Laserfiche WebLink
KEYNOTES <br />1O 3#3/0 + #6G - 2"C. <br />2O 3#8 + #1 G -1 "C. <br />30 2 SETS OF #350 + #8G - 2 1/2"C. <br />3O PROVIDE SURGE PROTECTIVE DEVICE AS REQUIRED. <br />GENERAL NOTE: <br />1. ALL METER SERVICE GROUNDING ELECTRODE CONDUCTORS TO REMAIN. <br />CONTRACTOR SHALL TEST OHM READINGS TO MEET NEC REQUIREMENTS FOR <br />ELECTRICAL SERVICES IN SCOPE OF PROJECT. <br />INDOORS <br />GENERAL NOTES <br />1. CONDUIT RUNS ON THIS RISER ARE SHOWN DIAGRAMMATICALLY AND <br />DO NOT REFLECT ACTUAL FIELD CONDITIONS. PRIOR TO <br />COMMENCEMENT OF WORK, THE CONTRACTOR SHALL FIELD VERIFY <br />ALL ROUTING WITH EXISTING FIELD CONDITIONS AND ALL OTHER <br />TRADES. <br />2. COORDINATE SERVICE ENTRANCE CONNECTIONS WITH THE UTILITY <br />CUSTOMER SERVICE PROJECT MANAGER PRIOR TO COMMENCEMENT <br />OF WORK AND PROVIDE ACCORDINGLY FOR A COMPLETE <br />ELECTRICAL INSTALLATION. <br />3. THE CONTRACTOR SHALL MAINTAIN THE FIRE RATING OF ALL WALL <br />AND FLOOR PENETRATIONS THROUGH WHICH CONDUITS PASS. <br />4. ALL ELECTRICAL EQUIPMENT SHALL BE PROPERLY LABELED TO <br />INDICATE POTENTIAL ELECTRICAL ARC FLASH HAZARDS IN <br />ACCORDANCE WITH NEC ARTICLE 110.16. <br />5. THE MANUFACTURER BASIS OF DESIGN FOR ALL POWER <br />DISTRIBUTION EQUIPMENT IS SCHNEIDER ELECTRIC. <br />6. THE MANUFACTURER BASIS OF DESIGN FOR ALL ATS EQUIPMENT IS <br />ASCO TECHNOLOGIES. <br />7. INCREASE FEEDER CONDUCTOR AND CONDUIT SIZES (AS REQUIRED) <br />IN ORDER TO MAINTAIN A MAXIMUM CUMULATIVE VOLTAGE DROP OF <br />TWO (2) PERCENT AT THE FURTHEST DOWNSTREAM EQUIPMENT. <br />WHERE EQUIPMENT IS UNABLE TO ACCOMMODATE UPSIZED <br />CONDUCTORS, PROVIDE LUG KITS (AS REQUIRED). WHERE LUG KITS <br />ARE UNABLE TO ACCOMMODATE UPSIZED CONDUCTORS, SPLICE AND <br />TRANSITION TO A SMALLER CONDUCTOR SIZE AT THE POINT OF <br />TERMINATION VIA AN AUXILIARY GUTTER, PULL BOX, WIREWAY, OR <br />OTHER SUITABLE DEVICE. <br />EQUIPMENT CONNECTION SCHEDULE <br />TAG <br />HP <br />LOAD <br />FLA (AMPS) <br />VOLTAGE <br />PHASE <br />CONDUIT/WIRE (AWG) <br />PANEL <br />CIRCUIT <br />NUMBER <br />STARTER <br />DISCONNCECT <br />Comments <br />NEMA SIZE <br />ENCLOS. TYPE <br />FURN. BY <br />(DIV.) <br />SWITCH SIZE <br />NO. OF POLES <br />ENCLOSE. <br />TYPE <br />FURN. BY <br />(DIV.) <br />DUPLEX 1 HP <br />PUMPS <br />1920 VA <br />8A <br />240 V <br />1 <br />2#12 + #12G - 3/4"C <br />HOUSE PANEL <br />1,3 <br />— <br />— <br />— <br />30A <br />2 <br />NEMA 3R <br />26 <br />EWHAA <br />13000 VA <br />54A <br />240 V <br />1 <br />2#4 + #8G - VC <br />1A <br />14,16 <br />— <br />— <br />— <br />100A <br />2 <br />NEMA 1 <br />26 <br />EWHA B <br />13000 VA <br />54A <br />240 V <br />1 <br />2#4 + #8G -1"C <br />113 <br />14,16 <br />-- <br />— <br />— <br />100A <br />2 <br />NEMA 1 <br />26 <br />EWH-2A <br />13000 VA <br />54A <br />240 V <br />1 <br />2#4 + #8G -1"C <br />2A <br />14,16 <br />-- <br />— <br />-- <br />100A <br />2 <br />NEMA 1 <br />26 <br />EWH-2B <br />13000 VA <br />54A <br />240 V <br />1 <br />2#4 + #8G -1"C <br />2B <br />14,16 <br />— <br />— <br />— <br />100A <br />2 <br />NEMA 1 <br />26 <br />LIFT STATION <br />3192 VA <br />13.3A <br />240 V <br />1 <br />2#10 + #10G - 3/4"C <br />HOUSE PANEL <br />2,4 <br />— <br />— <br />— <br />30A <br />2 <br />NEMA 3R <br />26 <br />MSCU-1A <br />3302 VA <br />13.76A <br />240 V <br />1 <br />2#12 +#12G - 3/4"C <br />1A <br />11,13 <br />— <br />— <br />- <br />30A <br />2 <br />NEMA 3R <br />26 <br />MSCU-1 B <br />3302 VA <br />13.76A <br />240 V <br />1 <br />2#12 + #12G - 3/4"C <br />1A <br />10,12 <br />— <br />-- <br />— <br />30A <br />2 <br />NEMA 3R <br />26 <br />MSCU-2A <br />3302 VA <br />13.76A <br />240 V <br />1 <br />2#12 + #12G - 3/4"C <br />113 <br />10,12 <br />— <br />— <br />— <br />30A <br />2 <br />NEMA 3R <br />26 <br />MSCU-213 <br />3302 VA <br />13.76A <br />240 V <br />1 <br />2#12 + #12G - 3/4"C <br />113 <br />11,13 <br />— <br />— <br />-- <br />30A <br />2 <br />NEMA 3R <br />26 <br />MSCU-3A <br />3302 VA <br />13.76A <br />240 V <br />1 <br />2#12 + #12G - 3/4"C <br />2A <br />10,12 <br />— <br />— <br />-- <br />30A <br />2 <br />NEMA 3R <br />26 <br />MSCU-36 <br />3302 VA <br />13.76A <br />240 V <br />1 <br />2#12 + #12G - 3/4"C <br />2A <br />11,13 <br />— <br />— <br />— <br />30A <br />2 <br />NEMA 3R <br />26 <br />MSCU-4A <br />3302 VA <br />13.76A <br />240 V <br />1 <br />2#12 + #12G - 3/4"C <br />2B <br />10,12 <br />— <br />— <br />— <br />30A <br />2 <br />NEMA 3R <br />26 <br />MSCU-46 <br />3302 VA <br />13.76A <br />240 V <br />1 <br />2#12 + #12G - 3/4"C <br />2B <br />11,13 <br />— <br />— <br />-- <br />30A <br />2 <br />NEMA 3R <br />26 <br />ELECTRICAL MECHANICAL EQUIPMENT SCHEDULE NOTES: <br />1. COORDINATE EQUIPMENT/DEVICE LOCATIONS WITH TRADE CONTRACTOR PRIOR TO ROUGH -IN. <br />2. CONTRACTOR TO MAKE FINAL CONNECTIONS FROM ELECTRICAL EQUIPMENT TO DEVICES. <br />Renna Enterprises, Inc. <br />P.E. y 85232 Irving Ho, P.E. <br />AUTH. N 00008631 Consulting Engineers <br />3231 Drone Field Road Ph. (863) 646 1258 <br />Lakeland, FI 33811 Fax. (863) 646 8881 <br />o <br />� <br />U <br />E <br />co <br />�o <br />M <br />_c <br />V <br />� <br />0 <br />� <br />N <br />s <br />O <br />U <br />ca <br />�/ V <br />0) <br />`■ti <br />0)0 <br />� <br />� <br />W <br />o <br />-0 <br />Q <br />0 2 <br />.�4 <br />sS/4� �R►DP�G1�'���� <br />//NA `' E\\��� <br />Z <br />z U) <br />W <br />o z <br />(n <br />mz <br />�W <br />W <br />0 <br />U~ <br />a <br />a <br />�♦�/^� <br />VJ <br />�— <br />2 a <br />�/ <br />ZIt <br />Q <br />F- <br />00 <br />L.` <br />w <br />W <br />LL LL <br />w <br />W O <br />�_j <br />pIr <br />(Y <br />co J_ <br />W0 <br />Q=2 <br />~� <br />} <br />0z <br />VJ <br />Q <br />U)0 <br />E5 <br />