GENERAL NOTES
<br />1. ALL WORK IS TO COMPLY WITH THE 2017 NATIONAL ELECTRIC CODE AND THE 7TH EDITION,
<br />2020 FLORIDA BUILDING CODE, AND ALL LOCAL CODES OR REGULATIONS THAT MAY APPLY TO
<br />THE PROJECT.
<br />2. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MAKING A SITE VISIT IN ORDER TO
<br />IDENTIFY EXISTING CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />THAT ANY ELECTRICAL SYSTEMS TO REMAIN ARE CODE COMPLIANT.
<br />3. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY POWER AND
<br />TEMPORARY LIGHTING AS REQUIRED FOR THE DURATION OF THE PROJECT.
<br />4. THE ELECTRICAL CONTRACTOR IS REQUIRED TO PROVIDE A WORKMANSHIP WARRANTY OVER
<br />THE PERIOD OF ONE YEAR AFTER PROJECT COMPLETION THAT IS SUFFICIENT TO COMPLY WITH
<br />THE PROJECT CONTRACT.
<br />5. THE ELECTRICAL CONTRACTOR IS TO PROVIDE A COMPLETE SET OF MARKED UP ELECTRICAL
<br />"AS BUILT" DRAWINGS TO THE GENERAL CONTRACTOR UPON COMPLETION OF THE PROJECT.
<br />6. THE ELECTRICAL CONTRACTOR IS TO PROVIDE AN OPERATION AND MAINTENANCE MANUAL
<br />FOR ALL EQUIPMENT REQUIRING MAINTENANCE ASSOCIATED WITH THE PROJECT.
<br />7. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL WORK WITH OTHER
<br />TRADES IN ORDER TO NOT INTERFERE WITH THE OVERALL PROJECT SCHEDULE.
<br />8. IF A DISCREPANCY IS FOUND BETWEEN THE ELECTRICAL PLANS AND THE SPECIFICATIONS, THE
<br />MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS WRITTEN APPROVAL IS GRANTED
<br />FROM THE ARCHITECT OR ENGINEER.
<br />9. ALL BREAKER, DISCONNECT AND WIRE SIZING MUST BE CONFIRMED BY THE ELECTRICAL
<br />CONTRACTOR PRIOR TO ROUGHIN.
<br />SUBMITTALS AND SHOP DRAWINGS
<br />1. PRIOR TO PROCUREMENT, THE CONTRACTOR IS REQUIRED TO PROVIDE SUBMITTALS AND
<br />SHOP DRAWINGS TO THE GENERAL CONTRACTOR, ENGINEER, AND ARCHITECT FOR APPROVALS.
<br />2. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO ENSURE THE SUBMITTED
<br />PRODUCTS WILL FORM A COMPLETE, FUNCTIONAL, AND CODE COMPLIANT ELECTRICAL
<br />SYSTEM.
<br />WIRING AND RACEWAYS
<br />1. NO WIRING IS TO BE SMALLER THAN #12 AWG UNLESS OTHERWISE NOTED.
<br />2. EACH CIRCUIT IS TO BE INSTALLED WITH A DEDICATED NEUTRAL UNLESS OTHERWISE NOTED.
<br />3. THE CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS COMBINED SHALL BE SIZED FOR A
<br />MAXIMUM AT 5% VOLTAGE DROP TOTAL PER FBC C405.5.3.
<br />4. TYPE MC CABLING IS ACCEPTABLE UNLESS PROHIBITED BY THE SPECIFICATIONS OF THE
<br />PROJECT, OR THE NATIONAL ELECTRIC CODE DUE TO THE OCCUPANCY TYPE OF THE PROJECT.
<br />5. NONMETALLIC CABLING (ROMEX) SHALL NOT BE USED.
<br />6. ALL WIRING IS TO BE SIZED ACCORDING TO THE NEC.
<br />7. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO UPSIZE ALL CONDUIT AND
<br />WIRING WHEN REQUIRED DUE TO VOLTAGE DROP POSED BY ONSITE CONDITIONS.
<br />8. PROVIDE COMPLETE RACEWAYS FOR ALL SYSTEMS AS REQUIRED BY THE NEC AND LOCAL
<br />CODES. TYPE PVC, EMT, AND RMC ARE PERMITTED AS REQUIRED BY THE LOCAL CODE.
<br />9. A GROUND CONDUCTOR IS TO BE SUPPLIED IN ALL RACEWAYS. SIZE THE GROUND CONDUCTOR
<br />PER THE NEC, OR AS SHOWN ON THE PLAN, WHICHEVER IS LARGER.
<br />10. RACEWAYS ARE TO BE CONCEALED AND EQUIPMENT IS TO BE FLUSH MOUNTED, UNLESS
<br />OTHERWISE NOTED, OR WHEN ONSITE CONDITIONS MAKE CONCEALING OR FLUSH MOUNTING
<br />IMPOSSIBLE.
<br />11. WHEN A RACEWAY PENETRATES A FIRE WALL OR FLOOR, THE RACEWAY IS TO BE SEALED IN A
<br />MANNER WHICH WILL MAINTAIN THE RATING OF THE WALL OR FLOOR.
<br />12. MINIMUM CONDUIT SIZE IS TO BE 3/4 INCH, UNLESS OTHERWISE NOTED.
<br />13. FLEXIBLE CONDUIT IS ALLOWABLE IN LENGTHS OF G OR LESS, WHEN IT IS MORE PRACTICAL TO
<br />MAKE CONNECTIONS TO EQUIPMENT.
<br />14. SEALTITE FLEXIBLE CONDUIT IS TO BE USED IN OUTDOOR APPLICATIONS.
<br />15. THE RACEWAY SYSTEM AS A WHOLE IS REQUIRED TO COMPLY WITH ALL NEC AND LOCAL CODE
<br />REQUIREMENTS.
<br />GROUNDING
<br />1. THE ELECTRICAL SYSTEM IS TO BE GROUNDED IN ITS ENTIRETY PER THE NEC.
<br />2. THE TELEPHONE / NETWORK BOARD IS TO HAVE NO.6 AWG GROUND WIRE TO THE MAIN
<br />SERVICE GROUND.
<br />3. ALL METALLIC EQUIPMENT INCLUDING RACEWAYS, PANELBOARDS, DISCONNECTS, BOXES, ARE
<br />TO BE CONNECTED TO THE GROUNDING SYSTEM PER NEC REQUIREMENTS.
<br />4. THE SERVICE GROUND IS TO BE SIZED ACCORDING TO NEC REQUIREMENTS AND IS TO BE
<br />CONNECTED TO BUILDING STEEL, COLD WATER PIPING, CONCRETE ENCASED STEEL, AND GAS
<br />PIPING IF REQUIRED.
<br />DEVICES
<br />1. LIGHT SWITCHES ARE TO BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO THE TOP OF
<br />THE DEVICE, UNLESS OTHERWISE NOTED.
<br />2. RECEPTACLES ARE TO BE MOUNTED 18 INCHES ABOVE FINISHED FLOOR TO THE CENTERLINE OF
<br />THE DEVICE, UNLESS OTHERWISE NOTED.
<br />3. THE COLOR AND STYLE OF OUTLETS AND SWITCHES ARE TO BE DETERMINED BY THE CLIENT.
<br />4. RECEPTACLES ARE TO BE GFCI TYPE WHERE NOTED.
<br />5. RECEPTACLES ARE TO BE SWITCHED TO COMPLY WITH FLORIDA BUILDING CODE ENERGY
<br />REGULATIONS WHERE REQUIRED.
<br />6. RECEPTACLES AND SWITCHES ARE TO BE FLUSH MOUNTED UNLESS OTHERWISE NOTED.
<br />7. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO ENSURE COMPATIBILITY OF
<br />SPECIAL RECEPTACLES WITH THE EQUIPMENT THEY ARE INTENDED TO SERVE.
<br />8. ALL EXTERIOR RECEPTACLES AND RECEPTACLES SUBJECT TO MOISTURE MUST BE OF GFCI TYPE
<br />REGARDLESS OF THE TYPE SHOWN ON THE ELECTRICAL PLANS.
<br />9. ALL EXTERIOR RECEPTACLES AND SWITCHES ARE REQUIRED TO BE INSTALLED WITH
<br />WEATHERPROOF "IN USE" TYPE COVERS.
<br />10. DEVICES ARE SHOWN ON THE ELECTRICAL PLANS FOR A REFERENCE LOCATION ONLY.
<br />COORDINATE EXACT LOCATION WITH ARCHITECTURAL PLANS AND OTHER TRADES. NOTE ANY
<br />CHANGES ON THE "AS BUILT" SET OF ELECTRICAL PLANS.
<br />SWITCHGEAR
<br />1. PANELBOARDS AND LOAD CENTERS ARE TO BE SQUARE D OR APPROVED EQUAL.
<br />2. PANELBOARDS AND LOAD CENTERS ARE TO BE PROVIDED WITH TRANSIENT VOLTAGE SURGE
<br />SUPPRESSION AS DESCRIBED IN THE ELECTRICAL PLANS.
<br />3. DISCONNECTS ARE TO BE HEAVY DUTY TYPE AND ARE TO BE FUSED WHERE THE EQUIPMENT IS
<br />NOT SUPPLIED BY THE APPROPRIATE BREAKER.
<br />4. ALL NEW BREAKERS ADDED TO EXISTING PANELS ARE TO MATCH THE EXISTING PANEL
<br />MANUFACTURER AND AIC RATING OF THE EXISTING BREAKERS.
<br />5. THE LOCATIONS OF ALL SWITCHGEAR, PANELS, DISCONNECTS, MCC'S, ETC. IS APPROXIMATE.
<br />CONSULT OWNER PRIOR TO ROUGH IN OF EQUIPMENT.
<br />6. PROVIDE TYPED PANEL SCHEDULES/DIRECTORIES FOR ALL PANELS UPON COMPLETION OF THE
<br />PROJECT. ENSURE THAT THE SCHEDULES PROVIDED REFLECT THE "AS BUILT" CONDITION AND
<br />ARE NOT SIMPLY COPIES OF THE PANEL SCHEDULES FROM THESE PLANS. IF AN EXISTING
<br />PANEL IS MODIFIED, IT IS ACCEPTABLE TO ADD THE MODIFICATION TO THE EXISTING SCHEDULE
<br />IN THE MANNER THE EXISTING SCHEDULE WAS ORIGINALLY CREATED.
<br />7. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS ON THE FRONT OF ALL PANELS,
<br />DISCONNECTS, TRANSFORMERS AND OTHER SWITCHGEAR. LABEL THE EQUIPMENT TO MATCH
<br />THE AS BUILT DRAWINGS TO ENSURE MAINTENANCE PERSONNEL ARE PROVIDED THE
<br />INFORMATION THEY NEED TO QUICKLY IDENTIFY THE ELECTRICAL SYSTEM.
<br />8. PROVIDE ALL OTHER IDENTIFICATION AS REQUIRED PER ANSI, NEC, AND ANY OTHER
<br />APPLICABLE STANDARDS / SPECIFICATIONS.
<br />9. IT IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY ALL NEC CLEARANCE
<br />REQUIREMENTS ARE MET BEFORE THE ROUGH -IN OF ANY EQUIPMENT. THE LAYOUT OF
<br />SWITCHGEAR AND OTHER EQUIPMENT ON THE PLANS IS DIAGRAMMATTCAL ONLY.
<br />LIGHTING
<br />1. CONNECT ALL EXIT SIGNS, EGRESS FIXTURES, AND NIGHT LIGHTS ON THE UNSWITCHED LEG
<br />OF A LOCAL LIGHTING CIRCUIT.
<br />2. MINIMUM EMERGENCY ILLUMINATION OF 1 FOOTCANDLE AT FLOOR LEVEL ALONG THE PATH
<br />OF EGRESS FOR 90 MINUTES IS REQUIRED. EMERGENCY LIGHTING FIXTURES SHALL BE
<br />ARRANGED BY THE CONTRACTOR TO ACCOMPLISH THIS REQUIREMENT.
<br />3. REFER TO THE ARCHITECTURAL CEILING PLAN FOR EXACT FIXTURE LOCATIONS.
<br />4. MULTIPLE FIXTURES MAY HAVE OPTIONS FOR MOUNTING IN GRID, OR DRYWALL CEILINGS. IT
<br />IS THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THE PROPER MOUNTING HARDWARE
<br />AND TRIM PIECES ARE ORDERED BASED ON THE CEILING TYPES SHOWN IN THE
<br />ARCHITECTURAL PLANS.
<br />5. ALL FIXTURES AND CONTROLS ARE FURNISHED AND INSTALLED BY THE ELECTRICAL
<br />CONTRACTOR, UNLESS OTHERWISE NOTED.
<br />PROFESSIONAL STATEMENT
<br />TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND
<br />SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING
<br />CODES AND THE APPLICABLE FIRE SAFETY STANDARDS AS DETERMINED
<br />BY THE LOCAL AUTHORITY IN ACCORDANCE WITH FLORIDA STATUTES.
<br />ABBREVIATIONS
<br />AFC
<br />- AVAILABLE FAULT CURRENT
<br />AFF
<br />- ABOVE FINISHED FLOOR
<br />AHU
<br />- AIR HANDLING UNIT
<br />BFG
<br />- BELOW FINISHED GRADE
<br />C
<br />- CONDUIT
<br />CW
<br />- COOL WHITE
<br />CU
<br />- CONDENSING UNIT
<br />CKT
<br />- CIRCUIT
<br />DACP
<br />- DOOR ALARM CONTROL PANEL
<br />DN
<br />-DOWN
<br />EF
<br />- EXHAUST FAN
<br />EG
<br />- EQUIPMENT GROUND
<br />ENCL
<br />-ENCLOSURE
<br />EWC
<br />- ELECTRIC WATER COOLER
<br />EWH
<br />- ELECTRIC WATER HEATER
<br />ETR
<br />- EXISTING TO REMAIN
<br />PNL
<br />- PANEL
<br />EOP
<br />- EDGE OF PAVEMENT
<br />EXP
<br />- EXPLOSION PROOF
<br />FCU
<br />- FAN COIL UNIT
<br />FHP
<br />- FRACTIONAL HORSE POWER
<br />FLA
<br />- FULL LOAD AMPERES
<br />G
<br />-GROUND
<br />GFCI
<br />- GROUND FAULT CIRCUIT INTERRUPTER
<br />HID
<br />- HIGH INTENSITY DISCHARGE
<br />HORIZ
<br />- HORIZONTAL
<br />IG
<br />- ISOLATED GROUND
<br />LW
<br />- LIGHT WHITE
<br />HP
<br />- HORSEPOWER / HEAT PUMP
<br />HVAC
<br />- HEATING, VENTILATING, AIR CONDITIONING
<br />JB
<br />- JUNCTION BOX
<br />LRA
<br />- LOCKED ROTOR AMPERES
<br />MCB
<br />- MAIN CIRCUIT BREAKER
<br />MLO
<br />- MAIN LUGS ONLY
<br />N
<br />-NEUTRAL
<br />NL
<br />- NIGHT LIGHT
<br />OB
<br />- OUTLET BOX
<br />PB
<br />- PULL BOX, PUSHBUTTON
<br />PS
<br />- PAY STATION
<br />RECEPT
<br />-RECEPTACLE
<br />SF
<br />- SUPPLY FAN
<br />SPEC
<br />- SPECIFICATIONS
<br />SPD
<br />- SURGE PROTECTION DEVICE
<br />SWECS
<br />- SMOKE WARNING EMERGENCY CALL SYSTEM
<br />TL
<br />- TWISTLOCK
<br />TTB
<br />- TELEPHONE TERMINAL BOARD
<br />TVTB
<br />- TELEVISION TERMINAL BOARD
<br />VERT
<br />- VERTICAL
<br />WM
<br />- WATT MISER
<br />WP
<br />- WEATHERPROOF
<br />WW
<br />- WARM WHITE
<br />XFMR
<br />- TRANSFORMER
<br />LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />PANELBOARD. 120/208V OR 120/MV
<br />DISCONNECT SWITCH
<br />1�c
<br />DUPLEX RECEPTACLE. 125V, 15A
<br />COUNTER HEIGHT DUPLEX RECEPTACLE.
<br />125V,15A
<br />®
<br />SPECIAL PURPOSE RECEPTACLE
<br />®
<br />EXIT FIXTURE
<br />EMERGENCY EXIT
<br />COMBINATION FIXTURE
<br />EMERGENCY FIXTURE
<br />p
<br />REMOTE EMERGENCY HEAD
<br />PENDENT FIXTURE
<br />O
<br />6" DOWNLIGHT (RECESSED)
<br />Q2x4
<br />LAY -IN FIXTURE
<br />$
<br />SINGLE -POLE SWITCH
<br />$A
<br />DMAER SWITCH
<br />$W
<br />LOW VOLTAGE SWITCH
<br />OCCUPANCY SENSOR SWITCH
<br />qp
<br />POWERPACK
<br />®
<br />OCCUPANCY SENSOR
<br />Q
<br />LOW VOLTAGE DUPLEX RECEPTACLE
<br />.
<br />LOW VOLTAGE DUPLEX RECEPTACLE
<br />(COUNTER HEIGHT)
<br />0
<br />EXHAUSTFAN
<br />G3
<br />RECIRCULATING PUMP
<br />GFCI
<br />GFCl/WP
<br />ETR
<br />HS
<br />SW
<br />F
<br />GROUND FAULT CIRCUIT INTERRUPTER
<br />WEATHER PROOF / GROUND FAULT
<br />EXISTING TO REMAIN
<br />HALF SWITCH RECEPTACLE
<br />SWITCHED RECEPTACLE
<br />FLUSH W/ FLOOR RECEPTACLE
<br />O©� REFERS TO LIKE NUMBER KEY NOTES
<br />UL SYSTEM No. WL1001
<br />(FORMERLY SYSTEM No. 147)
<br />7' RATING -1, 2, 3, AND 4 HR. (SEE ITEM 2 AND 3)
<br />'T' RATING - 0, 1, 2, 3, AND 4 HR. (SEE ITEM 3)
<br />SECTION A -A
<br />1. WALL ASSEMBLY- THE 1, 2, 3, OR 4 HOUR FIRE -RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE
<br />MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE
<br />RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES.
<br />a. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS CONSIST OF NOMINAL 2" x 4"
<br />LUMBER SPACED 16 INCHES O.C. WITH NOMINAL 2" x 4" LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN. 3-50 WIDE
<br />BY 1-3/8" DEEP CHANNELS SPACED MAX. 24" O.C.
<br />b. WALLBOARD GYPSUM -X' OR X' THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS,
<br />NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES
<br />DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAMETER OF OPENING IS 13)P.
<br />2. PIPE OR CONDUIT - NOMINAL 12" DIA (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL CONDUIT; NOM. 4" DIAMETER (OR SMALLER) STEEL
<br />ELECTRICAL CONDUIT MECHANICAL ORTYPE L (OR HEAVIER) COPPER TUBING OR NOM. V DIA (OR SMALLER) FLEXIBLE STEEL CONDUIT.
<br />3. FILL, VOID OR CAVITY MATERIALS - CAULK - CAULK FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR
<br />CONDUIT AND GYPSUM WALLBOARD AND W/ A MIN. y" DIA. BEAD OF CAULK APPLIED TO PERIMETER OF PIPE OR CONDUIT AT ITS EGRESS
<br />FROM THE WALL. CAULK INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY "F" RATING OF THE FIRESTOP
<br />SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED AS SHOWN IN THE FOLLOWING
<br />TABLE. THE HOURLY "T' RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE
<br />HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED AS TABULATED BELOW:
<br />MAX PIPE OR CONDUIT (DIA IN.) ANNULAR SPACE "F" RATING ,r RATING
<br />1 IN. 0 TO % IN. 1 OR 2 0+, 1 OR 2
<br />41N. 1/4TO1/2 30R4 30R4
<br />4 IN. 0 TO 1/4 1 OR 2 0
<br />4 IN. 1/4 TO 1/2 3 OR 4 0
<br />4 IN. 3/16 TO 3/8 1 OR 2 0
<br />+ WHEN COPPER IS USED, "T" RATING IS 0 H.
<br />MINNESOTA MINING & MFG. CO. - TYPES CP-25 S/L, CP-25 N/S, CP-25 WB, CP-25 WB+
<br />" BEARING THE UL CLASSIFICATION MARKING
<br />�1� 1.2• 3.4 HOUR FIRE RATED GYP. / STUD WALL ASSEMBLY
<br />SCALE = NONE
<br />UL SYSTEM No. CAJ1012
<br />(FORMERLY SYSTEM No. 129)
<br />"F" RATING -1 HR.
<br />'T' RATING - 0 HR.
<br />"L" RATING AT AMBIENT - LESS THEN 1 CFM/SQ. FT. (SEE ITEM 4)
<br />"L" RATING AT 400 F - LESS THEN 1 CFM/SQ. FT. (SEE ITEM 4)
<br />SECTION A -A SECTION A -A
<br />1. FLOOR OR WALL ASSEMBLY - MIN. 5" THICK REINFORCED NORMAL WEIGHT (100-150 pof) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF
<br />ANY UL CLASSIFIED CONCRETE BLOCKS". MAX. DIAMETER OF OPENING IS 6 INCHES. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE
<br />FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
<br />2. THROUGH - PENETRANTS - ONE METALLIC PIPE OR CONDUIT TO BE CENTERED WITHIN FIRESTOP SYSTEM. A NOM ANNULAR SPACE OF 3/4"
<br />IS REQUIRED WITHIN THE FIRESTOP SYSTEM, PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE FLOOR OR WALL
<br />ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR CONDUITS MAY BE USED:
<br />a. STEEL PIPE - NOM 4" DIA (OR SMALLER) SCHEDULE 6 (OR HEAVIER) STEEL PIPE.
<br />b. CONDUIT - NOM 4" DIA (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.
<br />3. PACKING MATERIAL - MIN 3" THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT
<br />FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR AS REQUIRED TO ACCOMMODATE THE REQUIRED
<br />THICKNESS FILL MATERIAL. PACKING MATERIAL TO BE CENTERED IN WALLS MID -DEPTH AND RECESSED TO ALLOW FOR INSULATION OF
<br />FILL MATERIAL.
<br />4. FILL, VOID OR CAVITY MATERIAL' - SEALANT OR FOAM - MIN 1/2" THCKNESS OF FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH TOP
<br />SURFACE OF FLOOR. IN WALLS, FILL MATERIAL TO BE APPLIED ON EACH SIDE OF PACKING MATERIAL. FOAMED SILICONE TO BE INSTALLED
<br />AS DESCRIBED IN THE MANUFACTURER'S APPLICATION INSTRUCTIONS AT A DENSITY OF 14 pa MIN TO 21 pcf MAX. THE THICKNESS OF FILL
<br />MATERIAL IS DEPENDANT UPON THE TYPE OF FILL MATERIAL AS SHOWN IN THE TABLE BELOW:
<br />FILL MATERIAL IDENTIFICATION MIN. THK OF FILL MATERIAL, in.
<br />TYPE F8-2001 1
<br />TYPE FB-2000 OR FB-2003 1/2
<br />MINNESOTA MINING & MFG Co. - TYPES FB-2000, FB-2000+, FB-2001, FB-2003 (FLOORS ONLY). (NOTE: L RATINGS APPLY ONLY WHEN FB-2000+
<br />IS USED.)
<br />BEARING THE UL CLASSIFICATION MARKING
<br />_T')i 1 HOUR FIRE RATED MASONRY FLOOR / WALL
<br />F.n n j SCALE = NONE
<br />ALIGN HORN ONLY DEVICE WITH TOP OF DOOR
<br />FRAME, STOBE OR HORN/STROBE DEVICE 80"
<br />AFF TO BOTTOM OF STROBE LENS
<br />FIRE ALARM HORN ONLY, 1
<br />STROBE OR HORN/STROBE,
<br />PAINT TO MATCH WALL I 2" ABOVE BACKSPLASH
<br />ALIGN WHEN
<br />ON SAME WALL � W
<br />4" ABOVE COUNTER `A' A
<br />FIRE ALARM PULL STATION W/O BACKSPLASH L
<br />iooi
<br />o m
<br />® Q 0
<br />0 30 0 CABINET
<br />rQy 7 (TYP.)
<br />��o P 0010
<br />FINISHED FLOOR
<br />NOTES:
<br />1. MOUNTING HEIGHTS SHOWN ARE FROM FINISHED FLOOR (A.F.F.), UNLESS OTHERWISE NOTED.
<br />2. LOCATIONS OF OUTLETS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL TAKE PRECEDENCE OVER
<br />THESE MOUNTING HEIGHTS. FIELD LOCATE OUTLETS WITH ARCHITECT DURING ROUGH -IN.
<br />3. INSTALL OUTLETS THAT ARE IN CLOSE PROXIMITY ON THE SAME CENTERLINE, OUTLETS THAT ARE
<br />WITHIN 2'-0" HORIZONTALLY AND WITHIN 1'40" VERTICALLY SHALL BE INSTALLED ON THE SAME
<br />HORIZONTAL CENTERLINE LOCATED HALF WAY BETWEEN THE HEIGHTS SHOWN. OUTLETS THAT ARE
<br />MORE THAN V-0" APART VERTICALLY SHALL BE INSTALLED ON THE SAME VERTICAL CENTERLINE.
<br />4. VERIFY MOUNTING HEIGHT WITH LOCAL AUTHORITY.
<br />5. ADA REQUIREMENTS SHALL SUPERCEDE STANDARD MOUNTING HEIGHTS WHEN THERE IS A
<br />CONFLICT.
<br />STANDARD MOUNTING HEIGHTS DETAIL
<br />Cam] 1
<br />(PNL)
<br />CKT:B-33
<br />St
<br />TIMECLOCK MODEL:
<br />INTERMATIC T101
<br />INTERNAL
<br />NT T OVERRIDE
<br />INTERIOR LI
<br />SCALE = NONE
<br />(PNL) CKT:B-33
<br />(PNL) CKT:B-33
<br />(PNL) CKT:B-35
<br />(PNL) CKT:B-39
<br />SPARE
<br />SPARE
<br />SPARE
<br />SPARE
<br />\ j
<br />SINGLE POLE SWITCH
<br />FOR MANUAL
<br />OVERRIDE. LOCATED
<br />ADJACENT TO
<br />TIMECLOCK AND
<br />CONTACTOR.
<br />CONTACTOR:
<br />SQUARE D 89036 120V CONTROL COIL.
<br />ELECTRICALLY HELD. SELECT APPROPRIATE
<br />NUMBER OF POLES WHEN ORDERING.
<br />L DIAGRAM
<br />° PNL-A- °
<br />208Y/120V 30 4W
<br />-C
<br />FED FROM MDP
<br />_ikE:
<br />111179 AFC
<br />o
<br />DINING LAY -INS
<br />DINING CANS
<br />KITCHEN LAY -INS
<br />DINING PENDANTS
<br />SPARE
<br />SPARE
<br />SPARE
<br />SPARE
<br />-EQUIPMENT NAME AS SPECIFIED ON PLANS
<br />-SYSTEM VOLTAGE
<br />-UPSTREAM EQUIPMENT SUPPLYING POWER
<br />AVAILABLE FAULT CURRENT AT EQUIPMENT
<br />-DATE OF FAULT CURRENT CALCULATION
<br />'ALL LABEL AT TOP OF ENCLOSURE
<br />1ALL DISTRIBUTION EQUIPMENT SUCH AS PANELBOARDS, SWITCHBOARDS, DISCONNECTS, TRANSFORMERS, ETC. SHALL BE
<br />PROVIDED WITH AN EQUIPMENT LABEL PER THE REQUIREMENTS OF THIS DETAIL.
<br />2. LABELS SHALL BE 2-PLY ENGRAVED PLASTIC LAMINATE WITH BLACK TYPEFACE LETTERS., LABEL BACKGROUND SHALL
<br />FOLLOW THE BELOW COLOR SCHEME:
<br />a. NORMAL POWER - WHITE
<br />b. UPS POWER - BLUE
<br />a LIFE SAFETY POWER - YELLOW
<br />3. LABEL MATERIAL SHALL BE DURABLE, UV STABLE, RATED FOR OUTDOOR USE, AND ABRASION RESISTANT. WHERE ATTACHED TO
<br />NEMA 4X EQUIPMENT, LABELS SHALL IN ADDITION BE CHEMICAL RESISTANT.
<br />4. LABELS SHALL BE PERMANENTLY ATTACHED TO ENCLOSURE COVER WITH RIVETS UNLESS DOING SO COMPROMISES ITS NEMA / IP
<br />RATING. LABELS FOR ENCLOSURES WITH WELDED SEAMS AND GASKETED DOORS SUCH AS THOSE RATED NEMA 12 OR NEMA 4
<br />SHALL BE INSTALLED USING PERMANENT WEATHER-, UV-, AND TEMPERATURE -RESISTANT DOUBLE -SIDED MOUNTING TAPE ONLY.
<br />5. A SUBMITTAL WITH A COMPLETE UST OF EQUIPMENT LABELS SHALL BE PROVIDED FOR ENGINEER APPROVAL PRIOR TO ORDERING.
<br />6. LABELS SHALL INDICATE NO LESS THAN THE FOLLOWING:
<br />a. EQUIPMENT NAME.
<br />b. THE NOMINAL SYSTEM VOLTAGE WHICH SAID EQUIPMENT IS CONNECTED TO.
<br />a THE EQUIPMENT NAME SUPPLYING POWER TO SAID EQUIPMENT.
<br />d. THE AVAILABLE FAULT CURRENT AT SAID EQUIPMENT.
<br />PANEL LABEL DETAIL
<br />GULF COAST
<br />ELECTRICAL DESIGN
<br />2111 Sunnydale Blvd. Suite D
<br />Clearwater, FL 33765
<br />(727) 330-4937 1 www.GCElectdcaiDesign.com
<br />Florida Board of Professional Engineers #33905
<br />A.
<br />,� 0� ••••••••"7s �I
<br />0 80 7
<br />:9% AEOF
<br />"Its in R%1110
<br />GIIIIIII
<br />z
<br />L-
<br />0 b-
<br />j� C E
<br />w A
<br />CL CL .rib
<br />a
<br />K%�ga 14
<br />r-I
<br />Z ,n
<br />Tj � 5
<br />00
<br />J lL_
<br />< d
<br />C�
<br />IL
<br />W
<br />h N
<br />9
<br />A E �
<br />Seal
<br />Andrew Z. Pavalis
<br />State of Florida License 096063
<br />Date: 2.9. 22
<br />Checked by: AZP
<br />Drawn: MAH
<br />Job: 21-042
<br />Sheet
<br />EO*O