A. PROVIDE DEAD -FRONT POWER DISTRIBUTION PANELBOARDS AS <br />INDICATED, WITH PANELBOARD SWITCHING AND PROTECTIVE <br />DEVICES IN QUANTITIES, RATINGS, TYPES, AND WiTH <br />ARRANGEMENT SHOWN, WiTH ANTi-TURN SOLDERLESS <br />PRESSURE TYPE MAIN LUG CONNECTORS APPROVED FOR USE <br />WiTH COPPER CONDUCTORS. SELECT UNIT WiTH FEEDERS <br />CONNECTING AT TOP OF PANEL UNLESS OTHERWISE INDICATED <br />ON PLANS. EQUIP WITH COPPER BUS BARS WiTH NOT LESS <br />THAN 98X CONDUCTIVITY, AND WiTH FULL-SIZED NEUTRAL BUS. <br />PROVIDE SUITABLE LUGS ON NEUTRAL BUS FOR OUTGOING <br />FEEDERS REQUIRING NEUTRAL CONNECTIONS. PROVIDE FUSIBLE <br />SWITCH OR MOLDED -CASE CIRCUIT BREAKER MAIN AND <br />BRANCH DEVICES AS INDICATED. CIRCUIT BREAKERS Shall <br />HAVE TOGGLE HANDLES THAT INDICATE WHEN TRIPPED. WHERE <br />MULTIPLE -POLE BREAKERS ARE INDICATED, PROVIDE WITH <br />COMMON TRIP SO OVERLOAD ON ONE POLE WILL TRIP ALL <br />POLE SIMULTANEOUSLY. PROVIDE ALL. PANELBOARDS WITH BARE <br />UNINSULATED GROUNDING BARS WiTH TERMINALS, BOLTED TO <br />ENCLOSURES. SELECT ENCLOSURES FABRICATED BY SAME <br />MANUFACTURER AS PANELBOARDS, WHICH MATE AND MATCH <br />PROPERLY WITH PANELBOARDS. <br />LIGHTING AND APPLIANCE PANELBOARDS <br />A. PROVIDE DEAD -FRONT SAFETY TYPE LIGHTING AND APPLIANCE <br />PANELBOARDS AS INDICATED, WiTH SWITCHING AND PROTECTIVE <br />DEVICES IN QUANTITIES, RATINGS, TYPES AND ARRANGEMENTS <br />SHOWN; WITH ANTI -BURN SOLDERLESS PRESSURE TYPE LUG <br />CONNECTORS APPROVED FOR USE WiTH COPPER CONDUCTORS; <br />CONSTRUCT UNIT FOR CONNECTING FEEDERS AT TOP OF PANEL <br />UNLESS OTHERWISE INDICATED ON DRAWINGS; EQUIP WITH <br />COPPER BUS BARS, FULL SIZED NEUTRAL BAR, WiTH BOLT -ON <br />TYPE HEAVY DUTY, QUICK -MAKE, QUICK -BREAK, SINGLE -POLE <br />CIRCUIT BREAKERS SEQUENCE -PHASED, UNLESS OTHERWISE <br />INDICATED WiTH TOGGLE HANDLES THAT INDICATE WHEN <br />TRIPPED. COPPER BUSBARS AND DETAILS SHALL BE 800 <br />AMPERES PER SQUARE INCH SECTION. PANELBOARDS SHALL <br />HAVE A SHORT CIRCUIT RATING GREATER THAN THE SHORT <br />CIRCUIT CURRENT AVAILABLE AT THE LINE LUGS. PROVIDE <br />SUITABLE LUGS ON NEUTRAL BUS FOR EACH OUTGOING <br />FEEDER REQUIRED. PROVIDE ALL PANELBOARDS WITH BARE <br />UNINSULATED GROUNDING BARS WITH TERMINALS, BOLTED TO <br />ENCLOSURES. SELECT ENCLOSURES FABRICATED BY SAME <br />MANUFACTURER AS PANELBOARDS, WHICH MATE AND MATCH <br />PROPERLY WITH PANELBOARDS. <br />EACH PANELBOARD COVER AND TRIM SHALL BE THOROUGHLY <br />CLEANED AND BONDERIZED BEFORE PAINTING. PAINTING SHALL. <br />CONSIST OF TWO COATS OF HIGH QUALITY OIL BASE PAINT OF <br />LIGHT GRAY COLOR, BOTH INSIDE AND OUTSIDE. ALL <br />PANELBOARDS OF THE SAME TYPE SHALL BE OF THE SAME <br />MANUFACTURER. THE USE OF PLUG-IN TYPE CIRCUIT <br />BREAKERS IS PROHIBITED. <br />B. PANELBOARDS SERVING NON-UNEAR LOADS SHALL HAVE <br />NEUTRAL BUS RATED AT 20OX OF THE PHASE BUS. <br />C. PROVIDE AN ISOLATED GROUND BUS WHERE INDICATED. <br />PANELBOARD ENCLOSURES <br />A. PROVIDE GALVANIZED SHEET STEEL CABINET TYPE ENCLOSURES, <br />IN SIZES AND NEMA TYPES AS INDICATED, CODEGAGE, MINIMUM <br />16-GAGE THICKNESS. CONSTRUCT WiTH MULTIPLE KNOCKOUTS <br />AND WIRING GUTTERS. PROVIDE FRONTS WITH ADJUSTABLE TRIM <br />CLAMPS, AND DOORS WITH FLUSH LOCKS AND KEYS, ALL <br />PANELBOARD ENCLOSURES KEYED ALIKE, WiTH CONCEALED <br />PIANO DOOR HINGES AND DOOR SWINGS AS INDICATED. DOORS <br />OVER 48" HIGH SHALL HAVE A 3-POINT COMBINATION CATCH <br />AND LOCK WiTH VAULT TYPE HANDLE PROVIDE 6 KEYS TO THE <br />OWNER. EQUIP WiTH INTERIOR CIRCUIT -DIRECTORY FRAME. AND <br />CARD WITH CLEAR PLASTIC COVERING. PROVIDE BAKED GRAY <br />ENAMEL FINISH OVER A RUST INHIBITOR COATING. DESIGN <br />ENCLOSURES FOR RECESSED MOUNTING. <br />B. WHERE DOUBLE TUB PANELBOARDS ARE INDICATED, EACH TUB <br />SHALL CONTAIN THE SAME NUMBER OF BREAKERS OR SPACES. <br />BOX AND TRIM SIZES SHALL BE IDENTICAL <br />C. CONNECT DOUBLE TUB PANELBOARDS WiTH CONDUIT NIPPLES <br />HAVING INSULATED BUSHINGS ON BOTH ENDS. PROVIDE PHASE, <br />NEUTRAL AND GROUNDING SUB -FEED CONDUCTORS OF THE <br />SAME SIZE AS THE FEEDER CONDUCTORS. <br />T Lil � �] y �aa r•� ��i l:i�il� !>111:�y ! 3 <br />A. PROVIDE FACTORY -ASSEMBLED, MOLDED -CASE CIRCUIT <br />BREAKERS OF FRAME SIZES, CHARACTERISTICS, AND RATINGS <br />INCLUDING RMS SYMMETRICAL INTERRUPTING RATINGS AS <br />INDICATED. SELECT BREAKERS WiTH PERMANENT THERMAL AND <br />INSTANTANEOUS MAGNETIC TRIP, AND WITH FAULT -CURRENT <br />UMiTING PROTECTION, AMPERE RATINGS AS INDICATED. CIRCUIT <br />BREAKERS WiTH GROUND FAULT INTERRUPTER SHALL BE <br />FURNISHED ON CIRCUITS FEEDING RECEPTACLES, OUTLETS, <br />UGHTING FIXTURES AND SINGLE PHASE FIXED EQUIPMENT <br />LOCATED IN WET AREAS, SUCH AS OUTDOOR RECEPTACLES, <br />KITCHEN OUTLETS, HYDROTHERAPUTIC EQUIPMENT. MULTIPLE <br />POLE CIRCUIT BREAKERS SHALL BE ARRANGED IN ORDER <br />BELOW SINGLE POLE CIRCUIT BREAKERS IN ORDERLY MANNER. <br />CONSTRUCT WiTH OVERCENTER, TRIP -FREE, TOGGLE -TYPE <br />OPERATING MECHANISMS WITH QUICK -MAKE. QUICK -BREAK <br />ACTION AND POSITIVE HANDLE TRIP INDICATION. CONSTRUCT <br />BREAKERS FOR MOUNTING AND OPERATING IN ANY PHYSICAL <br />POSITION, AND OPERATING IN AN AMBIENT TEMPERATURE OF 40 <br />DEGREES CELSIUS. PROVIDE BREAKERS WITH MECHANICAL <br />SCREW TYPE REMOVABLE CONNECTOR LUGS, AL/CU, RATED 75 <br />DEGREES CELSIUS. <br />B. CIRCUIT BREAKERS PROTECTING MULTI -MOTOR AND <br />COMBINATION -LOAD HEATING. AR CONDITIONING, AND <br />REFRIGERATION EQUIPMENT SHALL BE UL LISTED FOR THIS <br />APPLICATION AND MARKED "HACR TYPE" IN ACCORDANCE WiTH <br />NEMA STANDARDS. <br />EXISTING SWITCHBOARDS & POWER DISTRIBUTION PANELBOARDS <br />A. ADD NEW FUSIBLE SWITCH OR CIRCUIT BREAKER TYPE BRANCH <br />CIRCUIT DEVICES TO EXISTING SWITCHBOARDS AND POWER <br />DISTRIBUTION PANELBOARDS AS REQUIRED. <br />B. ALL NEW DEVICES SHALL BE THE SAME MANUFACTURER. TYPE <br />AND INTERRUPTING CAPACITY AS THE ORIGINAL EQUIPMENT. <br />C. PROVIDE NEW NAMEPLATES UPON COMPLETION OF ALL WIRING. <br />EXECUTION <br />A. FASTEN PANELBOARD ENCLOSURES FIRMLY TO WALLS AND <br />STRUCTURAL SURFACES, ENSURING THAT THEY ARE <br />PERMANENTLY AND MECHANICALLY ANCHORED. <br />B. FILL OUT PANELBOARD CIRCUIT DIRECTORY CARD UPON <br />COMPLETION OF INSTALLATION WORK FOR ALL NEW PANELS. <br />C. INSERT FUSES, IF ANY, OF RATINGS INDICATED, WITHIN <br />INSTALLED PANELBOARDS. <br />D. FOR EXISTING PANELBOARDS, NUMBER ASSOCIATED WiTH EACH <br />BRANCH CIRCUIT OUTLET IDENTIFIES THE BRANCH CIRCUIT TO <br />WHICH THE DEVICE SERVED BY THE OUTLET IS TO BE <br />CONNECTED. THE CIRCUIT NUMBER INDICATED IS FOR <br />REFERENCE AND GUIDANCE TO THIS CONTRACTOR AND IS NOT <br />INTENDED TO UMIT THE PANELBOARD CIRCUITRY ALL BRANCH <br />CIRCUITS SHALL BE CONNECTED TO BREAKERS AT THE <br />ELECTRICAL CONTRACTOR'S DISCRETION, IN ACCORDANCE WiTH <br />CIRCUIT REQUIREMENTS. THE ACTUAL CIRCUIT NUMBERS USED <br />SHALL BE INDICATED ON THE CONTRACTORS AS -BUILT' <br />DRAWINGS. THE BALANCING OF ALL LOADS SHALL BE THE <br />ELECTRICAL CONTRACTOR'S RESPONSIBILITY. <br />GROUNDING <br />A. PROVIDE EQUIPMENT GROUNDING CONNECTIONS FOR <br />PANELBOARD ENCLOSURES AS INDICATED. TIGHTEN <br />CONNECTIONS TO COMPLY WITH TIGHTENING TORQUES IN UL <br />486A TO ASSURE PERMANENT AND EFFECTIVE GROUNDS. <br />FIELD QUALITY CONTROL <br />A. PRIOR TO ENERGIZATiON OF ELECTRICAL CIRCUITRY, CHECK ALL <br />ACCESSIBLE CONNECTIONS TO MANUFACTURER'S TIGHTENING <br />TORQUE SPECIFICATIONS. <br />B• PRIOR TO ENERGIZATION OF PANELBOARDS, CHECK FEEDERS <br />WiTH GROUND RESISTANCE TESTER PHASE -TO -PHASE AND <br />PHASE -TO -GROUND INSULATION RESISTANCE LEVELS TO <br />ENSURE REQUIREMENTS ARE FULFILLED. <br />C. PRIOR TO ENERGIZATION, CHECK PANELBOARDS FOR <br />ELECTRICAL. CONTINUITY OF CIRCUITS AND SHORT-CIRCUITS. <br />16475 OVERCURRENT PROTECTIVE DEVICES <br />SUBMITTALS <br />A. SUBMIT PRODUCT DATA AND SHOP DRAWINGS ON <br />OVER -CURRENT PROTECTIVE DEVICES INCLUDING <br />SPECIFICATIONS, ELECTRICAL CHARACTERISTICS, INSTALLATION <br />INSTRUCTIONS, FURNISHED SPECIALTIES AND ACCESSORIES. <br />IN ADDITION, INCLUDE VOLTAGES AND CURRENT RATINGS, <br />INTERRUPTING RATINGS, CURRENT UMITATiON RATINGS, <br />TIME -CURRENT TRIP CHARACTERISTICS CURVES, AND <br />MOUNTING REQUIREMENTS. <br />FUSES <br />A. CLASS RK5, DUAL ELEMENT, TiME DELAY FUSES: <br />PROVIDE UL CLASS RK5 TIME DELAY FUSES RATED 250 OR <br />600 VOLTS, 60 HZ. 0 TO 600 AMPERES, WITH 2O0.000 <br />AMPERES RMS SYMMETRICAL INTERRUPTING CURRENT RATING <br />FOR PROTECTING PANELBOARDS, TRANSFORMER, MOTORS, AND <br />FEEDERS. <br />(BUSSMANN FUSETRON TYPE FRN-R 25OV, OR FRS-R 60OV) <br />B CLASS T REDUCED DIMENSION FUSES: PROVIDE UL CLASS T <br />FAST ACTING FUSES RATED 250 OR 600 VOLT, 60 HZ, UP TO <br />600 AMPERES, WITH 2O0,000 AMPERES RMS SYMMETRICAL <br />INTERRUPTING CURRENT RATING FOR PROTECTION OF <br />PHYSICALLY SMALL DEVICES WITH NO HEAVY UNRUSH <br />CURRENTS. (BUSSMANN T-TRON TYPE JJS) <br />C. IN-UNE FUSES: PROVIDE UL LISTED IN-UNE FAST ACTING <br />FUSES RATED 300 VOLTS, 60 HZ UP TO 15 AMPERES <br />COMPLETE WiTH FUSEHOLDER FOR FLUORESCENT BALLAST <br />PROTECTION. <br />1. FUSEHOLDER SHALL BE BUSSMANN TYPE HLR. <br />2. FUSE SHALL BE BUSSMANN TYPE GLR. <br />D. MOTOR STARTER CONTROL POWER TRANSFORMER CIRCUITS <br />SHALL BE FUSED AS RECOMMENDED BY THE EQUIPMENT <br />MANUFACTURER, <br />INDIVIDUALLY MOUNTED CIRCUIT BREAKERS <br />A. PROVIDE ENCLOSED CIRCUIT BREAKERS HAVING THE ELECTRICAL <br />CHARACTERISTICS, RATINGS AND AND MODIFICATIONS SHOWN ON <br />THE DRAWINGS. ALL ENCLOSED CIRCUIT BREAKERS SHALL HAVE <br />NEMA 1 GENERAL PURPOSE ENCLOSURES UNLESS NOTED <br />OTHERWISE, METAL NAMEPLATES, FRONT COVER MOUNTED, THAT <br />CONTAIN A PERMANENT RECORD OF CATALOG NUMBER AND <br />MAXIMUM RATING, AND HANDLES THAT ARE PADLOCKABLE IN <br />THE 'OFF' POSITION. <br />B• ALL CIRCUIT BREAKERS SHALL PROVIDE INVERSE TIME DELAY <br />AND INSTANTANEOUS PROTECTION FOR EACH POLE OF <br />BREAKER. ALL CIRCUIT BREAKERS MUST BE COMPLETELY <br />ENCLOSED IN A MOLDED CASE. AUTOMATIC OPERATION OF THE <br />CIRCUIT BREAKER SHALL BE OBTAINED BY MEANS OF THERMAL <br />AND/OR MAGNETIC DEVICES LOCATED IN EACH POLE OF THE <br />BREAKER. THE THERMAL DEVICE SHILL PROVIDE TIME DELAY <br />TRIPPING ON OVERLOADS, AND THE MAGNETIC DEVICE SHALL <br />PROVIDE INSTANTANEOUS TRIPPING ON SHORT CIRCUITS. THE <br />INSTANTANEOUS MAGNETIC TRIP SHALL BE ADJUSTABLE AND <br />ACCESSIBLE FROM THE FRONT OF THE BREAKER ON FRAME <br />SIZES ABOVE 100 AMPERES. NON-INTERCHANGABLE TRIP <br />BREAKERS SHALL HAVE THE TRIP UNIT SEALED TO PREVENT <br />TAMPERING. AMPERE RATINGS Stall BE CLEARLY VISIBLE. <br />CONTACTS SHALL BE OF NON -MOLDED SILVER ALLOY. ARC <br />EXTINCTION MUST BE ACCOMPUSHED BY MEANS OF ARC <br />CHUTES. <br />C. THE BREAKERS SHALL BE OPERATED BY A TOGGLE TYPE <br />HANDLE AND SHALL HAVE A QUICK -MAKE, QUICK -BREAK <br />OVER -CENTER SWITCHING MECHANISM THAT IS MECHANICAL <br />TRIP FREE SO THAT THE CONTACTS CAN NOT BE HELD CLOSED <br />AGAINST SHORT CIRCUITS AND ABNORMAL CURRENTS. TRIPPING <br />DUE TO OVERLOAD OR SHORT CIRCUIT SHALL BE CLEARLY <br />INDICATED BY THE HANDLE AUTOMATICALLY ASSUMING A <br />POSITION MIDWAY BETWEEN THE MANUAL "ON' AND 'OFF' <br />POSITIONS. ALL LATCH SURFACES SHALL BE GROUND AND <br />POLISHED. ALL POLES SHALL BE CONSTRUCTED SO THEY GIVE, <br />CLOSE AND TRIP SIMULTANEOUSLY. <br />D. THE MINIMUM INTERRUPTING RATINGS OF THE CIRCUIT BREAKER <br />SHALL BE AT LEAST EQUAL. TO THE AVAILABLE SHORT CIRCUIT <br />AT THE LINE TERMINALS. CIRCUIT BREAKER RATINGS, <br />MODIFICATIONS, ETC. SHALL BE AS INDICATED ON THE <br />DRAWINGS. <br />E. WHERE FRAME SIZE SHALL BE 100 AMPERES OR LESS, <br />MINIMUM CONTINUOUS AMP RATING WiTH UL LISTED <br />INTERRUPTING CAPACITY IN RMS SYMMETRICAL AMPERES AT <br />THE FOLLOWING VOLTAGES SHALL BE: <br />10,000 AMPS 240 VOLTS <br />14,000 AMPS 480 VOLTS <br />THESE BREAKERS SHALL HAVE FIXED TRIP UNITS FURNISHED <br />WITH BREAKERS <br />BREAKERS SHALL BE MANUFACTURED BY CUTLER HAMMER, <br />SIEMENS OR SQUARE D. <br />F. WHERE FRAME SIZE SHALL BE 250 AMPERES OR LESS <br />MINIMUM CONTINUOUS AMP RATING WITH UL LISTED <br />INTERRUPTING CAPACITY IN RMS SYMMETRICAL AMPERES AT <br />THE FOLLOWING VOLTAGES SHALL BE: <br />240 VOLTS 25,000 AMPS <br />480 VOLTS 22,000 AMPS <br />THESE BREAKERS SHALL HAVE INTERCHANGEABLE TRIP UNITS <br />FURNISHED WiTH BREAKER. <br />BREAKERS SHALL BE MANUFACTURED BY CUTLER HAMMER, <br />SIEMENS OR SQUARE D. <br />G. WHERE FRAME SIZE SHALL BE ABOVE 250 AMPERES, MINIMUM <br />CONTINUOUS AMP RATING WiTH UL LISTED INTERRUPTING <br />CAPACITY IN RMS SYMMETRICAL AMPERES AT THE FOLLOWING <br />VOLTAGES SHALL BE: <br />240 VOLTS 42,000 AMPS <br />480 VOLTS 30,000 AMPS <br />THESE BREAKERS SHALL HAVE INTERCHANGEABLE, ADJUSTABLE <br />RATING TRIP PLUGS FURNISHED WITH BREAKER. <br />BREAKERS SHALL BE CUTLER HAMMER "SELTRONIC" OR <br />SIEMENS "SENSITRIP" OR SQUARE D. <br />16500I LIGHTING <br />SUBMITTALS <br />A. SUBMIT UST OF MANUFACTURERS FOR UGHTiNG FIXTURES, <br />LAMPS AND LUMINARIES ACCESSORIES IN ACCORDANCE WiTH <br />LIGHTING FIXTURE SCHEDULE ONLY. <br />B. SUBMIT CUTS, SHOP DRAWINGS AND PHOTOMETRIC DATA FOR <br />EACH FIXTURE TYPE. PHOTOMETRIC DATA SHALL BE BASED ON <br />INDEPENDENT TESTING LABORATORY REPORTS, SUCH AS ETL, <br />ITL, ERL, AND UKE REPORTS. TESTING PROCEDURES SHALL BE <br />IN ACCORDANCE WiTH APPLICABLE IES STANDARDS. <br />LIGHTING FIXTURES <br />A. ALL INTERIOR, EXTERIOR AND EMERGENCY LIGHTING FIXTURES <br />SHALL BE COMPLETE WITH ALL REQUIRED ACCESSORIES AND <br />ATTACHMENTS. <br />B. FIXTURES SHALL BEAR UL LABEL AND SHALL BE WIRED AND <br />INSTALLED IN FULL COMPLIANCE WiTH APPLICABLE CODES. <br />C. THE OMISSION OF A TYPE IN THE LIGHTING FIXTURE SCHEDULE <br />SHALL NOT RELIEVE CONTRACTOR OF RESPONSIBILITY OF <br />FURNISHING ALL REQUIRED FIXTURES OF PROPER TYPE AS <br />SHOWN ON DRAWINGS. <br />D. FIXTURES SHALL BE RECESSED, SURFACE, OR PENDANT TYPE, <br />AS SPECIFIED IN FIXTURE SCHEDULE, AND SHALL INCLUDE <br />SOCKETS, DIFFUSERS, CEIUNG CANOPIES AND STEMS, HICKEYS, <br />AND ALL OTHER NECESSARY ACCESSORIES. <br />E. RECESSED MOUNTED UGHTiNG FIXTURES SHALL BE <br />CONNECTED TO A JUNCTION BOX WITH FLEXIBLE CONDUIT. <br />F. INCANDESCENT AND HID LAMP HOLDERS SHALL BE MADE OF <br />PORCELAIN HOUSING AND COPPER SCREW SHELLS, RATED AT <br />NO LESS THAN 660 WATTS, 250 VOLTS. LAMP HOLDERS SHALL <br />BE FIRMLY HELD IN PLACE SO AS TO PREVENT DAMAGE TO <br />CONDUCTOR INSULATION AND TO PREVENT SOCKET TURNING <br />DURING LAMP REPLACEMENT. PLASTIC LAMP HOLDERS ARE NOT <br />ACCEPTABLE. <br />G. ENAMELED FINISHES SHALL BE ELECTROSTATICALLY APPLIED <br />AND BAKED. FINISH OF FIXTURES SHALL BE UNIFORM IN <br />QUALITY AND APPEARANCE. DURABLE, AND FREE FROM <br />DEFECTS. <br />H. LABELS AND INSCRIPTIONS IN FIXTURES SHALL BE LOCATED IN <br />UNOBTRUSIVE PLACES SO THAT THEY ARE NOT VISIBLE TO <br />OCCUPANTS IN THE COMPLETED INSTALLATION. <br />I. SPECIAL AND/OR CUSTOM UGHTiNG FIXTURES, WIRING, LAMPS, <br />BALLASTS. AND OTHER ACCESSORIES SHALL BE AS INDICATED <br />ON DRAWINGS. <br />J. PLASTER FRAMES. ANGLES, AND CHANNELS FOR RECESSED <br />LIGHTING FIXTURES SHALL BE FURNISHED UNDER THIS <br />SECTION WHERE REQUIRED. PLASTER FRAMES SHALL BE <br />SPECIFICALLY CONSTRUCTED FOR THE APPLICATION BY THE <br />MANUFACTURER OF THE RELATED LIGHTING FIXTURE. <br />K. RECESSED COMPACT FLUORESCENT AND INCANDESCENT <br />LIGHTING FIXTURES SHALL BE THE PRODUCT OF ONE <br />MANUFACTURER UNLESS OTHERWISE NOTED. <br />L. LAY -IN RECESSED FIXTURES IN GRID -TYPE CEIUNG SHALL BE <br />INSTALLED AND SUPPORTED IN ACCORDANCE WiTH LOCAL <br />CODES. VERIFY ADEQUATE SUPPORT OF CEIUNG GRID TO <br />BUILDING STRUCTURE AND SECURE UGHTING FIXTURE TO GRID <br />BY MECHANICAL. MEANS SUCH AS SCREWS, BOLTS OR <br />APPROVED CUPS. <br />M. PENDANT OR SURFACE -MOUNTED FIXTURES SHALL BE <br />PROVIDED WiTH REQUIRED MOUNTING DEVICES AND <br />ACCESSORIES, INCLUDING HICKEYS, STUD EXTENSIONS, BALL <br />AUGNERS, CANOPIES AND STEMS. MOUNTING STEMS OF <br />PENDENT FIXTURES SHALL BE OF THE CORRECT LENGTH TO <br />UNIFORMLY MAINTAIN THE FIXTURE HEIGHTS SHOWN ON THE <br />DRAWINGS. VARIATION IN MOUNTING INDIVIDUAL FIXTURES SHALL <br />NOT EXCEED 1/4". THEIGHT SHALL NOT VARY MORE THAN <br />1/2" FROM THE FLOOR MOUNTING HEIGHT SHOWN ON THE <br />DRAWINGS. <br />N. UNDERCABINET LIGHTING FIXTURES SHALL BE CONNECTED TO <br />THE NEAREST 120V RECEPTACLE CIRCUIT AND CONTROLLED BY <br />AN INTEGRAL ROCKER SWITCH. MULTIPLE ADJACENT FIXTURES <br />SHALL BE CONTROLLED BY ONE INTEGRAL ROCKER SWITCH. <br />0. ANY LAMPS, BALLASTS, REFLECTORS, LENS, DIFFUSERS, SIDE <br />PANELS OR OTHER PARTS DAMAGED PRIOR TO THE FiNAL <br />INSPECTION SHALL BE REPLACED AT NO D(PENSE TO THE <br />OWNER. <br />P. AT TIME OF FINAL INSPECTION, ALL FIXTURES AND EQUIPMENT <br />SHALL BE FULLY LAMPED, AND SHALL BE COMPLETE WiTH <br />REQUIRED LENSES OR COMPONENTS NECESSARY. <br />BALLASTS <br />A. PROVIDE BALLASTS CONFORMING TO UL AND ANSI <br />STANDARDS USTING AND DISPLAYING LABELS OR SYMBOLS OF <br />LISTING BY UL. AND OF CERTIFICATIONS BY THE CBM, AS <br />TESTED BY THE ETL DESIGN, FABRICATE AND ASSEMBLE <br />COMPONENT PARTS OF BALLASTS IN ACCORDANCE WiTH THE <br />LATEST CODE REQUIREMENTS. MARK BALLASTS "CLASS P" <br />INDICATING APPROVED INTEGRAL BALLAST PROTECTION. THIS <br />BALLAST PROTECTION SHALL BE PROVIDED BY A BUILT-IN <br />SELF -RESETTING THERMALLY ACTUATED DEVICE THAT SHALL <br />REMOVE THE BALLAST FROM LINE WHEN EXCESSIVE BALLAST <br />TEMPERATURE IS REACHED. <br />B. PROVIDE BALLASTS HAVING THE LOWEST SOUND RATING <br />AVAILABLE FOR THE LAMPS SPECIFIED AND CLEARLY SHOWING <br />THEIR RESPECTIVE SOUND RATINGS. REPLACE BALLASTS FOUND <br />BY ARCHITECT OR ENGINEER TO BE UNDULY NOISY, WITHOUT <br />CHARGE, PRIOR TO ACCEPTANCE OF THE PROJECT. <br />C. PROVIDE IDENTICAL BALLASTS WITHIN EACH FIXTURE TYPE <br />UNLESS OTHERWISE NOTED. <br />D. BALLASTS FOR FLUORESCENT LAMPS SHALL BE SUITABLE FOR <br />THE ELECTRICAL CHARACTERISTICS OF THE SUPPLY CIRCUITS <br />TO WHICH THEY ARE TO BE CONNECTED AND WHICH ARE <br />SUITABLE FOR OPERATING THE SPECIFIED LAMPS. PROVIDE <br />BALLASTS WHICH ARE ELECTRONIC, HIGH POWER FACTOR, <br />SUPER LOW TEMPERATURE RISE, LOW HARMONIC DISTORTION, <br />HIGH -FREQUENCY (ABOVE 20KHZ) FULL OUTPUT TYPE, FOR <br />T-8 OR T-12 RAPID START 1-,2-,3- OR 4-LAMP <br />COMBINATIONS AS REQUIRED BY THE FIXTURE DESCRIBED IN <br />THE LIGHTING FIXTURE SCHEDULE. PROVIDE BI-LEVEL <br />SWITCHING OR DIMMING BALLASTS AS REQUIRED. <br />E. COMPACT FLUORESCENT FIXTURES SHALL BE PROVIDED WiTH <br />4-PIN HIGH POWER FACTOR ELECTRONIC BALLASTS AS NOTED <br />ON DRAWINGS. BALLASTS SHUT HAVE INTERNAL CIRCUITRY TO <br />DETECT END OF LAMP LIFE AND SHUT DOWN BALLAST. <br />PROVIDE DIMMING BLASTS WHERE REQUIRED. <br />F. HIGH INTENSITY DISCHARGE LIGHTING FIXTURE BALLASTS <br />SHALL BE HIGH POWER FACTOR AUTO -TRANSFORMER TYPE <br />G. BALLASTS SHALL HAVE A (2) YEAR WARRANTY FROM DATE OF <br />ACCEPTANCE OF THE COMPLETED INSTALLATION. <br />H. APPROVED BALLAST MANUFACTURERS SHALL BE TRIAD, <br />MAGNETEK, EBT, OSRAM/SYLVANIA OR ADVANCE. <br />I. PROVIDE ALL FLUORESCENT AND COMPACT FLUORESCENT <br />BALLASTS WiTH REQUIRED OVERLOAD PROTECTION. FUSE <br />HOLDER AND FUSE SHALL BE BUSSMANN HLR/GLR. <br />LAMPS <br />A. PROVIDE ELECTRIC LAMPS AS REQUIRED DURING <br />CONSTRUCTION, INCLUDING LAMPS FOR FIXTURE FURNISHED BY <br />OTHERS. <br />B. PROVIDE A COMPLETE SET OF NEW LAMPS IN EACH FiXTURE <br />AS SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE, ON <br />DRAWINGS, AND AS DESCRIBED BELOW. UPON COMPLETION OF <br />THE WORK, LEAVE FIXTURES AND LIGHTING EQUIPMENT <br />COMPLETELY LAMPED AND IN PROPER OPERATING CONDITION. <br />C. UNLESS SPECIFIED OTHERWISE, PROVIDE LAMPS AS FOLLOWS: <br />1) FOR UNEAR FLUORESCENT FIXTURES, PROVIDE ENERGY <br />SAVING 32 WATT T8 OR 34 WATT T12, "RAPID START" <br />LAMPS, WHICH DELVER AT LEAST 2900 INITIAL LUMENS <br />FOR STRAIGHT LAMPS, WITH 35W KELVIN COLOR, AS <br />INDICATED ON THE UGH71NG FIXTURE SCHEDULE. <br />2) FOR COMPACT FLUORESCENT FIXTURES, PROVIDE ENERGY <br />SAVING LAMPS OF THE WATTAGE INDICATED ON THE <br />LIGHTING FIXTURE SCHEDULE WITH 35W KELVIN <br />COLOR TEMPERATURE, UNLESS OTHERWISE INDICATED. <br />3) FOR INCANDESCENT FIXTURES, PROVIDE 130V LAMPS <br />UNLESS OTHERWISE INDICATED. <br />4) FOR OTHER FIXTURES, PROVIDE LAMPS AS SPECIFIED, OR <br />IF NOT SPECIFIED, PROVIDE AS REQUIRED BY THE <br />UGHnNG FIXTURE MANUFACTURER. IF SPECIFICATION IS <br />NOT COMPLETE, CONTACT ENGINEER FOR CLARIFICATION. <br />5) ALL LAMPS OF THE SAME CHARACTERISTICS SHALL BE <br />PROVIDED BY THE SAME MANUFACTURER UNLESS <br />SPECIFICALLY INDICATED OTHERWISE. <br />D. APPROVED LAMP MANUFACTURERS SHALL. BE GENERAL <br />ELECTRIC, PHILIPS. OSRAM/SYLVANIA, OR VENTURE. <br />EXIT, STAIRWAY AND DIRECTIONAL SIGNS <br />A. PROVIDE SIGNS IN COMPLIANCE WITH APPLICABLE CODES. <br />B. COLOR AND SIZE OF LETTERS, ARROWS AND FACEPLATE <br />BACKGROUND SHALL COMPLY WiTH APPLICABLE CODES. <br />AIR HANDUNG UGHTiNG FIXTURES <br />A. CONSTRUCT AIR HANDUNG TYPE LIGHTING FIXTURES IN A <br />MANNER WHICH WILL PERFECTLY ACCOMMODATE THE SECURE <br />AND AIRTIGHT ATTACHMENT OF ALL AIR HANDUNG COMPONENTS <br />THERETO. THE AIR TERMINAL AND UGHTING FIXTURE <br />MANUFACTURERS SHALL COORDINATE FIT, PERFORMANCE, AND <br />INSTALLATION REQUIREMENTS. FIXTURES OF THE SAME TYPE <br />SHALL BE CONSTRUCTED TO PRESENT THE SAME APPEARANCE <br />IN THE CEIUNG, WHETHER ACTIVE OR INACTIVE. <br />B. A QUANTITY OF AIR HANDLING TYPE FIXTURES ARE NOT <br />CONNECTED TO THE VENTILATING SYSTEM INITIALLY. SUCH <br />FIXTURES ARE DESIGNED INACTIVE, BUT SHALL HAVE THE <br />CAPABIUTY OF SUBSEQUENT ACTIVATION AND SHALL BE <br />PROVIDED UNDER THIS SECTION WITH REMOVABLE, AIRTIGHT <br />BLANKING PLATES ARE REMOVED AND APPROPRIATE AIR <br />TERMINALS ARE INSTALLED. <br />INSTALLATION <br />A. INSTALL UGHTiNG FIXTURES AND LAMPS AS SPECIFIED ON <br />DRAWINGS AND SCHEDULES. <br />B. PENDANT TYPE FIXTURES SHALL BE HUNG AT HEIGHTS AS <br />REQUIRED AND SPECIFIED. <br />C. FIXTURE LOCATIONS SHALL BE AS INDICATED ON THE <br />ARCHITECTURAL REFLECTED CEIUNG PLAN. THE ELECTRICAL <br />LIGHTING PLAN SHALL BE THE SECOND POINT OF REFERENCE. <br />ADDITIONAL. INFORMATION REGARDING FIXTURE LOCATION MAY BE <br />NOTED ON THE UGHTING FIXTURE SCHEDULE. <br />D. PROVIDE ALL LAMPS REQUIRED, INCLUDING REPLACEMENTS FOR <br />BURNED OUT LAMPS, UNTIL FINAL ACCEPTANCE OF THE <br />COMPLETED WORK. NO LIGHTING FIXTURE OR SIGN WILL BE <br />INSTALLED WITHOUT LAMPS. <br />E. IF PERMANENT UGHTING FIXTURES ARE TO BE USED IN UEU <br />OF TEMPORARY LIGHTING DURING THE CONSTRUCTION PERIOD. <br />THIS SHALL BE DONE ONLY AS PERMITTED BY ARCHITECT OR <br />ENGINEER, WHO MAY REQUIRE THE NEW LAMPS BE INSTALLED <br />AND FIXTURES CLEANED AT THE 11ME OF SUBSTANTIAL <br />COMPLETION AND OWNER OCCUPANCY. <br />F. OPEN DOWNUGHT REFLECTORS AND PARABOLIC LOUVERS <br />SHALL BE INSTALLED IN PLACE AFTER THE PROJECT BECOMES <br />DUST FREE. INSTALLER SHALL WEAR GLOVES TO PRECLUDE <br />SMUDGING THE REFLECTOR SURFACE AND LOUVERS. <br />G. PROTECTION: PROTECT INSTALLED FIXTURES FROM DAMAGE <br />DURING REMAINDER OF CONSTRUCTION PERIOD. <br />A. AFTER INSTALLATION, ADJUSTMENT AND INSPECTION, <br />FUNCTIONAL TESTS SHALL BE PERFORMED OF ALL LIGHTING <br />FIXTURES IN THE PRESENCE OF OWNER. THE TESTS SHALL <br />DEMONSTRATE THAT THE FIXTURES HAVE BEEN INSTALLED <br />PROPERLY AND FUNCTION AS REQUIRED BY THE CONTRACT <br />DOCUMENTS. <br />AIMING AND FOCUSING <br />A. INSTALL ALL ADJUSTABLE FIXTURES PER MANUFACTURER'S <br />RECOMMENDATIONS AND TO PROVIDE MAXIMUM UNIFORM <br />COVERAGE. <br />SPECIAL AREA LIGHTING <br />A. ANGULAR ADJUSTMENT AND FINAL PLACEMENT OF UGHTING <br />FIXTURES FOR DESIGNATED SPECIAL AREA LIGHTING SHALL BE <br />A FIELD CONDITION AND DETERMINED AT SITE. <br />B. CONTRACTOR SHALL COORDINATE WiTH ARCHITECT TO ESTABLISH <br />A TIME AND DATE FOR TRIAL LAYOUT OF UGHTING FIXTURES. <br />ARCHITECT OR ENGINEER SHALL BE PRESENT AT TRIAL LAYOUTS <br />TO FINALIZE FIXTURE PLACEMENT. <br />F16-70011 SYSTEMS <br />SUBMITTALS <br />A. SUBMIT MANUFACTURER'S DATA AND SHOP DRAWINGS FOR ALL <br />SYSTEMS. <br />B. SUBMIT WIRING DIAGRAMS WHERE REQUIRED. <br />TELEPHONE/DATA SYSTEM <br />A. PROVIDE AN EMPTY TELEPHONE/DATA RACEWAY SYSTEM AS <br />SHOWN ON THE DRAWINGS AND SPECIFIED. <br />B. WALL OUTLETS SHALL CONSIST OF A FLUSH MOUNTED, <br />MINIMUM 4 INCH SQUARE, 2-1/8 INCH DEEP OUTLET BOX <br />WITH SINGLE GANG PLASTER RING. <br />C. STUB CONDUIT FROM OUTLET BOX INTO ACCESSIBLE CORRIDOR <br />CEIUNG SPACE. CONDUIT SIZES SHALL BE AS SHOWN ON <br />DRAWINGS, OR MINIMUM 3/4 INCH. <br />D. WALL OUTLETS FOR MODULAR FURNITURE FEEDS SHALL <br />CONSIST OF A FLUSH MOUNTED 4 11/16 INCH SQUARE, 2 <br />1/8 INCH DEEP OUTLET BOX WiTH TWO -GANG PLASTER RING <br />AND 1 1/4 INCH CONDUIT STUBBED INTO ACCESSIBLE CEIUNG <br />SPACE. <br />E. PROVIDE INSULATED BUSHINGS ON BOTH ENDS OF CONDUITS. <br />F. PROVIDE 4'x8'x3/4" MARINE GRADE PLYWOOD PANTED TWO <br />COATS OF GRAY INTERIOR ENAMEL ON ALL SIDES IN <br />TELEPHONE CLOSETS AND WHERE INDICATED ON PLANS. <br />A. PROVIDE A COMPLETE EMPTY CONDUIT SYSTEM FOR THE <br />SECURITY SYSTEM OUTLETS. CONDUITS SHALL BE TERMINATED <br />IN THE ASSOCIATED COMMUNICATION SYSTEMS CLOSET. MINIMUM <br />CONDUIT SIZE SHALL BE 3/4 INCH. <br />B. CARD READER OUTLETS SHALL CONSIST OF A FLUSH <br />MOUNTED, MINIMUM 4 INCH SQUARE, 2 1/2 INCH DEEP <br />OUTLET BOX WITH A TWO -GANG PLASTER RING. JACKS AND <br />WALL PLATES WILL BE PROVIDED UNDER A SEPARATE <br />CONTRACT. <br />C. PROVIDE A CONDUIT CONNECTION TO DOOR FRAMES FOR <br />ELECTRIC DOOR STRIKES AND TO SENSORS WHERE SHOWN. <br />PROVIDE OUTLET BOX FOR SENSOR, FLUSH MOUNTED IN <br />CEILING. PROVIDE 120V CIRCUIT FROM NEAREST UNSWITCHED <br />RECEPTACLE CIRCUIT UNLESS OTHERWISE NOTED. <br />D. PROVIDE INSULATED BUSHINGS ON BOTH ENDS OF CONDUITS. <br />A. RELOCATE EXISTING DEVICES AND PROVIDE NEW DEVICES AS <br />REQUIRED FOR THE EXISTING FIRE ALARM SYSTEM. DEVICES <br />SHALL MATCH EXISTING SYSTEM DEVICES. <br />B. CONSULT WiTH MANUFACTURER AND INSTALUNG CONTRACTOR <br />FOR INSTALLATION OF EQUIPMENT AND MODIFICATIONS TO THE <br />EXISTING SYSTEM. <br />C. REPROGRAM EXISTING FIRE ALARM CONTROL PANELS AND <br />PROVIDE NEW MODULES AND DEVICES AS REQUIRED. <br />D. EXTEND EXISTING WIRING AND CONDUIT AND PROVIDE NEW <br />WIRING AND CONDUIT AS REQUIRED FOR A COMPLETE SYSTEM. <br />E. FIRE ALARM SYSTEM WIRING SHALL BE VERIFIED WITH THE <br />EQUIPMENT MANUFACTURER. ALL WIRE SHALL BE #14 AWG <br />SOLID COPPER CONDUCTOR WITH N.E.C. TYPE "THHN' 600 <br />VOLT INSULATION, UNLESS OTHERWISE NOTED. COLOR CODE <br />WIRING TO MATCH THE EXISTING BUILDING FIRE ALARM SYSTEM. <br />F. FIRE ALARM SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT, <br />MINIMUM SIZE 3/4". <br />G. UPON COMPLETION OF THE INSTALLATION, PROVIDE A <br />COMPLETE TEST OF THE SYSTEM TO VERIFY PROPER <br />OPERATION. <br />MEP / FP Engineer <br />EPSTEIN <br />600 West Fulton <br />Chicago, IL 60661 <br />312.454.9100 <br />Design Architect <br />EPSTEIN <br />600 West Fulton <br />Chicago, IL 60661 <br />312.454.9100 <br />Nestle Waters North America <br />Nestle Waters North America <br />4330 20th Street <br />Zephyrhills, Florida 33542-6703 <br />972.462.3663 <br />nfestIe <br />Waters <br />Expires <br />FEB 2 8 Z015 <br />`ears, I_ ."Et. s75, <br />STATE OF ; _ C <br />Ir <br />0 P . �,. <br />4 <br />3 <br />09.18.2013 <br />09.11.2013 <br />ISSUE FOR PERMIT <br />ISSUE FOR BIDS <br />2 <br />09.03.2013 <br />CD REVIEW PACKAGE <br />1 <br />NO. <br />08.16.2013 <br />DATE <br />DD REVIEW PACKAGE <br />REVISIONS/ISSUANCES <br />�PSTEIN <br />Architecture <br />Chicago <br />Interiors <br />New York <br />Engineering <br />Bucharest <br />Construction <br />Warsaw <br />600 W. Fulton Street <br />Chicago, IL 60661-1259 <br />T 312.454.9100 <br />www.epsteinglobal.com <br />PROJECT NUMBER: 12386 <br />PROJECT MANAGER: JK <br />ARCH/ENG: DD <br />SCALE: NOT TO SCALE <br />DRAWN BY: DD <br />CHECKED BY: MS <br />ELECTRICAL <br />SPECIFICATIONS <br />E-005 <br />A. Epstein and Sons International, Inc. All rights reserved. <br />