVE A THWN/THHN GROUND CONDUCTOR IN THE <br />FLEXIBLE CONDUIT WITH THE CIRCUIT CONDUCTORS. GROUND <br />CONDUCTORS SHALL BE TERMINATED AT EACH END IN <br />ACCORDANCE WITH CODE REQUIREMENTS. <br />COMMUNICATION GROUNDING <br />A. PROVIDE A NO. 4 AWG COPPER CONDUCTOR WITH TYPE THW <br />INSULATION TO GROUND BUS IN EACH TELEPHONE EQUIPMENT <br />ROOM. LEAVE 12' PIGTAIL AT TELEPHONE BOARD. <br />INSTALLATION <br />A. THE SYSTEM GROUND SHALL INCLUDE THE INCOMING SERVICE <br />AND ALL TRANSFORMER NEUTRALS. <br />THE EQUIPMENT GROUND SHALL INCLUDE ALL SWITCHGEAR, <br />TRANSFORMERS, CABLE SHEATHS, CABLE RACKS, CONDUIT <br />SYSTEM, MOTOR FRAMES, AND EQUIPMENT ENCLOSURES. <br />B. ALL GROUND CONDUCTORS SHALL BE IN CONDUIT EXCEPT <br />WHERE OTHERWISE INDICATED ON THE DRAWINGS. <br />C. THE CONDUIT SYSTEM OR SPRINKLER SYSTEM PIPING SHALL IN <br />NO CASE BE USED FOR ESTABUSHING A TRANSFORMER <br />NEUTRAL GROUNDING ELECTRODE. <br />D. MAKE ALL ELECTRICAL POWER GROUNDING AND CONTROL <br />CONNECTIONS TO EQUIPMENT FURNISHED BY OTHER TRADES <br />AND FURNISH WIRING, CONDUIT, OUTLET BOXES, DISCONNECT <br />SWITCHES, ETC., AS REQUIRED FOR SAME. <br />E. INSTALL GROUND CONDUCTORS CONTINUOUS BETWEEN <br />CONNECTIONS. SPUCES WILL NOT BE ALLOWED EXCEPT <br />INDICATED ON THE DRAWINGS. WHERE GROUND CABLES PASS <br />THROUGH FLOOR SLABS, BUILDING WALLS, ETC., AND ARE NOT <br />IN METALUC ENCLOSURES, PROVIDE THE SLEEVES OF <br />APPROVED NONMETALUC MATERIAL <br />F. USE RIGID METAL CONDUIT AND ELECTRICAL METALLIC TUBING <br />AS EQUIPMENT GROUNDING CONDUCTORS UNLESS NOTED <br />OTHERWISE. MAKE—UP COUPUNGS WRENCH TIGHT. INSTALL <br />GROUNDING CONDUCTOR IN NONMETALLIC RACEWAYS AND <br />UNDERFLOOR DUCTS. <br />G. INSTALL EQUIPMENT GROUNDING CONDUCTORS IN ALL <br />NONMETALLIC RACEWAYS. <br />H. GROUND INTERIOR UGHTING FIXTURES WITH GROUNDING <br />CONDUCTOR TO RIGID METAL RACEWAYS SERVING THEM. <br />FLEXIBLE METAL CONDUIT IN LENGTHS LESS THAN 6'-0" <br />INCHES MAY BE USED AS GROUNDING CONDUCTORS WHEN <br />TERMINATED WITH APPROVED FITTINGS ON CIRCUITS OF 20 <br />AMPERES OR LESS. <br />I. WHERE CONNECTIONS ARE MADE TO MOTORS OR EQUIPMENT <br />WITH FLEXIBLE METAL CONDUIT, GROUNDING CONDUCTOR SHALL <br />BE STRANDING COPPER CONDUCTOR WITHIN THE CONDUIT, <br />BONDED TO THE EQUIPMENT AND TO THE RIGID METAL <br />RACEWAY SYSTEM. <br />J. AT EACH CONVENIENCE OUTLET, INSTALL A GROUNDING CUP <br />ATTACHED TO THE OUTLET BOX AND LEAVE A SUFFICIENT <br />LENGTH OF J12 WIRE WITH GREEN COLORED INSULATION TO <br />CONNECT TO THE GROUNDING TERMINAL OF THE RECEPTACLE. <br />GROUNDING CUP SHALL BE EQUAL TO STEEL CITY TYPE G. <br />F164-6011 TRANSFORMERS <br />SUBMITTALS <br />A. SUBMIT SHOP DRAWINGS INDICATING PRODUCT DATA INCLUDING <br />RATED KVA, FREQUENCY, PRIMARY AND SECONDARY VOLTAGES, <br />PERCENT TAPS, POLARITY, IMPEDANCE AND CERTIFICATION OF <br />TRANSFORMER PERFORMANCE EFFICIENCY AT INDICATED LOADS, <br />PERCENTAGE REGULATION AT 10OX AND 80% POWER FACTOR, <br />NO—LOAD AND FULL —LOAD LOSSES IN WATTS, X IMPEDANCE AT <br />75 DEG. CELSIUS, <br />HOT —SPOT AND AVERAGE TEMPERATURE RISE ABOVE 40 DEG. <br />CELSIUS AMBIENT TEMPERATURE, SOUND LEVEL IN DECIBELS, <br />AND STANDARD PUBUSHED DATA. <br />IWIn:111IY_I0119:1:1 <br />CUTLER HAMMER <br />SIEMENS, INC. <br />SORGEL ELECTRICAL DIV.; SQUARE D CO. <br />HEAVY —DUN ELECTRIC DIV.; GENERAL SIGNAL CORP. <br />DRY —TYPE TRANSFORMERS (45 KVA OR LESS <br />A. PROVIDE FACTORY —ASSEMBLED, GENERAL PURPOSE, <br />AIR—COOLED, DRY —TYPE DISTRIBUTION TRANSFORMERS WHERE <br />SHOWN; OF SIZES, CHARACTERISTICS AND RATED CAPACITIES <br />INDICATED; SINGLE—PHASE; 60—HERTZ, 30 KV BIL, 4.OX <br />IMPEDANCE, WITH 480—VOLTS PRIMARY AND 240/120 VOLTS <br />SECONDARY OR THREE—PHASE: 60—HERTZ, 30 KV BIL, 4.OX <br />IMPEDANCE WITH 480—VOLTS DELTA CONNECTED PRIMARY AND <br />208/120 3 PHASE, 4 WIRE SECONDARY WYE CONNECTED, WITH <br />GROUNDED NEUTRAL PROVIDE PRIMARY WINDING WITH 2 TAPS; <br />BOTH 5X INCREMENTS BELOW FULL —RATED VOLTAGE FOR <br />DE —ENERGIZED TAP —CHANGING OPERATION. INSULATE WITH <br />CLASS H INSULATION BASED ON 150 DEG. CELSIUS RISE <br />ABOVE 40 DEG. AMBIENT. RATE TRANSFORMER FOR <br />CONTINUOUS OPERATION AT RATED KVA. UMIT TRANSFORMER <br />SURFACE TEMPERATURE RISE TO MAXIMUM OF 65 DEG. <br />CELSIUS PROVIDE TERMINAL ENCLOSURE, WITH COVER, TO <br />ACCOMMODATE PRIMARY AND SECONDARY COIL WIRING <br />CONNECTIONS AND ELECTRICAL SUPPLY RACEWAY TERMINAL <br />CONNECTOR. EQUIP TERMINAL LEADS WITH CONNECTORS <br />INSTALLED. LIMIT TERMINAL COMPARTMENT TEMPERATURE TO 75 <br />DEG. CELSIUS WHEN TRANSFORMER IS OPERATING <br />CONTINUOUSLY AT RATED LOAD WITH AMBIENT TEMPERATURE OF <br />40 DEG. CELSIUS PROVIDE WIRING CONNECTORS SUITABLE FOR <br />COPPER OR ALUMINUM WIRING. CUSHION —MOUNT <br />TRANSFORMERS WITH EXTERNAL VIBRATION ISOLATION <br />SUPPORTS; SOUND —LEVEL RATINGS NOT TO EXCEED 45 DB AS <br />DETERMINED IN ACCORDANCE WITH ANSI/NEMA STANDARDS. <br />ELECTRICALLY GROUND CORE AND COILS TO TRANSFORMER <br />ENCLOSURE BY MEANS OF FLEXIBLE METAL GROUNDING STRAP. <br />PROVIDE TRANSFORMERS WITH FULL —ENCLOSED SHEET STEEL <br />ENCLOSURES. APPLY MANUFACTURER'S STANDARD GRAY INDOOR <br />ENAMEL OVER CLEANED AND PHOSPHATED STEEL ENCLOSURE. <br />PROVIDE TRANSFORMERS SUITABLE FOR WALL MOUNTING. <br />B. TRANSFORMERS SERVING NON—UNEAR LOADS SHALL HAVE A <br />NEUTRAL CAPABLE OF CARRYING 200 PERCENT OF THE UNE <br />CURRENT CONTINUOUSLY. <br />INSTALLATION <br />A. INSTALL TRANSFORMERS AS INDICATED, COMPLYING WITH <br />MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLICABLE <br />REQUIREMENTS OF NEC, NESC, NEMA. ANSI AND IEEE <br />STANDARDS, AND IN ACCORDANCE WITH RECOGNIZED <br />INDUSTRY PRACTICES TO ENSURE THAT PRODUCTS FULFILL <br />REQUIREMENTS. <br />B. COORDINATE TRANSFORMER INSTALLATION WORK WITH <br />ELECTRICAL RACEWAY AND WIRE/CABLE WORK, AS <br />NECESSARY FOR PROPER INTERFACE. <br />C. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS, INCLUDING <br />SCREWS AND BOLTS, IN ACCORDANCE WITH EQUIPMENT <br />MANUFACTURER'S PUBUSHED TORQUE TIGHTENING VALUES FOR <br />EQUIPMENT CONNECTORS. WHERE MANUFACTURER'S TORQUING <br />REQUIREMENTS ARE NOT INDICATED, TIGHTEN CONNECTORS AND <br />TERMINALS TO COMPLY WITH TIGHTENING TORQUES SPECIFIED <br />IN UL STANDARD 486A AND 486B. <br />D. INSTALL WALL MOUNTED TRANSFORMERS ON PREFABRICATED <br />BRACKETS DESIGNED FOR THAT PURPOSE. <br />E. PROVIDE 4 INCH CONCRETE PAD WITH BEVELED EDGE FOR <br />FLOOR MOUNTED TRANSFORMERS. <br />GROUNDING <br />A. PROVIDE EQUIPMENT GROUNDING CONNECTIONS FOR POWER <br />/DISTRIBUTION TRANSFORMERS AS INDICATED. TIGHTEN <br />CONNECTIONS TO COMPLY WITH TIGHTENING TORQUES <br />SPECIFIED IN UL STANDARD 486A TO ASSURE PERMANENT AND <br />EFFECTIVE GROUNDING. <br />B. TRANSFORMER SECONDARY SHALL BE GROUNDED TO BUILDING <br />STEEL OR GROUND ELECTRODE SYSTEM. <br />TESTING <br />A. RATIO TESTS AT THE RATED VOLTAGE CONNECTION AND AT ALL <br />TAP CONNECTIONS. <br />B. POLARITY AND PHASE —RELATION TESTS ON THE RATED VOLTAGE <br />CONNECTION. <br />C. APPUED POTENTIAL TESTS. <br />D. INDUCED POTENTIAL TESTS. <br />E. NO—LOAD AND EXCITATION CURRENT AT RATED VOLTAGE ON <br />THE RATED VOLTAGE CONNECTION. ON RATINGS ABOVE 500 <br />KVA, THE FOLLOWING TEST IN ITEM 'F' SHALL ALSO BE <br />PERFORMED ON EACH TRANSFORMER. <br />F. RESISTANCE MEASUREMENTS OF ALL WINDINGS AT THE RATED <br />VOLTAGE CONNECTION OF EACH UNIT AND AT THE TAP <br />EXTREMES OF THE FIRST UNIT MADE OF A NEW DESIGN. <br />G. PRIOR TO ENERGIZATION OF TRANSFORMERS, CHECK ALL <br />ACCESSIBLE CONNECTIONS FOR COMPLIANCE WITH <br />MANUFACTURER'S TORQUE TIGHTENING SPECIFICATIONS. <br />H. PRIOR TO ENERGIZATION, CHECK CIRCUITRY FOR ELECTRICAL <br />CONTINUITY, AND FOR SHORT—CIRCUITS. <br />I. UPON COMPLETION OF INSTALLATION OF TRANSFORMERS, <br />ENERGIZE PRIMARY CIRCUITRY AT RATED VOLTAGE AND <br />FREQUENCY FROM NORMAL POWER SOURCE, AND TEST <br />TRANSFORMERS, INCLUDING, BUT NOT UMITED TO, AUDIBLE <br />SOUND LEVELS, TO DEMONSTRATE CAPABIUTY AND COMPUANCE <br />WITH REQUIREMENTS. WHERE POSSIBLE, CORRECT <br />MALFUNCTIONING UNITS AT SITE, THEN RETEST TO <br />DEMONSTRATE COMPUANCE; OTHERWISE, REMOVE AND <br />REPLACE WITH NEW UNITS OR COMPONENTS, AND PROCEED <br />WITH RETESTING. <br />16470 SWITCHBOARDS AND PANELBOARDS <br />SUBMITTALS <br />A. SUBMIT MANUFACTURER'S DATA AND SHOP DRAWINGS ON <br />SWITCHBOARDS, PANELBOARDS AND ENCLOSURES INCLUDING <br />VOLTAGES. CURRENT RATINGS, INTERRUPTING RATINGS AND <br />ELECTRICAL CHARACTERISTICS. IN ADDITION SUBMIT FULL POWER <br />STUDIES INCLUDING BUT NOT UMITED TO ARC FLASH STUDIES, <br />COORDINATION STUDIES AND SHORT CIRCUIT STUDIES. <br />MANUFACTURERS <br />A. SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PANELBOARD PRODUCTS OF ONE OF THE FOLLOWING (FOR <br />EACH TYPE AND RATING OF PANELBOARD AND ENCLOSURE): <br />CUTLER HAMMER <br />SIEMENS, INC. <br />SQUARE D COMPANY <br />MEP / FP Engineer <br />EPSTEIN <br />600 West Fulton <br />Chicago, IL 60661 <br />312.454.9100 <br />Design Architect <br />EPSTEIN <br />600 West Fulton <br />Chicago, IL 60661 <br />312.454.9100 <br />Nestle Waters North America <br />Nestle Waters North America <br />4330 20th Street <br />Zephyrhills, Florida 33542-6703 <br />972.462.3663 <br />F7jtIe1\ <br />ers <br />Expires <br />FEB ;� 0 Z015 <br />�• <br />�G`�,� G E N <br />7520 <br />• STATE OF <br />0'• , <br />0 R 4 Q Q �`�k' <br />1-� r- 109- <br />4 <br />09.18.2013 <br />ISSUE FOR PERMIT <br />3 <br />09.11.2013 <br />ISSUE FOR BIDS <br />2 <br />09.03.2013 <br />CD REVIEW PACKAGE <br />1 <br />08.16.2013 <br />DD REVIEW PACKAGE <br />NO. <br />DATE <br />REVISIONS/ISSUANCES <br />�PSTEIN <br />Architecture <br />Chicago <br />Interiors <br />New York <br />Engineering <br />Bucharest <br />Construction <br />Warsaw <br />600 W. Fulton Street <br />Chicago, IL 60661-1259 <br />T 312.454.9100 <br />www.epsteinglobal.com <br />PROJECT NUMBER: 12386 <br />PROJECT MANAGER: JK <br />ARCH/ENG: DD <br />SCALE: NOT TO SCALE <br />DRAWN BY: DD <br />CHECKED BY: MS <br />ELECTRICAL <br />SPECIFICATIONS <br />E-004 <br />A. Epstein and Sons International, Inc. All rights reserved. <br />