A. PROVIDE DEAD -FRONT POWER DISTRIBUTION PANELBOARDS AS
<br />INDICATED, WITH PANELBOARD SWITCHING AND PROTECTIVE
<br />DEVICES IN QUANTITIES, RATINGS, TYPES, AND WiTH
<br />ARRANGEMENT SHOWN, WiTH ANTi-TURN SOLDERLESS
<br />PRESSURE TYPE MAIN LUG CONNECTORS APPROVED FOR USE
<br />WiTH COPPER CONDUCTORS. SELECT UNIT WiTH FEEDERS
<br />CONNECTING AT TOP OF PANEL UNLESS OTHERWISE INDICATED
<br />ON PLANS. EQUIP WITH COPPER BUS BARS WiTH NOT LESS
<br />THAN 98X CONDUCTIVITY, AND WiTH FULL-SIZED NEUTRAL BUS.
<br />PROVIDE SUITABLE LUGS ON NEUTRAL BUS FOR OUTGOING
<br />FEEDERS REQUIRING NEUTRAL CONNECTIONS. PROVIDE FUSIBLE
<br />SWITCH OR MOLDED -CASE CIRCUIT BREAKER MAIN AND
<br />BRANCH DEVICES AS INDICATED. CIRCUIT BREAKERS Shall
<br />HAVE TOGGLE HANDLES THAT INDICATE WHEN TRIPPED. WHERE
<br />MULTIPLE -POLE BREAKERS ARE INDICATED, PROVIDE WITH
<br />COMMON TRIP SO OVERLOAD ON ONE POLE WILL TRIP ALL
<br />POLE SIMULTANEOUSLY. PROVIDE ALL. PANELBOARDS WITH BARE
<br />UNINSULATED GROUNDING BARS WiTH TERMINALS, BOLTED TO
<br />ENCLOSURES. SELECT ENCLOSURES FABRICATED BY SAME
<br />MANUFACTURER AS PANELBOARDS, WHICH MATE AND MATCH
<br />PROPERLY WITH PANELBOARDS.
<br />LIGHTING AND APPLIANCE PANELBOARDS
<br />A. PROVIDE DEAD -FRONT SAFETY TYPE LIGHTING AND APPLIANCE
<br />PANELBOARDS AS INDICATED, WiTH SWITCHING AND PROTECTIVE
<br />DEVICES IN QUANTITIES, RATINGS, TYPES AND ARRANGEMENTS
<br />SHOWN; WITH ANTI -BURN SOLDERLESS PRESSURE TYPE LUG
<br />CONNECTORS APPROVED FOR USE WiTH COPPER CONDUCTORS;
<br />CONSTRUCT UNIT FOR CONNECTING FEEDERS AT TOP OF PANEL
<br />UNLESS OTHERWISE INDICATED ON DRAWINGS; EQUIP WITH
<br />COPPER BUS BARS, FULL SIZED NEUTRAL BAR, WiTH BOLT -ON
<br />TYPE HEAVY DUTY, QUICK -MAKE, QUICK -BREAK, SINGLE -POLE
<br />CIRCUIT BREAKERS SEQUENCE -PHASED, UNLESS OTHERWISE
<br />INDICATED WiTH TOGGLE HANDLES THAT INDICATE WHEN
<br />TRIPPED. COPPER BUSBARS AND DETAILS SHALL BE 800
<br />AMPERES PER SQUARE INCH SECTION. PANELBOARDS SHALL
<br />HAVE A SHORT CIRCUIT RATING GREATER THAN THE SHORT
<br />CIRCUIT CURRENT AVAILABLE AT THE LINE LUGS. PROVIDE
<br />SUITABLE LUGS ON NEUTRAL BUS FOR EACH OUTGOING
<br />FEEDER REQUIRED. PROVIDE ALL PANELBOARDS WITH BARE
<br />UNINSULATED GROUNDING BARS WITH TERMINALS, BOLTED TO
<br />ENCLOSURES. SELECT ENCLOSURES FABRICATED BY SAME
<br />MANUFACTURER AS PANELBOARDS, WHICH MATE AND MATCH
<br />PROPERLY WITH PANELBOARDS.
<br />EACH PANELBOARD COVER AND TRIM SHALL BE THOROUGHLY
<br />CLEANED AND BONDERIZED BEFORE PAINTING. PAINTING SHALL.
<br />CONSIST OF TWO COATS OF HIGH QUALITY OIL BASE PAINT OF
<br />LIGHT GRAY COLOR, BOTH INSIDE AND OUTSIDE. ALL
<br />PANELBOARDS OF THE SAME TYPE SHALL BE OF THE SAME
<br />MANUFACTURER. THE USE OF PLUG-IN TYPE CIRCUIT
<br />BREAKERS IS PROHIBITED.
<br />B. PANELBOARDS SERVING NON-UNEAR LOADS SHALL HAVE
<br />NEUTRAL BUS RATED AT 20OX OF THE PHASE BUS.
<br />C. PROVIDE AN ISOLATED GROUND BUS WHERE INDICATED.
<br />PANELBOARD ENCLOSURES
<br />A. PROVIDE GALVANIZED SHEET STEEL CABINET TYPE ENCLOSURES,
<br />IN SIZES AND NEMA TYPES AS INDICATED, CODEGAGE, MINIMUM
<br />16-GAGE THICKNESS. CONSTRUCT WiTH MULTIPLE KNOCKOUTS
<br />AND WIRING GUTTERS. PROVIDE FRONTS WITH ADJUSTABLE TRIM
<br />CLAMPS, AND DOORS WITH FLUSH LOCKS AND KEYS, ALL
<br />PANELBOARD ENCLOSURES KEYED ALIKE, WiTH CONCEALED
<br />PIANO DOOR HINGES AND DOOR SWINGS AS INDICATED. DOORS
<br />OVER 48" HIGH SHALL HAVE A 3-POINT COMBINATION CATCH
<br />AND LOCK WiTH VAULT TYPE HANDLE PROVIDE 6 KEYS TO THE
<br />OWNER. EQUIP WiTH INTERIOR CIRCUIT -DIRECTORY FRAME. AND
<br />CARD WITH CLEAR PLASTIC COVERING. PROVIDE BAKED GRAY
<br />ENAMEL FINISH OVER A RUST INHIBITOR COATING. DESIGN
<br />ENCLOSURES FOR RECESSED MOUNTING.
<br />B. WHERE DOUBLE TUB PANELBOARDS ARE INDICATED, EACH TUB
<br />SHALL CONTAIN THE SAME NUMBER OF BREAKERS OR SPACES.
<br />BOX AND TRIM SIZES SHALL BE IDENTICAL
<br />C. CONNECT DOUBLE TUB PANELBOARDS WiTH CONDUIT NIPPLES
<br />HAVING INSULATED BUSHINGS ON BOTH ENDS. PROVIDE PHASE,
<br />NEUTRAL AND GROUNDING SUB -FEED CONDUCTORS OF THE
<br />SAME SIZE AS THE FEEDER CONDUCTORS.
<br />T Lil � �] y �aa r•� ��i l:i�il� !>111:�y ! 3
<br />A. PROVIDE FACTORY -ASSEMBLED, MOLDED -CASE CIRCUIT
<br />BREAKERS OF FRAME SIZES, CHARACTERISTICS, AND RATINGS
<br />INCLUDING RMS SYMMETRICAL INTERRUPTING RATINGS AS
<br />INDICATED. SELECT BREAKERS WiTH PERMANENT THERMAL AND
<br />INSTANTANEOUS MAGNETIC TRIP, AND WITH FAULT -CURRENT
<br />UMiTING PROTECTION, AMPERE RATINGS AS INDICATED. CIRCUIT
<br />BREAKERS WiTH GROUND FAULT INTERRUPTER SHALL BE
<br />FURNISHED ON CIRCUITS FEEDING RECEPTACLES, OUTLETS,
<br />UGHTING FIXTURES AND SINGLE PHASE FIXED EQUIPMENT
<br />LOCATED IN WET AREAS, SUCH AS OUTDOOR RECEPTACLES,
<br />KITCHEN OUTLETS, HYDROTHERAPUTIC EQUIPMENT. MULTIPLE
<br />POLE CIRCUIT BREAKERS SHALL BE ARRANGED IN ORDER
<br />BELOW SINGLE POLE CIRCUIT BREAKERS IN ORDERLY MANNER.
<br />CONSTRUCT WiTH OVERCENTER, TRIP -FREE, TOGGLE -TYPE
<br />OPERATING MECHANISMS WITH QUICK -MAKE. QUICK -BREAK
<br />ACTION AND POSITIVE HANDLE TRIP INDICATION. CONSTRUCT
<br />BREAKERS FOR MOUNTING AND OPERATING IN ANY PHYSICAL
<br />POSITION, AND OPERATING IN AN AMBIENT TEMPERATURE OF 40
<br />DEGREES CELSIUS. PROVIDE BREAKERS WITH MECHANICAL
<br />SCREW TYPE REMOVABLE CONNECTOR LUGS, AL/CU, RATED 75
<br />DEGREES CELSIUS.
<br />B. CIRCUIT BREAKERS PROTECTING MULTI -MOTOR AND
<br />COMBINATION -LOAD HEATING. AR CONDITIONING, AND
<br />REFRIGERATION EQUIPMENT SHALL BE UL LISTED FOR THIS
<br />APPLICATION AND MARKED "HACR TYPE" IN ACCORDANCE WiTH
<br />NEMA STANDARDS.
<br />EXISTING SWITCHBOARDS & POWER DISTRIBUTION PANELBOARDS
<br />A. ADD NEW FUSIBLE SWITCH OR CIRCUIT BREAKER TYPE BRANCH
<br />CIRCUIT DEVICES TO EXISTING SWITCHBOARDS AND POWER
<br />DISTRIBUTION PANELBOARDS AS REQUIRED.
<br />B. ALL NEW DEVICES SHALL BE THE SAME MANUFACTURER. TYPE
<br />AND INTERRUPTING CAPACITY AS THE ORIGINAL EQUIPMENT.
<br />C. PROVIDE NEW NAMEPLATES UPON COMPLETION OF ALL WIRING.
<br />EXECUTION
<br />A. FASTEN PANELBOARD ENCLOSURES FIRMLY TO WALLS AND
<br />STRUCTURAL SURFACES, ENSURING THAT THEY ARE
<br />PERMANENTLY AND MECHANICALLY ANCHORED.
<br />B. FILL OUT PANELBOARD CIRCUIT DIRECTORY CARD UPON
<br />COMPLETION OF INSTALLATION WORK FOR ALL NEW PANELS.
<br />C. INSERT FUSES, IF ANY, OF RATINGS INDICATED, WITHIN
<br />INSTALLED PANELBOARDS.
<br />D. FOR EXISTING PANELBOARDS, NUMBER ASSOCIATED WiTH EACH
<br />BRANCH CIRCUIT OUTLET IDENTIFIES THE BRANCH CIRCUIT TO
<br />WHICH THE DEVICE SERVED BY THE OUTLET IS TO BE
<br />CONNECTED. THE CIRCUIT NUMBER INDICATED IS FOR
<br />REFERENCE AND GUIDANCE TO THIS CONTRACTOR AND IS NOT
<br />INTENDED TO UMIT THE PANELBOARD CIRCUITRY ALL BRANCH
<br />CIRCUITS SHALL BE CONNECTED TO BREAKERS AT THE
<br />ELECTRICAL CONTRACTOR'S DISCRETION, IN ACCORDANCE WiTH
<br />CIRCUIT REQUIREMENTS. THE ACTUAL CIRCUIT NUMBERS USED
<br />SHALL BE INDICATED ON THE CONTRACTORS AS -BUILT'
<br />DRAWINGS. THE BALANCING OF ALL LOADS SHALL BE THE
<br />ELECTRICAL CONTRACTOR'S RESPONSIBILITY.
<br />GROUNDING
<br />A. PROVIDE EQUIPMENT GROUNDING CONNECTIONS FOR
<br />PANELBOARD ENCLOSURES AS INDICATED. TIGHTEN
<br />CONNECTIONS TO COMPLY WITH TIGHTENING TORQUES IN UL
<br />486A TO ASSURE PERMANENT AND EFFECTIVE GROUNDS.
<br />FIELD QUALITY CONTROL
<br />A. PRIOR TO ENERGIZATiON OF ELECTRICAL CIRCUITRY, CHECK ALL
<br />ACCESSIBLE CONNECTIONS TO MANUFACTURER'S TIGHTENING
<br />TORQUE SPECIFICATIONS.
<br />B• PRIOR TO ENERGIZATION OF PANELBOARDS, CHECK FEEDERS
<br />WiTH GROUND RESISTANCE TESTER PHASE -TO -PHASE AND
<br />PHASE -TO -GROUND INSULATION RESISTANCE LEVELS TO
<br />ENSURE REQUIREMENTS ARE FULFILLED.
<br />C. PRIOR TO ENERGIZATION, CHECK PANELBOARDS FOR
<br />ELECTRICAL. CONTINUITY OF CIRCUITS AND SHORT-CIRCUITS.
<br />16475 OVERCURRENT PROTECTIVE DEVICES
<br />SUBMITTALS
<br />A. SUBMIT PRODUCT DATA AND SHOP DRAWINGS ON
<br />OVER -CURRENT PROTECTIVE DEVICES INCLUDING
<br />SPECIFICATIONS, ELECTRICAL CHARACTERISTICS, INSTALLATION
<br />INSTRUCTIONS, FURNISHED SPECIALTIES AND ACCESSORIES.
<br />IN ADDITION, INCLUDE VOLTAGES AND CURRENT RATINGS,
<br />INTERRUPTING RATINGS, CURRENT UMITATiON RATINGS,
<br />TIME -CURRENT TRIP CHARACTERISTICS CURVES, AND
<br />MOUNTING REQUIREMENTS.
<br />FUSES
<br />A. CLASS RK5, DUAL ELEMENT, TiME DELAY FUSES:
<br />PROVIDE UL CLASS RK5 TIME DELAY FUSES RATED 250 OR
<br />600 VOLTS, 60 HZ. 0 TO 600 AMPERES, WITH 2O0.000
<br />AMPERES RMS SYMMETRICAL INTERRUPTING CURRENT RATING
<br />FOR PROTECTING PANELBOARDS, TRANSFORMER, MOTORS, AND
<br />FEEDERS.
<br />(BUSSMANN FUSETRON TYPE FRN-R 25OV, OR FRS-R 60OV)
<br />B CLASS T REDUCED DIMENSION FUSES: PROVIDE UL CLASS T
<br />FAST ACTING FUSES RATED 250 OR 600 VOLT, 60 HZ, UP TO
<br />600 AMPERES, WITH 2O0,000 AMPERES RMS SYMMETRICAL
<br />INTERRUPTING CURRENT RATING FOR PROTECTION OF
<br />PHYSICALLY SMALL DEVICES WITH NO HEAVY UNRUSH
<br />CURRENTS. (BUSSMANN T-TRON TYPE JJS)
<br />C. IN-UNE FUSES: PROVIDE UL LISTED IN-UNE FAST ACTING
<br />FUSES RATED 300 VOLTS, 60 HZ UP TO 15 AMPERES
<br />COMPLETE WiTH FUSEHOLDER FOR FLUORESCENT BALLAST
<br />PROTECTION.
<br />1. FUSEHOLDER SHALL BE BUSSMANN TYPE HLR.
<br />2. FUSE SHALL BE BUSSMANN TYPE GLR.
<br />D. MOTOR STARTER CONTROL POWER TRANSFORMER CIRCUITS
<br />SHALL BE FUSED AS RECOMMENDED BY THE EQUIPMENT
<br />MANUFACTURER,
<br />INDIVIDUALLY MOUNTED CIRCUIT BREAKERS
<br />A. PROVIDE ENCLOSED CIRCUIT BREAKERS HAVING THE ELECTRICAL
<br />CHARACTERISTICS, RATINGS AND AND MODIFICATIONS SHOWN ON
<br />THE DRAWINGS. ALL ENCLOSED CIRCUIT BREAKERS SHALL HAVE
<br />NEMA 1 GENERAL PURPOSE ENCLOSURES UNLESS NOTED
<br />OTHERWISE, METAL NAMEPLATES, FRONT COVER MOUNTED, THAT
<br />CONTAIN A PERMANENT RECORD OF CATALOG NUMBER AND
<br />MAXIMUM RATING, AND HANDLES THAT ARE PADLOCKABLE IN
<br />THE 'OFF' POSITION.
<br />B• ALL CIRCUIT BREAKERS SHALL PROVIDE INVERSE TIME DELAY
<br />AND INSTANTANEOUS PROTECTION FOR EACH POLE OF
<br />BREAKER. ALL CIRCUIT BREAKERS MUST BE COMPLETELY
<br />ENCLOSED IN A MOLDED CASE. AUTOMATIC OPERATION OF THE
<br />CIRCUIT BREAKER SHALL BE OBTAINED BY MEANS OF THERMAL
<br />AND/OR MAGNETIC DEVICES LOCATED IN EACH POLE OF THE
<br />BREAKER. THE THERMAL DEVICE SHILL PROVIDE TIME DELAY
<br />TRIPPING ON OVERLOADS, AND THE MAGNETIC DEVICE SHALL
<br />PROVIDE INSTANTANEOUS TRIPPING ON SHORT CIRCUITS. THE
<br />INSTANTANEOUS MAGNETIC TRIP SHALL BE ADJUSTABLE AND
<br />ACCESSIBLE FROM THE FRONT OF THE BREAKER ON FRAME
<br />SIZES ABOVE 100 AMPERES. NON-INTERCHANGABLE TRIP
<br />BREAKERS SHALL HAVE THE TRIP UNIT SEALED TO PREVENT
<br />TAMPERING. AMPERE RATINGS Stall BE CLEARLY VISIBLE.
<br />CONTACTS SHALL BE OF NON -MOLDED SILVER ALLOY. ARC
<br />EXTINCTION MUST BE ACCOMPUSHED BY MEANS OF ARC
<br />CHUTES.
<br />C. THE BREAKERS SHALL BE OPERATED BY A TOGGLE TYPE
<br />HANDLE AND SHALL HAVE A QUICK -MAKE, QUICK -BREAK
<br />OVER -CENTER SWITCHING MECHANISM THAT IS MECHANICAL
<br />TRIP FREE SO THAT THE CONTACTS CAN NOT BE HELD CLOSED
<br />AGAINST SHORT CIRCUITS AND ABNORMAL CURRENTS. TRIPPING
<br />DUE TO OVERLOAD OR SHORT CIRCUIT SHALL BE CLEARLY
<br />INDICATED BY THE HANDLE AUTOMATICALLY ASSUMING A
<br />POSITION MIDWAY BETWEEN THE MANUAL "ON' AND 'OFF'
<br />POSITIONS. ALL LATCH SURFACES SHALL BE GROUND AND
<br />POLISHED. ALL POLES SHALL BE CONSTRUCTED SO THEY GIVE,
<br />CLOSE AND TRIP SIMULTANEOUSLY.
<br />D. THE MINIMUM INTERRUPTING RATINGS OF THE CIRCUIT BREAKER
<br />SHALL BE AT LEAST EQUAL. TO THE AVAILABLE SHORT CIRCUIT
<br />AT THE LINE TERMINALS. CIRCUIT BREAKER RATINGS,
<br />MODIFICATIONS, ETC. SHALL BE AS INDICATED ON THE
<br />DRAWINGS.
<br />E. WHERE FRAME SIZE SHALL BE 100 AMPERES OR LESS,
<br />MINIMUM CONTINUOUS AMP RATING WiTH UL LISTED
<br />INTERRUPTING CAPACITY IN RMS SYMMETRICAL AMPERES AT
<br />THE FOLLOWING VOLTAGES SHALL BE:
<br />10,000 AMPS 240 VOLTS
<br />14,000 AMPS 480 VOLTS
<br />THESE BREAKERS SHALL HAVE FIXED TRIP UNITS FURNISHED
<br />WITH BREAKERS
<br />BREAKERS SHALL BE MANUFACTURED BY CUTLER HAMMER,
<br />SIEMENS OR SQUARE D.
<br />F. WHERE FRAME SIZE SHALL BE 250 AMPERES OR LESS
<br />MINIMUM CONTINUOUS AMP RATING WITH UL LISTED
<br />INTERRUPTING CAPACITY IN RMS SYMMETRICAL AMPERES AT
<br />THE FOLLOWING VOLTAGES SHALL BE:
<br />240 VOLTS 25,000 AMPS
<br />480 VOLTS 22,000 AMPS
<br />THESE BREAKERS SHALL HAVE INTERCHANGEABLE TRIP UNITS
<br />FURNISHED WiTH BREAKER.
<br />BREAKERS SHALL BE MANUFACTURED BY CUTLER HAMMER,
<br />SIEMENS OR SQUARE D.
<br />G. WHERE FRAME SIZE SHALL BE ABOVE 250 AMPERES, MINIMUM
<br />CONTINUOUS AMP RATING WiTH UL LISTED INTERRUPTING
<br />CAPACITY IN RMS SYMMETRICAL AMPERES AT THE FOLLOWING
<br />VOLTAGES SHALL BE:
<br />240 VOLTS 42,000 AMPS
<br />480 VOLTS 30,000 AMPS
<br />THESE BREAKERS SHALL HAVE INTERCHANGEABLE, ADJUSTABLE
<br />RATING TRIP PLUGS FURNISHED WITH BREAKER.
<br />BREAKERS SHALL BE CUTLER HAMMER "SELTRONIC" OR
<br />SIEMENS "SENSITRIP" OR SQUARE D.
<br />16500I LIGHTING
<br />SUBMITTALS
<br />A. SUBMIT UST OF MANUFACTURERS FOR UGHTiNG FIXTURES,
<br />LAMPS AND LUMINARIES ACCESSORIES IN ACCORDANCE WiTH
<br />LIGHTING FIXTURE SCHEDULE ONLY.
<br />B. SUBMIT CUTS, SHOP DRAWINGS AND PHOTOMETRIC DATA FOR
<br />EACH FIXTURE TYPE. PHOTOMETRIC DATA SHALL BE BASED ON
<br />INDEPENDENT TESTING LABORATORY REPORTS, SUCH AS ETL,
<br />ITL, ERL, AND UKE REPORTS. TESTING PROCEDURES SHALL BE
<br />IN ACCORDANCE WiTH APPLICABLE IES STANDARDS.
<br />LIGHTING FIXTURES
<br />A. ALL INTERIOR, EXTERIOR AND EMERGENCY LIGHTING FIXTURES
<br />SHALL BE COMPLETE WITH ALL REQUIRED ACCESSORIES AND
<br />ATTACHMENTS.
<br />B. FIXTURES SHALL BEAR UL LABEL AND SHALL BE WIRED AND
<br />INSTALLED IN FULL COMPLIANCE WiTH APPLICABLE CODES.
<br />C. THE OMISSION OF A TYPE IN THE LIGHTING FIXTURE SCHEDULE
<br />SHALL NOT RELIEVE CONTRACTOR OF RESPONSIBILITY OF
<br />FURNISHING ALL REQUIRED FIXTURES OF PROPER TYPE AS
<br />SHOWN ON DRAWINGS.
<br />D. FIXTURES SHALL BE RECESSED, SURFACE, OR PENDANT TYPE,
<br />AS SPECIFIED IN FIXTURE SCHEDULE, AND SHALL INCLUDE
<br />SOCKETS, DIFFUSERS, CEIUNG CANOPIES AND STEMS, HICKEYS,
<br />AND ALL OTHER NECESSARY ACCESSORIES.
<br />E. RECESSED MOUNTED UGHTiNG FIXTURES SHALL BE
<br />CONNECTED TO A JUNCTION BOX WITH FLEXIBLE CONDUIT.
<br />F. INCANDESCENT AND HID LAMP HOLDERS SHALL BE MADE OF
<br />PORCELAIN HOUSING AND COPPER SCREW SHELLS, RATED AT
<br />NO LESS THAN 660 WATTS, 250 VOLTS. LAMP HOLDERS SHALL
<br />BE FIRMLY HELD IN PLACE SO AS TO PREVENT DAMAGE TO
<br />CONDUCTOR INSULATION AND TO PREVENT SOCKET TURNING
<br />DURING LAMP REPLACEMENT. PLASTIC LAMP HOLDERS ARE NOT
<br />ACCEPTABLE.
<br />G. ENAMELED FINISHES SHALL BE ELECTROSTATICALLY APPLIED
<br />AND BAKED. FINISH OF FIXTURES SHALL BE UNIFORM IN
<br />QUALITY AND APPEARANCE. DURABLE, AND FREE FROM
<br />DEFECTS.
<br />H. LABELS AND INSCRIPTIONS IN FIXTURES SHALL BE LOCATED IN
<br />UNOBTRUSIVE PLACES SO THAT THEY ARE NOT VISIBLE TO
<br />OCCUPANTS IN THE COMPLETED INSTALLATION.
<br />I. SPECIAL AND/OR CUSTOM UGHTiNG FIXTURES, WIRING, LAMPS,
<br />BALLASTS. AND OTHER ACCESSORIES SHALL BE AS INDICATED
<br />ON DRAWINGS.
<br />J. PLASTER FRAMES. ANGLES, AND CHANNELS FOR RECESSED
<br />LIGHTING FIXTURES SHALL BE FURNISHED UNDER THIS
<br />SECTION WHERE REQUIRED. PLASTER FRAMES SHALL BE
<br />SPECIFICALLY CONSTRUCTED FOR THE APPLICATION BY THE
<br />MANUFACTURER OF THE RELATED LIGHTING FIXTURE.
<br />K. RECESSED COMPACT FLUORESCENT AND INCANDESCENT
<br />LIGHTING FIXTURES SHALL BE THE PRODUCT OF ONE
<br />MANUFACTURER UNLESS OTHERWISE NOTED.
<br />L. LAY -IN RECESSED FIXTURES IN GRID -TYPE CEIUNG SHALL BE
<br />INSTALLED AND SUPPORTED IN ACCORDANCE WiTH LOCAL
<br />CODES. VERIFY ADEQUATE SUPPORT OF CEIUNG GRID TO
<br />BUILDING STRUCTURE AND SECURE UGHTING FIXTURE TO GRID
<br />BY MECHANICAL. MEANS SUCH AS SCREWS, BOLTS OR
<br />APPROVED CUPS.
<br />M. PENDANT OR SURFACE -MOUNTED FIXTURES SHALL BE
<br />PROVIDED WiTH REQUIRED MOUNTING DEVICES AND
<br />ACCESSORIES, INCLUDING HICKEYS, STUD EXTENSIONS, BALL
<br />AUGNERS, CANOPIES AND STEMS. MOUNTING STEMS OF
<br />PENDENT FIXTURES SHALL BE OF THE CORRECT LENGTH TO
<br />UNIFORMLY MAINTAIN THE FIXTURE HEIGHTS SHOWN ON THE
<br />DRAWINGS. VARIATION IN MOUNTING INDIVIDUAL FIXTURES SHALL
<br />NOT EXCEED 1/4". THEIGHT SHALL NOT VARY MORE THAN
<br />1/2" FROM THE FLOOR MOUNTING HEIGHT SHOWN ON THE
<br />DRAWINGS.
<br />N. UNDERCABINET LIGHTING FIXTURES SHALL BE CONNECTED TO
<br />THE NEAREST 120V RECEPTACLE CIRCUIT AND CONTROLLED BY
<br />AN INTEGRAL ROCKER SWITCH. MULTIPLE ADJACENT FIXTURES
<br />SHALL BE CONTROLLED BY ONE INTEGRAL ROCKER SWITCH.
<br />0. ANY LAMPS, BALLASTS, REFLECTORS, LENS, DIFFUSERS, SIDE
<br />PANELS OR OTHER PARTS DAMAGED PRIOR TO THE FiNAL
<br />INSPECTION SHALL BE REPLACED AT NO D(PENSE TO THE
<br />OWNER.
<br />P. AT TIME OF FINAL INSPECTION, ALL FIXTURES AND EQUIPMENT
<br />SHALL BE FULLY LAMPED, AND SHALL BE COMPLETE WiTH
<br />REQUIRED LENSES OR COMPONENTS NECESSARY.
<br />BALLASTS
<br />A. PROVIDE BALLASTS CONFORMING TO UL AND ANSI
<br />STANDARDS USTING AND DISPLAYING LABELS OR SYMBOLS OF
<br />LISTING BY UL. AND OF CERTIFICATIONS BY THE CBM, AS
<br />TESTED BY THE ETL DESIGN, FABRICATE AND ASSEMBLE
<br />COMPONENT PARTS OF BALLASTS IN ACCORDANCE WiTH THE
<br />LATEST CODE REQUIREMENTS. MARK BALLASTS "CLASS P"
<br />INDICATING APPROVED INTEGRAL BALLAST PROTECTION. THIS
<br />BALLAST PROTECTION SHALL BE PROVIDED BY A BUILT-IN
<br />SELF -RESETTING THERMALLY ACTUATED DEVICE THAT SHALL
<br />REMOVE THE BALLAST FROM LINE WHEN EXCESSIVE BALLAST
<br />TEMPERATURE IS REACHED.
<br />B. PROVIDE BALLASTS HAVING THE LOWEST SOUND RATING
<br />AVAILABLE FOR THE LAMPS SPECIFIED AND CLEARLY SHOWING
<br />THEIR RESPECTIVE SOUND RATINGS. REPLACE BALLASTS FOUND
<br />BY ARCHITECT OR ENGINEER TO BE UNDULY NOISY, WITHOUT
<br />CHARGE, PRIOR TO ACCEPTANCE OF THE PROJECT.
<br />C. PROVIDE IDENTICAL BALLASTS WITHIN EACH FIXTURE TYPE
<br />UNLESS OTHERWISE NOTED.
<br />D. BALLASTS FOR FLUORESCENT LAMPS SHALL BE SUITABLE FOR
<br />THE ELECTRICAL CHARACTERISTICS OF THE SUPPLY CIRCUITS
<br />TO WHICH THEY ARE TO BE CONNECTED AND WHICH ARE
<br />SUITABLE FOR OPERATING THE SPECIFIED LAMPS. PROVIDE
<br />BALLASTS WHICH ARE ELECTRONIC, HIGH POWER FACTOR,
<br />SUPER LOW TEMPERATURE RISE, LOW HARMONIC DISTORTION,
<br />HIGH -FREQUENCY (ABOVE 20KHZ) FULL OUTPUT TYPE, FOR
<br />T-8 OR T-12 RAPID START 1-,2-,3- OR 4-LAMP
<br />COMBINATIONS AS REQUIRED BY THE FIXTURE DESCRIBED IN
<br />THE LIGHTING FIXTURE SCHEDULE. PROVIDE BI-LEVEL
<br />SWITCHING OR DIMMING BALLASTS AS REQUIRED.
<br />E. COMPACT FLUORESCENT FIXTURES SHALL BE PROVIDED WiTH
<br />4-PIN HIGH POWER FACTOR ELECTRONIC BALLASTS AS NOTED
<br />ON DRAWINGS. BALLASTS SHUT HAVE INTERNAL CIRCUITRY TO
<br />DETECT END OF LAMP LIFE AND SHUT DOWN BALLAST.
<br />PROVIDE DIMMING BLASTS WHERE REQUIRED.
<br />F. HIGH INTENSITY DISCHARGE LIGHTING FIXTURE BALLASTS
<br />SHALL BE HIGH POWER FACTOR AUTO -TRANSFORMER TYPE
<br />G. BALLASTS SHALL HAVE A (2) YEAR WARRANTY FROM DATE OF
<br />ACCEPTANCE OF THE COMPLETED INSTALLATION.
<br />H. APPROVED BALLAST MANUFACTURERS SHALL BE TRIAD,
<br />MAGNETEK, EBT, OSRAM/SYLVANIA OR ADVANCE.
<br />I. PROVIDE ALL FLUORESCENT AND COMPACT FLUORESCENT
<br />BALLASTS WiTH REQUIRED OVERLOAD PROTECTION. FUSE
<br />HOLDER AND FUSE SHALL BE BUSSMANN HLR/GLR.
<br />LAMPS
<br />A. PROVIDE ELECTRIC LAMPS AS REQUIRED DURING
<br />CONSTRUCTION, INCLUDING LAMPS FOR FIXTURE FURNISHED BY
<br />OTHERS.
<br />B. PROVIDE A COMPLETE SET OF NEW LAMPS IN EACH FiXTURE
<br />AS SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE, ON
<br />DRAWINGS, AND AS DESCRIBED BELOW. UPON COMPLETION OF
<br />THE WORK, LEAVE FIXTURES AND LIGHTING EQUIPMENT
<br />COMPLETELY LAMPED AND IN PROPER OPERATING CONDITION.
<br />C. UNLESS SPECIFIED OTHERWISE, PROVIDE LAMPS AS FOLLOWS:
<br />1) FOR UNEAR FLUORESCENT FIXTURES, PROVIDE ENERGY
<br />SAVING 32 WATT T8 OR 34 WATT T12, "RAPID START"
<br />LAMPS, WHICH DELVER AT LEAST 2900 INITIAL LUMENS
<br />FOR STRAIGHT LAMPS, WITH 35W KELVIN COLOR, AS
<br />INDICATED ON THE UGH71NG FIXTURE SCHEDULE.
<br />2) FOR COMPACT FLUORESCENT FIXTURES, PROVIDE ENERGY
<br />SAVING LAMPS OF THE WATTAGE INDICATED ON THE
<br />LIGHTING FIXTURE SCHEDULE WITH 35W KELVIN
<br />COLOR TEMPERATURE, UNLESS OTHERWISE INDICATED.
<br />3) FOR INCANDESCENT FIXTURES, PROVIDE 130V LAMPS
<br />UNLESS OTHERWISE INDICATED.
<br />4) FOR OTHER FIXTURES, PROVIDE LAMPS AS SPECIFIED, OR
<br />IF NOT SPECIFIED, PROVIDE AS REQUIRED BY THE
<br />UGHnNG FIXTURE MANUFACTURER. IF SPECIFICATION IS
<br />NOT COMPLETE, CONTACT ENGINEER FOR CLARIFICATION.
<br />5) ALL LAMPS OF THE SAME CHARACTERISTICS SHALL BE
<br />PROVIDED BY THE SAME MANUFACTURER UNLESS
<br />SPECIFICALLY INDICATED OTHERWISE.
<br />D. APPROVED LAMP MANUFACTURERS SHALL. BE GENERAL
<br />ELECTRIC, PHILIPS. OSRAM/SYLVANIA, OR VENTURE.
<br />EXIT, STAIRWAY AND DIRECTIONAL SIGNS
<br />A. PROVIDE SIGNS IN COMPLIANCE WITH APPLICABLE CODES.
<br />B. COLOR AND SIZE OF LETTERS, ARROWS AND FACEPLATE
<br />BACKGROUND SHALL COMPLY WiTH APPLICABLE CODES.
<br />AIR HANDUNG UGHTiNG FIXTURES
<br />A. CONSTRUCT AIR HANDUNG TYPE LIGHTING FIXTURES IN A
<br />MANNER WHICH WILL PERFECTLY ACCOMMODATE THE SECURE
<br />AND AIRTIGHT ATTACHMENT OF ALL AIR HANDUNG COMPONENTS
<br />THERETO. THE AIR TERMINAL AND UGHTING FIXTURE
<br />MANUFACTURERS SHALL COORDINATE FIT, PERFORMANCE, AND
<br />INSTALLATION REQUIREMENTS. FIXTURES OF THE SAME TYPE
<br />SHALL BE CONSTRUCTED TO PRESENT THE SAME APPEARANCE
<br />IN THE CEIUNG, WHETHER ACTIVE OR INACTIVE.
<br />B. A QUANTITY OF AIR HANDLING TYPE FIXTURES ARE NOT
<br />CONNECTED TO THE VENTILATING SYSTEM INITIALLY. SUCH
<br />FIXTURES ARE DESIGNED INACTIVE, BUT SHALL HAVE THE
<br />CAPABIUTY OF SUBSEQUENT ACTIVATION AND SHALL BE
<br />PROVIDED UNDER THIS SECTION WITH REMOVABLE, AIRTIGHT
<br />BLANKING PLATES ARE REMOVED AND APPROPRIATE AIR
<br />TERMINALS ARE INSTALLED.
<br />INSTALLATION
<br />A. INSTALL UGHTiNG FIXTURES AND LAMPS AS SPECIFIED ON
<br />DRAWINGS AND SCHEDULES.
<br />B. PENDANT TYPE FIXTURES SHALL BE HUNG AT HEIGHTS AS
<br />REQUIRED AND SPECIFIED.
<br />C. FIXTURE LOCATIONS SHALL BE AS INDICATED ON THE
<br />ARCHITECTURAL REFLECTED CEIUNG PLAN. THE ELECTRICAL
<br />LIGHTING PLAN SHALL BE THE SECOND POINT OF REFERENCE.
<br />ADDITIONAL. INFORMATION REGARDING FIXTURE LOCATION MAY BE
<br />NOTED ON THE UGHTING FIXTURE SCHEDULE.
<br />D. PROVIDE ALL LAMPS REQUIRED, INCLUDING REPLACEMENTS FOR
<br />BURNED OUT LAMPS, UNTIL FINAL ACCEPTANCE OF THE
<br />COMPLETED WORK. NO LIGHTING FIXTURE OR SIGN WILL BE
<br />INSTALLED WITHOUT LAMPS.
<br />E. IF PERMANENT UGHTING FIXTURES ARE TO BE USED IN UEU
<br />OF TEMPORARY LIGHTING DURING THE CONSTRUCTION PERIOD.
<br />THIS SHALL BE DONE ONLY AS PERMITTED BY ARCHITECT OR
<br />ENGINEER, WHO MAY REQUIRE THE NEW LAMPS BE INSTALLED
<br />AND FIXTURES CLEANED AT THE 11ME OF SUBSTANTIAL
<br />COMPLETION AND OWNER OCCUPANCY.
<br />F. OPEN DOWNUGHT REFLECTORS AND PARABOLIC LOUVERS
<br />SHALL BE INSTALLED IN PLACE AFTER THE PROJECT BECOMES
<br />DUST FREE. INSTALLER SHALL WEAR GLOVES TO PRECLUDE
<br />SMUDGING THE REFLECTOR SURFACE AND LOUVERS.
<br />G. PROTECTION: PROTECT INSTALLED FIXTURES FROM DAMAGE
<br />DURING REMAINDER OF CONSTRUCTION PERIOD.
<br />A. AFTER INSTALLATION, ADJUSTMENT AND INSPECTION,
<br />FUNCTIONAL TESTS SHALL BE PERFORMED OF ALL LIGHTING
<br />FIXTURES IN THE PRESENCE OF OWNER. THE TESTS SHALL
<br />DEMONSTRATE THAT THE FIXTURES HAVE BEEN INSTALLED
<br />PROPERLY AND FUNCTION AS REQUIRED BY THE CONTRACT
<br />DOCUMENTS.
<br />AIMING AND FOCUSING
<br />A. INSTALL ALL ADJUSTABLE FIXTURES PER MANUFACTURER'S
<br />RECOMMENDATIONS AND TO PROVIDE MAXIMUM UNIFORM
<br />COVERAGE.
<br />SPECIAL AREA LIGHTING
<br />A. ANGULAR ADJUSTMENT AND FINAL PLACEMENT OF UGHTING
<br />FIXTURES FOR DESIGNATED SPECIAL AREA LIGHTING SHALL BE
<br />A FIELD CONDITION AND DETERMINED AT SITE.
<br />B. CONTRACTOR SHALL COORDINATE WiTH ARCHITECT TO ESTABLISH
<br />A TIME AND DATE FOR TRIAL LAYOUT OF UGHTING FIXTURES.
<br />ARCHITECT OR ENGINEER SHALL BE PRESENT AT TRIAL LAYOUTS
<br />TO FINALIZE FIXTURE PLACEMENT.
<br />F16-70011 SYSTEMS
<br />SUBMITTALS
<br />A. SUBMIT MANUFACTURER'S DATA AND SHOP DRAWINGS FOR ALL
<br />SYSTEMS.
<br />B. SUBMIT WIRING DIAGRAMS WHERE REQUIRED.
<br />TELEPHONE/DATA SYSTEM
<br />A. PROVIDE AN EMPTY TELEPHONE/DATA RACEWAY SYSTEM AS
<br />SHOWN ON THE DRAWINGS AND SPECIFIED.
<br />B. WALL OUTLETS SHALL CONSIST OF A FLUSH MOUNTED,
<br />MINIMUM 4 INCH SQUARE, 2-1/8 INCH DEEP OUTLET BOX
<br />WITH SINGLE GANG PLASTER RING.
<br />C. STUB CONDUIT FROM OUTLET BOX INTO ACCESSIBLE CORRIDOR
<br />CEIUNG SPACE. CONDUIT SIZES SHALL BE AS SHOWN ON
<br />DRAWINGS, OR MINIMUM 3/4 INCH.
<br />D. WALL OUTLETS FOR MODULAR FURNITURE FEEDS SHALL
<br />CONSIST OF A FLUSH MOUNTED 4 11/16 INCH SQUARE, 2
<br />1/8 INCH DEEP OUTLET BOX WiTH TWO -GANG PLASTER RING
<br />AND 1 1/4 INCH CONDUIT STUBBED INTO ACCESSIBLE CEIUNG
<br />SPACE.
<br />E. PROVIDE INSULATED BUSHINGS ON BOTH ENDS OF CONDUITS.
<br />F. PROVIDE 4'x8'x3/4" MARINE GRADE PLYWOOD PANTED TWO
<br />COATS OF GRAY INTERIOR ENAMEL ON ALL SIDES IN
<br />TELEPHONE CLOSETS AND WHERE INDICATED ON PLANS.
<br />A. PROVIDE A COMPLETE EMPTY CONDUIT SYSTEM FOR THE
<br />SECURITY SYSTEM OUTLETS. CONDUITS SHALL BE TERMINATED
<br />IN THE ASSOCIATED COMMUNICATION SYSTEMS CLOSET. MINIMUM
<br />CONDUIT SIZE SHALL BE 3/4 INCH.
<br />B. CARD READER OUTLETS SHALL CONSIST OF A FLUSH
<br />MOUNTED, MINIMUM 4 INCH SQUARE, 2 1/2 INCH DEEP
<br />OUTLET BOX WITH A TWO -GANG PLASTER RING. JACKS AND
<br />WALL PLATES WILL BE PROVIDED UNDER A SEPARATE
<br />CONTRACT.
<br />C. PROVIDE A CONDUIT CONNECTION TO DOOR FRAMES FOR
<br />ELECTRIC DOOR STRIKES AND TO SENSORS WHERE SHOWN.
<br />PROVIDE OUTLET BOX FOR SENSOR, FLUSH MOUNTED IN
<br />CEILING. PROVIDE 120V CIRCUIT FROM NEAREST UNSWITCHED
<br />RECEPTACLE CIRCUIT UNLESS OTHERWISE NOTED.
<br />D. PROVIDE INSULATED BUSHINGS ON BOTH ENDS OF CONDUITS.
<br />A. RELOCATE EXISTING DEVICES AND PROVIDE NEW DEVICES AS
<br />REQUIRED FOR THE EXISTING FIRE ALARM SYSTEM. DEVICES
<br />SHALL MATCH EXISTING SYSTEM DEVICES.
<br />B. CONSULT WiTH MANUFACTURER AND INSTALUNG CONTRACTOR
<br />FOR INSTALLATION OF EQUIPMENT AND MODIFICATIONS TO THE
<br />EXISTING SYSTEM.
<br />C. REPROGRAM EXISTING FIRE ALARM CONTROL PANELS AND
<br />PROVIDE NEW MODULES AND DEVICES AS REQUIRED.
<br />D. EXTEND EXISTING WIRING AND CONDUIT AND PROVIDE NEW
<br />WIRING AND CONDUIT AS REQUIRED FOR A COMPLETE SYSTEM.
<br />E. FIRE ALARM SYSTEM WIRING SHALL BE VERIFIED WITH THE
<br />EQUIPMENT MANUFACTURER. ALL WIRE SHALL BE #14 AWG
<br />SOLID COPPER CONDUCTOR WITH N.E.C. TYPE "THHN' 600
<br />VOLT INSULATION, UNLESS OTHERWISE NOTED. COLOR CODE
<br />WIRING TO MATCH THE EXISTING BUILDING FIRE ALARM SYSTEM.
<br />F. FIRE ALARM SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT,
<br />MINIMUM SIZE 3/4".
<br />G. UPON COMPLETION OF THE INSTALLATION, PROVIDE A
<br />COMPLETE TEST OF THE SYSTEM TO VERIFY PROPER
<br />OPERATION.
<br />MEP / FP Engineer
<br />EPSTEIN
<br />600 West Fulton
<br />Chicago, IL 60661
<br />312.454.9100
<br />Design Architect
<br />EPSTEIN
<br />600 West Fulton
<br />Chicago, IL 60661
<br />312.454.9100
<br />Nestle Waters North America
<br />Nestle Waters North America
<br />4330 20th Street
<br />Zephyrhills, Florida 33542-6703
<br />972.462.3663
<br />nfestIe
<br />Waters
<br />Expires
<br />FEB 2 8 Z015
<br />`ears, I_ ."Et. s75,
<br />STATE OF ; _ C
<br />Ir
<br />0 P . �,.
<br />4
<br />3
<br />09.18.2013
<br />09.11.2013
<br />ISSUE FOR PERMIT
<br />ISSUE FOR BIDS
<br />2
<br />09.03.2013
<br />CD REVIEW PACKAGE
<br />1
<br />NO.
<br />08.16.2013
<br />DATE
<br />DD REVIEW PACKAGE
<br />REVISIONS/ISSUANCES
<br />�PSTEIN
<br />Architecture
<br />Chicago
<br />Interiors
<br />New York
<br />Engineering
<br />Bucharest
<br />Construction
<br />Warsaw
<br />600 W. Fulton Street
<br />Chicago, IL 60661-1259
<br />T 312.454.9100
<br />www.epsteinglobal.com
<br />PROJECT NUMBER: 12386
<br />PROJECT MANAGER: JK
<br />ARCH/ENG: DD
<br />SCALE: NOT TO SCALE
<br />DRAWN BY: DD
<br />CHECKED BY: MS
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />E-005