TIMBER <br />- ALL FRAMING LUMBER SHALL BE #2 SPRUCE, PINE, FIR OR BETTER, U.N.O <br />- ALL EXTERIOR WALL AND ALL INTERIOR LOAD BEARING OVER 8'-0" IN HEIGHT <br />SHALL BE S.Y.P. #2 GRADE OR BETTER <br />- ALL INTERIOR LOAD BEARING WALLS 8'-0" OR LESS IN HEIGHT SHALL BE <br />SPRUCE, PINE, FIR OR BETTER. <br />- INTERIOR NON -LOAD BEARING WALLS SHALL BE #2 SPRUCE, PINE, FIR OR BETTER <br />- BLOCKING IS REQUIRED IN ALL WALLSTUDS OVER 8'-0" AT MID -HEIGHT AND <br />SHEATHING JOINT. <br />- ALL LUMBER IN CONTACT WITH MASONRY OR CONCRETE SHALL BE PRESSURE <br />TREATED WOOD. <br />EXTERIOR WINDOWS AND DOOR NOTES / 2014 FBC 5 TH EDITION 301.1.2(7) <br />1. ALL EXTERIOR WINDOWS AND GLASS DOORS ARE REQUIRED <br />TO BE TESTED IN ACCORDANCE WITH ANSI/AMMA/NWWDA 101 /152 <br />STANDARD AND BEAR AN AMMA OR WDMA LABEL IDENTIFYING <br />THE MANUFACTURER, PERFORMANCE CHARACTERISTICS AND <br />APPROVED PRODUCT TESTING ENTITY. <br />2. ALL EXTERIOR WINDOWS AND DOORS SHALL BE ANCHORED PER <br />PUBLISHED MANUFACTURER'S RECOMMENDATIONS TO ACHIEVE <br />THE DESIGN PRESSURE SPECIFIED. <br />3. ALL EXTERIOR WINDOWS AND DOORS WHERE BUCK THICKNESS <br />IS LESS THAN 1-1/2 INCHES SHALL BE ANCHORED THROUGH <br />JAMB INTO STRUCTURAL SUBSTRATE. <br />4. ALL EXTERIOR WINDOWS AND DOORS WHERE BUCK THICKNESS <br />IS 1-1/2 INCHES OR GREATER MUST HAVE THE BUCK ATTACHED <br />IN A MANNER THAT TRANSFERS THE LOAD DIRECTLY TO THE <br />STRUCTURE. WINDOWS AND DOORS SHALL BE ANCHORED THROUGH <br />THE JAMB INTO THE WOOD BUCK. <br />5. WINDOW BUCKS SHALL EXTEND BEYOND THE INTERIOR LIP OF <br />THE WINDOW. <br />6. MULLIONS AND ADJACENT DOOR ASSEMBLIES ARE REQUIRED TO <br />BE TESTED OR ENGINEERED TO TRANSFER 1.5 TIMES THE <br />DESIGNED LOADS TO THE ROUGH OPENING SUBSTRATE. <br />7. A COMPLETE DOOR AND WINDOW SCHEDULE INCLUDING MANUFACTURER <br />AND MODEL NUMBER HAS BEEN INCLUDED AS PART OF THE <br />CONSTRUCTION DRAWINGS. <br />8. GARAGE DOOR INSTALLATION DETAILS AND DATA INDICATING <br />COMPLIANCE WITH THE WIND LOAD REQUIREMENTS OF <br />FBC2014 5 TH EDITION HAS BEEN INCLUDED AS PART OF THE CONSTRUCTION <br />DRAWINGS. <br />FRAMING INSPECTION NOTE: <br />ALL PLUMBING, ELECTRICAL AND MECHANICAL ROUGH -INS <br />MUST BE COMPLETE, INSPECTED AND APPROVED BEFORE <br />REQUESTING A FRAMING INSPECTION. FBC2014 5 TH EDITION <br />hilm • ' D 1 • - 'A 0 <br />1. BASIC WIND SPEED = 145 MPH <br />2. BUILDING CATEGORY = RESIDENTIAL <br />3. APPLICABLE INTERNAL PRESSURE COEFFICIENT = 1.00 <br />4. COMPONENTS AND CLADDING = 10.5 PSF -21.5 PSF <br />5. WIND EXPOSURE = B <br />6. RISK CATEGORY II per FBC table 1604.5. <br />WINDOW NOTES: <br />ALL WINDOWS ARE TO MEET OR EXCEED DESIGN <br />WIND LOAD PRESSURES OF FLORIDA BUILDING CODE <br />2014 5 TH EDITION R301.1,2(7) <br />VERIFY ALL WINDOWS FIT ROUGH OPENINGS <br />TERMITE PROTECTION - 2014 FBC 5TH EDITION 318 <br />SOIL CHEMICAL BARRIER METHOD TO BE USED. <br />1. A PERMANENT SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER <br />AND NEED FOR RE -INSPECTION AND TREATMENT CONTRACT RENEWAL SHALL <br />BE PROVIDED. THE SIGN SHALL BE POSTED NEAR THE WATER HEATER OF <br />ELECTRIC PANEL. <br />2. CONDENSATE AND ROOF DOWN SPOUTS SHALL DISCHARGE AT LEAST 1'-0" <br />AWAY FROM BUILDING SIDE WALLS. <br />3. IRRIGATION/SPRINKLER SYSTEMS INCLLUDING ALL RISERS AND SPRAY HEADS <br />SHALL NOT BE INSTALLED WITHIN 1'-0" OF BUILDING SIDE WALLS. <br />4. TO PROVIDE FOR INSPECTION FOR TERMITE INFESTATION, BETWEEN WALL <br />COVERING AND FINAL EARTH GRADE SHALL NOT BE LESS THAN 6 INCHES. <br />EXCEPTION: PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS THAN 5/8" <br />THICK ADHERED DIRECTLY TO THE FOUNDATION WALL. <br />5. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND BACKFILL <br />IS COMPLETE. <br />6. SOILD DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RETREATED <br />INCLUDED SPACES BOXED OR FORMED. <br />7. BOXED AREAS IN CONCRETE FLOORS FOR SUBSEQUENT INSTALLATIONS OF TRAPS, <br />EXT., SHALL BE MADE WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT <br />FORMS MUST BE OF A SIZE AND DEPTH THAT WILL ELIMINATE THE DISTURBANCE <br />OF SOIL AFTER THE INITAL TREATMENT. <br />8. MINIMUM 6 MIL. VAPOR RETARDER MUST BE INSTALLED TO PROTECT AGAINST <br />RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE VAPOR RETARDER PLACEMENT, <br />RETREATMENT IS REQUIRED. <br />9. CONCRETE OVERPOUR AND MORTAR ALONG THE FOUNDATION PERIMETER MUST <br />BE REMOVED BEFORE EXTERIOR SOIL TREATMENT. <br />10. SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR <br />GRADE WITHIN 1'-0" OF THE STRUCTURE SIDEWALLS. <br />11. AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER <br />CONSTRUCTION IS COMPLETE INCLUDING LANDSCAPING AND IRRIGATION. ANY SOIL <br />DISTURBED AFTER THE VERTICAL BARRIER IS APPLIED, SHALL BE <br />RETREATED. <br />12. ALL BUILDINGS ARE REQUIRED TO HAVE PRE -CONSTRUCTION TREATMENT. <br />13. A CERTIFICATE OF COMPLIANCE MUST BE ISSUED TO THE BUILDING DEPARTMENT <br />BY A LICENSED PEST CONTROL COMPANY BEFORE A CERTIFICATE OF OCCUPANCY <br />WILL BE ISSUED. THE CERTIFICATE OF COMPLIANCE SHALL STATE: "THE BUILDING HAS <br />RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN <br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE <br />FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES.: . <br />14. AFTER ALL WORK IS COMPLETED, LOOSE WOOD AND FILL MUST BE REMOVED <br />FROM BELOW AND WITHIN 1'-0" OF THE BUILDING. THIS INCLUDES ALL GRADE STAKES, <br />TUB TRAP BOXES, FORMS, SHORING OR OTHER CELLULOSE CONTAINING MATERIAL. <br />15. NO WOOD, VEGETATION, STUMPS, CARDBOARD, TRASH, ETC., SHALL BE BURIED <br />WITHIN 15'-0" OF ANY BUILDING OR PROPOSED BUILDING. <br />SOIL IS TO BE COMPACTED TO 95% MODIFIED PROCTOR AS DEFINED BY ASTM D 1557-91 <br />CONDENSATE LINES SHALL DISCHARGE <br />AT LEAST 1 FOOT AWAY FROM THE <br />STRUCTURE SIDEWALL, WHETHER BY <br />UNDERGROUND PIPING, TAIL <br />EXTENSIONS, OR SPLASH BLOCKS. <br />DESIGN CRITERIA <br />WIND SPEED (SSTD 10-97) FBC 2014 145 MPH <br />CONCRETE (AT 28 DAYS) fc=3,000 PSI MIN. <br />CONCRETE MASONRY UNITS ASTM A-615 GRADE 40 <br />REINFORCING STEEL <br />MIN. LAP FOR BARS <br />#4 BAR = 25" <br />#7 BAR = 35" ASTM C-90 OR C-143 <br />#5 BAR - 27" <br />STANDARD HOOK = 10" LEG <br />STRUCTURAL STEEL ASTM A-36 <br />MORTAR TYPE M OR S <br />GROUT F'c = 3,000 PSI @ 28 DAYS <br />SHALL HAVE 3/8" AGGREGATE, 8" - 11" SLUMP (ASTM C-1019) <br />TIMBER MIN fb=1,150 PSI <br />SOUTHERN YELLOW PINE #2, FOR CONCRTUCTION <br />OR HEM -FIR #2 <br />OR DOUGLAS -FIR #2 OR CONSTRUCTION <br />SOIL PRESSURE (ASSUMED) 2,000 PSF <br />TO BE VERIFIED PRIOR TO PLACEMENT OF <br />REINFORCING OR CONCRETE FOR FOUNDATION. <br />COVER OVER REINFORCING STEEL <br />FOUNDATION CONCRETE CAST IN EARTH 3" ABOVE EARTH <br />CONCRETE AGAINST FORMS & ALL OTHER 1-1/2" <br />WINDOW NOTES <br />INSTALLATION DETAILS FOR NON -IMPACT FLANGE, SINGLE HUNG <br />WINDOWS IN WIND ZONES OF 150 MPH OR LESS (PER FBC 2014 5TH EDITION) <br />BUCKSTRIPS MUST BE SET IN A BEAD OF SEALANT. THE EXTERIOR <br />JOINT BETWEEN THE BUCKSTRIP AND MASONRY MUST ALSO BE <br />SEALED. BUCKSTRIPS SHALL RUN THE ENTIRE LENGTH OF THE <br />ROUGH OPENING. A BUCKSTRIP IS NOT NECESSARY AT THE SILL <br />IF IT IS PRECAST. ALL GAPS MUIST BE SEALED, BUCKSTRIPS <br />SHOULD BE PRESSURE TREATED YELLOW PINE, SPRUCE OR <br />COMPARABLE LUMBER, IN ACCORDANCE WITH THE FLORIDA <br />BUILDING CODE, A TAPER, OR BEVEL ON THE BUCK IS ACCEPTABLE <br />AT BOTH THE INTERIOR AND EXTERIOR. <br />IF USING 3/4" THICK WOOD BUCKSTRIPS: <br />INSTALLATION FASTENERS SHOULD BE A MINIMUM 3/16" X 2-3/4" <br />MASONRY SCREWS, INSTALLED THROUGH THE WINDOW AND <br />BUCKSTRIP INTO THE MASONRY. WINDOW MAY BE SHIMMED AS <br />NECESSARY, PROVIDED A MINIMUM SCREW EMBEDMENT OF 1-1/4" <br />IS MAINTAINED IN THE MASONRY. FASTENERS SHOULD BE LOCATED <br />A MAXIMUM OF 4" FROM EACH CORNER AND A MAXIMUM OF 18" O.C. <br />IT IS RECOMMENDED THAT FASTENERS NOT BE INSTALLED THROUGH <br />THE SILL OF THE WINDOW. THE ACTUAL SIZE OF THE BUCSTRIPS <br />SHOULD BE NO LESS THE 3/4" X 2-1/8". <br />IF USING 1-1/2" THICK OR GREATER WOOD BUCKSTRIPS. <br />WINDOW INSTALLATION FASTENERS SHOULD BE A MINIMUM #10 X 1-1/2" <br />WOOD SCREWS, INSTALLED THROUGH THE WINDOW INTO THE <br />BUCKSTRIP. WINDOW MAY BE SHIMMED AS NECESSARY, PROVIDED <br />A MINIMUM SCREW EMBEDMENT OF 1-1/4" IS MAINTAINED IN THE <br />BUCKSTRIP. WINDOW FASTENERS SHOULD BE LOCATED A MAXIMUM <br />OF 18" O.C. IT IS RECOMMENDED THAT FASTENERS NOT BE <br />INSTALLED THROUGH THE SILL OF THE WINDOW. THE ACTUAL <br />SIZE OF THE BUCKSTRIPS SHOULD BE NO LESS THAN 1-1/2" X 2-1/81' <br />. <br />BUCKSTRIPS SHOULD BE INSTALLED USING 3/16" X 2-3/4" MASONRY <br />SCREWS, TO MAINTAIN 1-1/4" EMBEDMENT AND BE 18" O.C. <br />�> <br />w � Y <br />t <br />NZA�° <br />ivfN <br />LoCA °LLW. <br />Q0-3 ul <br />COMPONENT & CLADDING DESIGN PRESSURE <br />. (145 M..P.H. A3 SEC. GUST. MIN. 2. 1 1/2 PITCH.. EXPOSURE "B" <br />(PSF) <br />TRIBUTARY AREA ROOF <br />WALL <br />(FT2) <br />(GCP1= +/- .18) <br />(GCP1= +/- .18) <br />10 17.5 -58.7 <br />(A) 30.4 -40.7 <br />20 16.0 -53.3 <br />(B) 29.0 -38.0 <br />50 13.9 -46.1 <br />(C) 27.2 -34.3 <br />100 12.4 -40.7 <br />(D) 25.9 -31.6 <br />125 12.4 -40.7 <br />(E) 25.5 -30.8 <br />1. FOR EFFECTIVE AREA OR WIND SPEEDS BETWEEN THOSE GIVEN ABOVE <br />THE LOAD MAY BE INTERPOLATED. OTHERWISE, USE THE <br />LOAD <br />ASSOCIATED WITH THE LOWER EFFECTIVE AREA <br />2. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARD AND <br />AWAY FROM THE BUILDING SURFACES <br />_z <br />0 <br />a <br />Z <br />4 <br />.. <br />w <br />111 <br />a <br />W <br />U <br />UJ <br />to <br />f- <br />Q <br />v <br />U <br />ao <br />uai <br />m <br />+� <br />a <br />z <br />} <br />C� <br />%Q <br />Z <br />2Lzu <br />Q <br />-4w <br />Q <br />A� <br />Q <br />lu <br />M <br />.4 <br />�(L <br />� <br />� <br />x <br />Q <br />SHEET NO, <br />NOTES <br />0 <br />