<br />LIGHTING RENOVATION PLAN
<br />E3.1) 1/811 = 1 1-011
<br />GENERAL LIGHTING NOTES
<br />1 . PULL UNSWITCHED HOT CONDUCTOR FROM LOCAL LIGHTING CIRCUIT
<br />TO EMERGENCY EGRESS LIGHTS. RUN 3 #12 - 1 #12 GND - 3/4"C TO
<br />INCLUDE UNSWITCHED CONDUCTOR.
<br />2. PULL UNSWITCHED HOT CONDUCTOR FROM LOCAL LIGHTING CIRCUIT
<br />TO EXIT SIGNS. RUN 2 # 12 - 1 #12 GND - 3/4"C.
<br />3. LIGHT FIXTURES BEING REUSED SHALL BE REPAIRED, CLEANED AND
<br />RELAMPED.
<br />4. SWITCHES SHALL BE GANGED WHEN THEY APPEAR ADJACENT
<br />TO ONE ANOTHER ON PLANS WHEREVER PRACTICABLE. PROVIDE
<br />MULTI -GANG JUNCTION BOX AND COVER PLATE AS REQUIRED.
<br />5. DASHED ARCS INDICATE CONTINUATION OF BRANCH CIRCUIT BUT NOT
<br />SWITCH CONTROL.
<br />6. UNLESS OTHERWISE NOTED, ALL FIXTURES AND DEVICES SHOWN ON
<br />THIS PLAN ARE NEW. ALL NEW FIXTURES AND SWITCHES SHALL
<br />MATCH WELL 65 IN WINTERPARK.
<br />7. VERIFY THAT DIMMER MATCHES LAMP TYPE PRIOR TO ORDI
<br />8. ELECTRICAL CONTRACTOR SHALL PROVIDE A LUMINAIRE DISCONNECT
<br />CONNECTOR FOR ALL FLUORESCENT FIXTURES, AS REQUIRED BY N.E.C.
<br />410.130(g)3 2011. UL LISTED CONNECTORS ARE MANUFACTURER BY
<br />IDEAL, THOMAS AND BETTS AND WAGO, ANY UL LISTED CONNECTOR
<br />WILL BE ACCEPTABLE. INSTALL PER MANUFACTURERS SPECIFICATIONS.
<br />9. EASTING BRANCH CIRCUITS I -LAVE BEEN TAKEN FROM FIELD
<br />INVESTIGATION AND/OR ORIGINAL DOCUMENTS AND SHOWN FOR
<br />THE CONVENIENCE OF THE ELECTRICAL CONTRACTOR AND SHALL NOT
<br />BE CONSIDERED "AS -BUILT" CONDITION. BEFORE CONSTRUCTION
<br />BEGINS, ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL BRANCH
<br />CIRCUITS.
<br />10. CONTRACTOR SHALL INCLUDE COMMISSIONING OF LIGHTING
<br />CONTROL SYSTEM BY MANUFACTURER IN BASE BID.
<br />11. VERIFY CEILING TYPES BEFORE ORDERING LIGHT FIXTURES.
<br />LIGHTING PLAN NOTES
<br />(D FEED FIXTURES FROM EXISTING, LOCAL LIGHTING CIRCUIT. FIELD
<br />VERIFY EXACT CIRCUIT NUMBER. TYPICAL ALL EXIT SIGNS. RUN
<br />//B\ 2#12 1 #12 GND - 3/4" C.
<br />PROVIDE A NEW EXTERIOR GRADE BUILDING WALL MOUNTED
<br />LED LIGHT FIXTURE (ANPLIGHTING TYPE
<br />ORB220-FR-MOl 6LDD-W-35K-RTCW) COORDINATE MOUNTING
<br />SOURCE, CORD STYLE AND FINISHES WITH ARCHITECT/OWNER
<br />PRIOR TO ORDERING. CONNECT ALL BUILDING MOUNTED
<br />LIGHTS TO PANEL VIA TIME CLOCK WITH PHOTOCELL. REFER TO
<br />EXTERIOR LIGHTING/SIGNAGE WIRING DIAGRAM.
<br />n
<br />ROVIDER WORK
<br />ROOM
<br />F --I
<br />_132
<br />--- Do
<br />-1 -1
<br />1901
<br />-
<br />---------
<br />- ------------------
<br />-------
<br />lr�
<br />--------------
<br /><
<br /><
<br /><
<br /><
<br />WELLNESS SUITE 4�'.
<br />5
<br />WELLNfSS SUITE
<br />WELLNESS SUITE
<br />I k
<br />WELLNESS SUITGE(
<br />11-2
<br />6
<br />7
<br />rw
<br />0 BI-29 JPPPVIDER WORK
<br />Al 7-
<br />G
<br />FF 132
<br />G
<br />4 -5 LJ L J L
<br />G A
<br />0 B
<br />DJMAl-21 Al-
<br />L
<br />Ll NESS SU T Al-
<br />Alf- 1 -1 T AZOMM -28 1 1 AUTOCLAVE
<br />,M7 111-27
<br />A.
<br />Al-22-- I Al 18
<br />11 L Al- 6
<br />L - - i il
<br />r AL3_7,/
<br />CORRIDOR if %_
<br />4 F 123 BI-25
<br />L - - -
<br />b I UKAur I
<br />106 Al-13
<br />FECR �AlA
<br />L EIR
<br />G
<br />Ell Fim
<br />0!:::::: L I Al� BREA M
<br />Al-8
<br />Al-15
<br />Al-9 0 " �I
<br />01 LOBBY -4
<br />G
<br />Af&I - LU Al-1
<br />MMUNITY
<br />F 7-1 co
<br />-1-04 r Al-17 _G_+
<br />Al-12
<br />-4
<br />G I
<br />7 7:7 J � _f
<br />.7 - - - - - - - -
<br /><
<br />7- . : . , . . . - ; -2 - - .4
<br />'-_� 2 POWER RENOVATION PLAN
<br />E3.1) 1/8', = v-0.
<br />4211 BACK BOX
<br />34" Y OF OUTLIET BOX
<br />CONFIGURATION B:
<br />LCD BOX LOCATION
<br />NOTE:
<br />CONFIGURATIONA! REFERS TO KEYED NOTE
<br />CONFIGURATION VREFERS TO KEYED NOTE
<br />------------------
<br />GENER,,1II,I,L POWER NOTES
<br />1 . INDICATED CIRCUIT NUMBERS ARE SUGGESTED FROM EXISTING
<br />SPARE BREAKERS AND SPACES IN EXISTING PANELS.
<br />CONTRACTOR MAY USE DIFFERENT CIRCUIT NUMBERS TO MATCH
<br />FIELD CONDITIONS.
<br />2. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH INTERIOR
<br />DESIGN PACKAGE FOR ALL MILLWORK AND WALL DESIGNS PRIOR
<br />TO COMMENCING WORK.
<br />3. EXISTING BRANCH CIRCUITS PAVE BEEN TAKEN FROM FIELD
<br />INVESTIGATION AND /OR ORIGINAL DOCUMENTS AND SHOWN
<br />FOR THE CONVENIENCE OF THE ELECTRICAL CONTRACTOR AND
<br />SHALL NOT BE CONSIDERED "AS -BUILT" CONDITION. BEFORE
<br />CONSTRUCTION BEGINS, ELECTRICAL CONTRACTOR SHALL FIELD
<br />VERIFY ALL BRANCH CIRCUITS.
<br />4. PROVIDE TYPED, UPDATED PANEL SCHEDULES UPON COMPLETION
<br />OF WORK.
<br />5. PROVIDE SHOW WINDOW RECEPTACLES ABOVE ALL WINDOWS
<br />PER CODE LISTED IN THIS NOTE:
<br />Definition per Article 100 of NEC for Show Window - Any
<br />h\ window, including windows above doors, used or designed
<br />to be used for the display of goods or advertising material,
<br />whether it is fully or partly enclosed or entirely open at the
<br />rear and whether or not it has a platform raised higher
<br />than the street floor level.
<br />e Article 210.62 of NEC Show Windows - provide at least (1)
<br />receptacle within 18in of top of show window for each 12
<br />feet or major faction thereof (6' or more) of show window
<br />measured horizontally.
<br />Article 210.14(G) and 220.43(A) regarding load calculations
<br />- 210.14(G) allows calculations for unit load per receptacle
<br />(180VA). We will use this method. 220.43(A) is for show
<br />window linear lighting which does not apply.
<br />REFER TO FIRE ALARM NOTES, RISER AND SPECIFICATIONS FOR MORE
<br />INFORMATIOI�.
<br />POWER PLAN NOTES
<br />0 CONNECT ELECTRIC WATER HEATER. PROVIDE 30A, 31), 240V,
<br />N-1, NON -FUSED DISCONNECT SWITCH. COORDINATE WITH
<br />PLUMBING CONTRACTOR. RUN 3#10, 1 #10 GND - 3/4" C.
<br />PROVIDE FLUSH MOUNTED FLOOR BOX WITH 120V QUAD
<br />RECEPTACLE AND TELE/DATA OUTLETS, WALKER OMNIBOX
<br />SERIES (#880S2-TWO GANG) OR APPROVED EQUAL. SAWCUT
<br />FLOOR AS REQUIRED. RUN 2#12, 1 #12 FOR 120V POWER.
<br />RUN 1-1 /4" CONDUIT WITH PULLSTRING FOR LOW VOLTAGE
<br />CABLING. PROVIDE ALL ACCESSORIES REQUIRED FOR A
<br />COMPLETE SYSTEM. COORDINATE EXACT LOCATION, FINISHES,
<br />COVERPLATES AND TYPE OF LOW VOLTAGE OUTLETS WITH
<br />OWNER.
<br />NEW CARD READER AND ELECTRIC STRIKE. PROVIDE 3/4"
<br />RACEWAY TO ACCESSIBLE CEILING FOR LOW VOLTAGE POWER.
<br />COORDINATE WITH CARD READER VENDOR. TENANT SECURITY
<br />SYSTEM SHALL BE CONNECTED TO BUILDING FIRE ALARM
<br />SYSTEM TO RELEASE ALL LOCKS UPON ACTIVATION. PROVIDE
<br />ALL CONNECTIONS AND ACCESSORIES REQUIRED FOR A FULLY
<br />OPERATIONAL SYSTEM. ANY CARD READERS INSTALLED IN
<br />SUCH A WAY THAT THEY PREVENT FREE EGRESS SHALL BE IN
<br />COMPLIANCE WITH SECTION 7.2.1.6.2 FOR ACCESS
<br />CONTROLLED EGRESS DOOR ASSEMBLIES (NFPA 101)
<br />------------------------------------ ----
<br />PROVIDE RECESSED 2-GANG BOX AT 42" A. F.F FOR AN
<br />CABLING. TYPICAL FOR ALL ALL WELLNESS SUITES. ARLINGTON
<br />MODEL #TVBS81 0.
<br />PROVIDE JUNCTION BOXES AND 120V CIRCUIT FOR DOOR
<br />OPENER. COORDINATE EXACT REQUIREMENTS WITH VENDOR.
<br />PROVIDE 8H X 4W X 3/4"D PLYWOOD BACK BOARD ON WALL
<br />FOR TELECOMMUNICATION EQUIPMENT. PANT WITH GRAY FIRE
<br />RETARDENT PANT. INSTALL DOUBLE DUPLEX RECEPTACLE
<br />MOUNTED @ 42" AFF. RUN 2" E.C. TO E)QSTING MAIN
<br />TELEPHONE TERMINAL BOARD. PROVIDE #6 GROUND WITH
<br />BUS BAR CONNECTED TO BUILDING GROUND LUG.
<br />A
<br />E� B
<br />C C
<br />U7 CONNECT 120V POWER TO NEW EXHAUST FAN. PROVIDE
<br />MOTOR -RATED SWITCH. COORDINATE WITH MECHANICAL
<br />CONTRACTOR. FAN HAS MOTION SENSOR CONTROL.
<br />CONNECT SPLIT SYSTEM. PROVIDE 30A, 21), 240V, N-3R FUSED
<br />DISCONNECT SWITCH ON ROOF. FUSE PER MANUFACTURERS
<br />NAMEPLATE. COORDINATE WITH MECHANICAL CONTRACTOR.
<br />ELECTRICAL POWER IS THROUGH CONDENSING UNIT THEN TO
<br />INDOOR UNIT.
<br />RUN 2 #10 - 1 #10 GND - 3/4"C TO CONDENSING UNIT AND 2
<br />#10 - 1 #10 GND - 3/4"C TO INDOOR UNIT.
<br />PROVIDE 30A, 2P, 240V, N-1, FUSED DISCONNECT SWITCH AT
<br />INDOOR UNIT, FUSE AS MANUFACTURER'S NAMEPLATE.
<br />EXTEND CONDUIT (2)4"C. TO NEW COMM ROOM.
<br />PROVIDE RECESSED, FLANGELESS BOX WITH DUPLEX
<br />RECEPTACLE AT HEIGHT SHOWN DRAWING 2/E3.1. ARLINGTON
<br />MODEL #TVBS81 0.
<br />CONNECT 120V POWER TO NEW EXHAUST FAN. PROVIDE
<br />MOTOR -RATED SWITCH. COORDINATE WITH MECHANICAL
<br />CONTRACTOR. FAN SHALL RUN CONTINUOUSLY.
<br />PROVIDE 36" PROPER CLEARANCE PER NEC IN FRONT OF NEW
<br />PANELS.
<br />PROVIDE NEW FLOW AND TAMPER SWITCHES ON EXISTING
<br />BACKFLOW PREVENTER. CONNECT PER MANUFATURERS
<br />SPECIFICATIONS.
<br />REFER TO ARCHITECTS DRAWING 2/A0.5 FOR RECESSED
<br />DRYWALL NICHE. LOCATE DUPLEX RECEPTACLE IN SIDE WALL OF
<br />NICHE AS SHOWN.
<br />PAIIENT CARE AFIEA 8YMBOL LEGEND
<br /><0> GENERAL CARE - CATEGORY 2
<br />NOTES:
<br />1. THERE ARE NO CRITICAL OR WET PATIENT AREAS IN THE SCOPE OF WORK.
<br />2. GENERAL PATIENT CARE AREAS REQUIRE A WIRING METHOD WITH A REDUNDANT
<br />GROUND AS PER ARTICLE 517.13 OF THE NEC.
<br />GROUNDING 0 FALL RECEPTACLES, LIGHTING AND FIXED EQUIPMENT IN PATIENT
<br />CARE AREAS SHALL COMPLY WITH NEC ARTICLE 517.13 (A) AND (B)
<br />E
<br />F
<br />MEP CONSULTING
<br />ENGINEERS
<br />SINCE 1977
<br />FIL REG NO. 30BE
<br />2016 ALDEN RD.
<br />ORLANDO, FL
<br />32803
<br />(407) 246-1688
<br />WWW.PEIFLA.COM
<br />PEII PROJECT
<br />22121
<br />CAMPBELL + VAN DUSEN
<br />11A R C H I T E C T U R E INTERIOR DESIGNI
<br />www.CVDstudio.com
<br />CAMPBELL + VAN DUSEN Design Studio, LLC.
<br />255 South Orange Avenue Suite # 1240
<br />Orlando, Florida 32801
<br />Phone: 407.930.6016
<br />FL. Lic. No. AA26003339
<br />ARCHITECT OF RECORD
<br />FRANK W. CAMPBELL AIA
<br />FLLIC NO. AR0016053
<br />COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
<br />SEALED AND DATED BY THE ARCHITECT OF RECORD
<br />G - S PA
<br />No. 64601
<br />STATE OF
<br />0 *% "t OR10t-I
<br />AL
<br />Bryan G. Spangler, PE,
<br />FL Reg. No. 64601
<br />COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
<br />SEALED AND DATED BY THE ENGINEER OF RECORD
<br />_J
<br />LI
<br />_J
<br />0
<br />F_
<br />CL
<br />CL
<br />LU
<br />r-4
<br />L#0
<br />UJ
<br />LU
<br />>
<br />_J
<br />0
<br />F-
<br />+
<br />LI
<br />(-)
<br />-,0
<br />cle
<br /><
<br />LL1
<br />LU
<br />0
<br />>J
<br />C)
<br />-0 "It
<br />0 Lr)
<br />LU
<br />W
<br /><
<br />3::
<br />ot-,,)
<br />CL
<br />PL-U4
<br />("Y'r))
<br />CONSTRUCTION DOCUMENTS
<br />03.24.2023
<br />PRINCIPAL IN CHARGE
<br />F. CAMPBELL
<br />.......................... I ............. I ...........................
<br />PROJECT MANAGER
<br />M. TORRES
<br />....................................................................
<br />ADVENT HEALTH
<br />WELL 65+
<br />ZEPHYRHILLS
<br />22-0328-01
<br />ELECTRICAL
<br />RENOVATION PLANS
<br />E3. I
<br />
|