TABLE R301.2(1)
<br />CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
<br />GROUND
<br />SNOW
<br />WIND DESIGN
<br />SEISMIC
<br />DESIGN
<br />SUBJECT TO DAMAGE FROM
<br />WINTER
<br />DESIGN
<br />ICE BARRIER
<br />UNDER-
<br />LAYMENT
<br />FLOOD
<br />HAZARDS e
<br />AIR
<br />FREEZING
<br />MEAN
<br />ANNUAL
<br />Speed"
<br />Topographic
<br />Frost Line
<br />LOAD
<br />(mph)
<br />effectsk (NA)
<br />CATEGORY e
<br />Weatheringa
<br />Depth"
<br />Termite°
<br />TEMPS
<br />REQUIRED r
<br />INDEX'
<br />TEMP'
<br />NA
<br />See Figure
<br />R301.2(4)
<br />NA
<br />Negligible
<br />NA
<br />Very Heavy
<br />NA
<br />NA
<br />NA
<br />For S1:1 pound per square foot = 0.0479 kPa, 1 mile per hour = 0.447 m/s
<br />a. Weathering may require a higher strength concrete or grade of masonry than necessary to satisfy the structural requirements of this code. The weathering column
<br />shall be filled in with the weathering index (i.e., "negligible," "moderate" or "severe") for concrete as determined from the Weathering Probability Map [Figure R301.2(3)].
<br />The grade of masonry units shall be determined from ASTM C 34, C 55, C 62, C 73, C 90, C 129, C 145, C 216 or C 652.
<br />b. Reserved.
<br />C. Termite infestation per Figure R301.2(6) is "very heavy."
<br />d. Wind speed shall be from the basic wind speed map [Figure R301.2(4)]. Wind exposure category shall be determined on a site -specific basis in accordance with
<br />Section R301.2.1.4.
<br />e. The outdoor design dry-bulb temperature shall be selected from the columns of 971/2-percent values for winter from Appendix D of the Florida Building Code,
<br />Plumbing. Deviations from the Appendix D temperatures shall be permitted to reflect local climates or local weather experience as determined by the building official.
<br />f. Reserved.
<br />g. The applicable governing body shall, by local floodplain management ordinance, specify (a) the date of the jurisdiction's entry into the National Flood Insurance
<br />Program (date of adoption of the first code or ordinance for management of flood hazard areas), (b) the date(s) of the Flood Insurance Study and (c) the panel numbers
<br />and dates of all currently effective FIRM and FBFM, or other flood hazard map adopted by the authority having jurisdiction, as amended.
<br />h. Reserved.
<br />I. Reserved.
<br />j. Reserved.
<br />k. Reserved.
<br />TABLE R301.2(2)
<br />COMPONENT AND CLADDING LOADS FOR A BUILDING WITH A MEAN
<br />ROOF HEIGHT OF 30 FEET LOCATED IN EXPOSURE B (psf) a,b,c,d,e,f,g
<br />ZONE
<br />EFFECTIVE
<br />WIND
<br />AREA
<br />(feet2)
<br />Ultimate Design Wind Speed Vu/t (mph)
<br />110
<br />115
<br />120
<br />130
<br />140
<br />150
<br />160
<br />180
<br />200
<br />8.9
<br />-21.8
<br />9.7
<br />-23.8
<br />10.5
<br />-25.9
<br />12.4
<br />-30.4
<br />14.3
<br />-35.3
<br />16.5
<br />-40.5
<br />18.7
<br />-46.1
<br />23.7
<br />-58.3
<br />29.3
<br />-72.0
<br />1
<br />20
<br />8.3
<br />-21.2
<br />9.1
<br />-23.2
<br />9.9
<br />-25.2
<br />11.6
<br />-29.6
<br />13.4
<br />-34.4
<br />15.4
<br />-39.4
<br />17.6
<br />-44.9
<br />22.2
<br />-56.8
<br />27.4
<br />-70.1
<br />1
<br />50
<br />7.6
<br />-20.5
<br />8.3
<br />-22.4
<br />9.0
<br />-24.4
<br />10.6
<br />-28.6
<br />123
<br />-33.2
<br />14.1
<br />-38.1
<br />16.0
<br />-43.3
<br />20.3
<br />-54.8
<br />25.0
<br />-67.7
<br />1
<br />100
<br />7.0
<br />-19.9
<br />7.7
<br />-21.8
<br />8.3
<br />-23.7
<br />9.8
<br />-27.8
<br />11.4
<br />-32.3
<br />13.0
<br />-37.0
<br />14.8
<br />-42.1
<br />18.8
<br />-53.3
<br />23.2
<br />-65.9
<br />0
<br />8.9
<br />-36.5
<br />9.7
<br />-39.9
<br />10.5
<br />-43.5
<br />12.4
<br />-51.0
<br />14.3
<br />-59.2
<br />16.5
<br />-67.9
<br />18.7
<br />-77.3
<br />23.7
<br />-97.8
<br />29.3
<br />-120.7
<br />'
<br />2
<br />20
<br />8.3
<br />-32.6
<br />9.1
<br />-35.7
<br />9.9
<br />-38.8
<br />11.6
<br />-45.6
<br />13.4
<br />-52.9
<br />15.4
<br />-60.7
<br />17.6
<br />-69.0
<br />22.2
<br />-87.4
<br />27.4
<br />-107.9
<br />0
<br />2
<br />50
<br />7.6
<br />-27.5
<br />8.3
<br />-30.1
<br />9.0
<br />-32.71
<br />10.6
<br />-38.4
<br />12.3
<br />-44.5
<br />14.1
<br />-51.1
<br />16.0
<br />-58.2
<br />20.3
<br />-73.6
<br />25.0
<br />-90.9
<br />A
<br />2
<br />100
<br />7.0
<br />-23.6
<br />7.7
<br />-25.8
<br />8.3
<br />-28.11
<br />9.8
<br />-33.0
<br />11.4
<br />-38.2
<br />13.0
<br />-43.9
<br />14.8
<br />-50.0
<br />18.8
<br />-63.2
<br />23.2
<br />-78.1
<br />8.9
<br />-55.0
<br />9.7
<br />-21.8
<br />10.5
<br />-65.4
<br />12.4
<br />-76.8
<br />14.3
<br />-89.0
<br />16.5
<br />-102.2
<br />18.7
<br />-116.3
<br />23.7
<br />-147.2
<br />29.3
<br />-181.7
<br />Ir
<br />3
<br />20
<br />8.3
<br />-45.5
<br />9.1
<br />-21.2
<br />9.9
<br />-54.2
<br />11.6
<br />-63.6
<br />13.4
<br />-73.8
<br />15.4
<br />-84.7
<br />17.6
<br />-96.3
<br />22.2
<br />-121.9
<br />27.4
<br />-150.5
<br />3
<br />50
<br />7.6
<br />-33.1
<br />8.3
<br />-20A
<br />9.0
<br />-39.3
<br />10.6
<br />-46.2
<br />12.3
<br />-53.5
<br />14.1
<br />-61.5
<br />16.0
<br />-69.9
<br />20.3
<br />-88.5
<br />25.0
<br />-109.3
<br />3
<br />1 100
<br />7.0
<br />-23.6
<br />7.7
<br />-19.8
<br />8.3
<br />-28.1
<br />9.8
<br />-33.0
<br />11.4
<br />-38.2
<br />13.0
<br />-43.9
<br />14.8
<br />-50.0
<br />18.8
<br />-63.2
<br />23.2
<br />-78.1
<br />12.5
<br />-19.9
<br />13.7
<br />-37.9
<br />14.9
<br />-23.7
<br />17.5
<br />-27.8
<br />23.3
<br />-37.0
<br />28.5
<br />-42.1
<br />33.6
<br />-53.3
<br />41.5
<br />-65.9
<br />1
<br />20
<br />11.4
<br />-19.4
<br />12.5
<br />-34.9
<br />13.6
<br />-23.0
<br />16.0
<br />-27.0
<br />18.5
<br />-31.4
<br />21.3
<br />-36.0
<br />24.2
<br />-41.0
<br />30.6
<br />-51.9
<br />37.8
<br />-64.0
<br />1
<br />50
<br />10.0
<br />-18.6
<br />10.9
<br />-30.9
<br />11.9
<br />-22.2
<br />13.9
<br />-26.0
<br />16.1
<br />-30.2
<br />18.5
<br />-34.6
<br />21.1
<br />-39.4
<br />26.7
<br />-49.9
<br />32.9
<br />-61.6
<br />1
<br />100
<br />8.9
<br />-18.1
<br />9.7
<br />-27.8
<br />10.5
<br />-21.5
<br />12.4
<br />-25.2
<br />14.3
<br />-29.3
<br />16.5
<br />-33.6
<br />18.7
<br />-38.2
<br />23.7
<br />-48.4
<br />29.3
<br />-59.8
<br />12.5
<br />-34.7
<br />13.7
<br />-56.0
<br />14.9
<br />-41.3
<br />17.5
<br />-48.4
<br />23.3
<br />-64.5
<br />28.5
<br />-73.4
<br />33.6
<br />-92.9
<br />41.5
<br />-114.6
<br />r`
<br />c�
<br />2
<br />20
<br />11.4
<br />-31.9
<br />12.5
<br />-52.4
<br />13.6
<br />-38.0
<br />16.0
<br />-44.6
<br />18.5
<br />-51.7
<br />21.3
<br />-59.3
<br />24.2
<br />-67.5
<br />30.6
<br />-85.4
<br />37.8
<br />-105.5
<br />°
<br />2
<br />50
<br />10.0
<br />-28.2
<br />10.9
<br />-47.6
<br />11.9
<br />-33.6
<br />13.9
<br />-39.4
<br />16.1
<br />-45.7
<br />18.5
<br />-52.5
<br />21.1
<br />-59.7
<br />26.7
<br />-75.61
<br />32.9
<br />-93.3
<br />A
<br />2
<br />100
<br />8.9
<br />-25.5
<br />9.7
<br />-44.0
<br />10.5
<br />-30.3
<br />12.4
<br />-35.6
<br />14.3
<br />-41.2
<br />16.5
<br />-47.3
<br />18.7
<br />-53.9
<br />23.7
<br />-68.2
<br />29.3
<br />-84.2
<br />0
<br />12.5
<br />-51.3
<br />13.7
<br />23.8
<br />14.9
<br />-61.0
<br />17.5
<br />-71.6
<br />23.3
<br />95.4
<br />28.5
<br />-108.5
<br />33.6
<br />137.3
<br />41.5
<br />-169.5
<br />m°
<br />3
<br />20
<br />11.4
<br />-47.9
<br />12.5
<br />-22.6
<br />13.6
<br />-57.1
<br />16.0
<br />-67.0
<br />18.5
<br />-77.7
<br />21.3
<br />-89.2
<br />24.2
<br />-101.4
<br />30.6
<br />-128.4
<br />37.8
<br />-158.5
<br />3
<br />50
<br />10.0
<br />-43.5
<br />10.9
<br />-21.0
<br />11.9
<br />-51.8
<br />13.9
<br />-60.8
<br />16.1
<br />-70.5
<br />18.5
<br />-81.0
<br />21.1
<br />-92.1
<br />26.7
<br />-116.6
<br />329
<br />-143.9
<br />3
<br />100
<br />8.9
<br />-40.2
<br />9.7
<br />-19.8
<br />10.5
<br />-47.9
<br />12.4
<br />-56.2
<br />14.3
<br />-65.1
<br />16.5
<br />-74.8
<br />18.7
<br />-85.1
<br />23.7
<br />-107.7
<br />29.3
<br />-132.9
<br />1
<br />10
<br />19.9
<br />-21.8
<br />21.8
<br />-27.6
<br />23.7
<br />-25.9
<br />27.8
<br />-30.4
<br />32.3
<br />-35.3
<br />37.0
<br />-40.5
<br />42.1
<br />-46.1
<br />53.3
<br />-58.3
<br />65.9
<br />-72.0
<br />1
<br />20
<br />19.4
<br />-20.7
<br />21.2
<br />-26.6
<br />23.0
<br />-24.6
<br />27.0
<br />-28.9
<br />31.4
<br />-33.5
<br />36.0
<br />-38.4
<br />41.0
<br />-43.7
<br />51.9
<br />-55.3
<br />64.0
<br />-68.3
<br />1
<br />50
<br />18.6
<br />-19.2
<br />20.4
<br />-25.0
<br />22.2
<br />-22.8
<br />26.0
<br />-26.8
<br />30.2
<br />-31.1
<br />34.6
<br />-35.7
<br />39.4
<br />-40.6
<br />49.9
<br />-51.41
<br />61.6
<br />-63.4
<br />1
<br />100
<br />18.1
<br />-18.1
<br />19.8
<br />-23.8
<br />21.5
<br />-21.5
<br />25.2
<br />-25.2
<br />29.3
<br />-29.3
<br />33.6
<br />-33.6
<br />38.2
<br />-38.2
<br />48.4
<br />-48.4
<br />59.8
<br />-59.8
<br />'°
<br />2
<br />10
<br />19.9
<br />-25.5
<br />21.8
<br />-27.8
<br />23.7
<br />-30.31
<br />27.8
<br />-35.61
<br />32.3
<br />-41.2
<br />37.0
<br />-47.3
<br />42.1
<br />-53.9
<br />53.3
<br />-68.2
<br />65.9
<br />-84.2
<br />v
<br />2
<br />20
<br />19.4
<br />-24.3
<br />21.2
<br />-26.6
<br />23.0
<br />-29.01
<br />27.0
<br />-34.0
<br />31.4
<br />-39.4
<br />36.0
<br />-45.3
<br />41.0
<br />-51.5
<br />51.9
<br />-65.2
<br />64.0
<br />-80.5
<br />n
<br />2
<br />50
<br />18.6
<br />-22.9
<br />20.4
<br />-25.0
<br />22.2
<br />-27.2
<br />26.0
<br />-32.0
<br />30.2
<br />-37.1
<br />34.6
<br />-42.5
<br />39.4
<br />-48.4
<br />49.9
<br />-61.3
<br />61.6
<br />-75.6
<br />2
<br />100
<br />18.1
<br />-21.8
<br />19.8
<br />-23.8
<br />21.5
<br />-25.9
<br />25.2
<br />-30.4
<br />29.3
<br />-35.3
<br />33.6
<br />-40.5
<br />38.2
<br />-46.1
<br />48.4
<br />-58.3
<br />59.8
<br />-72.0
<br />3
<br />10
<br />19.9
<br />-25.5
<br />21.8
<br />-27.8
<br />23.7
<br />-30.3
<br />27.8
<br />-35.6
<br />32.3
<br />-41.2
<br />37.0
<br />-47.3
<br />42.1
<br />-53.9
<br />53.3
<br />-68.2
<br />65.9
<br />-84.2
<br />3
<br />1 20
<br />19.4
<br />-24.3
<br />21.2
<br />-26.6
<br />23.0
<br />-29.0
<br />27.0
<br />-34.0
<br />31.4
<br />-39.4
<br />36.0
<br />-45.3
<br />41.0
<br />-51.5
<br />51.9
<br />-65.2
<br />64.0
<br />-80.5
<br />3
<br />1 50
<br />18.6
<br />-22.9
<br />20.4
<br />-25.0
<br />22.2
<br />-27.2
<br />26.0
<br />-32.0
<br />30.2
<br />-37.1
<br />34.6
<br />-42.5
<br />39.4
<br />-48.4
<br />49.9
<br />-61.3
<br />61.6
<br />-75.6
<br />3
<br />1 100
<br />18.1
<br />-21.8
<br />19.8
<br />-23.6
<br />21.5
<br />-25.9
<br />25.2
<br />-30.4
<br />29.3
<br />-35.3
<br />33.6
<br />-40.5
<br />38.2
<br />-46.1
<br />48.4
<br />-58.3
<br />59.8
<br />-72.0
<br />21.8
<br />23.6
<br />23.8
<br />25.8
<br />25.9
<br />-28.11
<br />30.4
<br />33.0
<br />40.5
<br />43.9
<br />46.1
<br />50.0
<br />58.3
<br />63.2
<br />72.0
<br />78.1
<br />4
<br />20
<br />20.8
<br />-22.6
<br />22.7
<br />-24.7
<br />24.7
<br />-26.9
<br />29.0
<br />-31.6
<br />33.7
<br />-36.7
<br />38.7
<br />-42.1
<br />44.0
<br />-47.9
<br />55.7
<br />-60.6
<br />68.7
<br />-74.8
<br />4
<br />50
<br />19.5
<br />-21.3
<br />21.3
<br />-23.3
<br />23.2
<br />-25.4
<br />27.2
<br />-29.8
<br />31.6
<br />-34.6
<br />36.2
<br />-39.7
<br />41.2
<br />-45.1
<br />52.2
<br />-57.1
<br />64.4
<br />-70.6
<br />4
<br />100
<br />18.5
<br />-20.4
<br />20.2
<br />-22.2
<br />22.0
<br />-24.2
<br />25.9
<br />-28.4
<br />30.0
<br />-33.0
<br />34.4
<br />-37.8
<br />39.2
<br />-43.1
<br />49.6
<br />-54.5
<br />61.2
<br />-67.3
<br />4
<br />500
<br />16.2
<br />-18.1
<br />17.7
<br />-19.8
<br />19.3
<br />-21.5
<br />22.7
<br />-25.2
<br />26.3
<br />-29.3
<br />30.2
<br />-33.6
<br />34.3
<br />-38.2
<br />43.5
<br />-48.4
<br />53.7
<br />-59.8
<br />21.8
<br />-29.1
<br />23.8
<br />-31.91
<br />25.9
<br />-34.7
<br />30.4
<br />-40.7
<br />40.5
<br />-54.2
<br />46.1
<br />-61.7
<br />58.3
<br />-78.0
<br />72.0
<br />-96.3
<br />5
<br />20
<br />20.8
<br />-27.2
<br />22.7
<br />-29.7
<br />24.7
<br />-32.4
<br />29.0
<br />-38.0
<br />33.7
<br />-44.0
<br />38.7
<br />-50.5
<br />44.0
<br />-57.5
<br />55.7
<br />-72.8
<br />68.7
<br />-89.9
<br />5
<br />50
<br />19.5
<br />-24.6
<br />21.3
<br />-26.9
<br />23.2
<br />-29.3
<br />27.2
<br />-34.3
<br />31.6
<br />-39.8
<br />36.2
<br />-45.7
<br />41.2
<br />-52.0
<br />52.2
<br />-65.8
<br />64.4
<br />-81.3
<br />5
<br />100
<br />18.5
<br />-22.6
<br />20.2
<br />-24.7
<br />22.0
<br />-26.9
<br />25.9
<br />31.6
<br />30.0
<br />-36.7
<br />34.4
<br />-42.1
<br />39.2
<br />-47.9
<br />49.6
<br />-60.6
<br />61.2
<br />-74.8
<br />5
<br />500
<br />16.2
<br />-18.1
<br />17.7
<br />-19.8
<br />19.3
<br />-21.5
<br />22.7
<br />25.2
<br />26.3
<br />29.3
<br />30.2
<br />33.6
<br />34.3
<br />382
<br />43.5
<br />48.4
<br />53.7
<br />59.8
<br />a. The effective wind area shall be equal to the span length multiplied by an effective width. This width shall be permitted to be not be less
<br />than one-third the span length. For cladding fasteners, the effective wind area shall not be greater than the area that is tributary to an individual
<br />fastener.
<br />b. For effective areas between those given above, the load may be interpolated; otherwise, use the load associated with the lower effective
<br />area.
<br />C. Table values shall be adjusted for height and exposure by multiplying by the adjustment coefficient in Table R301.2(3).
<br />d. See Figure R301.2(7) for location of zones.
<br />e. Plus and minus signs signify pressures acting toward and away from the building surfaces.
<br />f. Positive design wind pressures shall not be less than +16 psf and negative design wind pressures shall not be less than -16 psf.
<br />g. For allowable stress design and for testing as specified in Section R301.2.1.6, component and cladding loads are permitted to be
<br />multiplied by 0.6.
<br />TABLE R301.2(3)
<br />HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENTS FOR TABLE R301.2(2)
<br />MEAN
<br />ROOF HEIGHT
<br />EXPOSURE
<br />B
<br />C
<br />D
<br />15
<br />MON/1.00
<br />1.21
<br />1.47
<br />20
<br />1.00
<br />1.29
<br />1.55
<br />25
<br />1.00
<br />1.35
<br />1.61
<br />30
<br />1.00
<br />1.40
<br />1.66
<br />35
<br />1.05
<br />1.45
<br />1.70
<br />40
<br />1.09
<br />1.49
<br />1.74
<br />45
<br />1.12
<br />1.53
<br />1.78
<br />50
<br />1.16
<br />1.56
<br />1.81
<br />55
<br />1.19
<br />1.59
<br />1.84
<br />60
<br />1.22
<br />1.62
<br />1.87
<br />TABLE R301.2(4)
<br />GARAGE DOOR LOADS FOR A BUILDING WITH A MEAN ROOF HEIGHT OF 30 FEET
<br />LOCATED IN EXPOSURE B
<br />Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 (MPH - 3 SECOND GUST)
<br />ROOF > 10 DEGREES
<br />EFFECTIVE AREA:
<br />90
<br />100
<br />110
<br />120
<br />130
<br />140
<br />150
<br />WIDTH (FT)
<br />HEIGHT (FT)
<br />9
<br />7
<br />12.8 -14.5
<br />15.8 -17.9
<br />19.1 -21.6
<br />22.8 -25.8
<br />26.7 -30.2
<br />31.0 -35.1
<br />35.6 -40.2
<br />16
<br />7
<br />12.3 -13.7
<br />15.2 -16.9
<br />18.3 -20.4
<br />1 21.8 -24.3
<br />1 25.6 -28.5
<br />1 29.7 -33.1
<br />1 34.1 -38.0
<br />For SI: 1 foot = 304.8 mm, 1 mile per hour = 1.609 km/h, 1 psf = 47.88 N/m2.
<br />1. For effective areas or wind speeds between those given above the load may be interpolated, otherwise use the load associated
<br />with the lower effective area.
<br />2. Table values shall be adjusted for height and exposure by multiplying by the adjustment coefficient in Table R301.2(3).
<br />3. Plus and minus signs signify pressures acting toward and away from the building surfaces.
<br />4. Negative pressures assume door has 2 feet of width in building's end zone.
<br />5. Table values include the 0.6 load reduction factor.
<br />TABLE R301.5
<br />MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS
<br />(in pounds per square foot)
<br />USE
<br />LIVE LOAD
<br />Uninhabitable attics without storage b
<br />10
<br />Uninhabitable attics with limited storage b,g
<br />20
<br />Habitable attics & attics served w/ fixed stairs
<br />30
<br />Decks e
<br />40
<br />Exterior balconies if area < 100 sq. ft.
<br />Exterior balconies if area > 100 sq. ft.
<br />60PSF
<br />100 PSF
<br />Fire escapes
<br />40
<br />Guardrails and handrails d
<br />200'
<br />Guardrails in -fill components f
<br />50,
<br />Passenger vehicle garages a
<br />50 a
<br />Rooms other than sleeping rooms
<br />40
<br />Sleeping rooms
<br />30
<br />Stairs
<br />40"'
<br />For SI: 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm2
<br />1 pound = 4.45 N.
<br />a. Elevated garage floors shall be capable of supporting a 2,000-pound load applied over a
<br />20-square-inch area.
<br />b. Uninhabitable attics without storage are those where the maximum clear height between
<br />joists and rafters is less than 42 inches, or where there are not two or more adjacent trusses
<br />with web configurations capable of accommodating an assumed rectangle 42 Inches high by
<br />24 inches in width, or greater, within the plane of the trusses. This live load need not be
<br />assumed to act concurrently with any other live load requirements.
<br />c. Individual stair treads shall be designed for the uniformly distributed live load or a
<br />300-pound concentrated load acting over an area of 4 square inches, whichever produces the
<br />greater stresses.
<br />d. A single concentrated load applied in any direction at any point along the top.
<br />e. See Section R502.2 for decks attached to exterior walls.
<br />f. Guard in -fill components (all those except the handrail), balusters and panel fillers shall be
<br />designed to withstand a horizontally applied normal load of 50 pounds on an area equal to 1
<br />square foot. This load need not be assumed to act concurrently with any other live load
<br />requirement.
<br />g. Uninhabitable attics with limited storage are those where the maximum clear height
<br />between joists and rafters is 42 inches or greater, or where there are two or more adjacent
<br />trusses with web configurations capable of accommodating an assumed rectangle 42 inches
<br />in height by 24 inches in width, or greater, within the plane of the trusses.
<br />The live load need only be applied to those portions of the joists or truss bottom chords where
<br />all of the following conditions are met:
<br />1. The attic area is accessible from an opening not less than 20 inches in width b 30
<br />P 9 Y
<br />inches in length that is located where the clear height in the attic is a minimum of 30 inches.
<br />2. The slopes of the joists or truss bottom chords are no greater than 2 inches vertical to
<br />12 units horizontal.
<br />3. Required insulation depth is less than the joist or truss bottom chord member depth.
<br />The remaining portions of the joists or truss bottom chords shall be designed for a uniformly
<br />distributed concurrent live load of not less than 10 Ib/ft2.
<br />h. Glazing used in handrail assemblies and guards shall be designed with a safety factor of 4.
<br />The safety factor shall be applied to each of the concentrated loads applied to the top of the
<br />rail, and to the load on the in -fill components. These loads shall be determined independent of
<br />one another, and loads are assumed not to occur with any other live load.
<br />TABLE R301.2.1.2 WINDBORNE DEBRIS
<br />PROTECTION FASTENINGS HEDULE FOR
<br />WOOD STRUCTURAL PANELSa,b,e,d
<br />FASTENER SPACING (inches) I.b
<br />4 Feet
<br />6 Feet
<br />Panel Span
<br />< panel
<br />< panel
<br />5 4 Feet
<br />Span < 6
<br />span < 8
<br />FASTENER TYPE
<br />feet
<br />Feet
<br />No. 8 wood screw based
<br />anchor with 2-inch
<br />16
<br />10
<br />8
<br />embedment length
<br />No. 10 wood screw based
<br />anchor with 2-inch
<br />16
<br />12
<br />9
<br />embedment length
<br />1 /4" lag screw based anchor
<br />with 2-inch embedment
<br />16
<br />16
<br />16
<br />length
<br />For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N,
<br />1 mile per hour = 0.447 m/s.
<br />a. This table is based on 130 mph wind speeds and a 33-foot mean roof height.
<br />b. Fasteners shall be installed at opposing ends of the wood structural panel.
<br />Fasteners shall be located a minimum of 1 inch from the edge of the panel.
<br />c. Anchors shall penetrate through the exterior wall covering with an embedment length of
<br />2 inches minimum into the building frame. Fasteners shall be located a minimum of 21/2
<br />inches from the edge of concrete block or concrete.
<br />d. Where panels are attached to masonry or masonry/stucco, they shall be
<br />attached using vibration -resistant anchors having a minimum ultimate withdrawal capacity
<br />of 1500 pounds.
<br />1609.1.2 Protection of openings. In wind-borne debris regions, glazed openings in
<br />buildings shall be impact resistant or protected with an impact -resistant covering meeting
<br />the requirements of SSTD 12, ANSI/DASMA 115 (for garage doors and rolling doors) or
<br />TAS 201, 202 and 203, AAMA 506. ASTM E 1996 and ASTM E 1886 referenced herein,
<br />or an approved impact -resistant stan-lard as follows:
<br />1. Glazed openings located within 30 feet (9144 mm) of grade shall meet the
<br />requirements of the large missile test of ASTM E 1996.
<br />2. Glazed openings located more than 30 feet (9144
<br />mm) above grade shall meet the provisions of the small missile test of ASTM E 1996.
<br />3. Storage sheds that are not designed for human habi-tation and that have a floor
<br />area of 720 square feet (67 m2) or less are not required to comply with the mandatory
<br />windborne debris impact standards of this code.
<br />4. Openings in sunrooms, balconies or enclosed porches constructed under existing
<br />roofs or decks are not required to be protected provided the spaces are separated from
<br />the building interior by a wall and all openings in the separating wall are protected in
<br />accordance with Section 1609.1.2 above. Such spaces shall be permitted to be designed
<br />as either partially enclosed or enclosed structures.
<br />FIGURE R301.2(7) COMPONENT AND
<br />CLADDING PRESSURE ZONES
<br />N
<br />T
<br />fai fai
<br />a= 3 _2_ _2_ 3
<br />a=
<br />2
<br />r
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />Q
<br />I
<br />I
<br />I
<br />�
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />Q
<br />I
<br />I
<br />I
<br />2
<br />I
<br />I
<br />I
<br />I
<br />L_
<br />I
<br />I
<br />I
<br />I
<br />_J
<br />3
<br />2
<br />2 10
<br />GABLE ROOFS
<br />0-10,
<br />a
<br />va
<br />0
<br />_Jh
<br />10'<0<45'
<br />a=
<br />GABLE ROOFS
<br />10' < 0 < 45'
<br />For SI: 1 foot = 304.8 mm, 1 degree = 0.0175 rad. Note: a = 4 feet in all cases.
<br />Note: a = 4 feet in all cases.
<br />a= 3 2 3
<br />1
<br />N 2. i 2 d
<br />2' 1D 1 2 2( 1D 1 2
<br />I la al I
<br />I I
<br />I 2 ^ 2 I
<br />2 i 2 `I
<br />i Q �
<br />-, 3
<br />N
<br />HIP ROOFS
<br />10°< 0 < 30'
<br />TABLE R301.2.1.3
<br />WIND SPEED CONVERSIONS a, b, c:
<br />Vult 1100 1110 1120 113011401150116011701 18olligoll 200
<br />Vasd 1 78 1 85 1 93 1 1011 10811161 1241 1321 139 147 155
<br />For SI: 1 mile per hour = 0.447 m/s.
<br />a. Linear interpolation is permitted.
<br />b. Vasd = nominal design wind speed.
<br />C. Vult = ultimate design wind speed determined from Figure R301.2(4).
<br />R301.2.1.3 Wind speed conversion.
<br />When required ultimate design wind speeds, Vult, of Figure R301.2(4) shall be
<br />converted to nominal design wind speeds, Vasd, using Table R301.2.1.3.
<br />TABLE R302.6
<br />DWELLING/GARAGE SEPARATION
<br />�:hl
<br />0 < 10`
<br />h
<br />10° < 0 < 30'
<br />SEPARATION
<br />MATERIAL
<br />From the residence and attics
<br />Not less than 1/2-inch gypsum board or equivalent
<br />applied to the garage side
<br />From all habitable rooms above the garage
<br />Not less than 5/8-inch Type X gypsum board or
<br />equivalent
<br />Structure(s) supporting floor/ceiling assemblies used
<br />Not less than 1/2-inch gypsum board or equivalent
<br />for separation required by this section
<br />Garages located less than 3 feet from a dwelling unit
<br />Not less than 1/2-inch gypsum board or equivalent
<br />on the same lot
<br />applied to the interior side or exterior walls that are
<br />within this area
<br />For or SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
<br />GARAGES & CARPORTS
<br />R302.5 Dwelling/garage opening/penetration protection. Openings and penetrations through the walls or ceilings
<br />separating the dwelling from the garage shall be in accordance with Sections R302.5.1 through R302.5.3.
<br />R302.5.1 Opening protection. Openings from a private garage directly into a room used for sleeping purposes
<br />shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors
<br />not less than 13/8 inches (35 mm) in thickness, solid or honeycomb -
<br />core steel doors not less than 13/8 inches (35 mm) thick, or 20-minute fire -rated doors, equipped with a selfclosing
<br />device.
<br />R302.5.2 Duct penetration. Ducts in the garage and ducts penetrating the walls or ceilings separating the dwelling
<br />from the garage shall be constructed of a minimum No. 26 gage (0.48 mm) sheet steel, 1 inch (25.4 mm) minimum
<br />rigid nonmetallic Class 0 or Class 1 duct board, or other approved material and shall have no openings into the
<br />garage.
<br />R302.5.3 Other penetrations. Penetrations through the separation required in Section R302.6 shall be protected as
<br />required by Section R302.11, Item 4.
<br />R302.6 Dwelling/garage fire separation. The garage shall be separated as required by Table R302.6. Openings in
<br />garage walls shall comply with Section R302.5. This provision does not apply to garage walls that are
<br />perpendicular to the adjacent dwelling unit wall.
<br />R302.7 Under -stair protection. Enclosed accessible space under stairs shall have walls, under -stair surface and
<br />any soffits protected on the enclosed side with 1/2-inch (12.7 mm) gypsum board
<br />SECTION R309
<br />GARAGES AND CARPORTS
<br />R309.1 Floor surface. Garage floor surfaces shall be of approved noncombustible material.
<br />The area of floor used for parking of automobiles or other vehicles shall be sloped to facilitate the movement of
<br />liquids to a drain or toward the main vehicle entry doorway.
<br />R309.2 Carports. Carports shall be open on at least two sides. Carport floor surfaces shall be of approved
<br />noncom-bustible material. Carports not open on at least two sides shall be considered a garage and shall comply
<br />with the provisions of this section for garages.
<br />'�ill9 Pa�k�z
<br />Lueku�
<br />i���$�14� YirynP
<br />DATE:
<br />09/14/2015
<br />JOB NO:
<br />HA9139
<br />DESIGN BY:
<br />--
<br />DRAWN BY:
<br />JRH
<br />CHECKED BY:
<br />GC
<br />PROJECT:
<br />3615-HA9139
<br />CHECKED BY:
<br />JRH,JGZ
<br />EST:
<br />--
<br />CONST. MNGR:
<br />--
<br />SUPER:
<br />101,08.1
<br />T t, l
<br />r�co M
<br />V ) J CV
<br />W r
<br />Q 00
<br />^ T
<br />G
<br />_J.._ W
<br />L
<br />-I
<br />Q
<br />T
<br />T
<br />CV
<br />r
<br />i-
<br />z
<br />CY)
<br />0.)
<br />U00
<br />LLj
<br />U
<br />CY)
<br />'-
<br />... J
<br />_J
<br />z
<br />00
<br />LLI
<br />M
<br />T
<br />=
<br />11
<br />MODEL:
<br />9-15
<br />SPECS
<br />CUSTOMER:
<br />LUCKEY
<br />39119 PARK DR.
<br />ZEPHRYHILLS, FL 3354
<br />""'
<br />E E
<br />0 0
<br />U U
<br />v
<br /><
<br />v 00
<br />Ln
<br />� � N
<br />a0 Ln
<br />0 m
<br />Em
<br />m
<br />o L
<br />0 00
<br />on o v
<br />u_
<br />L
<br />0
<br />M s
<br />-r>a
<br />ENGINEER'S SEAL
<br />I HEREBY CERTIFY THAT THIS PLAN &
<br />SPECIFICATIONS WERE PREPARED/REVIEWED
<br />BY ME OR UNDER MY DIRECT SUPERVISION
<br />AND COMPLIES WITH THE FLORIDA BUILDING
<br />CODE 5th EDITION 2014,
<br />RESIDENTIAL/BUILDING. ALL SIGNED/SEALED
<br />DRAWINGS PRESENT IN THIS PLAN ARE FOR
<br />STRUCTURAL DESIGN ONLY AND ARE VALID
<br />'9R 12 MONTHS FROM THE SIGNED DATE.
<br />,� �ope.o�oepeory�il. ©®
<br />4 47 74/
<br />A p
<br />0
<br />a
<br />STATE OF400 � 46-/�
<br />NAIL
<br />_1110%,�°e
<br />9114115
<br />Guo-jie- Zhang. PhD, PE Date
<br />Florida PE No. 47744
<br />2911 Folklore Dr. -- Valrico, FL 33596
<br />(813) 657-8865
<br />Al .2
<br />
|