K
<br />ELECTRICAL LEGEND
<br />F21 O
<br />FLUORESCENT TROFFER, TYPE AS NOTED
<br />DUPLEX RECEPTACLE
<br />18" AFF OR AS NOTED, NEMA 5-20R
<br />LAFLUORESCENT
<br />TROFFER, TYPE AS NOTED
<br />PROVIDE WITH EMERGENCY BALLAST
<br />wP
<br />WEATHER PROOF DUPLEX RECEPTACLE
<br />18" AFF OR AS NOTED, NEMA 5-20R
<br />®
<br />FLUORESCENT TROFFER, TYPE AS NOTED
<br />DUPLEX RECEPTACLE
<br />ABOVE COUNTER OR AS NOTED, NEMA 5-20R
<br />®
<br />FLUORESCENT TROFFER, TYPE AS NOTED
<br />PROVIDE WITH EMERGENCY BALLAST
<br />QUAD RECEPTACLE
<br />18" AFF OR AS NOTED, NEMA 5-20R
<br />Q
<br />RECESSED CAN FIXTURE, TYPE AS NOTED
<br />IG
<br />DUPLEX RECEPTACLE
<br />18" AFF OR AS NOTED, NEMA 5-20R
<br />O
<br />RECESSED CAN FIXTURE, TYPE AS NOTED
<br />PROVIDE WITH EMERGENCY BALLAST
<br />SPECIAL PURPOSE RECEPTACLE
<br />18" AFF OR AS NOTED, SEE SCHEDULE
<br />F--o---i
<br />FLUORESCENT STRIP FIXTURE
<br />WALL / CEILING MOUNTED JUNCTION BOX
<br />(Di
<br />WALL MOUNTED FIXTURE, TYPE AS NOTED
<br />60/3/1
<br />0i
<br />UNFUSED DISCONNECT SWITCH
<br />RATING/POLES/NEMA RATING
<br />PENDANT FIXTURE, TYPE AS NOTED
<br />60/3/3R/40
<br />FUSED DISCONNECT SWITCH
<br />RATING/POLES/NEMA RATING/FUSE SIZE
<br />PENDANT FIXTURE, TYPE AS NOTED
<br />PROVIDE WITH EMERGENCY BALLAST
<br />MOTOR
<br />44+
<br />TRACK LIGHT FIXTURE, TYPE AS NOTED
<br />—I��
<br />GROUND
<br />IN
<br />EMERGENCY LIGHT
<br />TRANSFORMER
<br />41
<br />EXIT/EMERGENCY LIGHT COMBINATION
<br />OM
<br />UTILITY GRADE METER
<br />®
<br />CEILING MOUNTED EXIT SIGN
<br />®
<br />TRANSIENT VOLTAGE SURGE SUPPRESSOR
<br />WALL MOUNTED EXIT SIGN
<br />v
<br />TELEPHONE OUTLET, PROVIDE 4" BOX
<br />SINGLE GANG PLASTER RING, 3/4" C ABOVE CEILING
<br />$
<br />SINGLE POLE SWITCH, 44" AFF
<br />V
<br />DATA OUTLET, PROVIDE 4" BOX
<br />SINGLE GANG PLASTER RING, 3/4" C ABOVE CEILING
<br />TWO SINGLE POLE SWITCHES GANGED TOGETHER
<br />FOR INNER/OUTER CONTROL OF LAMPS, 44" AFFsm
<br />©
<br />TELEVISION/CABLE OUTLET
<br />THREE SINGLE POLE SWITCHES GANGED TOGETHER
<br />44" AFF
<br />®
<br />TELEPHONE OUTLET, PROVIDE 4" BOX
<br />FLUSH IN FLOOR, 3/4" C ABOVE CEILING
<br />$3
<br />THREE WAY SWITCH, 44" AFF
<br />®
<br />DATA OUTLET, PROVIDE 4" BOX FLUSH IN FLOOR, 3/4" C ABOVE CEILING
<br />03
<br />TWO THREE WAY SWITCHES GANGED TOGETHER
<br />FOR INNER/OUTER CONTROL OF LAMPS, 44" AFF
<br />DOOR HOLD -OPEN DEVICE
<br />$4
<br />FOUR WAY SWITCH, 44" AFF
<br />a
<br />TRANSFORMER, SEE ONE LINE
<br />WALL BOX DIMMER 1000W UNLESS NOTED DIFFERENTLY
<br />44" AFF
<br />SPEAKER STROBE
<br />$Wp
<br />WEATHER PROOF SWITCH, 44" AFF
<br />HORN
<br />$M
<br />MOTOR RATED SWITCH, 44" AFF OR AS NOTED
<br />Q
<br />PULL STATION
<br />$pg
<br />COMBINATION SWITCH AND OCCUPANCY SENSOR, 44" AFF
<br />Q
<br />FIRE ALARM STROBE, MIN 75 CANDELA
<br />CEILING / WALL MOUNT
<br />$T
<br />DIGITAL TIMER SWITCH, 44" AFF
<br />am
<br />DUCT MOUNTED SMOKE DETECTOR
<br />Q
<br />CEILING MOUNTED OCCUPANCY SENSOR
<br />OS
<br />SMOKE DETECTOR
<br />t
<br />WALL MOUNTED OCCUPANCY SENSOR, 44" AFF
<br />OH
<br />HEAT DETECTOR
<br />®
<br />TIME CLOCK
<br />OS
<br />TAMPER SWITCH
<br />LC
<br />LIGHTING CONTACTOR
<br />FS
<br />FLOW SWITCH
<br />®
<br />PHOTO CELL
<br />RACEWAY CONCEALED IN WALL OR ABOVE CEILING
<br />®
<br />8" CONE SPEAKER IN CEILING
<br />EC TO PROVIDE BLACK SPEAKER
<br />RACEWAY EXPOSED
<br />8" CONE SPEAKER IN WALL
<br />EC TO PROVIDE BLACK SPEAKER
<br />RACEWAY CONCEALED IN FLOOR SLAB, BELOW SLAB OR GRADE
<br />BELOW SLAB OR GRADE, OR UNDER RAISED ACCESS FLOOR
<br />VOLUME CONTROL
<br />-0
<br />DENOTES CONDUIT TURNING UP IN PLAN VIEW
<br />PLYWOOD EQUIPMENT BACKBOARD
<br />4'X8' UNLESS NOTED OTHERWISE
<br />-3
<br />DENOTES CONDUIT TURNING DOWN IN PLAN VIEW
<br />®4
<br />CLOSED CIRCUIT TELEVISION CAMERA
<br />- 3
<br />STUB UP
<br />COAXIAL CABLE OUTLET
<br />XXXX
<br />SHORT CIRCUIT AVAILABLE CURRENT
<br />(NOTE: ALL SYMBOLS SHOWN MAY NOT APPEAR ON DRAWINGS AND ARE USED AS APPLICABLE TO THIS PROJECT)
<br />ABBREVIATIONS
<br />ELECTRICAL SPECIFICATIONS
<br />A. DEFINITIONS
<br />1. 'PR❑VIDE't FURNISH AND INSTALL, COMPLETE AND READY FOR ❑PERATI❑N,
<br />2. 'INSTALL'i RECEIVE, MOUNT, AND CONNECT, COMPLETE AND READY FOR ❑PERATI❑N.
<br />3. 'FURNISH'i SUPPLY, DELIVER TO JOB SITE, PROTECT AND STORE.
<br />B. WORK INCLUDEDi PR❑VIDE ALL LABOR, TOOLS, MATERIAL, EXCAVATION, BACKFILL, CUTTING,
<br />PATCHING, TESTING, ADJUSTING, AND TRADE C❑ORDINATION REQUIRED FOR A COMPLETE AND
<br />FULLY ❑PERATI❑NAL INSTALLATION, AS DESCRIBED ON THE DRAWINGS OR IN THE
<br />SPECIFICATIONS,
<br />C. CODES, RULES, AND REGULATIONS, COMPLY WITH ALL CODES ENFORCED BY THE LOCAL
<br />INSPECTION AUTH❑RITY, THE EDITION OF THE NATI❑NAL ELECTRICAL CODE BEING ENFORCED FOR
<br />THIS PROJECT BY THE LOCAL INSPECTION AUTH❑RITY, ALL APPLICABLE LAWS AND ORDINANCE,
<br />NFPA FIRE CODES, STANDARD BUILDING CODE. GIVE ALL NECESSARY NOTICES, OBTAIN ALL
<br />REQUIRED PERMITS, AND PAY ALL INSPECTION AND OTHER FEES REQUIRED BY AUTHORITIES
<br />HAVING JURISDICTION OVER THE WORK.
<br />D. MATERIALS ALL MATERIAL SHALL BE NEW, AND SHALL COMPLY WITH THE INDICATED STANDARDS,
<br />ALL MATERIAL SHALL BE UL LABELED OR UL LISTED, ALL MATERIAL SHALL BE OF A SUITABLE
<br />TYPE AND RATING FOR THE INTENDED USE, AND SHALL BE INSTALLED IN CONFORMANCE WITH
<br />THE INSTRUCTIONS AND RECOMMENDATIONS OF THE MANUFACTURER,
<br />E. DRAWINGS
<br />1. THE DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL OF THE REQUIRED
<br />DETAILS OF THE WORK, ALL MATERIALS CUSTOMARILY CONSIDERED TO BE A PART OF THE
<br />ELECTRICAL WORK AND REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION SHALL
<br />BE PROVIDED WITH❑UT ADDITIONAL COST TO THE OWNER.
<br />2. THE CONTRACTOR SHALL REFER ALSO TO THE ARCHITECTURAL DRAWINGS AND TO THE
<br />DRAWINGS OF ALL OTHER TRADES TO COORDINATE THE ELECTRICAL INSTALLATION, WHERE
<br />ELECTRICAL EQUIPMENT IS SHOWN ON ARCHITECTURAL DRAWINGS OR DETAILS, THE
<br />EQUIPMENT SHALL BE INSTALLED AS SHOWN ON THE ARCHITECTURAL DRAWINGS.
<br />3. EQUIPMENT OF OTHER TRADES IS SHOWN SCHEMATICALLY ON THE ELECTRICAL DRAWINGS,
<br />THE CONTRACTOR SHALL EXAMINE THE DRAWINGS OF THE TRADE PROVIDING THE EQUIPMENT
<br />BEFORE ROUGHING IN THE CONNECTIONS FOR IT, THE CONTRACTOR SHALL CONNECT THE
<br />EQUIPMENT WHERE ACTUALLY INSTALLED, INCLUDING WIRING THROUGH ANY LINE VOLTAGE
<br />CONTROLLERS, WITHOUT ANY ADDITI❑NAL COST TO THE OWNER.
<br />4. PRIOR TO ROUGHING IN CIRCUITS FOR EQUIPMENT FURNISHED BY OTHER TRADES, AND PRIOR
<br />TO RELEASING FOR MANUFACTURE PANELBOARDS, STARTERS OR MOTOR CONTROL CENTERS
<br />FEEDING SUCH EQUIPMENT, THE CONTRACTOR SHALL C❑❑RDINATE THE ELECTRICAL
<br />PROVISIONS BEING PLANNED WITH THE TRADE PROVIDING THE EQUIPMENT AND SUBMIT ANY
<br />CONFLICTS IN WRITING TO THE ARCHITECT,
<br />5. THE ARCHITECT MAY DIRECT THE REL❑CATION OF ANY ELECTRICAL OUTLET, FIXTURE, OR
<br />OTHER EQUIPMENT TO A L❑CATI❑N WITHIN 10 FEET OF THE LOCATION SHOWN ON THE
<br />DRAWINGS AT NO ADDITIONAL COST TO THE OWNER PROVIDED SUCH RELOCATION IS
<br />DIRECTED PRIOR TO THE INSTALLATION OF THE OUTLET, FIXTURE OR EQUIPMENT BEING
<br />RELOCATED,
<br />D. SUBMITTAL D❑CUMENTSi PRODUCT DATA AND SHOP DRAWINGS SHALL BE SUBMITTED IN SIX C❑PIES
<br />TO THE ARCHITECT FOR REVIEW PRIOR TO THE RELEASE OF THE MATERIAL FOR MANUFACTURE,
<br />REVIEW OF SUBMITTALS BY THE ARCHITECT WILL BE ONLY FOR GENERAL CONFORMANCE WITH
<br />THE DRAWINGS AND SPECIFICATIONS. REVIEW WILL BE MADE ONLY OF INFORMATION CLEARLY
<br />AND SPECIFICALLY INDICATED IN THE SUBMITTAL, AND DOES NOT IMPLY THE ACCEPTABILITY OF
<br />DETAILS WHICH ARE NOT S❑ DESCRIBED IN THE SUBMITTAL. REVIEW OF THE SUBMITTAL
<br />DOCUMENTS BY THE ARCHITECT DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO
<br />COMPLY WITH ALL REQUIREMENTS OF THE DRAWINGS AND SPECIFICATIONS. SUBMITTAL IS
<br />REQUIRED FOR PANELBOARDS AND L❑ADCENTERS, LIGHT FIXTURES, WIRING DEVICES, FIRE ALARM
<br />DEVICES, AND SURFACE ALUMINUM RACEWAY.
<br />G. AS -BUILT DRAWINGS AS -BUILT DRAWINGS SHALL BE MAINTAINED AT THE J❑BSITE, AND SHALL
<br />BE AVAILABLE FOR REVIEW DURING CONSTRUCTION. AS -BUILT DRAWINGS SHALL BE KEPT
<br />CURRENT DURING THE CURSE OF CONSTRUCTION OF THE WORK. SUBMIT AS -BUILT DRAWINGS TO
<br />THE ARCHITECT AT THE COMPLETION OF THE PROJECT.
<br />H. TESTINGi TEST ALL PARTS OF THE WORK TO VERIFY COMPLIANCE WITH THE DRAWINGS AND
<br />SPECIFICATIONS, VERIFY TIGHTNESS OF ALL MECHANICAL AND ELECTRICAL CONNECTIONS. VERIFY
<br />INTEGRITY OF ALL WIRING SYSTEMS TO ASSURE CONTINUITY, ABSENCE OF UNINTENTI❑NAL
<br />GROUNDS, AND INTEGRITY OF REQUIRED GROUNDS.
<br />I. CHANGE REQUEST (CHANGE ORDER) APPROVAL, CHANGE REQUESTS WILL NOT BE CONSIDERED
<br />UNLESS THE CONTRACTOR'S DETAILED LABOR AND MATERIAL ESTIMATE DESCRIBING THE CHANGE
<br />IS SUBMITTED TO THE ARCHITECT ALONG WITH THE CHANGE REQUEST, WITH MATERIAL PRICES
<br />AND LABOR UNITS ASSIGNED TO EACH LINE ITEM OF THE ESTIMATE. MATERIAL PRICES SHALL BE
<br />THE ACTUAL PRICE PAID BY THE CONTRACTOR FOR MATERIAL PURCHASED OR THE ACTUAL PRICE
<br />QUOTED TO THE CONTRACTOR BY THE MATERIAL VENDOR PROPOSED BY THE CONTRACTOR.
<br />J. COORDINATION WITH THE WORK OF OTHERS COORDINATE WITH EACH TRADE FURNISHING
<br />EQUIPMENT REQUIRING ELECTRICAL SERVICE TO INSURE THAT THE CHARACTERISTICS SHOWN ON
<br />THE DRAWINGS FOR THE CIRCUIT SERVING THE EQUIPMENT ARE COMPATIBLE WITH THE
<br />REQUIREMENTS OF THE EQUIPMENT BEING FURNISHED, CIRCUIT BREAKERS, FUSES, DISC❑NNECT
<br />SWITCHES AND ASSOCIATED BRANCH CIRCUITS SHOWN ON THE DRAWINGS TO FEED HVAC
<br />EQUIPMENT, KITCHEN EQUIPMENT, ELEVATOR MOTORS, AND OTHER EQUIPMENT HAVE BEEN
<br />SELECTED BASED UPON THE CHARACTERISTICS OF EQUIPMENT BY ONE MANUFACTURER AND MAY
<br />NOT BE CORRECT FOR THE EQUIPMENT BEING PR❑VIDED BY THE CONTRACTOR, THE CONTRACTOR
<br />SHALL DETERMINE THE OPERATING CHARACTERISTICS OF THE EQUIPMENT ACTUALLY BEING
<br />PROVIDED AND SHALL PR❑VIDE AT NO ADDITI❑NAL COST TO THE OWNER CIRCUIT BREAKERS,
<br />FUSES, DISCONNECT SWITCHES AND BRANCH CIRCUITS AS REQUIRED BY THAT EQUIPMENT,
<br />K. EXISTING WORK, THE EXISTING ELECTRICAL INSTALLATION SHALL REMAIN AS -IS AND IN
<br />OPERATION EXCEPT WHERE OTHERWISE REQUIRED, GIVE WRITTEN NOTICE OF ANY UNFORESEEN
<br />EXISTING CONDITIONS WHICH MAY AFFECT THE WORK, WORK INVOLVING EXISTING SYSTEMS OR
<br />EXISTING SPACES SHALL BE ACCOMPLISHED WITH MINIMUM INCONVENIENCE TO THE OWNER, AND
<br />SHALL BE DONE IN A MANNER AND TIME APPROVED BY THE OWNER, ANY INTERRUPTIONS SHALL
<br />BE DURING TIMES DESIGNATED BY THE OWNER.
<br />A, AMPS
<br />AMPERES
<br />FLA
<br />FULL LOAD AMPERES
<br />NO
<br />NORMALLY OPEN,
<br />A/C
<br />AIR CONDITIONER
<br />GND
<br />GROUND
<br />NUMBER L.
<br />DEM❑LITIONi IN THE AREA SHOWN ON THE ARCHITECTURAL DRAWINGS TO BE DEMOLISHED REMOVE
<br />AC
<br />ALTERNATING CURRENT
<br />GALV
<br />GALVANIZED
<br />NTS
<br />NOT TO SCALE
<br />ALL EXISTING CONDUITS, CONDUCTORS, BOXES, FIXTURES, SERVICE ENTRANCE CONDUCTORS,
<br />AF
<br />AMPERE FRAME
<br />GRS
<br />GALVANIZED RIGID STEEL
<br />PNL
<br />PANELBOARD
<br />DISTRIBUTION EQUIPMENT, AND ALL OTHER ELECTRICAL EQUIPMENT NOT SHOWN TO REMAIN.
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />GFCI
<br />GROUND FAULT
<br />PVC
<br />POLYVINYL CHLORIDE
<br />UNLESS OTHERWISE INDICATED, MATERIAL BEING REMOVED INCLUDING WIRE, C❑NDUIT, AND
<br />AFG
<br />ABOVE FINISHED GRADE
<br />CIRCUIT INTERRUPTER
<br />RGS
<br />RIGID GALVANIZED
<br />HANGING MATERIALS BEING REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND
<br />AIC
<br />AMPERE
<br />STEEL CONDUIT
<br />SHALL BE REMOVED FROM THE PREMISES. EQUIPMENT NOTED TO REMAIN THE PROPERTY OF THE
<br />INTERRUPTING CURRENT
<br />GFI
<br />GROUND FAULT INTERRUPTER
<br />RMC
<br />RIGID METALLIC
<br />OWNER SHALL BE STORED ON SITE AS DIRECTED BY THE ARCHITECT, CO❑RDINATE WITH OTHER
<br />AL
<br />ALUMINUM
<br />HD
<br />HEAT DETECTOR
<br />CONDUIT (GALVANIZED)
<br />TRADES AND DISC❑NNECT MOTORS, HEATERS, OR OTHER EQUIPMENT AS REQUIRED FOR THE
<br />ANSI
<br />AMERICAN NATIONAL
<br />HP
<br />HORSEPOWER
<br />RMS
<br />ROOT -MEAN -SQUARE
<br />DEMOLITION OF OTHER TRADES WORK. CUT OFF ALL IN FLOOR CONDUITS, GRIND SMOOTH WITH
<br />STANDARDS INSTITUTE
<br />IMC
<br />INTERMEDIATE METAL CONDUIT
<br />RNC
<br />RIGID NON-METALLIC
<br />FLOOR AND PREPARE FOR PATCHING BY OTHERS, REMOVE CONDUCTORS AND DEVICES FROM WALL
<br />ISC
<br />INTERRUPTING SHORT CIRCUIT
<br />CONDUIT
<br />AND CEILING OUTLETS AND PREPARE OUTLET FOR PATCHING BY OTHERS, CONTRACTOR SHALL
<br />AWG
<br />AMERICAN WIRE GAUGE
<br />IG
<br />ISOLATED GROUND
<br />SCA
<br />SHORT CIRCUIT
<br />DENOTE ALL DEMOLISHED CIRCUITS ON EXISTING PANEL DIRECTORIES AND NOTE ALL SPARE
<br />BC
<br />BKBD
<br />BARE COPPER
<br />BACKBOARD
<br />INST
<br />INSTANTANEOUS
<br />AVAILABLE
<br />BREAKERS,
<br />JB
<br />JUNCTION BOX
<br />SWBD
<br />SWITCHBOARD
<br />C
<br />CONDUIT
<br />KAIC
<br />KILO (THOUSAND) AMPERES
<br />SWGR
<br />SWITCHGEAR M.
<br />BASIC MATERIALS AND METHODSi
<br />CB
<br />CKT
<br />CIRCUIT BREAKER
<br />CIRCUIT
<br />INTERRUPTING CAPACITY
<br />TBD
<br />TO BE DETERMINED
<br />1. ALL WORK SHALL BE SUPPORTED FROM STRUCTURAL ELEMENTS OF THE BUILDING, EXCEPT
<br />CU
<br />COPPER
<br />KCMIL
<br />KILO (THOUSAND)
<br />TCP
<br />TEMPERATURE CONTROL
<br />CEILING MOUNTED EQUIPMENT SUCH AS LIGHT FIXTURES, DETECTORS, REMOTE LAMPS, ETC,
<br />DIST
<br />DISTRIBUTION
<br />CIRCULAR MILS
<br />PANEL
<br />CEILING MOUNTED EQUIPMENT SHALL BE SUPPORTED FROM CEILING STRUCTURAL MEMBERS,
<br />DN
<br />DOWN
<br />KV
<br />KILO (THOUSAND) VOLTS
<br />TD
<br />TIME DELAY
<br />INDEPENDENT OF CEILING TILES, SIZE AND SPACING OF SUPPORTS SHALL BE DETERMINED
<br />DP
<br />DISTRIBUTION PANEL
<br />KVA
<br />KILO (THOUSAND)
<br />TEL
<br />TELEPHONE
<br />BY THE LOAD TO BE SUPPORTED SUCH THAT THE WORKING LOAD OF SUPPORTS WILL NOT
<br />DWG
<br />DRAWING
<br />VOLT-AMPERES
<br />TVSS
<br />TRANSIENT VOLTAGE
<br />EXCEED A SAFETY FACTOR OF 411, PLASTIC ANCHORS ARE NOT ACCEPTABLE, ELECTRICAL
<br />EB
<br />ENCASED BURIAL
<br />KW
<br />KILO (THOUSAND) WATTS
<br />SURGE SUPPRESSION
<br />WORK SHALL NOT BE SUPPORTED FROM PIPING, DUCTS, OR WORK OF OTHER TRADES,
<br />KWH
<br />KILO (THOUSAND) WATT-HOURS
<br />TYP
<br />TYPICAL
<br />EC
<br />EMPTY CONDUIT
<br />LFMC
<br />LIQUID -TIGHT FLEXIBLE
<br />UG
<br />UNDERGROUND
<br />2. PROVIDE ENGRAVED PLASTIC NAMEPLATES FOR ALL SWITCHB❑ARDS, PANELBOARDS, MOTOR
<br />EEW
<br />ENERGIZED ELECTRICAL WORK
<br />METAL CONDUIT
<br />UL
<br />UNDERWRITER'S LABORATORIES
<br />CONTROL CENTERS, STARTERS, DISCONNECTS, PRIMARY SELECTOR SWITCHES, AND
<br />EGC
<br />EQUIPMENT GROUNDING
<br />MCB
<br />MAIN CIRCUIT BREAKER
<br />UON
<br />UNLESS OTHERWISE
<br />TRANSFORMERS. INDICATE EQUIPMENT NAME, CIRCUIT SOURCE AND NUMBER, CIRCUIT SIZE,
<br />CONDUCTOR
<br />MCM
<br />THOUSAND CIRCULAR MILS
<br />UNDERGROUND PULLBOX
<br />AMPERE RATING, VOLTAGE AND PHASE. NAMEPLATES SHALL BE BLACK BACKGROUND
<br />ELR
<br />END -OF -LINE RESISTOR
<br />MCCB
<br />MOLDED CASE
<br />V
<br />VOLTS
<br />LAMA(❑ID PLASTIC WITH 0,25' WHITE LETTERS,
<br />EWC
<br />ELECTRIC WATER COOLER
<br />MLO
<br />MAIN LUGS ONLY
<br />VA
<br />VOLT-AMPERES
<br /><E>
<br />EXISTING
<br />N
<br />NEUTRAL
<br /><ER>
<br />EXISTING TO REMAIN
<br />NEC
<br />NATIONAL ELECTRICAL
<br />VFD
<br />VARIABLE
<br /><EX>
<br />EXISTING
<br />CODE
<br />FREQUENCY DRIVE
<br />FA
<br />FIRE ALARM
<br />NESC
<br />NATIONAL ELECTRICAL
<br />WH
<br />WATER HEATER
<br />FAA
<br />FIRE ALARM ANNUNCIATOR
<br />SAFETY CODE
<br />WP
<br />WEATHERPROOF
<br />FACP
<br />FIRE ALARM CONTROL PANEL
<br />NIC
<br />NOT IN CONTRACT
<br />WT
<br />WATERTIGHT
<br />NL
<br />NIGHT LIGHT
<br />XFMR
<br />TRANSFORMER
<br />3. ALL PENETRATI❑NS OF FIRE RATED WALLS, SLABS, PARTITI❑NS, AND CEILINGS SHALL BE
<br />FIREPR❑OFED WITH A U.L. LISTED SYSTEM THAT WILL MAINTAIN THE ORIGINAL FIRE RATING
<br />OF THE PENETRATED STRUCTURE. ALL FIREPR❑❑FING MATERIALS APPLIED AT ANY ONE
<br />PENETRATION SHALL BE THE PRODUCT OF ONE MANUFACTURER AND SHALL BE APPLIED AS
<br />DESCRIBED BY THE UL FIREPR❑❑FING SYSTEM BEING CONSTRUCTED. FIREPROOFING OF
<br />SLEEVES, CABLE TRAYS, TROUGHS, AND NIPPLES TO BE USED FOR LOW VOLTAGE CABLES
<br />SHALL BE INDEFINITELY NON -HARDENING AND REMOVABLE WITH COMMON HAND TOOLS.
<br />4. BACKBOARDS SHALL BE 8 FT, HIGH BY LENGTH SHOWN ON THE DRAWINGS AND SHALL BE
<br />UL LABELED FIRE TREATED PLYWOOD.
<br />5, PROVIDE ALL POWER WIRING AND CONNECTIONS FOR ALL ELECTRICALLY OPERATED
<br />EQUIPMENT. POWER WIRING INCLUDES WIRING THROUGH ANY LINE VOLTAGE CONTROL
<br />DEVICES, SUCH AS THERMOSTATS AND MANUAL STARTERS, INSTALL ALL STARTERS AND
<br />CONTACTORS EXCEPT THOSE FURNISHED AS AN INTEGRAL PART OF THE EQUIPMENT,
<br />6. CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING EQUIPMENT NOT
<br />INSTALLED IN A PLENUM SPACE SHALL BE MADE WITH A SHORT LENGTH OF LIQUIDTIGHT
<br />FLEXIBLE C❑NDUIT, MINIMUM 18', INSTALLED IN A MANNER TO PERMIT MOVEMENT OF
<br />EQUIPMENT,
<br />7. PERFORM ALL EXCAVATING, BACKFILLING, CUTTING AND REPAIRING REQUIRED FOR
<br />INSTALLATION OF ELECTRICAL WORK,
<br />B. CONTRACTOR SHALL X-RAY FLOOR SLABS, WALLS, OR CEILING CONCRETE PRIOR TO ALL
<br />CORE DRILLINGS.
<br />N. C❑NDUITi FEEDERS AND BRANCH CIRCUIT HOME RUNS SHALL BE CONSTRUCTED OF EMT WITH ALL
<br />STEEL RAINTIGHT OR SET -SCREW FITTINGS, CONNECTORS SHALL BE INSULATED THROAT TYPE,
<br />PR❑VIDE METALLIC BUSHINGS WITH PLASTIC INSERTS FOR 3' OR LARGER. C❑NDUITS FEEDING OR
<br />CONNECTING TO EQUIPMENT PROVIDED BY OTHER TRADES SHALL NOT BE INSTALLED UNTIL SUCH
<br />EQUIPMENT IS INSTALLED OR UNTIL SPECIFIC R❑UGH-IN INSTRUCTIONS ARE PROVIDED BY THE
<br />TRADE PROVIDING THE EQUIPMENT. UNLESS OTHERWISE INDICATED, CONDUITS SHALL BE
<br />CONCEALED, RACEWAYS INSTALLED IN OR UNDER SLABS, ON GRADE, OR AS EXTERIOR DUCT BANKS
<br />SHALL BE PVC SCHEDULE 40 OR 80. RUN EXPOSED C❑NDUITS PARALLEL OR PERPENDICULAR TO
<br />STRUCTURAL ELEMENTS, TWO OR MORE RACEWAYS RUN TOGETHER SHALL BE INSTALLED ON GANG
<br />TRAPEZE TYPE HANGERS, SUCH RACEWAYS ASSEMBLIES SHALL BE RUN PARALLEL OR
<br />PERPENDICULAR TO STRUCTURAL ELEMENTS. C❑NDUITS EMBEDDED IN SLABS SHALL HAVE A
<br />MINIMUM OF 1' COVER OF CONCRETE ON ALL SIDES, OUTSIDE DIAMETER OF CONDUIT SHALL NOT
<br />EXCEED 1/3 OF THE SLAB THICKNESS. PROVIDE 0.25' NYLON PULL TAPE IN ALL EMPTY
<br />C❑NDUITS, BRANCH CIRCUITS MAY UTILIZE TYPE MC ARMORED CABLE ASSEMBLY WITH COPPER
<br />CONDUCTORS AND FULL SIZE EQUIPMENT GROUNDING CONDUCTORS FOR INDIVIDUAL DROPS TO
<br />DEVICES. TYPE MC CABLE SHALL BE SUPPORTED AT 48' INTERVALS AND SHALL NOT LAY ON
<br />THE CEILING GRID OR INTERFERE WITH THE REMOVAL OF CEILING.
<br />0, CONDUCTORS, ALL BUILDING WIRE SHALL BE 600 VOLT RATED THHN OR THWN COPPER, STRANDED
<br />FOR SIZES #8AWG AND LARGER, S❑LID FOR SIZES 10 AND SMALLER UNLESS APPLIED FOR
<br />CONTROL. ALL BUILDING WIRE AND SPECIAL CABLES FOR SYSTEMS SHALL BE INSTALLED IN A
<br />RACEWAY, ALL WIRE AND CABLE SHALL BE DELIVERED TO THE J❑BSITE IN ORIGINAL UNBROKEN
<br />PACKAGES, CARTONS OR REELS, WITH THE MANUFACTURERS NAME, UL LABEL, AND
<br />CHARACTERISTICS OF THE PRODUCT PLAINLY VISIBLE. ALL WIRE AND CABLE SHALL BE
<br />MANUFACTURED IN THE UNITED STATES OF AMERICA. WIRES SHALL BE COLOR CODED AS FOLLOWS
<br />(A,B,C,N,G)i 120/208-BLACK, RED, BLUE, WHITE, GREEN] 480/277 - BROWN, ORANGE, YELLOW,
<br />GRAY, GREEN. SPLICES SHALL BE COMPRESSION TYPE. CONTROL CONDUCTORS SHALL BE
<br />TERMINATED WITH INSULATED CONNECTORS, T&B STAK❑N. 120 VOLT CIRCUITS WITH H❑MERUN
<br />LENGTH OVER 125 FEET AND 277 VOLT CIRCUITS WITH A H❑MERUN LENGTH OVER 250 FEET
<br />SHALL HAVE #10 MINIMUM HOMERUN CONDUCTORS. ALL THREE PHASE BRANCH CIRCUITS WITH A
<br />COMMON NEUTRAL SHALL HAVE #10 MINIMUM NEUTRAL.
<br />P. B❑XESi OUTLET BOXES SHALL BE SHEET STEEL, MINIMUM 4' SQUARE, MINIMUM 1.5' DEEP, WITH
<br />PLASTER RING IN PLASTER OR BRICK CONSTRUCTION, OUTLETS BOXES IN POURED CONCRETE
<br />SHALL BE CONCRETE RINGS, MASONRY BOXES SHALL BE USED IN MASONRY OR TILE
<br />CONSTRUCTION. OUTLET BOXES FOR SURFACE ALUMINUM RACEWAY SHALL BE 4-11/16 WITH
<br />PLASTER RINGS ORIENTED HORIZONTALLY, BOXES SHALL BE SECURELY ANCHORED IN PLACE, AND
<br />SHALL BE SUPPORTED INDEPENDENT OF THE RACEWAY SYSTEM. PULL BOXES SHALL BE
<br />GALVANIZED SHEET STEEL, MINIMUM 12 GAUGE, WITH SCREW COVERS, AND WELDED
<br />CONSTRUCTION. WELDS SHALL BE COLD GALVANIZED, USING PERMANENT WATER PROF WIDE
<br />BLACK MARKER, CLEARLY LABEL COVER OF ALL BRANCH CIRCUIT JUNCTION AND PULL BOXES
<br />WITH PANEL AND CIRCUIT NUMBER OF CIRCUITS CONTAINED IN OR PASSING THROUGH THE BOX.
<br />BRANCH CIRCUIT AND FEEDER JUNCTION AND PULL BOXES USED WITH EMERGENCY FEEDERS AND
<br />CIRCUITS SHALL BE PAINTED RED. PR❑VIDE P-TOUCH OR DYM❑ LABELS ON COVER OF EACH
<br />FEEDER PULL OR JUNCTION BOX INDICATING FEEDER DESIGNATION, SOURCE, LOAD, AND VOLTAGE.
<br />Q. WIRING DEVICES, SWITCHES FOR LIGHTING CIRCUITS SHALL BE 120/277 VOLT, 20 AMP, A.C.
<br />ONLY, QUIET TYPE, WITH GROUND BONDING SCREW, SPECIFICATION GRADE. MOMENTARY CONTACT
<br />SWITCHES SHALL BE SINGLE POLE DOUBLE THROW, CENTER OFF GE #5935 OR EQUAL. DUPLEX
<br />RECEPTACLES SHALL BE 15 AMP HUBBELL 5262 OR EQUAL. DEDICATED DUPLEX RECEPTACLES
<br />SHALL BE ORANGE 20AMP HUBBELL IG5362 OR EQUAL, SPECIAL RECEPTACLES SHALL BE OF
<br />SIMILAR CONSTRUCTION. FACE PLATES SHALL BE SMOOTH NYLON OR THERMOSET PLASTIC.
<br />ADJACENT OUTLETS SHALL BE INSTALLED IN MULTI -GANG BOXES WITH A SINGLE MULTI -GANG
<br />FACE PLATE, RECEPTACLES CONNECTED TO AN EMERGENCY CIRCUIT SHALL BE RED. C❑❑RDINATE
<br />COLOR OF DEVICES AND FACEPLATE WITH ARCHITECT,
<br />R. GR❑UNDINGi ALL FEEDERS AND BRANCH CIRCUITS SHALL BE PR❑VIDED WITH INSULATED GREEN
<br />EQUIPMENT GROUNDING CONDUCTOR. C❑NDUIT GROUNDS ONLY ARE NOT PERMITTED,
<br />S. LIGHTING+ SPARE FLUORESCENT LAMPS SHALL MATCH BUILDING STANDARD UNLESS OTHERWISE
<br />NOTED, INCANDESCENT LAMPS SHALL BE 130VOLT, NEW BALLASTS SHALL BE SOILD STATE
<br />ELECTR❑NIC, EXIT FIXTURES SHALL MATCH BUILDING STANDARD, FIXTURE LOCATIONS SHALL BE
<br />AS SHOWN ON THE REFLECTED CEILING PLAN, PROVIDE LAY -IN FIXTURES WITH TWO REMOVABLE
<br />CLIPS ATTACHING FIXTURE TO CEILING GRID. FLANGED FIXTURES SHOWN TO BE INSTALLED IN
<br />C❑NTINU❑US ROWS SHALL NOT HAVE INTERMEDIATE FLANGES. ALL PENDANT FIXTURES SHALL BE
<br />MOUNTED TO STRUCTURE, SEISMIC SUPPORT WIRES AND/OR COMPRESSION STRUTS FOR LAY -IN
<br />FIXTURES SHALL BE SUBJECT TO LOCAL AHJ LATEST REQUIREMENTS.
<br />T. FIRE ALARM DEVICES NEW FIRE ALARM DEVICES SHALL BE COMPATIBLE WITH EXISTING
<br />BUILDING ADDRESSABLE FIRE ALARM SYSTEM. INSTALL NEW DEVICES AND CONNECT TO NEAREST
<br />SIGNALING OR NOTIFICATION DEVICE CIRCUIT WITHIN THE AREA, CONTRACTOR SHALL VERIFY
<br />CIRCUIT HAS CAPACITY FOR ADDED LOAD. SYSTEM SHALL BE CERTIFIED BY FIRE ALARM VENDOR
<br />AFTER COMPLETION OF WORK.
<br />U. PANELBOARDS, DEAD FRONT PANEL CONSTRUCTION WITH SEPARATELY MOUNTED INTERIOR TRIM.
<br />MAIN AND BRANCH DEVICES SHALL BE BOLT -ON, MULTI -POLE BREAKERS SHALL BE COMMON TRIP,
<br />WIDTH SHALL NOT EXCEED 22' FOR PANELB❑ARD AND ENCLOSURE SHALL MATCH BUILDING
<br />STANDARD. PROVIDE GROUND BUS IN PANELB❑ARD AND PROVIDE DEVICE MOUNTING HARDWARE
<br />WHERE A SPACE IS SCHEDULED. PANEL AND OCPD SHORT CIRCUIT RATINGS SHALL BE AT LEAST
<br />10% GREATER THAN AVAILABLE SHORT CIRCUIT CURRENT AT PANELB❑ARD,
<br />V. DRY -TYPE TRANSFORMERS TRANSFORMERS SHALL BE DRY -TYPE, ENCLOSED, SELF -COOLED,
<br />VENTILATED TYPE, DEAD -FRONT DRIP PROOF, PRIMARY AND SECONDARY TAPS SHALL BE
<br />ACCESSIBLE FROM THE FRONT. TRANSFORMERS SHALL MEET OR EXCEED BUILDING STANDARD
<br />TRANSFORMERS SPECIFICATIONS. PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR IN THE PRIMARY
<br />FEED TO THE TRANSFORMER, SUPPLEMENTAL GROUND TO NEAREST ACCESSIBLE PRIMARY
<br />STRUCTURAL MEMBER OR EQUIPMENT ROOM GROUND BUS BAR. SIZE PER NEC AND RUN IN C❑NDUIT
<br />WITH BOND BUSHING AT EACH END. NEUTRAL AND GROUNDING CONDUCTOR SHALL BE BONDED TO
<br />ENCLOSURE.
<br />li
<br />Fri'!
<br />U
<br />Ono
<br />�NT
<br />�
<br />Zwo F-
<br />V
<br />�..ACDmm
<br />�NoN
<br />A �U co
<br />U)co�
<br />wE*Uwse
<br />.uzo
<br />w W p
<br />V ~J co
<br />ri Q Z U
<br />V p CNI
<br />CN
<br />LL
<br />0
<br />Lo
<br />0
<br />v
<br />�aaaaarr�f�
<br />$ter
<br />f:r
<br />BPJ�ygt�4�i
<br />2-15-16
<br />0
<br />0
<br />0
<br />0
<br />0
<br />0
<br />0
<br />CONTRACT DATE:
<br />BUILDING TYPE:
<br />PLAN VERSION:
<br />SITE NUMBER:
<br />STORE NUMBER:
<br />01.05.2016
<br />N/A
<br />DEC 2015
<br />N/A
<br />N/A
<br />SHELL BUILDOUT
<br />5935 GALL BLVD
<br />ZEPHYRHILLS, FL 33541
<br />REMODEL
<br />PHASE 1
<br />ELECTRIAL
<br />SPECIFICATIONS
<br />EOmO
<br />PLOT DATE:
<br />
|