Laserfiche WebLink
IYey� "ti <br />Aems <br />IIMININIENERENE1 <br />ITM711 <br />INNERENEININIENEI <br />NEI <br />Appliance Access <br />M1305.1 Appliance access for inspection service, repair and replacement. <br />Appliances shall be accessible for inspection, service, repair and replacement without removing permanent <br />construction, other appliances, or any other piping or ducts not connected to the appliance being inspected, <br />serviced, repaired or replaced. A level working space at least 30 inches deep and 30 inches wide (762 mm by <br />762 mm) shall be provided in front of the control side to service an appliance. Installation of room heaters shall <br />be permitted with at least an 18-inch 457 mm working space. A platform shall not be required for room <br />P ( ) 9 P P q <br />heaters. <br />M 1305.1.1 Furnaces and air handlers. <br />Furnaces and air handlers within compartments o lcoves shall have a minimum working space clearance of 4 <br />dor g p <br />Inches (102 mm) along the sides, back and top with a total width of the enclosing space being at least 12 <br />inches (305 mm) wider than the furnace or air handler. Furnaces having a firebox open to the atmosphere shall <br />have at least a 6-inch (152 mm) working space along the front combustion chamber side. Combustion air <br />openings at the rear or side of the compartmentshall com I with the requirements of Chapter 17. <br />PY q P <br />Exception: This section shall not apply to replacement appliances Installed in existing compartments and <br />alcoves where the working space clearances are in accordance with the equipment or appliance <br />manufacturer's Installation instructions. <br />M 1305.1.2 Appliances In rooms. <br />Appliances installed in a compartment, basement or similar space all be accessed b an opening or <br />tment alcove bas h cc <br />PP P . P Y P 9 <br />door and an unobstructed passageway measuring not less than 24 Inches (610 mm) wide and large enough to <br />allow removal of the largest appliance in the space, provided there is a level service space of not less than 30 <br />Inches (762 mm) deep and the height of the appliance, but not less than 30 inches (762 mm), at the front or <br />service side of the appliance with the door open. <br />Pen. <br />M 1305.1.3 Appliances in attics. <br />Attics containing appliances shall be provided with an opening and a clear and unobstructed passageway large <br />enough to allow removal of the largest appliance, but not less than 30 inches (762 mm) high and 22 inches <br />(559 mm) wide and not more than 6 feet (1829 mm) long measured along the centerline of the passageway <br />from the opening to the appliance. The passageway shall have continuous solid flooring In accordance with <br />Chapter 5 not less than 24 inches 610 mm wide. A level services ace at least 30 inches 762 mm deep and <br />P ( ) P ( ) P <br />30 inches (762 mm) wide shall be present along all sides of the appliance where access is required. The clear <br />access opening dimensions shall be a minimum of 20 inches by 30 Inches (508 mm by 762 mm), and large <br />enough to allow removal of the largest appliance. <br />9 9 PP <br />Exception: The passageway and level service space are not required where the appliance can be serviced and <br />removed through the required opening. <br />M1305.1.3.1 Electrical requirements. <br />A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be <br />Installed at or near the appliance location in accordance with Chapter 34. <br />M1305.1.3.2 Air -handling units. <br />Air -handling units shall be allowed in attics if the following conditions are met: <br />1. The service panel of the equipment is located within 6 feet (1829 mm) of an attic access. <br />2. A device is installed to alert the owner or shut the unit down when the condensation drain is not <br />working properly. <br />3. The attic access opening is of sufficient size to replace the air handler. <br />4. A notice is posted on the electric service panel indicating to the homeowner that the air handler is <br />located in the attic. Said notice shall be in all capitals, in 16 point type, with the fitle and first paragraph in bold: <br />NOTICE TO HOMEOWNER <br />A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR HANDLER, IS LOCATED IN THE ATTIC. FOR <br />PROPER, EFFICIENT AND ECONOMIC OPERATION OF THE AIR CONDITIONING SYSTEM, YOU MUST <br />ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. YOUR AIR CONDITIONING SYSTEM IS <br />EQUIPPED WITH ONE OR BOTH OF THE FOLLOWING: <br />1) A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION DRAIN IS NOT WORKING <br />PROPERLY OR <br />2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE CONDENSATION DRAIN IS NOT <br />WORKING. <br />TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF SERVICE, IT IS <br />RECOMMENDED THAT YOU ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE EACH <br />SEASON OF PEAK OPERATION. <br />Plumbing Notes <br />1. Provide plumbing fixtures, as selected by practical conet. complete with all trim traps, stop valves, supplies <br />and escutcheons. <br />2. All plumbing shall be is strict accordance with standard plumbing codes and local ordinances. <br />3. Soil waste and vent piping shall be schedule 40 pvc. <br />4. All water piping shall be Type "1" with 95-5 soldered joints or c.p.v.c. <br />5. Copper piping underground and in contract with dissimilar metals shall be coated with tar enamel <br />AWWA-C-203 or equal. <br />6. Provide individual water stops at all water closets, lavatories and kitchen sink installations. <br />7. Run all pipes concealed in wall, floors, above ceilings or below grade. <br />8. Verify all rough in requirements with the fixtures that are selected. <br />9. Coordinate all work with trades. <br />10. Provide full size piping from hot water p&t valve to exterior. <br />11. Water piping run through concrete or masonry shall be wrapped with 10-ml vinyl plumbing tape. <br />12. Hot water piping shall be insulated In accordance with county wide energy code. <br />13. gallon water heater (future). Unless noted otherwise. <br />14. Tank type water closet volume 1.5 gallons. <br />15. Water -flow rate. Shower heads 259 P. m. privatefacilities 2.2 b 9Pm. <br />16. Plumbers must use a metal or plastic material to box out areas in concrete where drains are to be installed. <br />17. Thermal expansion protection is required when the water service is equipped with a back flow prevention <br />device. <br />18. All back flow prevention devices are required to be tested and test results submitted to the building <br />department before the certificate of occupancy is issued. <br />19. Loop hot water piping for Instant hot water option. <br />Protection Against Termites <br />R318.1 Termite Protection. Termite protection shall be provided by registered termiticides, including soil applied <br />pesticides, baiting systems, and pesticides applied to wood, or other approved methods of termite protection <br />labeled for use as a preventative treatment to new construction. See Section 202, REGISTERED <br />TERMITICIDE. Upon completion of the application of the termite <br />Protective treatment a Certificate of <br />Compliance shall be issued to the building department by the licensed pest control company that contains the <br />following statement: "The building has received a complete treatment for the prevention of subterranean <br />termites. Treatment is in accordance with rules and laws established by the <br />Florida Department of Agriculture and Consumer Services " R319.1.1 If soil treatment is used for subterranean termite prevention, the initial chemical soil treatment inside <br />the foundation perimeter shall be done after all excavation, backfllling and compaction Is complete. <br />R318.1.2 If soil treatment Is used for subterranean termite prevention, soil area disturbed after initial chemical <br />soil treatment shall be retreated with a chemical soil treatment, Including spaces boxed or formed. <br />R318.1.3 If soil treatmentis used for subterranean space In concrete floors box out or <br />termite prevention, boxed t <br />P �P <br />formed for the subsequent installation of plumbing traps, drains or any other purpose shall be created by using <br />plastic or metal permanently placed forms of sufficient depth to eliminate any planned soil disturbance after <br />initial chemical soil treatment. <br />R318.1.4 If soil treatment Is used for subterranean termite prevention, chemically treated soil shall be protected <br />with a minimum 6 mil vapor retarder to protect against rainfall dilution. If rainfall occurs before vapor retarder <br />placement, retreatment is required. Any work, including placement of reinforcing steel, done after chemical <br />treatment until the concrete floor is poured, shall be done in such manner as to avoid penetrating or disturbing <br />treated soil. <br />R318.1.5 If soil treatment is used for subterranean termite prevention, concrete overpour or mortar accumulated <br />along the exterior foundation perimeter shall be removed prior to exterior chemical soil treatment to enhance <br />vertical penetration of the chemicals. <br />R318.1.6 If soil treatment is used for subterranean termite prevention, chemical soil treatments shall also be <br />applied under all exterior concrete or grade within 1 foot (305 mm) of the primary structure sidewalls. Also, a <br />vertical chemical barrier shall be applied promptly after construction is completed, including initial landscaping <br />and irrigation/sprinkler Installation. Any soil disturbed after the chemical vertical barrier is applied shall be <br />promptly retreated. <br />R318.1.7 If a registered termiticide formulated and registered as a bait system is used for subterranean termite <br />prevention, Section R318.1.1 through Section R318.1.6 do not apply; however, a signed contract assuring the <br />in&-ut;lation, maintenance and monitoring of the baiting system that is in compliance with the requirements of <br />Chapter 482, Florida Statutes, shall be provided to the building official prior to the pouring of the slab, and the <br />system must be installed prior to final building approval. <br />If the baiting system directions for use require a monitoring phase prior to installation of the pesticide active <br />ingredient, the Installation of the monitoring phase components shall be deemed to constitute installation of the <br />system. <br />R318.1.8 If a registered termiticide formulated and registered as a wood treatment Is used for subterranean <br />termite prevention, Sections R318.1.1 through R318.1.6 do not Application of the wood treatment termiticide <br />shall be as required by label directions for use, and must be completed prior to final building approval. <br />R318.2 Penetration. Protective sleeves around piping penetrating concrete slab -on -grade floors shall not be of <br />cellulose containing materials. If soil treatment is used for subterranean termite protection, the sleeve shall have <br />a maximum wall thickness of 0.010 inch (0.25 mm), and be sealed within the <br />slab using a non corrosive clamping device to eliminate the annular space between the pipe and the sleeve. No <br />termiticides shall be applied Inside the sleeve. <br />R318.3 Cleaning. Cells and cavities in masonry units and air gaps between brick, stone or masonry veneers <br />and the structure shall be cleaned of all nonpreservative-treated or nonnaturally durable wood, or other <br />cellulose-contalning material prior to concrete placement. <br />Exception: Inorganic material manufactured for closing cells in foundation concrete masonry unit construction or <br />clean earth fill placed in concrete masonry unit voids below slab level before termite treatment Is performed. <br />R318.4 Concrete bearing ledge. Brick, stone or other veneer shall be supported by a concrete bearing ledge at <br />least equal to the total thickness of the brick, stone or other veneer which is poured integrally with the concrete <br />foundation. No supplemental concrete foundation pours which will create a hidden <br />cold joint shall be used without supplemental treatment in the foundation unless there is an approved physical <br />barrier. An approved physical barrier shall also be Installed from below the wall sill plate or first block course <br />horizontally to embed In a mortar joint. If masonry veneer extends below grade, a <br />termite protective treatment must be applied to the cavity created between the veneer and the foundation, In <br />lieu of a physical barrier. <br />Exception: Veneer supported by a structural member secured to the foundation sidewall in accordance with ACI <br />530/ASCE 5/TMS 402, provided at least a 6 inch (152 mm) dear inspection space of the foundation sidewall <br />exterior exists between the veneer and the top of any soil, sod, mulch or other organic landscaping component, <br />deck, apron, porch, walk or any other work Immediately adjacent <br />to or adjoining the structure. <br />R318.5 Protection against decay and termites. Condensate lines, irrigation/sprinkler system risers for spray <br />heads, and roof downspouts shall discharge at least 1 foot (305 mm) away from the structure sidewall, whether <br />by underground piping, tail extensions or splash blocks. Gutters with downspouts <br />are required on all buildings with inches 5 horizontal projection except for able <br />q g heaves of less than 6 i he (1 2 mm) h p �g <br />end rakes or on a roof above another roof. <br />R318.6 Preparation of building site and removal of debris. <br />P 9 <br />R318.6.1 All building sites shall be graded to provide drainage under all portlons of the building not occupied by <br />basements. <br />R318.6.2 The foundation and the area encompassed within 1 foot (305 mm) therein shall have all vegetation, <br />stumps, dead roots, cardboard, trash and foreign material removed and the fill material shall be free of <br />vegetation and foreign material. The fill shall be compacted to assure adequate support of the foundation. <br />R318.6.3 After all work is completed, loose wood and completely removed from under the <br />debris shall be co <br />P P Y <br />buildingand within 1 foot 305 mm thereof. All wood f s shall be completely removed_ This <br />forms and supports ( ) PPo P Y <br />includes, but Is not limited to: wooden grade stakes, forms, contraction spacers, tub trap boxes, plumbing <br />supports, bracing, shoring, forms or other cellulose -containing material placed in any location where such <br />materials are not clearly visible and readily removable prior to completion of the <br />work. Wood shall not be stored in contact with the ground under any building. <br />R318.7 Inspection for termites. In order to provide for inspection for termite infestation, clearance between <br />exterior wall coverings and final earth grade on the exterior of a building shall not be less than 6 inches (152 <br />mm). <br />Exceptions: <br />1. Paint or decorative cementitious finish less than 5/8 inch (17.1 mm) thick adhered directly to the <br />masonry foundation sidewall. <br />2. Access or vehicle ramps which rise to the interior finish floor elevation for the width of such ramps only. <br />3. A 4-inch (102 mm) inspection space above patio and garage slabs and entry areas. <br />Stair treads and risers <br />Stair treads and risers shall meet the requirements of this section. For the purposes of this section all <br />dimensions and dimensioned surfaces shall be exclusive of carpets, rugs or runners. <br />R311.7.5.1 Risers. The maximum riser height shall be 73/4 inches (196 mm). The riser shall be measured <br />vertically between leading edges of the adjacent treads. The greatest riser height within any flight of stairs shall <br />not exceed the smallest by more than 3/8 inch (9.5 mm). Risers shall be vertical or sloped from the underside <br />of the nosing of the tread above at an angle not more than 30 degrees (0.51 rad) from the vertical. Open risers <br />are permitted provided that the opening between treads does not permit the passage of a 4-inch-diameter (102 <br />mm) sphere. <br />Exception: The opening between adjacent treads is not limited on stairs with a total rise of 30 inches (762 mm) <br />or less. <br />R311.7.5.2 Treads. The minimum tread depth shall be 10 inches (254 mm). The tread depth shall be measured <br />horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the <br />tread's leading edge. The greatest tread depth within any flight of stairs shall not exceed the smallest by more <br />than 3/8 inch (9.5 mm). <br />II <br />111111111111111111111111 <br />. <br />III <br />WIWI <br />IN. <br />I 11 <br />1. <br />= <br />M <br />� <br />MENEM <br />070 <br />IIIIIIIIIIIIIIIIIN <br />M ii�liililllllliii; <br />M I <br />17PS-110 <br />MEME <br />I <br />MEEM <br />M <br />M <br />Em 11 <br />NONE <br />- <br />,,I <br />M <br />I IIIIIIIIIIIIIIIII <br />M PONNE"112=1 <br />EM! <br />-1141 <br />. <br />- <br />iiiiiiiiiiiiiiiiiiiiiillillillillillI <br />. <br />Masonry & Concrete <br />1. All concrete shall have a minimum compressive strength of 3,000 psi at 28 days. <br />2. U.N.O. All reinforcing steel to be new domestic deformed billet steel conforming to ASTM A-615 grade 40, <br />CASTCRETE lintels & stemwall foundations require the use of grade 60 rebar. <br />3. Welded wire fabric shall conform to A-185. <br />4. Contractor shall verify locations of all openings, sleeves, anchor bolts, inserts, etc. as required by other trades before <br />concrete Is placed. No sleeves, openings pr inserts may be placed In beams or slabs unless approved by the <br />designer/engineer and shown on shop drawings. <br />5. All reinforcingdetails to conform to "manual of standard practice for detailing e' to structures A p g reinforced concrete CI 315, <br />unless detailed otherwise on structural drawings. <br />6. Provide spacers, chairs. bolts, etc. as required to assemble, place and support all reinforcing In place. <br />7. Provide corner bars for all footings. <br />8. All footing dowel bars shall have a standard 90° bend and shall be embedded 5" into -inch footings and a minimum of <br />e <br />6 into all others. Dowel bars lap m o vertical wall reinforcement a minimum f 40 bar diameters. <br />9. Steel reinforcement shall have a minimum yield strength of 40,000 psi in accordance with ASTM A-61.5. <br />10. Concrete Masonry Units, if any, shall be hollow core / load bearing in accordance to astm C90 or C145, 1,900 psi <br />minimum. <br />11. Grout, if any, shall have 3/8" maximum aggregate, 8 to 11 inch slump 2,500 psi as per ASTM C476. <br />12. Mortar, if any, shall be Type M or S In conformance ASTM C270. <br />R609.3 Vertical reinforcement. Vertical reinforcement shall be provided In conformance With Sections R609.3.1 through <br />R609.3.6. <br />R609.3.1 One reinforcement bar shall be provided in each comer, Including interior corners and comers created by a <br />change In wall direction or offsetting of walls. <br />R609.3.2 Openings. A minimum of one bar of the size used for vertical wall reinforcement shall be provided one each <br />side of openings wider than 6 feet (1829 mm). If more vertical reinforcement Is Interrupted by an opening than Is provided <br />beside the opening (total in the first and second cells adjacent to the opening), one-half of the equivalent area of <br />reinforcement Interrupted by the opening shall be placed on each side of the opening. This reinforcement shall be placed <br />within the first and/or second cells beside the opening. <br />R609.4 Masonry gables. Gable end walls of concrete or masonry shall be constructed full height to the roof line. <br />Exception: Gable end trusses or wood framed gable end walls in conformance with Tables R609.4A and R609.46 and <br />Figure R609.4. Wood gable stud wall connectors shall be capable of resisting the vertical and horizontal loads of Table <br />R609AB as well as the uplift load stipulated at Figure R609.4. Where masonry gable end walls do not go to the roof, a <br />bond beam complying with Section R609.2 shall be provided at the top of the masonry. <br />R609.4.1 Rake beam. Where concrete or masonry is carried full height to the roof line, a cast -in -place rake beam as <br />detailed In Figure R609.4.1 shall be provided. The minimum thickness of the rake beam from top of masonry shall be 4 <br />inches (102 mm). One No. 5 continuous reinforcing bar shall be placed in the rake beam along the roof line. <br />R609.4.2 Vertical reinforcement. Vertical reinforcement shall be provided at the maximum spacing as set forth in Tables <br />R609.3.3B-1 through R609.3.3B-4 as applicable. <br />R609.4.3 Termination. Required vertical reinforcement shall terminate at the rake beam in accordance with Section <br />R606.9.8. <br />R609.4.4 Nailer A minimum 2 feet 4 inch nailer for connecting roof sheathing shall be bolted to the top of the wall with a <br />minimum of 1/2 inch (12.7 mm) anchor bolts spaced as set forth in Table R609.4.4. The nailer shall be permitted to be <br />bolted to the inside or outside of the wall. <br />R609.4.5 Gable overhang. Gable overhangs up to 2 feet (610 mm) in width complying with Figure 609.4.5 shall be <br />permitted. <br />MASONRY CONSTRUCTION MATERIALS <br />2103.1 Concrete masonry units. Concrete masonry units shall conform to the following standards: ASTM C 55 for <br />concrete brick ; ASTM C73 for calcium silicate face brick; ASTM C 90 for load -bearing concrete masonry units or ASTM <br />C 744 for prefaced concrete and calcium silicate masonry units. <br />General Window & Door Notes <br />1. Exterior front and back doors, windows, garage doors, cladding and components are submitted with the "Technical <br />Manual" for installation and technical material specifications. <br />2. Nail and glue bucks, the wood between the doorjamb and the wall. <br />3. The mullions - strips between a series of windows - must be certified to withstand the designed wind capacity. <br />4. Windows and glass doors must meet the impact standards. Window mfg. must have labels attached listing <br />manufacturer, performance characteristics and certification that they have been tested. Labels must stay on until the final <br />inspection. Or, if non -impact resistant glazing to be used: provide approved glazing protection over all non -impact <br />resistant windows and glass doors. Woods structural panel with a minimum thickness of 7/16" and maximum span of 8 <br />feet 2438 mm shall be permitted for opening protection In one- and <br />two-story buildings. Panel shall be recut and <br />( ) P P 9 P rY 9 P <br />attached to the framing surrounding the opening containing the product with the glazed opening. Panels shall be <br />redrilled as required for the anchorage method and a secured ' shall b with the attachment hardware provided. <br />P q 9 <br />Attachments shall be designed to resist the component and cladding loads determined in accordance with either Table <br />R301.2(2) or ASCE 7, with the permanent corrosion -resistant attachment hardware provided and anchors permanently <br />installed on the building. Attachment in accordance with Table R301.2.1.2 is permitted for buildings with a mean roof <br />height of 33 feet (10058 mm) or less where Vasd determined in accordance with Section R301.2.1.3 does not exceed <br />130 miles per hours (58 m/s). <br />Wood Notes <br />1. All framing members bearing interior & exterior shall be wood members with properties equal to or better than those <br />given by the Southern Pine Inspection bureau for surfaced dried Souther Pine no. 2 (minimum allowable bending stress <br />-1290 psi for single members uses and 1400 psi for repetitive member uses.Modules of elasticity -1,600,000 psi). <br />- <br />2. All wood non bearing exterior and interior walls to be #2 spruce pine fur (fb 1,000 psi). <br />3. All wood girders shall have a min. of (4) - 2"x4" studs placed directly under the girder and double plate. <br />4. All lumber in contact with masonry or concrete shall be pressure treated. <br />5. All roof rafters a prefabricated wood trusses securely f and shall be s c fastened to ' a n d heir supporting wall or beams with <br />P Y <br />orti <br />pP 9 <br />hurricane clips or anchors as noted. <br />6. Prefabricated wood trusses shall be designed in accord <br />ance with the latest edition of he " SIGN <br />g t NATIONAL DE <br />SPECIFICATION FOR STRESS -GRADE LUMBER" and it's fasteners as recommended by the national forest products <br />association. <br />7. Truss member and connections shall be proportioned (with a maximum allowable stress increase for load duration of <br />25% to withstand the load given in note. <br />8. Truss manufacturer shall submit shop drawings and design note with an engineers seal for approval. Design notes <br />are to include the rated load capacity of the connectors used to secure the members, certification of the connector <br />capacity's and manufacturers license to fabricate trusses utilizing the connectors system proposed. <br />9. Bridging for pre-engineered truss shall be as required by truss manufacturer in addition to member show on drawings. <br />10. Roof decks shall be 1/2" plywood or O.S.B. for fiberglass shingle roofs and 5/8" plywood for concrete or clay tile <br />roofs. Use 8d nails with 4" spacing at all panel edges and 6" spacing intermediate supports. Provide plyclips at <br />unsupported edges. <br />11. All wood frame details shall be in accordance with "NATIONAL D SIGN SPECIFICATION FOR WOOD <br />CONSTRUCTION" latest addition, national forest products assocla on, unless detailed otherwise on the structural <br />drawings_ <br />12. Roof live load =20 sf. Roof dead load =20 sf 1 <br />P P <br />13. Gable endwalls adjacent to cathedral ceilings are required to be lcontinuous from floor to roof diaphragm. FBC 2007 <br />2304.3.4.2. <br />14_ Attach plywood sheathing to supporting trusses or other framing with common nails for gable diaphrams only:(unless <br />otherwise noted) 8d: <br />a. 4" o.c. along edges of plywood panels. <br />b. 6" o.c. along field of plywood panels. <br />General Notes <br />NONE <br />NONE <br />ME = <br />0soon on <br />1. General contractor will verify all dimensions shown or implied before starting any work. <br />2. General contractor will comply with all building codes both state and local, and comply with all local authorities having <br />jurisdiction. <br />3. It is the contractors sole responsibility to determine erection procedure and sequence to Insure the safety of the <br />building and component parts during erection this includes but is not limited to the addition whatever temporary bracing, <br />guys, or tie downs that may be necessary. such material shall be removed and shall remain the property of the <br />contractor after completion of the project. <br />4. All dimensions and elevations shown on the structural drawings shall be verified and shall conform to the architectural <br />drawings. <br />5. Wall siding, Including brick facing, painted block or stucco, must end 6 inches above the ground to allow for future <br />termite Inspections. the contractor can paint the bare band or apply a plaster -like finish less than 5/8" inch thick directly <br />to the foundation wall. <br />6. Pre -manufactured roof trusses to be designed in accordance with - <br />g the latest ANSIlTPI 1 design requirements. The <br />truss manufacturer is responsible to furnish all reaction loads for dead loads, live loads and wind loads. Manufacturer to <br />submit truss layout and details signed by a Florida registered engineer. <br />7. All exterior concrete block walls are designed as shear walls or shear wall segments with Dur-a-wall reinforcement <br />every other block as per the requirements of the National Concrete Masonry Institute. If Dur-a-wall reinforcement Is not <br />used for the entire building, length of actual shear wall will be designated on the plans. The above can be omitted when a <br />#5 down bar Is Installed @ each side of an opening. All vertical #5 rebar installed @ ends of shear wall segments (SWS) <br />may be lap spliced & shall be tied to, w/ standard hook, the horizontal rebar In the bond beam in the top course of the <br />wall & footing below. <br />8. All openings greater than 5 feet to have (1)-#5 bar on each side of opening and filled with grout. openings greater than <br />12 feet to have (2)-#5 bars on each side of opening. <br />9. Contractor to verify all dimensions and conditions in the field. <br />10. Any changes to sealed drawings must be approved by the professional engineer of record. <br />Emergency Escape and Rescue Required. <br />Basements, habitable attics and every sleeping room shall have at least one operable emergency escape and rescue <br />opening. Where basements contain one or more sleeping rooms, emergency egress and rescue openings shall be <br />required in each sleeping room. Where emergency escape and rescue openings are provided they shall have a sill height <br />of not more than 44 inches 1118 mm measured from the ( ) finished floor to the bottom of the clear opening above the . <br />floor. Where a door opening having a threshold below the adjacent ground elevation serves as an emergency escape <br />and rescue opening and Is provided with a bulkhead enclosure, the bulkhead enclosure shall comply with Section <br />R310.3. The net clear opening dimensions required by this section shall be obtained by the normal operation of the <br />emergency escape and rescue opening from the inside. Emergency escape and rescue openings with a finished sill <br />height below the adjacent ground elevation shall be provided with a window well in accordance with Section R310.2. <br />Emergency escape and rescue openings shall open directly into a public way, or to a yard or court that opens to a public <br />way. <br />R310.1.1 Minimum opening area. All emergency escape and rescue openings shall have a minimum net clear opening <br />of 5.7 square feet (0.530 m2). <br />Exception: Grade floor openings shall have a minimum net clear opening of 5 square feet (0.465 m2). <br />R310.1.2 Minimum opening height. The minimum net clear opening height shall be 24 inches (610 mm). <br />R310.1.3 Minimum opening width. The minimum net clear opening width shall be 20 inches (508 mm). <br />R310.1.4 Operational constraints. Emergency escape and rescue openings shall be operational from the inside of the <br />room <br />Means of Egress <br />R311.1 Means of egress. All dwellings shall be provided with a means of egress as provided in this section. <br />The means of egress shall provide a continuous and unobstructed path of vertical and horizontal egress travel <br />from all portions of the dwelling to the exterior of the dwelling at the required egress door without requiring <br />travel through a garage. <br />R311.2 Egress door. At least one egress door shall be provided for each dwelling unit. The egress door shall <br />be sidehinged, and shall provide a minimum clear width of 32 Inches (813 mm) when measured between the <br />face of the door and the stop, with the door open 90 degrees (1.57 rad). The minimum clear height of the door <br />opening shall not be less than 78 inches (1981 mm) in height measured from the top of the threshold to the <br />bottom of the stop. Other doors shall not be required to comply with these minimum dimensions. Egress doors <br />shall be readily openable from inside the dwellgwiptah}pI.Ofe{c pahkp <br />r j}M, 1!I.� pgvledge or effort. <br />1'�<L.`T\II.i`,(I ( ( I?,, `, k i.(ll ih.1 [ :!1.[%l ; i <br />Framing Inspection <br />XD <br />1.) All Plumbing, Electrical, and Mechanical roLgrm r t,U,4 Iilgfe� O" �ci 1 pproved <br />1, <br />t \ <br />l <br />I 1 I <br />r I I I � :.� <br />before requesting the framing inspection. ( -,l \' {I �;.1,, ..�.i.� 1-,`'�),\�-I • <br />Foundation Inspection <br />1.) A foundation survey shall be performed and a copy of the survey shall be on site for the building <br />inspector's use. or all property markers shall be exposed and a string stretched from marker to marker <br />to verify required setbacks. PH ,: C <br />J` <br />C, s - <br />T <br />Y�IS4 <br />C. F <br />_ N <br />0^" Yj�MfLLS <br />PLANS <br />313 t!q Pam -EXAMINER_ ()._ <br />67 a. <br />�3e / <br />�N �, l �" <br />�PR PROVED) PR T � 0 0 UC S LIST <br />STRUCTURAL DESIGN CRITERIA <br />ULTIMATE WIND SPEED (Vult) =140 MPH <br />NOMINAL WIND SPEED (Valt) = 108 MPH <br />AS PER R301.2(4) HURRICANE MAP <br />INTERNAL PRESSURE COEFFICIENT = t0.18 <br />COMPONENTS AND CLADDING: REFER TO SHEET A1.2 FOR DESIGN WIND PRESSURES <br />IN TERMS OF PSF (KN/M2) <br />RISK CATEGORY: II <br />WIND EXPOSURE "B" <br />USE OF BUILDING/SITE: IIIB <br />CODES & REFERENCES <br />FLORIDA BUILDING CODE 5th EDITION 2014, BUILDING/RESIDENTIAL <br />AMERICAN CONCRETE INSTITUTE OF STRUCTURAL CONCRETE (ACI 318) <br />AMERICAN CONCRETE INSTITUTE OF MASONRY STRUCTURES (ACI-530/ASCE-5/TMS <br />402 AND SPECIFICATIONS FOR MASONRY STRUCTURES (ACI 530 VASCE 6/TMS 602) <br />AMERICAN SOCIETY OF CIVIL ENGINEERS MINIMUM DESIGN LOADS FOR BUILDINGS <br />AND OTHER STRUCTURES (ASCE-7) <br />SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL <br />STEEL FOR BUILDINGS LATEST EDITION <br />DESIGN SPECIFICATION FOR LIGHT METAL PLATE CONNECTED WOOD TRUSSES BY THE <br />TRUSS PLATE INSTITUTE (TPI) LATEST EDITION <br />NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION (NDS) LATEST EDITION <br />AMERICAN PLYWOOD ASSOCIATION DESIGN / CONSTRUCTION GUIDE. (APA) LATEST <br />EDITION <br />ARCHITECTURAL LEGEND <br />I <br />!k <br />­ <br />, I <br />SECTION NO./ SHEET NO. <br />T.G.C. or G.C. THE GENERAL CONTRACTOR <br />OIl4OA <br />ELEVATION NO./ SHEET NO. <br />EXIST. or EX. EXISTING <br />0�D <br />DETAIL NO./ SHEET NO. <br />S.W.S. SHEAR -WALL SEGMENT <br />AREVISION <br />NO. <br />U.N.O. UNLESS NOTED OTHERWISE <br />0 <br />PRE-CAST/STRESSED LINTELS <br />N.T.S. NOT TO SCALE <br />KEYED NOTES <br />DESIGNER'S NOTES <br />1. ISSUANCE F PLANS FROM THIS DESIGNERS <br />O H S DESIG ER OFFICE SHALL NOT RELIEVE THE <br />BUILDER OF RESPONSIBILITY TO REVIEW AND VERIFY ALL NOTES, DIMENSIONS, AND <br />ADHERENCE TO APPLICABLE BUILDING CODES PRIOR TO COMMENCEMENT OF ANY <br />CONSTRUCTION. <br />2.) ANY DISCREPANCY OF ERROR IN NOTES, DIMENSIONS, OR ADHERENCE TO <br />APPLICABLE BUILDING CODES SHALL BE BROUGHT TO THE ATTENTION OF THE <br />DESIGNERS OFFICE FOR CORRECTION BEFORE COMMENCEMENT OF ANY <br />CONSTRUCTION. <br />3.) ANY REVISIONS OR CHANGES, NOT RELATED TO THE CORRECTION OF ERRORS <br />THAT ARE MADE AFTER THE FINAL P V PLANS HAVE BEEN COMPLETED SHALL BE SUBJECT <br />TO ADDITIONAL FEES. <br />4) IF.ANY MODIFICATIONS ARE MADE TO THESE PLANS BY ANY OTHER PARTY OTHER <br />THAN THE DESIGNERS OFFICE, THE DESIGNER SHALL NOT BE HELD RESPONSIBLE. <br />5.) THIRD PARTY SERVICES: HARTWELL DESIGN GROUP, INC. WILL NOT BE RESPONSIBLE FOR <br />ANY ENGINEERING,INTER( I N SURVEY, <br />OR DESIGN, , SU ,ESTIMATING OR ANY OTHER THIRD PARTY <br />SERVICE ERRORS. <br />.�., <br />TYPICAL NAILING SCHEDULE <br />NAIL, <br />SH ATHIN � G <br />ROOF <br />d <br />OMMO 7 1 <br />- A8 C N/ 6 5/8 NO INALWALL <br />8d <br />COMMON 7/16"--► 5/8" N MINALFLOOR <br />MM <br />10d <br />COMMON 3/4"T.G. <br />ALL SHEATHING APA APPROVED CDX, OSB, UNLESS NOTED OTHERWISE <br />I ­ . ­­ ­.. - - - - --- <br />Foundation Notes <br />Verify location of building at site using owners approved plot plan and adjust concrete footing, slab, <br />landing, and steps, as grade requires. If conflicts between existing site conditions and approved plot <br />plan arise contact T.G.C. <br />1. Prepare soil to receive 4" concrete slab min. w/ compressive strength of 3,000 p.s.i. @ 28 days w/ <br />6x6 W1.4XW1.4 w.w.m. on chairs in the top 1-1 /2" of slab orfibermesh reinforced conc. on vapor <br />barrier, on clean, well compacted fill treated for termites. If fibermesh is used cut I" joint every 15'-0" <br />each way. <br />2. All footings to be 18" wide x 10" deep w/ (2) #5 rebar continuous (unless noted otherwise). <br />3. All thickened slabs (bell footing) to be 18" wide x 16" deep w/ (2) # 5 rebar continuous (place uplift <br />strapping or anchors as may be required per code) unless noted otherwise. <br />4. All column pad to be a minimum 24" x 24" x 12" w/ #5 rebars @ 6" c.c. each way (unless noted <br />otherwise). <br />5. All thickened edge slabs to be 12" x 12" w/ (1) #5 rebar (unless noted otherwise). <br />6. Thickened slab at floor elevation change is to be 8" deep x 16" wide w/ (2) #5 rebar continuous <br />(unless noted otherwise). <br />7. Fill core with concrete and place (1) #5 rebar vertical from footing to tie -beam. <br />8. Pitch slab at grade at 1" in 10' typical (in direction of arrow). unless noted otherwise <br />9. Recess floor slab 3/4" at all sliding glass doors and extend slab 1 1/2" past block face. unless <br />noted otherwise <br />10. Extend slab edge at exterior doors 1 1/2" past block face. unless noted otherwise <br />11. Sunken shower to be 4" concrete recessed slab (min. u.n.o.) w/ 6x6 #10 w.w.m. (or fiber mesh). <br />12. Air conditioner compressor pad by mechanical contractor to be placed 8" from wall, typical. <br />13. All stone or brick veneer footings to be 22" wide x 10" deep w/ (3) #5 rebars (min.) continuous <br />(unless noted otherwise). <br />14. all footingfor 2 story to be 24" wide x 12" deep w/ 3 #5 rebar continuous. min. <br />Y P O <br />15. All thickened slab (bell footing) w/ two stories bearing to be 24" wide x 16" deep w/ (3) #5 rebars <br />(place uplift strapping or anchors as may be required per code). <br />16. Thickened slab (bell footing) where at bearing wall occurs at change in floor elevation shall be a <br />min. 16" deep x 16" wide continuous. <br />17. Soil noted as compacted is 95% modified proctor, ASTM D1557. <br />18. The outer foundation bars shall be continuous around comers by bending the bar. In both cases <br />the minimum bar lap shall be 40 bar diameter likewise, the bond beam reinforcement shall be <br />continuous around all comers. <br />19. Provide 4" x 4" clean out for all concrete filled cells. at the base of wall. <br />Product Category <br />Sub Category <br />Manufacturer <br />Product <br />State of Florida <br />xpira ioh <br />A roval Number <br />Exterior Doors <br />Swinging Exterior Door Assemblies <br />Therma-tru Corporation <br />FL14991-Rl(FL14991.1) <br />PO3,131/2016 <br />Swinging Exterior Door Assemblies <br />Plastpro Inc. / Nanya Plastics Corp. <br />FL15180-Rl (FL15180.11,FL15180.16) <br />12/31/2018 <br />Sectional Exterior Door Assemblies <br />Amarr Garage Doors <br />FL7152-R6 (FL7152.1) <br />01/01/2099 <br />Windows <br />Single Hung <br />Custom Windows Systems, Inc. <br />FL163-R7 (FL163.1) <br />02/23/2025 <br />Fixed Glass <br />Custom Windows Systems, Inc. <br />FL7852-R4 (FL7852.1) <br />07121/2020 <br />Horizontal Slider <br />Custom Windows Systems, Inc. <br />FL7013-R4 (FL7013.1) <br />07/21/2020 <br />Roofing <br />Asphalt Shingles <br />Atlas Roofing Corporation <br />FL16305-R3 (FL16 .1) <br />Underlayments <br />Atlas Roofing Corporation <br />FL16226-R2 (FL16226.1) <br />12/31/2020 <br />Roofing Accessories that are an <br />Lomanco, Inc. <br />750 Roof Louver <br />FL3792-R7 (FL3792.3) <br />08/16/2016 <br />Integral Part of the Roofing System <br />Panel Walls <br />Soffits <br />Norandex Building Materials Distribution <br />FL12505-R3 (FL12 55.1) <br />1 1 015 <br />Siding <br />KAYCAN LTD. <br />FL16299-R2 (FL16299.1) <br />12/31/2016 <br />Siding <br />James Hardie Building Products, Inc. <br />FL13192-R3 (FL13192.2, FL13192.4) <br />01/01/2016 <br />Shutters <br />Storm Panels <br />Town and Country Industries <br />I. <br />- FL1139 - 1 .')- <br />Structural Components <br />Wood Connector Anchors <br />Simpson Stong-Tie Co. <br />. FL10456-R3 <br />12/31/2015 <br />FL10655-R3 <br />12/31/2015 <br />FL10655-R3 <br />12131 /2015 <br />FL10852-R3 <br />12/31/2015 <br />FL10849-R3 <br />12/31/2015 <br />FL10860-R3 <br />12/31/2015 <br />FL11473-R3 <br />12/31/2015 <br />FL11496-R3 <br />12/31/2015 <br />Products Introduced as a Result of <br />Quality Precast or Commercial Concrete <br />FL1774-R4 (FL1774.1) <br />05/24/2024 <br />New Technology <br />Products <br />DATE: � <br />09/14/2015 <br />JOB NO: <br />HA9139 <br />DESIGN BY: <br />-- <br />DRAWN BY: <br />JRH <br />CHECKED BY: <br />GC <br />PROJECT: <br />3615-HA9139 <br />CHECKED BY: <br />JRH,JGZ <br />EST: <br />-- <br />CONST. MNGR: <br />-- <br />SUPER <br />I <br />I <br />(.5 <br />Z <br />Cn <br />W <br />:�E <br />W <br />I-- <br />Q <br />F- <br />J <br />J <br />Q <br />MODEL: <br />9-15 <br />SPECS <br />N co <br />ti <br />M co <br />co ' <br />_1 N <br />II CO <br />I <br />Q T- <br />1 T <br />2 CO <br />Q <br />I- � <br />_ U- <br />LIJ <br />T- <br />Q TT <br />J N <br />Q ' <br />M� <br />j-- <br />co Cn <br />Z I <br />CO <br />U <br />00 <br />Z L1J <br />O Z <br />O I) <br />co <br />T = <br />T M <br />CUSTOMER: <br />LUCKEY <br />39119 PARK DR. <br />ZEPHRYHILLS, FL 335421 <br />E E <br />0 0 <br />U u <br />3 3 <br />" L- <br />m M <br />L L <br />3 % <br />3s <br />3 Z <br />0 <br />m• a( > <br />Q ­1M <br />W <br />m � <br />rV <br />-O Ql N <br />e. tz <br />CO q., <br />E m , <br />o�m <br />,1 <br />o co <br />m o v <br />Cf t$ •L C 19to <br />t;s <br />_4 > a. <br />ENGINEER'S SEAL <br />I HEREBY CERTIFY THAT THIS PLAN & <br />SPECIFICATIONS WERE PREPARED/REVIEWED <br />BY ME OR UNDER MY DIRECT SUPE <br />RVISION <br />AND COMPLIES WITH THE FLORIDA BUILDING <br />CODE 5th 2 EDITION 14 0 <br />RESIDENTIAL/BUILDING. ALL SIGNED/SEALED <br />DRAWINGS PRESENT IN THIS PLAN ARE FOR <br />STRUCTURAL. DESIGN ONLY AND ARE VALID <br />FOR 12 MONTHS FROM THE SIGNED DATE, <br />U, VVU'i11dbU�pOB O <br />eepe�'�yJ� AGO <br />Clio° ��r,E1i eee� Ads <br />U1 e <br />47� 4 e o <br />% * 'eo <br />eo <br />e � <br />o s <br />i CC � <br />�I e <br />1, STATE IF ; W <br />c e b/ ®ern <br />@� `�- <br />.,�. �� <br />51 .o� <br />L4 .1.5 <br />Guo-jie- Zhang. PhD, PE Dato <br />Florida PE No. 47744 <br />2911 Folklore Dr. -- Valrico, FL 33596 <br />(813)657-8865 <br />A1.1 <br />ry <br />?- 1 <br />