ELECTRICAL SPECIFICATIONS:
<br />THE WORK UNDER THE REQUIREMENTS OF THESE SPECIFICATIONS SHALL BE
<br />OIN CONFORMANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL
<br />CODE. THE INSTALLATION SHALL ALSO COMPLY WITH ALL APPLICABLE
<br />RULES AND REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES.
<br />OALL ELECTRICAL EQUIPMENT SHALL HAVE UL LABEL AND SHALL BE OF
<br />SPECIFICATION GRADE.
<br />POWER DISTRIBUTION HOUSE PANELBOARD: PROVIDE DEAD -FRONT,
<br />OSAFETY -TYPE POWER DISTRIBUTION PANELBOARDS AS INDICATEDi WITH
<br />PANELBOARD SWITCHING AND PROTECTIVE DEVICES IN QUANTITIES, RATINGS,
<br />TYPES, AND WITH ARRANGEMENT SHOWN± WITH ANTI -TURN, SOLDERLESS
<br />PRESSURE TYPE MAIN LUG CONNECTORS APPROVED FOR USE WITH COPPER
<br />CONDUCTORS.
<br />HOUSE PANELBOARDS IS EXISTING EQUAL TO SQUARE D TYPE "NQOD".
<br />®VOLTAGE SHALL BE AS INDICATED. ACCEPTABLE MFG.i G.E., SIEMENS AND
<br />CUTLER -HAMMER
<br />TENANT PANELBOARDS: PROVIDE DEAD -FRONT SAFETY TYPE LIGHTING
<br />OAND BRANCH CIRCUIT PANELBOARDS AS INDICATED± WITH SWITCHING AND
<br />PROTECTIVE DEVICES IN QUANTITIES, RATINGS, TYPES AND ARRANGEMENTS
<br />SHOWN± WITH ANTI -TURN, 5OLDERLES-5 PRESSURE TYPE LUG CONNECTORS
<br />APPROVED FOR USE WITH COPPER CONDUCTORS.
<br />TENANT PANELBOARDS SHALL BE SQUARE D TYPE "QO". PANELBOARD
<br />OBOXES SHALL BE FIVE AND THREE -FOURTHS INCHES (5 3/4") DEEP.
<br />VOLTAGE SHALL BE AS INDICATED.
<br />ALL PANELBOARDS SHALL BE CONNECTED, DISTRIBUTED PHASE WITH
<br />OCIRCUIT NUMBERING AS INDICATED ON THE DRAWINGS. PANELBOARDS SHALL
<br />BE NUMBERED WITH ODD NUMBERS ON THE LEFT SIDE OF THE PANEL AND
<br />EVEN NUMBERS ON THE RIGHT SIDE OF THE PANEL.
<br />UNLESS OTHERWISE INDICATED, PROTECTIVE DEVICES SHALL BE MOUNTED
<br />WITH TOP OF CABINET OR ENCLOSURE 6'-6" ABOVE FINISHED FLOOR, SHALL
<br />OBE PROPERLY ALIGNED, AND SHALL BE ADEQUATELY SUPPORTED
<br />INDEPENDENTLY OF THE CONNECTING RACEWAYS. ALL STEEL SHAPES, ETC.,
<br />NECESSARY FOR THE SUPPORT OF THE EQUIPMENT SHALL BE FURNISHED
<br />AND INSTALLED BY THE CONTRACTOR WHERE THE BUILDING STRUCTURE IS
<br />NOT SUITABLE FOR MOUNTING THE EQUIPMENT DIRECTLY THEREON, UNLESS
<br />OTHERWISE INDICATED, ALL BRANCH CIRCUIT PROTECTIVE DEVICES
<br />ENCLOSURES SHALL BE NEMA TYPE I, GENERAL PURPOSE TYPE. CIRCUIT
<br />PROTECTIVE DEVICES INSTALLED OUTDOORS OR EXPOSED TO THE
<br />WEATHER SHALL HAVE WEATHERPROOF ENCLOSURES, NEMA TYPE "3R" OR
<br />TYPE "4"
<br />ALL SAFETY SWITCHES SHALL BE GENERAL DUTY TYPE. SWITCH MECHANISM
<br />OSHALL BE QUICK -MAKE, QUICK -BREAK COVER SHALL BE INTERLOCKED WITH
<br />MECHANISM TO PREVENT OPENING UNLESS SWITCH IS IN THE "OFF" POSITION.
<br />ALL ENCLOSURES SHALL BE PRIMED AND FINISHED TO RESIST RUSTING AND
<br />CORROSION. SWITCHES SHALL BE ITE, GENERAL ELECTRIC, SQUARE-D, OR
<br />CUTLER -HAMMER
<br />CIRCUIT BREAKERS FOR MOUNTING IN HOUSE PANELBOARD SHALL BE
<br />10 BOLT -ON TYPE, MOLDED PLASTIC CASE, AIR CIRCUIT BREAKER TYPE.
<br />BREAKERS SHALL HAVE THERMAL MAGNETIC TRIP UNITS AND MULTI -POLE
<br />BREAKERS SHALL HAVE A COMMON TRIP BAR SO THAT THE TRIPPING OF
<br />ONE POLE WILL AUTOMATICALLY TRIP ALL POLES OF THE BREAKER
<br />BREAKERS SHALL BE TRIP FREE AND TRIP INDICATING AND SHALL HAVE
<br />QUICK -MAKE, QUICK -BREAK CONTACTS.
<br />UPON COMPLETION OF WORK CORRECT ALL PANELBOARD CIRCUIT
<br />DIRECTORY CARDS TO REFLECT AS -BUILT CONDITIONS. PANELBOARD
<br />11 DIRECTORIES SHALL BE UPDATED WITH TYPEWRITTEN ACCURATE AND
<br />CURRENT INFORMATION BY THE CONTRACTOR AT THE END OF CONSTRUCTION.
<br />DIRECTORIES SHALL REFLECT RECORD CONDITIONS AND INCLUDE CIRCUIT
<br />NUMBER, TYPE AND LOCATION OF LOAD, A SET OF AS -BUILT DRAWINGS
<br />SHALL ALSO BE PREPARED AND TURNED OVER TO THE OWNER
<br />ALL CONDUCTORS SHALL BE THHN/THWN COPPER 012 MIN_ AND INSTALLED IN
<br />12 ALL
<br />COMPLETELY ENCLOSED RACEWAY SYSTEM.
<br />UNLESS SPECIFICALLY NOTED ON DRAWINGS, RACEWAYS SHALL COMPLY
<br />13 WITH THE FOLLOWING:
<br />RACEWAYS EXPOSED TO THE WEATHER OR IN DAMP LOCATIONS
<br />SHALL BE GALVANIZED RIGID STEEL WITH THREADED CONNECTIONS.
<br />RACEWAYS SHALL BE SIZED FOR THE CONDUCTORS INSTALLED,
<br />MINIMUM 1/2". FULL SIZE MC CABLE IS ACCEPTABLE IN DRY LOCATIONS
<br />THAT ARE NOT PATIENT AREAS- HOMERUNS TO PANELS TO BE IN
<br />CONDUIT.
<br />14 RACEWAYS RUN BELOW GRADE SHALL BE RIGID STEEL REDUNDANT GROUND
<br />PATH REQUIRED, EXPOSED ON BUILDING EXTERIOR SHALL BE RIGID STEEL
<br />CONDUIT.
<br />15 ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY
<br />SECURE AT ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS, AND
<br />EQUIPMENT -
<br />ALL RACEWAYS SHALL BE SECURELY SUPPORTED FROM THE BUILDING
<br />STRUCTURE.
<br />17 ALL RACEWAYS SHALL BE PROVIDED WITH EQUIPMENT GROUND CONDUCTOR -
<br />ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH
<br />SUITABLE SCREW FASTENED COVERS. OPEN KNOCK -OUTS OR HOLES IN
<br />BOXES SHALL BE PLUGGED WITH A SUITABLE BLANKING DEVICES.
<br />OUTLET BOXES FOR EXPOSED WALL MOUNTING AND OUTDOOR INSTALLATION
<br />19 SHALL BE CAST METAL TYPE "FS" OR "FD" BOXES WITH SUITABLE
<br />GALVANIZED SHEET STEEL COVERS, OR CAST METAL WEATHERPROOF OR
<br />VAPOR TIGHT COVERS WHEN NOTED ON THE DRAWINGS-
<br />20 UNLESS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER NO. 12
<br />AWG. MINIMUM. OR SIZE AS SHOWN ON DRAWINGS. CONDUCTORS SHALL HAVE
<br />TYPE ' 'THHN/THWN' INSULATION.
<br />SPLICES, TAPS AND ATTACHMENT FITTINGS AND LUGS SHALL BE
<br />21 ELECTRICALLY AND MECHANICALLY SECURE AND SOLDERLESS FOR
<br />CONDUCTORS SIZES NO. 8 AWG AND LARGER THERE SHALL BE PLENTY OF
<br />SLACK CABLE IN BOXES, OUTLETS AND CABINETS TO INSURE THAT THERE IS
<br />NO BINDING AT THE BUSHINGS. ALL LUGS SHALL BE OF THE CORRECT SIZES
<br />FOR THE CONDUCTORS JOINED AND IN NO CASE SHALL STRANDS BE CUT
<br />FROM A CONDUCTOR IN ORDER TO FIT THE CONDUCTOR INTO A LUG. TAPING
<br />OF JOINTS SHALL BE WITH VINYL PLASTIC ELECTRICAL TAPE TO SECURE
<br />INSULATION STRENGTH EQUAL TO THAT OF THE CONDUCTORS JOINED.
<br />THE INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND
<br />22 EFFECTIVELY GROUNDED AS REQUIRED BY THE NEC AND AS SPECIFIED
<br />HEREINAFTER
<br />23 CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS.
<br />THE CONTRACTOR SHALL VERIFY ALL LOCATIONS WITH THE OWNER PRIOR TO
<br />INSTALLATION. THEY SHALL NOT BE CHARGED FOR MINOR LOCATION
<br />CHANGES PRIOR TO INSTALLATIONS. LOCATIONS ARE APPROXIMATE. (DO
<br />NOT SCALE DRAWINGS).
<br />THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL ELECTRICAL
<br />25 LAYOUTS FOR BIDDING PURPOSES ONLY. IT IS THE RESPONSIBILITY OF THE
<br />CONTRACTOR TO PREPARE DETAILED SHOP DRAWINGS AND CONFIRM
<br />SPACE ALLOCATIONS.
<br />THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES
<br />26 FOR ELECTRICAL CONDUIT ROUTING AND EQUIPMENT PLACEMENT. AVOID
<br />INTERFERENCE WITH ARCHITECTURAL AND STRUCTURAL FEATURES SUCH AS:
<br />BEAMS, FOOTINGS, WINDOWS, ETC. NOTIFY ARCHITECT IMMEDIATELY OF ANY
<br />coNFL ICTS.
<br />THE ELECTRICAL CONTRACTOR THE HVAC FOREMAN AND GENERAL
<br />27 CONTRACTOR PROJECT MANAGER SHALL INSPECT t REVIEW THE
<br />CONDITIONS, AND SHALL COORDINATE THEIR WORK SO AS TO PROVIDE
<br />ADEQUATE SPACE ALLOWANCE ABOVE CEILING FOR ALL TRADES.
<br />THE PLANS 614OW THE LOCATION of ALL FIXTURES AND EQUIPMENT AND ARE
<br />28 INTENDED TO DEPICT THE GENERAL INTENT OF THE WORK IN SCOPE, LAYOUT
<br />AND QUALITY OF WORKMANSHIP. THEY ARE NOT INTENDED TO SHOW IN MINUTE
<br />DETAIL EVERY AND ALL ACCESSORIES INTENDED FOR THE PURPOSE OF
<br />EXECUTION OF THE WORK, BUT SHALL BE UNDERSTOOD THAT SUCH DETAILS
<br />WILL BE PART OF THIS WORK,
<br />THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE
<br />2g AND FUNCTIONAL SYSTEM: CONTROLS, AND CONNECTIONS TO NEW SERVICES,
<br />SUPPORTS, AND HARDWARE REQUIRED FOR THE SATISFACTORY OPERATION
<br />OF THE SYSTEM, WHETHER SPECIFICALLY SHOWN OR NOT ON THE DRAWINGS -
<br />WHERE DRAWINGS AND SPECIFICATIONS CONFLICT, IT SHALL BE THE
<br />30 RESPONSIBILITY OF THIS CONTRACTOR TO BRING SUCH CONFLICT TO THE
<br />ATTENTION OF THE ENGINEER FOR CLARIFICATION.
<br />ELECTfRICAL & r150L LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />I X 4 FLUORESCENT FIXTURE
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />2 X 4 FLUORESCENT FIXTURE
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />SHADING DENOTES FIXTURE WITH EM BATTERY PACK.
<br />SEE FIXTURE
<br />'NL' DENOTES FIXTURE UNSWITCHED FOR NIGHT LIGHT
<br />SCHEDULE
<br />FLUORESCENT STRIP FIXTURE
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />FLUORESCENT WALL BRACKET FIXTURE
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />O
<br />PL FLUORESCENT DOWNLIGHT
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />e
<br />EXIT -OR EM EXIT. LETTER
<br />SEE FIXTURE
<br />INDICATES TYPE. PROVIDE ARROWS AS REQUIRED.
<br />SCHEDULE
<br />SINGLE POLE SWITCH (20,4-120/2-1-1)
<br />45" AFF OR AS
<br />S S3 So
<br />'3' DENOTES 3-WAY 'O' DENOTES OCCUPANCY SENSOR
<br />NOTED
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />18" AFF OR AS
<br />'IG' DENOTES ISOLATED GROUND
<br />NOTED
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />18" AFF OR AS
<br />NOTED
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />48 AFF OR AS
<br />NOTED
<br />QUADRAPLEX RECEPTACLE, 125V, 20A
<br />18" AFF OR AS
<br />NOTED
<br />O
<br />COMBINATION VOICE/DATA OUTLET
<br />IS" AFF OR AS
<br />NOTED
<br />Tv
<br />T.V. OUTLET
<br />18" AFF OR AS
<br />NOTED
<br />SEE PANEL
<br />PANELBOARD 120/240V
<br />SCHEDULE
<br />/—�
<br />RACEWAY CONCEALED IN WALL OR ABOVE CEILING
<br />SEE SPECIFICATIONS
<br />HOMERUN TO PANEL, LETTERS INDICATE PANEL,
<br />SEE SPECIFICATIONS
<br />NUMBERS INDICATE CIRCUIT. NOTE: HASH MARKS
<br />INDICATES THE NUMBER OF WIRES EXCLUDING
<br />THE REQUIRED EQUIPMENT GROUND.
<br />MOTOR, NUMERAL INDICATES HORSEPOWER
<br />AS NOTED
<br />MOTOR RATED SWITCH WITH OVERLOAD
<br />MOUNTED ADJACENT
<br />RELAYS IF REQUIRED,
<br />TO EQUIPMENT
<br />E:J
<br />NON -FUSIBLE SAFETY SWITCH -SIZE AS NOTED
<br />SEE SPECIFICATIONS
<br />FUSIBLE SAFETY SWITCH -SIZE AS NOTED
<br />SEE SPECIFICATIONS
<br />R
<br />OR
<br />FIRE ALARM I DUCT DETECTOR Cf;Z4'DENOTES
<br />MOUNTED IN
<br />RETURN AIR 'SA' DENOTES SUPPLY AIR)
<br />HVAC DUCTWORK
<br />R
<br />FAN OR AIR HANDLER SHUTDOWN RELAY
<br />MOUNTED ADJACENT
<br />TO EQUIPMENT
<br />Q
<br />FIRE ALARM VISUAL SIGNAL
<br />80" AFF OR
<br />AS NOTED
<br />Q
<br />FIRE ALARM MANUAL PULLSTATION
<br />45" AFF OR
<br />A8 NOTED
<br />FIRE ALARM AUDIBLE/VISUAL SIGNAL. ADA
<br />60" AFF OR
<br />�4
<br />COMPATIBLE
<br />AS NOTED
<br />0
<br />FIRE ALARM SMOKEON
<br />DETECTOR
<br />CEILING OR
<br />AS NOTED
<br />FAO
<br />FIRE ALARM PANEL CFACP' DENOTES FIRE ALARM
<br />60" AFF OR
<br />FM
<br />CONTROL PANEL, 'FAA' DENOTES ANNUNCIATOR)
<br />AS NOTED
<br />EX
<br />DENOTES EXISTING DEVICE OR CIRCUIT TO REMAIN
<br />R
<br />DENOTE NEW LOCATION FOR RELOCATED DEVICE
<br />O O
<br />REFER TO LIKE NUMBERED NOTES
<br />NOTE -ALL MOUNTING HEIGHTS SHOWN ARE TO THE TOP OF THE
<br />DEVICE UNLESS NOTED OTHERWISE.
<br />NOT ALL SYMBOLS APPEAR ON PLANS.
<br />,ABBRE V I AT IONS:
<br />AFF - ABOVE FINISHED FLOOR
<br />AHU - AIR HANDLING UNIT
<br />BFG - BELOW FINISHED GRADE
<br />C - CONDUIT
<br />CW - COOL WHITE
<br />DACP - DOOR ALARM CONTROL PANEL
<br />DN - DOWN
<br />EF - EXHAUST FAN
<br />EG - EQUIPMENT GROUND
<br />ENCL - ENCLOSURE
<br />EWC - ELECTRIC WATER COOLER
<br />EWH - ELECTRIC WATER HEATER
<br />EX - EXISTING
<br />FCU - FAN COIL UNIT
<br />FHP - FRACTIONAL HORSE POWER
<br />FLA - FULL LOAD AMPERES
<br />G - GROUND
<br />GFI - GROUND FAULT INTERRUPTER
<br />HID - HIGH INTENSISTY DISCHARGE
<br />HORIZ - HORIZONTAL
<br />I - ISOLATED GROUND
<br />LW - LIGHT WHITE
<br />HP - HORSEPOWER, HEAT PUMP
<br />HVAC - HEATING, BENTILATING, AIR CONDITIONING
<br />JB - JUNCTION BOX
<br />LRA - LOCKED ROTOR AMPERES
<br />MCB - MAIN CIRCUIT BREAKER
<br />MLO - MAIN LUGS ONLY
<br />N - NEW
<br />NL - NIGHT LIGHT
<br />OB - OUTLET BOX
<br />PB - PULL BOX, PUSH-BUTTON
<br />R - RELOCATED
<br />RECEPT - RECEPTACLE
<br />SF - SUPPLY FAN
<br />SPEC - SPECIFICATIONS
<br />SWECS - SMOKE WARNING EMERGENCY CALL SYSTEM
<br />TL - TW16TLOCK
<br />TTB - TELEPHONE TERMINAL BOARD
<br />TVTB - TELEVISION TERMINAL BOARD
<br />UNO - UNLESS NOTED OTHERWISE
<br />VERT - VERTICAL
<br />WM - WATT MISER
<br />WP - WEATHERPROOF
<br />WW - WARM WHITE
<br />XFMR - TRANSFORMER
<br />System No. C-AJ-1259
<br />F Rating - 3 Hr
<br />T Rating - 0 Hr
<br />�A
<br />Section A -A
<br />1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Floor may also be
<br />constructed of any min 6 in. thick UL Classified hollow -core Precast Concrete Units*. Wall may also be constructed of any UL
<br />Classified Concrete Blocks*. Max diam of opening is 7 in.
<br />See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of
<br />manufacturers.
<br />2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the
<br />firestop system. The annular space between the pipe, conduit or tubing and the periphery of the opening shall be a min of 0 in.
<br />(point contact) to a max of 3 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The
<br />following types and sizes of metallic pipes, conduit or tubing may be used:
<br />A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
<br />B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe.
<br />C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit.
<br />D. Copper Tube - Nom 4 in. diam (or smaller) Type L (or heavier) copper tube.
<br />3. Forming Material - (Optional, Not Shown) - Mineral wool batt packing material or polyurethane backer rod friction fitted into
<br />opening and recessed from floor or wall surfaces as required to accommodate required thickness of fill material.
<br />4. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. thickness of fill material applied within the annulus, flush with both
<br />surfaces of floor or wall. At the point contact location between penetrating item and concrete, a min 1/4 in. thick bead of fill
<br />material shall be applied at the concrete/penetrating item interface on both sides of floor or wall.
<br />SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant
<br />*Bearing the UL Classification Mark
<br />7-7- Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876
<br />Reproduced courtesy of Underwriters Laboratories, Inc. �`
<br />Created or Revised: January 2, 2009
<br />C-AJ-1259
<br />STI (800)992-1180 - (908)526-8000 - FAX (908)231-8415 - E-Mail:techserv@stifirestop.com • Webs ite:www.stifirestop.corn PAGE 1 OF 1
<br />System No. W-L-1079
<br />F Ratings - 1 and 2 Hr (See Item 1B)
<br />T Rating - 0 Hr
<br />L Rating At Ambient - Less Than 1 CFM/sq ft
<br />L Rating At 400 F - Less Than 1 CFM/sq ft
<br />A
<br />��A
<br />Jectlon A -A
<br />1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the
<br />manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall
<br />include the following construction features:
<br />A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in.
<br />lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in. wide and
<br />spaced max 24 in. OC.
<br />B. Gypsum Board* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number of
<br />layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire
<br />Resistance Directory. Max diam of opening is in wood stud walls is 13 in. Max diam of opening in steel stud walls is 16 in.
<br />The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
<br />2. Through Penetrant - One metallic pipe or conduit to be installed either concentrically or eccentrically within the firestop
<br />system. The annular space between pipes or conduits and periphery of opening shall be min 0 in. (point contact) to max 3 in.
<br />Pipe or conduit to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or
<br />conduits may be used:
<br />A. Steel Pipe - Nom 12 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
<br />B. Iron Pipe - Nom 12 in. diam (or smaller) cast or ductile iron pipe.
<br />C. Conduit - Nom 4 in. diam (or smaller) electrical metallic tubing, nom 6 in. diam (or smaller) steel conduit or nom 1 in. diam
<br />(or smaller) flexible steel tubing.
<br />D. Copper Pipe - Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
<br />E. Copper Tube - Nom 6 in. diam (or smaller) Type L (or heavier) copper tube.
<br />Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876
<br />Reproduced courtesy of Underwriters Laboratories, Inc. (W-L-107
<br />�`
<br />STI Created or Revised: January 2,2009
<br />(800)992-1180 - (908)526-8000 - FAX (908)231-8415 - E-Mail:techserv@stifirestop.com - Website:www.stifirestop.com PAGE 1 OFZ
<br />OELECTRICAL fir-"1IC,4TIO1�1S
<br />SCALE: NOT TO SCALE
<br />GENERAL PROJECT AND DEMOLITION NOTES:
<br />1. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH
<br />EXISTING CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AND
<br />SCOPE OF WORK THE SUBMISSION OF A BID WILL BE EVIDENCED THAT
<br />SUCH AN EXAMINATION HAS BEEN MADE- LATER CLAIMS FOR LABOR,
<br />EQUIPMENT OR MATERIALS REQUIRED, OR FOR DIFFICULTIES
<br />i=NCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN
<br />=xAMINATION BEEN MADE, WILL NOT BE ALLOWED.
<br />2, ,ALL EXISTING CIRCUITS TO REMAIN SHALL IBE RECONNECTED IUHETHER
<br />INDICATED OR NOT ON PROJECT DOCUMENTS.
<br />3, NEW AND EXISTING CIRCUIT DESIGNATIONS MAY NOT REPRESENT ACTUAL
<br />1=1ELD CONDITIONS, FIELD VERIFY WHERE REQUIRED AND INDICATE
<br />.ACTUAL CIRCUIT USED ON THE AS -BUILT DRAWINGS.
<br />4- COORDINATE WITH OTHER TRADES FOR ITEMS IN THEIR SCOPE OF WORK
<br />WHICH WOULD REQUIRE ELECTRICAL WORK
<br />"DISCONNECTION/RECONNECTION ETC.) AND ARE NOT INDICATED ON THE
<br />ELECTRICAL PLANS.
<br />5, WHERE EXISTING PARTITIONS OR WALLS ARE SHOWN TO BE REMOVED
<br />CONTRACTOR SHALL REMOVE DEVICES TO NEAREST SOURCE JUNCTION
<br />30X AND SHALL MAINTAIN SERVICE TO REMAINING DOWNSTREAM
<br />ELECTRICAL OUTLETS. COORDINATE THE DEMOLITION OF THE EXISTING
<br />IJALLS WITH ARCHITECTURAL DRAWINGS,
<br />6,-ROTECT EXISTING ELECTRICAL EQUIPMENT AND INSTALLATIONS
<br />NECESSARY TO REMAIN. IF DAMAGED OR DISTURBED IN THE COURSE OF
<br />THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS
<br />OF, EQUAL CAPACITY, QUALITY, AND FUNCTIONALITY.
<br />-1, REMOVE ELECTRICAL EQUIPMENT AND INSTALLATIONS, INDICATED TO BE
<br />DEMOLISHED, IN THEIR ENTIRETY, WHERE THE EXISTING EQUIPMENT
<br />NDICATED TO BE DEMOLISHED CONTAINS BRANCH CIRCUITRY SERVICING
<br />OUTLETS THAT ARE EXISTING TO REMAIN, RELOCATE THE BRANCH CIRCUIT
<br />TO AN ALTERNATE PANEL AND INDICATE THE CHANGE ON THE AS -BUILT
<br />DRAWINGS.
<br />8. ABANDONED WORK: CUT OR REMOVE RACEWAY SLEEVES AND WIRING,
<br />NDICATED TO BE ABANDONED IN PLACE, BELOW THE SURFACE OF
<br />ADJACENT CONSTRUCTION. CAP RACEWAYS AND PATCH SURFACE TO
<br />I"IATCH EXISTING FINISH.
<br />9. THE CONTRACTOR SHALL INCLUDE WITHIN THE BID ALL REQUIRED OFF
<br />HOUR, OVERTIME, AND NON -BUSINESS HOUR WORK AS REQUIRED TO
<br />PERFORM THE DEMOLITION WITHOUT DISRUPTING THE BUILDING TENANTS
<br />NORMAL BUSINESS OPERATIONS.
<br />10, ALL DEMOLISHED EQUIPMENT AND WIRING SHALL BE REMOVED FROM SITE
<br />AND PROPERLY DISPOSED OF, OR TURNED OVER TO THE OWNER AT THE
<br />OWNER'S SOLE OPTION.
<br />Wall Opening Protective Materials (CLIV)
<br />SPECIFIED TECHNOLOGIES INC R14288
<br />SUITE 2 200 EVANS WAY, SOMERVILLE, NJ 08876 USA
<br />SpeeSeal Putty Pads, for use with max 4-11/16 by 4-11/16 in. flush device UI, Listed metallic
<br />cutlet boxes installed with steel cover plates in 1 and 2 h fire rated gypsum wallboard wall assemblies
<br />framed with min 3-1/2 in. deep wood or steel studs and constructed of the materials and in the manner
<br />specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance
<br />Directors•. Min 3/16 in. thick moldable putty pads are to be installed to completely cover the exterior
<br />surfaces of the outlet box (except for the side of the outlet box against the stud) and completely seal
<br />against the stud within the stud cavity. An additional 3/16 in. thickness of putty to be formed around
<br />the connector securing the end of each electrical metallic tube or conduit to the box. When used with
<br />tactallic outlet boxes larger than 4 by 4 in., a ball of putty is to be installed to plug the open end of
<br />tach electrical metallic tube or conduit within the outlet box. When max 4 by 4 in. metallic outlet
<br />loxes are used, the ball of putty in the open end of each electrical metallic tube or conduit within the
<br />cutlet box is optional. When moldable putty pad outlet box protective material is used on boxes on
<br />both sides of wall as directed, the horizontal separation between outlet boxes on the opposite sides of
<br />the wall may be less than 24 in. provided that the boxes are not installed back-to-back.
<br />SpeeSeal Putty Pads for use with max 4 by 3-3/4 by 3 in. deep UL Listed Nonmetallic Outlet
<br />Boxes manufactured by Carlon Electrical Products and made from polyvinyl chloride, max 4 by 3-3/4
<br />l)y 3 in. deep ITI, Listed Nonmetallic Outlet Boxes manufactured by Allied Moulded Products Inc. and
<br />iaade from fitter -reinforced thermosetting plastic or max 4-1/16 by 3-5/8 by 3-1/8 in. deep UL Listed
<br />Nonmetallic Outlet Boxes manufactured by Thomas & Betts Corp. and made from fiber -reinforced
<br />thermosetting plastic. Boxes shall also bear a 2 h rating under the "Outlet Boxes and Fittings Classified
<br />for Fire Resistance" category in the Fire Resistance Directory. Boxes installed with steel or plastic
<br />cover plates. Putty pads and boxes for use in l and 2 h fire rated gypsum ,valltx)ard/wood stud wall
<br />t ssemblies constructed of the materials and in the manner specified in the individual U 300 Series Wall
<br />,.nd Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of
<br />two riling tabs iin conjunction with nails supplied with the outlet box. Min 3/16 in. thick moldable
<br />putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the
<br />ide of the outlet box against the stud) nicluding nailing tabs and completely seal against the stud
<br />N ithin the stud eavity. An additional 3/16 in. thickness of putty, to be formed around the end of each
<br />nonmetallic sheathed cable at its connection to the box and to extend a minimum of 1 in. from the box
<br />onto the nonmetallic sheathed cable within the stud cavity. When moldable putty pad outlet box
<br />protective material is used on boxes on both sides of wall as directed; the horizontal separation
<br />between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are
<br />not installed back-to-back.
<br />Flies .PENETRATION DETAILS METALLIC 5OXES
<br />NOT TO SCALE
<br />REVISIONS
<br />BY
<br />f,
<br />00
<br />�---� r-,
<br />f _x .
<br />ti
<br />`u
<br />v
<br />ti 3
<br />CV
<br />►� Y ti
<br />U
<br />"x
<br />�..
<br />W
<br />------------
<br />a
<br />U
<br />4° "p
<br />E
<br />0
<br />No.
<br />06-09-15 rff
<br />STATE
<br />®®9 : (1(�A_� �' y
<br />3
<br />U
<br />pN
<br />U �
<br />z
<br />U
<br />a fl
<br />tU
<br />L
<br />O
<br />ti
<br />c
<br />O
<br />v
<br />'O
<br />'E
<br />� O
<br />V) m
<br />o` LL.
<br />•o m vi
<br />w Q
<br />N
<br />D iV
<br />16-
<br />0
<br />a�
<br />c
<br />Date: 06. 09. 15
<br />Scale: AS NOTED
<br />Project Mgr: RNS
<br />Drawn: IT/WR
<br />Job: 15-50
<br />Sheet
<br />E4
<br />
|