<br />ELECTRICAL SYMBOL LEGEND
<br />NOTE: ALL SYMBOLS MAY NOT BE USED ON THIS PROJECT
<br />HOMERUN TO PANELBOARD, NO. OF ARROWS INDICATE
<br />NO. OF CIRCUITS
<br />CONDUIT CONCEALED IN WALL, IN SLAB ABOVE, OR ABOVE CEILING
<br />CONDUIT CONCEALED IN OR BELOW FLOOR OR UNDERGROUND
<br />CONDUIT RUN EXPOSED, RUN PARALLEL OR PERPENDICULAR
<br />TO STRUCTURE OR WALL
<br />CIRCUITING CONTINUED ON ANOTHER SHEET
<br />Ju I t:
<br />)PPER CASE LETTER ADJACENT TO LUMINAIRE DENOTES TYPE
<br />.OWER CASE LETTER ADJACENT TO LUMINAIRE DENOTES SWITCHING
<br />a® A
<br />RECESSED -MOUNTED LUMINAIRE
<br />O A
<br />CEILING —MOUNTED LUMINAIRE
<br />I-Q A
<br />WALL —MOUNTED LUMINAIRE
<br />A
<br />2'x4' FLUORESCENT LUMINAIRE, CEILING —MOUNTED
<br />A
<br />F
<br />2'x2' FLUORESCENT LUMINAIRE, CEILING -MOUNTED
<br />L
<br />"NL' INDICATES LUMINAIRE ON UNSWITCHED NIGHT LIGHT CIRCUIT
<br />�--i A
<br />FLUORESCENT STRIP LUMINAIRE
<br />FLUORESCENT LUMINAIRE, WALL -MOUNTED
<br />A
<br />EMERGENCY BATTERY PACK LUMINAIRE
<br />�X ®X
<br />EXIT LIGHTS, PROVIDE ARROWS AS REQUIRED
<br />A
<br />EXTERIOR LUMINAIRE AND POLE
<br />IV
<br />TRACK LIGHTING
<br />SINGLE -POLE SWITCH, 48" AFF
<br />$3
<br />THREE-WAY SWITCH, 48" AFF
<br />$4
<br />FOUR-WAY SWITCH, 48" AFF
<br />$D
<br />DIMMING SWITCH, 48" AFF
<br />$P
<br />SINGLE -POLE SWITCH WITH PILOT LIGHT, 48" AFF
<br />$F
<br />FAN SPEED CONTROL SWITCH - LUTRON
<br />MOTION SWITCH
<br />®
<br /># DENOTES # OF BUTTONS
<br />XX
<br />DETAIL CALL -OUT
<br />XX
<br />TOP NUMBER IS DETAIL NUMBER, BOTTOM
<br />NUMBER IS WHERE DETAIL IS LOCATED
<br />[FAC'PI
<br />FIRE ALARM CONTROL PANEL
<br />FIRE ALARM MANUAL PULL STATION
<br />0
<br />SMOKE DETECTOR
<br />FOQ
<br />FIRE ALARM HORN/STROBE
<br />SD
<br />DUCT -MOUNTED SMOKE DETECTOR
<br />TS
<br />TAMPER SWITCH
<br />FS
<br />FLOW SWITCH
<br />GROUND PER NEC
<br />ELECTRIC METER AND CABINET
<br />FLUSH- OR SURFACE -MOUNTED PANELBOARD
<br />n MOLDED CASE CIRCUIT BREAKER
<br />JO JUNCTION BOX
<br />20A, 125V DUPLEX RECEPTACLE 5-20R
<br />TWO 20A, 125V, 3W DUPLEX RECEPTACLE, MOUNTED 18" AFF
<br />20A, 125V, 3W DUPLEX ISOLATED GROUND, RECEPTACLE MOUNTED
<br />SIG 18" AFF
<br />TWO 20A, 125V, 3W DUPLEX ISOLATED GROUND, 5-20R MOUNTED
<br />SIG 18" AFF
<br />20A, 125V, 3W DUPLEX RECEPTACLE, MOUNTED 48" AFF OR 2"
<br />ABOVE COUNTER, AS REQUIRED
<br />20A, 125V, 3W SIMPLEX RECEPTACLE, MOUNTED 18" AFF
<br />20A, 125V,
<br />3W
<br />DUPLEX
<br />RECEPTACLE IN FLUSH
<br />FLOOR BOX
<br />20A, 125V,
<br />3W
<br />DUPLEX
<br />ISOLATED -GROUND RECEPTACLE IN FLUSH
<br />® IG
<br />FLOOR BOX
<br />20A, 125V,
<br />3W
<br />DUPLEX
<br />CLEAN POWER RECEPTACLE, MOUNTED
<br />18" AFF
<br />20A, 125V,
<br />3W
<br />DUPLEX
<br />CLEAN POWER RECEPTACLE, MOUNTED
<br />48" AFF OR
<br />2"
<br />ABOVE
<br />COUNTER, AS REQUIRED
<br />®
<br />20A, 125V, 3W DUPLEX CLEAN POWER RECEPTACLE
<br />IN FLUSH FLOOR BOX
<br />20A
<br />TWIST -LOCK RECEPTACLE L5-20R, PLUG L5-20P 20A 125V.
<br />Q
<br />CORD #12.
<br />20A
<br />TWIST -LOCK RECEPTACLE 1_1 1-20R, PLUG L1 1-20P 20A 250V 30.
<br />CORD #12.
<br />30A
<br />TWIST -LOCK RECEPTACLE L5-30R, PLUG L5-30P 30A 125V.
<br />CORD #10.
<br />30A
<br />TWIST -LOCK RECEPTACLE L6-30R, PLUG L6-30P 30A 250V.
<br />Q
<br />CORD # 10.
<br />50A
<br />TWIST -LOCK RECEPTACLE L15-50R, PLUG L15-50P 50A 250V
<br />Q
<br />30. CORD #6.
<br />60A
<br />TWIST -LOCK RECEPTACLE L15-60R, PLUG L15-60P 60A 250V
<br />30. CORD #4.
<br />XX/X/X
<br />DISCONNECT SWITCH, XX/XX/X DENOTES AMPERAGE, FUSE AND
<br />POLES
<br />MECHANICAL EQUIPMENT CALLOUT, INCLUDES DISCONNECT BY EC,
<br />GE)
<br />AS REQUIRED BY NEC
<br />XX
<br />C�
<br />ELECTRIC MOTOR
<br />EO
<br />EQUIPMENT CONNECTION POINT
<br />®
<br />RELAY
<br />(-QS
<br />WALL -MOUNTED SPEAKER
<br />QS
<br />CEILING -MOUNTED SPEAKER
<br />TELEPHONE OUTLET
<br />GENERAL NOTES
<br />1. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST NEC, STATE AND
<br />LOCAL REQUIREMENTS.
<br />2. THE DRAWINGS ARE DIAGRAMMATIC AND THE OMISSION OF AN ITEM
<br />NECESSARY FOR THE PROPER FUNCTIONING ON THE SYSTEM DOES NOT
<br />RELIEVE THE ELECTRICAL CONTRACTOR FROM SUPPLYING THAT ITEM.
<br />3. ALL POWER AND LIGHTING RACEWAY SHALL HAVE A GREEN -GROUND
<br />CONDUCTOR.
<br />4. COORDINATE ALL ELECTRICAL WORK WITH THAT OF OTHER TRADES PRIOR TO
<br />THE INSTALLATION OF THAT WORK.
<br />5. ARRANGE ALL INSPECTIONS AND OBTAIN ALL CERTIFICATES REQUIRED BY
<br />THE LOCAL CODE ENFORCEMENT AGENCY.
<br />6. EC MAY INSTALL MULTIPLE CIRCUITS INDICATED ON PANEL SCHEDULE IN A
<br />SINGLE CONDUIT. EC SHALL BE RESPONSIBLE FOR VERIFYING THAT CONDUIT
<br />FILL AND CONDUCTOR DERATING MEETS NEC. ON ISOLATED GROUND
<br />CIRCUITS, ALL NEUTRALS SHALL BE CONSIDERED A CURRENT -CARRYING
<br />CONDUCTOR AND EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL
<br />AND ISOLATED -GROUNDING CONDUCTOR (NO SHARING).
<br />7. EC SHALL FIRESTOP ALL ELECTRICAL PENETRATIONS OF FIRE -RATED
<br />PARTITIONS (WALLS, FLOORS, OR CEILINGS) WITH AN APPROVED FIRESTOP
<br />SYSTEM RATED FOR THE APPLICATION. FIRESTOP SYSTEM SHALL BE
<br />UL-LISTED AND INSTALLED IN STRICT COMPLIANCE WITH THE
<br />MANUFACTURER'S INSTRUCTIONS.
<br />8. ALL EXIT AND EMERGENCY LIGHTS SHALL BE CONNECTED TO THE
<br />UNSWITCHED LEG OF THE LOCAL LIGHTING CIRCUIT.
<br />9. THE LOCATION AND SIZE OF LOADS SHALL BE CHECKED WITH THE OWNER,
<br />ARCHITECT OR APPROPRIATE SUBCONTRACTOR AND ADJUSTMENTS MADE
<br />ACCORDINGLY.
<br />10. THE DESIGN IS BASED ON THHN/THWN COPPER CONDUCTOR. MINIMUM
<br />CONDUCTOR SIZE IS NO. 12 AWG.
<br />11. DO NOT SCALE FROM THESE DRAWINGS. REFER TO ARCHITECTURAL PLANS
<br />OR FIELD MEASUREMENTS FOR DIMENSIONS.
<br />12. EXPOSED INTERIOR CONDUIT IS NOT PERMITTED WITHOUT THE WRITTEN
<br />AUTHORIZATION OF THE OWNER. WHEN ALLOWED, SURFACE -MOUNTED
<br />RACEWAY SHALL BE WIREMOLD, OR EQUIVALENT METALLIC SURFACE
<br />RACEWAY. EC SHALL PROVIDE ALL RACEWAY, BOXES AND FITTINGS REQUIRED
<br />FOR A COMPLETE INSTALLATION. WIRING IN NONPUBLIC AREAS MAY BE IN
<br />EMT.
<br />13. ALL MECHANICAL EQUIPMENT SHALL HAVE A MEANS OF DISCONNECT AS
<br />REQUIRED BY NEC. EC SHALL FURNISH AND INSTALL A MOTOR SNAP SWITCH
<br />OR DISCONNECT SWITCH, WITH OR WITHOUT FUSES (PER MANUFACTURER'S
<br />RECOMMENDATION), WHERE REQUIRED BY CODE. FOR ALL OTHER
<br />MECHANICAL/PLUMBING EQUIPMENT. COORDINATE REQUIREMENTS WITH
<br />DIVISION 15.
<br />14. EC SHALL VERIFY WITH AHJ THE REQUIREMENT FOR SHOW WINDOW LIGHTING
<br />AND PROVIDE RECEPTACLES, AS REQUIRED.
<br />15. COORDINATE ELECTRICAL SERVICE REQUIREMENTS WITH LOCAL UTILITY
<br />COMPANY. PROVIDE ALL CONSTRUCTION IN COMPLIANCE WITH UTILITY
<br />COMPANY REQUIREMENTS.
<br />16. PRIOR TO ROUGH IN, EC SHALL VERIFY ELECTRICAL REQUIREMENTS FOR ALL
<br />KITCHEN EQUIPMENT AND COORDINATE RECEPTACLE LOCATION WITH
<br />SUPPLIED EQUIPMENT. EC SHALL PROVIDE PROPER RECEPTACLE, CORD AND
<br />PLUG FOR ALL EQUIPMENT SHOWN ON THE KITCHEN EQUIPMENT SCHEDULE.
<br />17. ALL 120V, 15- AND 20-AMP RECEPTACLES IN THE KITCHEN, BAR AND
<br />SERVICE AREAS SHALL BE GFCI RECEPTACLES. IN COMPLIANCE WITH NEC
<br />210.8.
<br />18. EC SHALL VERIFY ELECTRICAL REQUIREMENTS FOR WALK-IN COOLER AND
<br />WALK-IN FREEZER PRIOR TO ROUGH IN AND MAKE ADJUSTMENTS, AS
<br />REQUIRED, WITH NO ADDITIONAL COST TO OWNER. EC SHALL PROVIDE ALL
<br />POWER AND CONTROL WIRING AND RACEWAY, AS REQUIRED, FOR A FULLY
<br />OPERATIONAL WALK-IN COOLER AND WALK-IN FREEZER, INCLUDING LIGHTS,
<br />HEATERS, SENSORS AND REFRIGERATION SYSTEMS.
<br />19. SHUNT -TRIP BREAKER FEEDING PANEL K3 SHALL BE ACTIVATED BY THE
<br />ANSUL SYSTEM.
<br />20. EC TO PROVIDE BOX AND CONDUIT FOR ALL DATA AND TELEVISION OUTLETS.
<br />ALL DATA AND TELEVISION CABLING AND DEVICES TO BE FURNISHED AND
<br />INSTALLED BY OTHERS.
<br />21. MOTION SWITCH TO BE SENSORSWITCH WSD-W OR EQUIVALENT.
<br />22. FAN SPEED CONTROL SWITCH TO BE LUTRON NTFS-I2E-WH.
<br />23. FLOOR BOX TO BE WALKER 880CS1-1 WITH BRASS FLANGE AND COVER
<br />PLATE.
<br />24. ALL PANELS AND DISCONNECT SWITCHES SHALL BE SQUARE D, NO
<br />EXCEPTIONS.
<br />25. ALL LIGHT FIXTURES TO BE AS SHOWN ON THE LIGHTING FIXTURE
<br />SCHEDULE, NO EXCEPTIONS.
<br />26. LIGHTING CONTROL SYSTEM SHALL BE LUTRON, NO EXCEPTIONS.
<br />27. ROOF TOP UNITS TO SHUT DOWN UPON ACTIVATION OF THE DUCT SMOKE
<br />DETECTOR. EC SHALL WIRE AS NECESSARY AND COORDINATE WITH
<br />MECHANICAL.
<br />28. SOUND SYSTEM, INCLUDING SPEAKERS AND WIRING, TO BE FURNISHED AND
<br />INSTALLED BY OTHERS.
<br />29. SYSTEM TERMINAL BOARD TO BE MOUNTED IN A 24"Wx36" Hx6" D
<br />FLUSH -MOUNTED ENCLOSURE WITH LOCKING DOOR.
<br />30. BREAKERS IN PANEL MDP FEEDING DOWNSTREAM PANELS SHALL BE
<br />SELECTED TO SERIES RATE TO ALLOW 10K AIC BRANCH BREAKERS IN THE
<br />DOWNSTREAM PANELS.
<br />�D DATA OUTLET
<br />c�
<br />�v TELEVISION OUTLET
<br />DICKENS & ASSOCIATES, INC.
<br />232 Bay Street Phone: (386) 253-1511
<br />Daytona Beach, FL 32114 Fax: (386) 252-0673
<br />CA #: 002396 Project #: 4542.00
<br />Engineer: Stephen Byrne PE #: 17584
<br />u
<br />L
<br />O
<br />>
<br />•L
<br />C:
<br />0
<br />0�
<br />c
<br />�c
<br />c
<br />0
<br />0
<br />Q
<br />0
<br />UZ)
<br />u
<br />.:.c
<br />L
<br />0
<br />LO LO O
<br />,o
<br />0000CN
<br />r_�. rl�QQ
<br />00
<br />v v
<br />c
<br />O `'-
<br />a.
<br />O
<br />00
<br />D C%I
<br />cY)
<br />0
<br />a) O
<br />c .}
<br />0
<br />-0 �0
<br />c
<br />L 0
<br />LO c=i, O
<br />C
<br />C Co
<br />Lo
<br />a
<br />a
<br />N cr-
<br />(D copyright
<br />C7
<br />CV
<br />L0
<br />C Y)
<br />L M
<br />0 0
<br />>
<br />a) .
<br />L
<br />O O
<br />vi
<br />� s
<br />'O >`
<br />O s
<br />'O C1
<br />revisions:
<br />I
<br />i
<br />drawn:
<br />slb
<br />checked:
<br />spb
<br />date:
<br />3-21-08
<br />prof. no:
<br />P07-15B
<br />E 0.02