GENERAL PLUMBING NOTES
<br />�I✓
<br />CONNECT TO
<br />WC-2
<br />NICKLE BRONZE ADJUSTABLE
<br />SCORIATED SECURED COVER.
<br />FLUSH WITH
<br />FLOOR LINE BRONZE TAPER THREAD PLUG
<br />WITH COUNTER SUNK HEAD
<br />45' WYE AND 1/8TH BEND
<br />FITTING OR COMBINATION FLANGE
<br />FITTING
<br />WASTE LINE LENGTH
<br />TO SUIT
<br />�Iml
<br />NOTE:
<br />CLEAN -OUT TO BE J.R. SMITH MODEL 4100-F SERIES OR EQUAL INSTALLATION SHALL BE
<br />LV-1 FLUSH WITH SURROUNDING FLOOR SURFACES.
<br />FLOOR CLEANOUT DETAIL
<br />PLUMBING FIXTURE SCHEDULE
<br />FIXTURE TAG
<br />DRAIN
<br />VENT
<br />CW
<br />HW
<br />FIXTURE DESCRIPTION
<br />FIXTURE SPECIFICATION
<br />VALVE/FACUET SPECIFICATION
<br />WC-1
<br />3
<br />1-1/2"
<br />3/4"
<br />KOHLER WELLWORTH
<br />ELONGATED PRESSURE ASSIST TANK -TYPE TOILET. CENTOCO 500 STSCCSS, EXTRA HEAVY DUTY SOLID PLASTIC, ELONGATED OPEN FRONT SEAT, WHITE,
<br />SLOAN FLUSH -MATE PRESSURE ASSIST
<br />WATER CLOSET - TANK
<br />K3493
<br />COVER WITH SLOW CLOSE SNAP -OFF HINGES. TANK COVER LOCK.
<br />WC-2
<br />3
<br />1-1/2"
<br />3/4"
<br />KOHLER HIGHLINE
<br />ELONGATED PRESSURE ASSIST TANK -TYPE TOILET. CENTOCO 500 STSCCSS, EXTRA HEAVY DUTY SOLID PLASTIC, ELONGATED OPEN FRONT SEAT, WHITE,
<br />SLOAN FLUSH -MATE PRESSURE ASSIST
<br />ADA WATER CLOSET - TANK
<br />K3505
<br />COVER WITH SLOW CLOSE SNAP -OFF HINGES. TANK COVER LOCK. ADA COMPLIANT.
<br />UR-1
<br />2
<br />1-1/4"
<br />3/4"
<br />SLOAN
<br />VITREOUS CHINA, WALL HUNG SIPHON JET WITH FLUSHING RIM, 3/4" TOP SPUD; JAY R. SMITH 0644 FLOOR CARRIER. MOUNT AT HANDICAP HEIGHT.
<br />MANUAL FLUSH
<br />URINAL
<br />SU-1005-.5
<br />SLOAN ROYAL180-1.0
<br />LV-1
<br />1.5
<br />1.25
<br />0.5
<br />0.5
<br />PROFLOW
<br />VITREOUS CHINA, 19"X15" SELF RIMMIN WITH OVERFLOW & GRID DRAIN, 4" CENTERS; PROVIDE CHROME PLATED LOOSE KEY ANGLE STOP, P-TRAP,
<br />KOHLER K-7404 4" CENTERS
<br />COUNTER -MOUNT LAVATORY
<br />PF20174
<br />ESCUTCHEON AND SUPPLIES. INSTALLED PER ADA ACCESSIBILITY.
<br />MANUALTWO - LEVER WITH WRISTBLADES
<br />SK-1
<br />1.5
<br />1.25
<br />0.5
<br />0.5
<br />ELKAY
<br />SINGLE COMPARTMENT, 20-GAUGE 304 STAINLESS STEEL SELF -RIMMING, FULLY COATED UNDERSIDE; DELTA FAUCET 21984LF, 3-HOLES WITH 4TH HOLE FOR
<br />LARGE SINGLE BOW SINKL
<br />LRAD312255
<br />SPRAY NOZZLE, SWIVEL GOOSENECK SPOUT, INSTALL PER ADA ACCESSIBILITY.
<br />FD-1
<br />3
<br />1.5
<br />JAY R. SMITH
<br />CAST IRON BODY AND FLASHING COLLAR; 6" NICKEL BRONZE ROUND STRAINER; VANDLE PROOF GRATE; P-050 TRAP PRIMER OPTION. CAST IRON GRATES
<br />FLOOR DRAIN
<br />2010.00
<br />NOT PERMITTED.
<br />FCO-1
<br />4
<br />JAY R. SMITH
<br />CAST IRON CLEANOUT; NICKEL BRONZE 6" ROUND ADJUSTABLE SCORIATED VANDAL PROOF TOP; GASKET SEAL ABS THREADED PLUG WITH SLOT TO
<br />FLOOR CLEAN OUT
<br />4020S
<br />RECEIVE 1/2" BAR STOCK. ARFCO- ACID RESITANT OPTION.
<br />WCO-1
<br />4
<br />JAY R. SMITH
<br />CAST IRON SPIGOT FERRULE; CAST BRONZE TAPER THREADED COUNTERSUNK PLUG WITH SLOT TO RECEIVE 1/2" BAR STOCK
<br />WALL CLEAN OUT
<br />4420.00
<br />EWC-1
<br />1.5
<br />1.25
<br />0.5
<br />OASIS
<br />WALL HUNG, BARRIER FREE. SPLIT LEVEL, ALL STAINLESS STEEL CABINET; 8 GPH OF 50' WATER AT 90 'AMBIENT; 1/4 HP, 120V/1 PH. PROVIDE QUARTER
<br />ELEC WTR COOLER
<br />P8ACSL
<br />TURN ANGLED STOP, P-TRAP AND SUPPLIES. INSTALLED PER ADA ACCESSIBILITY.
<br />WHA
<br />JAY R. SMITH 5000 SERIES
<br />STAINLESS STEEL PRESSURIZED COMPRESSION CHAMBER; THREADED NIPPLE CONNECTION; SIZE AS INDICATED ON DRAWINGS
<br />WATER HAMMER ARRESTOR
<br />MS-1
<br />3
<br />1.5
<br />0.75
<br />0.75
<br />FIAT
<br />ONE PIECE SERVICE BASIN; AND 3.0 GPM FLOW RESTRICTOR; DELTA 28T910 STAINLESS STEEL MOP HOLDER; 28T911 HEAVY DUTY 31" LONG REINFORCED
<br />DELTA 28T9
<br />MOP SERVICE BASIN
<br />MSB-3636 OR 24X24
<br />HOSE, BRASS COUPLING, STAINLESS STEEL HANGER BRACKET, W/RUBBER GRIP.
<br />WITH INTERGRAL VACUUM BREAKER
<br />MXV-1
<br />.75(X2)
<br />POWERS
<br />MULTI -FIXTURE MIXING VALVE, SOLID BRASS WITH INTEGRAL CHECK. THREADED UNION CONNECTIONS. ASSE1017
<br />MIXING VALVE
<br />LM490
<br />TP-1
<br />0.5
<br />PPP
<br />PRESSURE ACTIVATED TRAP PRIMER- PROVIDE DISTRIBUTION FITTING FOR UP TO 4 OUTLETS AS SHOWN ON DRAWINGS.
<br />PRESSURE ACT.TRAP PRIMER
<br />PR-500
<br />1. ALL FIXTURES, EQUIPMENT, TRIM, FITTINGS, ETC. SHALL COMPLY WITH LOCAL, STATE AND/OR FEDERAL REGULATIONS AND CODES, INCLUDING BUT NOT LIMITED TO WATER AND ENERGY CONSERVATION CODES, AND THE AMERICANS WITH DISABILITIES ACT (ADA). THE SCHEDULE REFLECTS FIXTURES AND EQUIPMENT
<br />WHICH ARE MINIMUM CRITERIA AND SHALL BE THE BASIS FOR CONTRACTORS BASE BID. WHERE SPECIFIED FIXTURES AND/OR EQUIPMENT ARE NOT IN COMPLIANCE WITH GOVERNING CODES AND REGULATIONS, THE CONTRACTOR SHALL PROVIDE AN ALTERNATE BID FOR THE SUBSTITUTIONS OF COMPLYING FIXTURES,
<br />EQUIPMENT, FITTINGS, ETC. THE ABSENCE OF AN ALTERNATE BID SHALL BE CONSTRUED TO MEAN THAT THE CONTRACTORS BASE BID INCLUDES ALL COSTS NECCESSARY TO MEET ALL REGULATIONS AND CODES.
<br />WATER HEATER SCHEDULE
<br />LAYOUT
<br />STORAGE
<br />GAS INPUT
<br />OUTPUT
<br />ELECTRICAL
<br />GPH RECOVERY
<br />TEMP
<br />ELEC
<br />EXPANSION TANK
<br />MARK
<br />TYPE
<br />BASIS
<br />GALLONS
<br />MBH
<br />MBH
<br />CAPACITY KW
<br />@80 DEG RISE
<br />SETTING
<br />VOLT/PHASE
<br />ACCPETANCE GAL
<br />WH-1
<br />ELEC STORAGE
<br />PROMAX
<br />40
<br />--
<br />--
<br />4.5KW
<br />60.00
<br />110
<br />208/1
<br />5
<br />1. PROVIDE ARMSTRONG LST EXP TANK AND T&P SET AT 150 PSI DISCHARGE TO HUB DRAIN. DO NOT ROUTE INTO DRAIN PAN.
<br />2. PROVIDE 2" DEEP DRAIN PAN BENEATH STORAGE TYPE WATER HEATER TO ENCASE ENTIRE
<br />WATER HEATER
<br />FOOTPRINT.
<br />TINSTALL PER PDI
<br />STANDARDS AND
<br />MANUFACTURER'S
<br />PDI I i INSTRUCTIONS.
<br />SIZE PROVIDE A WHA
<br />„A„ AT ALL QUICK -
<br />CLOSING VALVES.
<br />SINGLE FIXTURE
<br />PDI
<br />SIZE
<br />PIPE
<br />SIZE
<br />FIXTURE
<br />UNIT LOAD
<br />A
<br />1/2"
<br />1-11
<br />B
<br />3/4"
<br />12-32
<br />C
<br />1"
<br />33-60
<br />D
<br />1-1/4"
<br />61-113
<br />E
<br />1-1/2"
<br />114-154
<br />F
<br />2"
<br />154-330
<br />r- HOT OR COLD WATER SUPPLY
<br />IF HORIZONTAL BRANCH IS LESS THAN 20'
<br />LONG, PROVIDE ONE WHA AT END OF LINE.
<br />IF BRANCH IS GREATER THAN 20' LONG,
<br />PROVIDE ANOTHER WHA IN MIDDLE, EACH
<br />SIZED FOR HALF THE FIXTURE UNITS. -
<br />MULTIPLE FIXTURES
<br />FIXTURE UNIT TABULATION
<br />FIXTURE
<br />COLD
<br />HOT
<br />VALVE WATER CLOSET
<br />10
<br />--
<br />TANK WATER CLOSET
<br />3
<br />--
<br />LAVATORY/SINK
<br />2
<br />2
<br />SHOWER/BATHTUB
<br />2
<br />2
<br />DO NOT PROVIDE AIR CHAMBERS. PROVIDE WATER HAMMER ARRESTERS BY SIOUX CHIEF,
<br />PRECISION PLUMBING PRODUCTS, WATTS OR APPROVED EQUIVALENT WITH PISTON AND 0-RING
<br />CONSTRUCTION, HAVING PDI #WH-201, ASSE # 1010 AND ANSI # Al 12.26.1 M CERTIFICATION.
<br />INSTALL IN HORIZONTAL OR VERTICAL POSITION, BUT NEVER UPSIDE DOWN. INSTALL IN LINE
<br />WITH WATER FLOW IF POSSIBLE. SIZE THE UNITS AS SHOWN ON THE DRAWINGS AND/OR PER THE
<br />TABLES SHOWN ABOVE. SIOUX CHIEF "MINI -RESTER" MAY BE USED AT EACH FIXTURE. PROVIDE
<br />ACCESSIBILITY TO "WHA" WHERE REQUIRED BY LOCAL CODE.
<br />1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. IT IS INTENDED THAT A COMPLETE PLUMBING AND
<br />FIRE PROTECTION SYSTEM BE PROVIDED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES AND CONTROLS COMPLETELY COORDINATED WITH ALL DISCIPLINES.
<br />ALL PARAMETERS GIVEN IN THESE DOCUMENTS SHALL BE STRICTLY CONFORMED TO. ANY ITEMS AND LABOR REQUIRED FOR A COMPLETE PLUMBING AND FIRE
<br />PROTECTION SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES, STANDARDS, LOCAL AUTHORITIES AND THESE CONTRACT DOCUMENTS SHALL BE FURNISHED
<br />WITHOUT INCURRING ANY ADDITIONAL COST TO THE OWNER. CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND THE DESIGN OF OTHER TRADES BEFORE
<br />PREPARING SHOP DRAWINGS.
<br />2. COORDINATE ALL WORK WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL TRADES. PIPE ROUTING SHOWN IS DIAGRAMMATIC. PROVIDE ALL
<br />OFFSETS, ETC. TO AVOID INTERFERENCES WITH EQUIPMENT, PIPING, DUCT WORK, LIGHTS, CONDUITS, AND STRUCTURAL ITEMS, ETC...
<br />3. ALL DRAINAGE PIPING AND POTABLE WATER PIPING SHALL BE CONCEALED INSIDE WALLS AND PIPE CHASES OR ABOVE CEILINGS AS HIGH AS POSSIBLE.
<br />4. EXPOSED PIPING AT FIXTURES SHALL BE SECURED TO WALLS CONSTRAINED AGAINST ANY FREE -MOVEMENT OF PIPING.
<br />5. CONTRACTOR SHALL MAKE FINAL CONNECTION TO ALL DOMESTIC WATER, SANITARY SEWERS, STORM DRAINS, FIRE SUPPLY AND GAS SERVICES AT
<br />APPROXIMATELY 5'-0" FROM BUILDING STRUCTURE UNLESS OTHERWISE NOTED.
<br />6. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR LOCATION OF ALL PLUMBING FIXTURES. EXACT LOCATION OF ALL PLUMBING FIXTURES MUST BE VERIFIED
<br />IN FIELD PRIOR TO INSTALLATION. FINAL LOCATIONS AND HEIGHTS SHALL BE AS DIRECTED BY ARCHITECT.
<br />7. PLUMBING CONTRACTOR SHALL MAKE FINAL CONNECTION TO ALL EQUIPMENT INDICATED ON DRAWINGS INCLUDING KITCHEN AND LAUNDRY EQUIPMENT PER
<br />MANUFACTURER'S SPECIFIC INSTALLATION INSTRUCTIONS. FINAL CONNECTION SHALL INCLUDE ANY ADAPTERS, NIPPLES SHUTOFF VALVES, PRESSURE
<br />REGULATING VALVES, SHOCK ABSORBERS, BACKFLOW PREVENTION DEVICES, ETC. CONTRACTOR SHALL COMPLETELY REVIEW EACH EQUIPMENT ITEM'S
<br />INSTALLATION INSTRUCTIONS PRIOR TO COMMENCEMENT OF WORK. ALL ITEMS REQUIRED FOR INSTALLATION ARE INCLUDED IN THE PLUMBING CONTRACTOR'S
<br />SCOPE.
<br />8. DO NOT RUN PLUMBING OR FIRE PROTECTION PIPING THROUGH TRANSFORMER VAULTS, ELECTRICAL CLOSETS, ELECTRICAL SWITCHGEAR ROOMS, ELEVATOR
<br />EQUIPMENT ROOMS, COMPUTER ROOMS OR TELEPHONE ROOMS. DO NOT RUN ANY PIPING ABOVE ELECTRICAL PANELS OR OTHER ELECTRICAL/CONTROLS
<br />COMPONENTS.
<br />9. ALL COMMERCIAL FIXTURES SPECIFIED BY AN EQUIPMENT PROVIDER SHALL OVERRIDE ANY SPECIFIED PLUMBING FIXTURES ON THIS PLAN. THE PLUMBER SHALL
<br />COORDINATE FINAL REQUIRED FIXTURES WITH OWNER/EQUIPMENT SUPPLIER. VERIFY CONNECTION SIZE AND LOCATION OF ALL ITEMS WITH KITCHEN EQUIPMENT
<br />DRAWINGS.
<br />10.PROVIDE AN EXPANSION JOINT ON ALL PIPING SYSTEMS THAT CROSS BUILDING EXPANSION JOINTS.
<br />11.PROVIDE CONNECTION TO EXISTING WATER SERVICE WHERE AVAILABLE. PROVIDE WATER METER, PRV STATION WITH FULL SIZE BYPASS, AND RPZ VALVE.
<br />COORDINATE METER AND BACKFLOW REQUIREMENTS WITH LOCAL AUTHORITY AND UTILTIY COMPANIES. CONNECT TO EXISTING SANITARY AND KITCHEN WASTE
<br />STUB WHERE AVAIALBLE. CONNESTIONS TO EXISTING UTILTIES SHALL BE COORDINATED IN THE FIELD FOR EXACT LOCATION AND INVERT AVAILABILITY.
<br />12.PROVIDE GAS CONNECTION TO EXISTING METER WHERE POSSIBLE. PROVIDE CONNECTION TO ROOF MOUNTED EQUIPMENT AND TO KITCHEN EQUIPMENT AS
<br />INDICATED ON KITCHEN EQUIPMENT DRAWING. PROVIDE SHUT-OFF VALVES AT ALL POINTS OF CONNECTION. PROVIDE SOLENOID SHUT-OFF VALVE FOR GAS ITEMS
<br />UNDER KITCHEN HOODS. INTERLOCK SOLENOID WITH HOOD FIRE PROTECTION SYSTEM. GAS PIPING SHALL NOT BE ROUTED BELOW FLOORS. PIPING INDICATED AS
<br />BELOW SLAB SHALL BE PROVIDED IN A PREFABRICATED MODULAR STAINLESS STEEL UTILITY TRENCH.
<br />13.ALL PLUMBING FIXTURES, PIPING, AND MATERIALS SHALL BE LISTED OR LABELED AND INSTALLED AS PER A RECOGNIZED APPROVAL AGENCY.
<br />14.ALL WORK WITHIN THIS SCOPE OF WORK SHALL COMPLY WITH ALL CITY, STATE AND NATIONAL PLUMBING CODES. ALL WORK SHALL CONFORM TO BUILDING
<br />STANDARDS.
<br />15.PLUMBING CONTRACTOR SHALL VERIFY VOLTAGE, PHASE AND WIRE SIZE OF PLUMBING EQUIPMENT REQUIRING ELECTRICAL CONNECTION WITH ELECTRICAL
<br />CONTRACTOR PRIOR TO PURCHASE OF EQUIPMENT
<br />16.ALL PLUMBING UTILTIY AND SERVICE REQUIREMNTS SHALL BE COORDINATED BY THE CONTRACTOR WITH THE LOCAL CODE AUTHORITIES AND UTILITY COMPANIES.
<br />ANY ADDITIONAL REQUIREMENTS FOR UTILTY SERVICES SHALL BE INCLUDED IN CONTRACTOR SCOPE.
<br />17.COORDINATE ALL UNDERGROUND PIPING WITH GRADE BEAMS, WALL FOOTINGS, COLUMN FOUNDATIONS AND OTHER STRUCTURAL CONDITIONS.
<br />18.ALL DRAINAGE PIPING AND VENT PIPING SHALL SLOPE AT 1/8 INCH PER FOOT UNLESS OTHERWISE NOTED.
<br />19.FLOORS WHERE INDICATED ON ARCHITECTURAL AND /OR STRUCTURAL DRAWINGS SHALL SLOPE TO FLOOR DRAINS. MAXIMUM SLOPE IN ANY DIRECTION SHALL
<br />NOT EXCEED 1/4 INCH PER FOOT. EXACT LOCATION OF ALL FLOOR DRAINS AND HUB DRAINS FOR EQUIPMENT MUST BE VERIFIED IN FIELD PRIOR TO INSTALLATION.
<br />FINAL LOCATION SHALL BE AS DIRECTED BY ARCHITECT. FLOOR DRAIN SHALL BE COMPLETELY FLUSH WITH THE LOWEST LEVEL OF THE FLOOR SLOPE AND SHALL
<br />NOT PROTRUDE BEYOND THE FLOOR SO AS TO CAUSE POOLING AROUND THE DRAIN. CUTTING OF ANY FLOOR DRAINAGE FIXTURE GRATE SHALL NOT BE PERMITTED
<br />20. EXACT LOCATION OF ALL CLEANOUTS MUST BE COORDINATED AND APPROVED BY ARCHITECT PRIOR TO INSTALLATION.
<br />21. COORDINATE ALL FIXTURE GRATES, ORIENTATIONS, AND REQUIRED GRATE SPACING WITH THE KITCHEN EQUIPMENT SUPPLIER. VERIFY ALL FLOOR DRAIN AND
<br />FLOOR SINK LOCATIONS WITH THE KITCHEN CONSULTANT. HALF -GRATES SHALL BE PROVIDED FOR HUB DRAIN COLLECTING INDIRECT SINK DISCHARGE.
<br />CONTRACTOR SHALL COORDINATE FINAL FLOOR SINK LOCATIONS WITH SINK SUPPORT LEGS TO AVOID SUPPORTS SITTING ON GRATES.
<br />22. SANITARY VENTS MUST TERMINATE A MINIMUM OF 10 FT. FROM OR 2 FT. ABOVE AIR INTAKES, WINDOWS OR VENT SHAFTS.
<br />23. INDIRECT WASTE RECEPTORS MUST BE LOCATED WHERE READILY ACCESSIBLE FOR INSPECTION AND CLEANING.
<br />24. ALL HOSE BIBBS AND WASHDOWN FAUCETS ARE REQUIRED TO HAVE PROPER BACKFLOW PREVENTERS WHERE HOSES ARE ATTACHED AND LEFT UNATTENDED.
<br />CHEMICAL FEED SYSTEMS AT COMMERCIAL KITCHENS SHALL HAVE DEDICATED BACKFLOW PREVENTERS SEPARATE FROM WASHO-DOWN OR HOSE BIB FIXTURES.
<br />25. PVC PIPING SHALL BE PROHIBITTED IN ANY AIR PLENUM SPACES. PIPING SHALL NOT BE PROVIDED WITHING INSULATED COOLER/FREEZER PANEL WALLS.
<br />26. PROVIDE 12" x 12" ACCESS PANELS FOR SHOCK ABSORBERS, TRAP PRIMERS AND ALL VALVES LOCATED ABOVE NON -ACCESSIBLE CEILINGS AND INSIDE PIPE
<br />CHASES. EXACT LOCATION MUST BE COORDINATED WITH ARCHITECTURAL DRAWINGS AND APPROVED BY ARCHITECT PRIOR TO INSTALLATION. ALL ACCESS
<br />PANELS SHALL BE LOCATED SO THAT THEY ARE NOT VISIBLE TO PUBLIC VIEW.
<br />27. WALL HYDRANTS AND HOSE BIBBS SHALL BE MOUNTED 1'- 6" ABOVE GRADE OR FLOOR LEVELS.
<br />28. PIPING ISULATION SHALL BE PROVIDED WITH CONTIUOUS AIR -TIGHT VAPOR BARRIER WITH NO LOOSE TAPE OR EXPOSED INSULATION MATERIAL. CONDENSATE
<br />PIPING SHALL BE PROVIDED WITH ELASTOMERIC INSULATION. ALL INSULATION AND WRAPPING JOINTS AND SEEMS SHALL BE PROVIDED WITH 1 OVERLAP AND
<br />MANUFACTURER RECOMMENDED, AIR-TIGH MASTIC AT ANY INSULATION OR VAPOO BARTER JOINTS. INSULATION SHALL BE INSTALLED WITH FULL THICKNESS, FREE
<br />OF ANY INSUALTION COMPRESSION. PROVIDE RIGID INSULATION SECTION AT ALL PIPING HANGERS,
<br />29. PROVIDE REDUCED PRESSURE BACKFLOW PREVENTER AT ALL CONNECTIONS TO MECHANICAL EQUIPMENT, KITCHEN AND LAUNDRY EQUIPMENT, IRRIGATION AND
<br />POOL CONNECTIONS, WATER SOFTENERS, VENDING MACHINES, ETC. AS REQUIRED BY CODE AND LOCAL AUTHORITIES. CONTRACTOR IS TO VERIFY WITH THE LOCAL
<br />AUTHORITY THE TYPE OF BACKFLOW PREVENTION DEVICE REQUIRED FOR ALL APPLICATIONS PRIOR TO INSTALLATION. DRAINAGE FIXTURE AND PIPING (HUB
<br />DRAIN/FLOOR DRAIN ETC) SHALL BE PROVIDED FOR EACH BFP CONTAINING A BACKFLOW DISCHARGE.
<br />30. EXTEND ALL PVC CONDUITS CONTAINING BEVERAGE LINES, HOT AND COLD WATER PIPING, ETC. BELOW FLOOR/GROUND A MINIMUM OF ONE INCH ABOVE FINISHED
<br />FLOOR AND SEAL AROUND PIPING TO ENSURE WATER- TIGHT CONNECTIONS. OFFSET ALL PVC BEVERAGE CONDUITS WITH 24" MINIMUM RADIUS FITTINGS. REFER
<br />TO KITCHEN EQUIPMENT DRAWINGS FOR ADDITIONAL DETAILS AND REQUIREMENTS.
<br />31. PROVIDE A VALVED BYPASS AT ALL EQUIPMENT INCLUDING WATER HEATERS, STORAGE TANKS WATER SOFTENERS, BOOSTER PUMPS, FIRE PUMPS, ETCO FOR
<br />MAINTENANCE OF EQUIPMENT.
<br />32. PROVIDE BALL VALVES AT ALL BRANCH LINES SERVING MULTIPLE FIXTURES. PROVIDE ACCESSIBLE BALL VALVE AT EACH FIXTURE CONNECTION (IN ADDITION TO
<br />ANY EXPOSED STOPS) OR FIXTURE HEADER BRANCH CONNECTION.
<br />33. INSTALL VACUUM BREAKERS A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF A FIXTURE SERVED WITH NO SHUT-OFF DEVICES BEYOND THE DISCHARGE OF THE
<br />VACUUM BREAKER.
<br />34. THE USE OF RISER CLAMPS TO SUPPORT VERTICAL PIPE ALONG WALLS, OR COLUMNS IS PROHIBITED. PROVIDE B-LINE 22 STRUT & B-2000 PIPE CLAMPS
<br />35. CONTRACTOR SHALL HANG ALL PIPING FROM THE STRUCTURAL MEMBERS (W-SHAPES, BAR JOISTS) WITH CLAMP -TYPE CONNECTIONS. PIPING SHALL NOT BE
<br />SUPPORTED FROM THE METAL DECK. STRUCTURAL MEMBERS SHALL NOT BE CUT OR DRILLED.
<br />36. ALL JOINTS, ANNULAR SPACES, OR OPENINGS INTO HOLLOW OR INACCESSIBLE AREAS ARE TO BE CLOSED TO 1/32" OR LESS FOR FOOD SERVICE AREAS.
<br />37. ALL ANNULAR SPACES ARE TO BE CLOSED AND ESCUTCHEON PLATES AT HAND WASHING AREAS MUST BE SECURED.
<br />38. TRAP FOR FLOOR DRAINS, FLOOR SINKS, OR HUB DRAINS ASSOCIATED WITH THE FOOD SERVICE AREAS AND NOT AS AN INDIRECT WASTE RECEPTOR SHALL BE
<br />PROVIDED WITH A WATER SEAL OF AT LEAST 4" DEEP.
<br />39. INSTALL VACUUM BREAKERS A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF THE FIXTURE SERVED WITH NO SHUT-OFF DEVICES BEYOND THE DISCHARGE OF
<br />THE VACUUM BREAKER.
<br />40. ALL JOINTS, ANNULAR SPACES, OR OPENINGS INTO HOLLOW OR INACCESSIBLE AREAS ARE TO BE CLOSED TO 1/32" OR LESS FOR FOOD SERVICE AREAS.
<br />INSTALL ALL FITTINGS AT FULL
<br />LINE SIZE WITH CLEAR ACCESS
<br />TO ALL ACCESS PORTS AND
<br />FITTING HANDLE SWING
<br />CLEARANCES.
<br />PRESSURE
<br />GAUGE
<br />STRAINER
<br />1" WATTS
<br />25 UAB-DU-Z3
<br />W/INTEGRAL
<br />STRAINER
<br />1-1/4" ff't_ ; u)
<br />WATTS 009 RPZ BACKFLOW-
<br />COORDINATE WITH LOCAL WATER
<br />UTILITY COMPANY REQUIREMENTS.
<br />ROUTE DISCHARGE TO HUB DRAIN.
<br />W IQ
<br />SET AT 70# i}
<br />Im
<br />Ill
<br />1-1/4" WATER SERVICE DETAIL
<br />U
<br />�I
<br />r�
<br />V
<br />H
<br />Zz
<br />_Qom
<br />C)
<br />� C)
<br />co aC110C)
<br />Nco
<br />W U) (o coajVwwcnLn
<br />U (� V rn
<br />♦` CwwDQ�
<br />vl~TIUQ[=c�
<br />co
<br />� N
<br />0
<br />LL
<br />•
<br />aIdofi6
<br />16009
<br />v
<br />0
<br />n
<br />0
<br />O
<br />z
<br />w
<br />U)
<br />z
<br />w
<br />U
<br />J
<br />Q
<br />❑
<br />o:
<br />O
<br />J
<br />U-
<br />o=
<br />Q
<br />z
<br />U)
<br />D
<br />CONTRACT DATE:
<br />01.05.2016
<br />BUILDING TYPE:
<br />N/A
<br />PLAN VERSION:
<br />DEC 2015
<br />SITE NUMBER:
<br />N/A
<br />STORE NUMBER:
<br />N/A
<br />SHELL BUILDOUT
<br />5935 GALL BLVD
<br />ZEPHYRHILLS, FL 33541
<br />REMODEL
<br />PHASE 1
<br />SANITARY WASTE
<br />AND
<br />VENT
<br />FLOOR PLANS
<br />Pi mi
<br />' �' �11
<br />WATER HAMMER ARRESTOR DETAIL
<br />PLOT DATE:
<br />
|