Laserfiche WebLink
HVAC CONTRACTOR NOTE: THIS DESIGN WAS CREATED FOR HEAT LOAD AND ENERGY CODE CALCULATION PURPOSES ONLY. INSTALLING HVAC CONTRACTOR MAY USE OR MODIFY THiS DESIGN AS NEEDED TO SATISFY THE PERMIT JURISDICTION - <br />OF THE BUILDING CODES WILL VARY BY JURISDICTION AND PLANS EXAMINER DESPITE THE BUILDING CODES BEING "UNIFIED". ALL PERMIT COMMENTS MUST BE ADDRESSED BY THE INSTALLING HVAC CONTRACTOR. INSTALLING <br />REQUIRED TO SON THE <br />CALCULATIONS FOR PERMITTING. INSTALLING HVAC CONTRACTOR HAS THE OPTION OF PROVIDING ALTERNATE HVAC DRAWINGS AND CALCULATIONS. <br />HVAC NOTES - FLORIDA BUILDING CODE 6TH EDITION - EFFECTIVE 12/31/2017 <br />THIS DESIGN COMPLIES WITH 6TH EDITION FLORIDA BUILDING, RESIDENTIAL, EXISTING RESIDENTIAL, MECHANICAL, AND ENERGY CODES. <br />RESIDENTIAL BASIS OF DESIGN / CONTRACTOR NOTES: <br />These HVAC drawings, h eat load calculations and energy calculations <br />ns are based on the architectural drawings provided for permit application. This HVAC design and specifications are In accordance <br />J manual <br />with 8 -o t u 8th edition room by room heat load calculation proc <br />edure. This design incorporates <br />DOE "Right Size HVAC Design Guide'view <br />online hops://www.nrel.gov/docslfyl2osti/53352.pdf. <br />For duct design: h s: /(ener ov/ i gn ttp gy g s tes/prod/files{2013/12ff5/cq5_duct_splitter_box_beach.pdf. Right size hvac systems are designed to operate continuously during. climatic design conditions - <br />outdoor climatic design conditions are listed in manual J table I (cooling season outdoor temperature examples: Tampa=91, Sarasota=92, St. Petersburg=93) and the indoor temperatures are fixed <br />by the energy code section FEC302 at 72 degrees for winter / 75 degrees for summer. Single stage cooling equipment will have no reserve equipment capacity included for record breaking outdoor <br />temperatures, unusually low indoor temperatures, entertaining large amount of occupants, or any other item not listed on the "Total Building Summary Loads" page - shown on these hvac drawings. <br />Forequipment seleC ! ton designed to neutralize outdoor ea c t weather auditions that can include h <br />g , t t the highest site recorded outdoor temperature, a lower than 75 degree indoor temperature, and <br />occupancy quantities larger than code allowances, see section FEC403.7.1.3 for selection of staged cooling equipment. The lowest operating capacity of staged cooling equipment can be no greater <br />than 15% of the heat load calculations performed at the climatic design conditions (or the closest equipment capacity match available that neutralizes both the sensible and latent heat toads). The <br />highest capacity of staged cooling equipment has no sizing limitations. HVAC installing contractor must use Manual D duct design procedure for designing the larger duct system associated with the <br />staged capacity oversized equipment - or contact the original designer for an updated HVAC system design. <br />Using the architectural construction drawings, ACCA HVAC design procedures were performed: (1) room by room heat load calculations are performed to determine the buildings thermal zones and <br />room b room demands in accordance with m y th antral J 8th edition heat load calculation procedure (2) the heat load calculations were used to select the HVAC equipment capacities in compliance with <br />manual S equipment selection procedure (3) the room by room demand calculations were used to design the duct system in accordance with manual D duct design (4) room air device type, size, and <br />location were based on the rooms required cfm demand, the duct type, and room geometry, in accordance with manual T room air distribution selection procedure (5) Florida energy calculations were <br />performed based On the ACCA hvac design procedures shown above. Note: if a duct zoning control system is shown with multiple thermostats that are served from a single hvac system, Manual ZR <br />was used for the thermal zone grouping and bypass duct design. All calculations performed are data linked to the 3D CAD energy modeling software program that is specific only to this building. <br />For detailed building envelope information (component layers, insulation R values, NFRC glass values, component types and colors, quantity, etc.) see "Total Building Summary Loads" page shown <br />on these hvac drawings. HVAC installer g must field inspect the building envelope component types and sizes prior to any HVAC installation - be sure the building constructed matches the "Tote! <br />Building Summary Loads" page, the room by room floor plan layout, and the energy code forms. Building envelope construction practice "semi tight" was used in the building infiltration calculations, <br />field verify the building envelope (air barrier in contact with the thermal barrier) fully encapsulates the conditioned space. HVAC Installer must field verify sealed draft stops exist that are isolating the <br />wall cavities from the exterior and/or hot vented attic spaces. Buildings with hot vented attic spaces require the air and thermal barriers to be located at the ceiling plane. Buildings with unvented <br />attics / or single assembly roofs (solid flat, law slope, sealed pitched, open web flat truss) require the air and thermal layer be located at the roof plane. Note: acoustical the ceilings are not air <br />barriers, paper faced insulation is not an air barrier - thermal layers in contact with a grid ceiling are ignored in the heat load and energy code calculations. <br />The room air devices, air cfm values, and branch duct sizes shown per room are based on the peak cooling season design conditions with hvac equipment capacities based on manual S equipment <br />selection procedure for he buildings <br />O O <br />p t !d ngs specific site location. This peak demand makes up approximately 15% of the cooling season, the remaining 85 la of the cooling season (part load conditions) <br />requires dedicated dehumidification equipment if year round control of indoor moisture content is expected. Year round moisture control is not part of this construction drawing and requires the <br />latent heat load calculations are performed at part load design conditions, resulting in latent demands at least 20% higher when compared to the peak design conditions. Dedicated dehumidification <br />equipment is required to control moisture content year round in Florida. Dehumidification equipment (Honeywell DH-90 or Ultra -Air XT150H) will monitor and control moisture content year round <br />using a humidistat or dew point se <br />nsor. Provide ducted dedicated dehumidifier(s) for buildings that contain an unvented "sealed attic" space (example: spray foam insulation at roof deck underside <br />or roof is insulated above the roof deck). Mount the dehumidifiers) in the sealed attic near the roof peak. For buildings with a hot vented attic space, the dehumidification equipment is ducted to the <br />conditioned space and controls the moisture content inside the conditioned space using a humidistat or dew point sensor. For healthier and cleaner indoor air, install a Plasma Air Model 600 ionizer <br />(contact Cyril John 813 888 9000 / Tom Barrow Co.) + a large capacity HEPA filter as shown on the HVAC equipment schedule. <br />These HVAC drawings, heat load calculations, and energy code forms were based on the architectural drawings provided for permit application. Any modifications to the building room layout, <br />occupancy amount, building use or classification, building compass orientation, or building envelope component material type and / or size must be communicated to the original HVAC designer. <br />HVAC Installer should red line sketch on these HVAC drawings any field changes to be made during construction and submit the "as built"red line sketch to the original HVAC designer for review and <br />redesign - prior to any further HVAC installation. Alternate air ducts sizes and air device sizes must be equal to the listed size shown, don't exceed a 3/1 aspect ratio on alternate duct sizes. Don't <br />install a cooling system into a building thatis missing o fu <br />ll building envelope. Installing <br />ng HVAC contractor must provide a copy of the "permit set" HVAC drawings, HVAC calculations (Manua!'s <br />J S D T ZR}, and energy code form <br />s to the building owner for approval. Installing HVAC contractor must perform the "owner survey" as shaven in manual J 8th edition, Appendix 1, to discuss desired <br />indoor temperatures, filtration, indoor air quality, year round moisture control, health issues that require special indoor conditions, interior mounted heat producing equipment (both latent and <br />sensible heat outputs), occupancy amounts above manual J maximums, and any information not shown on the "Total Building Summary Loads" page shown on these HVAG drawings. <br />CODE OFFICIAL + HVAC CONTRACTOR NOTES: <br />Florida Residential Code section abbreviations: FBC = Building, FMC = Mechanical, FEC = Energy <br />These HVAC drawings are not intended to show exact detail of every item required to meet the code requirements, see the isometric details for code section compliance references. The proposed <br />duct routing is general in nature, field co <br />nditions and building structure may dictate the exact mounting configuration of the HVAC system(s). Florida building code sections are listed for each HVAC <br />drawing symbol to be used by the installing HVAC contractor and code official(s). Installer should reference the code sections prior to fabrication or installation of any HVAC system component. <br />These HVAC drawings comply with the Florida Building Codes 6th Edition (2017-2020) sections FBC101.4.2, FBC101.4.6, FBC105.3.1.2, FBC107.3.5 "Mechanical" Plan review criteria. <br />1) HVAC installation must comply with the 6th edition Florida building codes, energy conservation codes, and mechanical codes effective 12/31/2017. Obtain all required permits and inspections per <br />code sections FBC105, FBC107, and FBC110. <br />2) Ventilation air provided per FBC1203 + FMC401.2 + FEC403.6. This design includes mechanically induced controlled ventilation for buildings that contain a forced air duct system, pressurizing the <br />building interior during air handler operation, provided by a ventilation air duct and motorized damper as shown. In cases when the ventilation rate is satisfied by the building infiltration rate, no <br />ventilation air duct will be shown. The ventilation rate may also be satisfied by use of properly sized windows to the outdoors per FBC1203.5, manually operated by the occupant. For large buildings <br />with few occupants, the building envelope infiltration rate may satisfy the minimum ventilation rate required, see "Total Building Summary Loads" page for infiltration rate. Small buildings with many <br />occupants will usually require a ventilation air duct, motorized damper, and ventilation air duct routed to an approved exterior location, see "Total Building Summary Loads" page for ventilation air <br />cfm amount. A mandatory blower door test, FEC402.4.1.2, must be performed to quantify the building's natural infiltration air cfm rate and determine the design ventilation air cfm amount will <br />successfully pressurize the building's interior. The motorized ventilation air damper is dual controlled by both "run-time" and "manually on" control cycles. Installer may also add an air handler fan <br />cycler to provide automatic air exchange during part load conditions. Interlock the ventilation air damper motor with the air handler fan motor for "run time" cycling. The occupants may also select <br />"fan -on" cycle for continuous ventilation when the outdoor conditions are favorable (low heat and low moisture content). <br />3) Coordinate location of all equipment, fans, air devices, and building penetrations with the general contractor. Coordinate air device locations with the electrical contractor (smoke detectors), G.C. , <br />and building owner - the proposed hvac air device locations are shown in the ideal location per Manual T room air device selection procedure, design alternate air device locations per Manual T. <br />HVAC installer must field verify clearances and accessibility prior to fabrication or installation of the HVAC components. Protect the building structure per FMC302. Provide accessibility for elevated <br />equipment per FMC306.5. Fabricate and install HVAC system components per FMC304 + FBC1307, and product manufacturers envelope penetration detail, FBC107.3.5 wind data for wall and roof <br />penetrations, HVAC product installation instructions, HVAC equipment manufacturers installation instructions, and AHRI energy + equipment manufacturers expanded capacity ratings must be <br />available on the construction site at time of code official inspections per FBC110. <br />4) All exterior building penetrations and exterior mounted HVAC equipment, wall vent caps, roof vent caps, intake air vents, and relief air caps, etc. must comply with FBC1609 wind loads. HVAC <br />installing contractor must supply engineered product or equipment ANSI/AMCA 540 test information for attachment to the building envelope component per section FBC1609.1.2. A structural <br />engineer's sealed drawing detail may be required for exterior equipment mounted above ground level per FBC1510.10. This hvac design does not provide structural, equipment, or hood tie down <br />details. See structural engineer's drawings and details for equipment support and tie down info when equipment manufacturers engineered data is not available. <br />5) All duct sizes shown are clear interior "free area" duct dimensions based on FMC603.2 manual D duct design. Add 3" to listed sizes for R-6 exterior duct dimensions - add 4" to listed sizes for R-8 <br />exterior duct dimensions. Fiberglass duct board shown is equal to Knauf 1.5", R-6, fabricate and install per SMACNA standards. Flexible ducts shown are equal to Atco 36 series R-6 class one air <br />duct, not limited in length perFMC603.6.1.1. For prescriptive energy compliance method using form FEC402-2017, use R-8 supply ducts as required by energy code section R403.3.1. Construct all <br />ducts per manufacturer's installation instructions and SMACNA standards for a maximum 1" w.g. Suspend and support the ducts from the building structure per FMC603. Use 26 gauge sheet metal or <br />rigid foil face fiberglass duct board for rigid duct penetrations of private garages per FMC603.7 and protect ducts per FMC607. Mastic seal all ducts installed outside the building's thermal envelope <br />per UL-181 and FMC603.9. Provide accessible volume control dampers in branch ducts per FMC603.18. General exhaust ducts used for exhaust fan duct, clothes dryer duct, make up air duct, and <br />residential cooking appliance duct up to 14" in diameter (or equal free area in rectangular) are constructed from 28 gauge sheet metal "snap lock pipe", ", use SMACNA standards for required gauge <br />of larger metal ducts, mastic seal ducts per table FMC603.9. Use flexible air ducts or 28 gauge sheet metal "snap lock pipe" for ventilation air ducts. Test ducts > 40 linear feet when using energy code <br />compliance method 402 as required by FEC403.3.3. <br />6) Provide a condensate drain piping system per FMC307, and a refrigerant piping system per FMCI107. Extend condensate drain discharge 12" minimum from the building exterior wall, discharge to <br />grass or other approved location, a condensate drywell may be required. Provide piping and supports for both condensate and refrigerant piping per FMC305. <br />7) Provide a balanced return air system per FMC601.6. All enclosable rooms require a 1" undercut on the interior door, allowing about 30 cfm of air relief per 30" wide door. Habitable spaces require <br />door undercut plus a means for air transfer or a ducted return air. Pressure differentials across the restricted room can't exceed .01 inch w.g. Enclosable rooms located on the building exterior <br />envelope should be balanced slightly positive. Size ducted transfer air ducts free area 1.5 times larger than the supply air delivered to the enclosed room(s). Size direct through wall Or door grilles at <br />50 square inches of grille free area to 100 cfm. <br />8) Attic mounted equipment must contain a shut off device to alert the home owner if the primary condensate drain line is not working properly. Using 16 point bold text, Post a "home owner notice" <br />on the electrical service panel alerting the home owner that the HVAC air handler is located in the attic space, see FEC403.3.6 for full compliance description and "notice to home owner" language <br />required. Provide a sealed attic access panel for hot vented attics, a safe workers access deck, an attic light fixture with switch, and an electrical plug outlet. <br />9) This design complies with climate zone 2A of the Florida energy conservation code design conditions FEC302, 72 degree heating set point and 75 degree cooling set point. Compliance <br />demonstration is provided by energy conservation code form R402 prescriptive or R405 performance depending on construction type. The building envelope details are shown on the HVAC drawings <br />basis of design (see "Total Building Summary Loads") as required by FEC303.1. HVAC heat load calculations and HVAC equipment capacity selection per section FEC403.7.1.1 and FEC403.7.1.2. Air <br />distribution thermal insulation layer as required by FEC403.3.1 and FEC405.5.2. Duct sealing as required by FEC403.3.2. Refrigerant piping insulation per FEC403.4. And HVAC equipment controls per <br />FEC403.1. <br />10) Upon completion of the HVAC system installation, per manual D chapter 16, test equipment operating capacities for both cooling and heating to verify the equipment is functioning to the listed <br />capacity. Verify the air handler total air flow cfm matches the HVAC equipment schedule or heat load calculation minimum system airflow rate. No duct system is self -balancing, adjust each room's <br />branch duct volume damper to achieve the listed air flow values shown or to meet the building owner's needs. Use the air device volume damper for the last 10% of air balance to avoid noise at the air <br />device face. Room air flow balance for buildings with concealed ducts can be accomplished during the "rough in" stage of construction, prior to concealment of ducts. With the building air barrier <br />fully intact, install and operate the air handler until proper air flow is adjusted per room, a balanced return air path must also be present. Use a self -compensating air flow hood for airflow <br />measurements, perform air balance procedure in accordance with manual B or NEBB standards. When required by code, provide the air balance report to the building owner and code officials. A <br />blower door test must be performed to verify that the building envelope natural leakage rate does not exceed the infiltration or ventilation cfm rate shown on the "Total Building Summary Loads" <br />page, shown on these drawings. <br />11) HVAC sequence of proper operation: The thermostat is set to "auto" mode and will monitor the conditioned space temperature and provide heating, cooling, and ventilation when required. Upon <br />a call for heating, the air handler fan interlock will open the ventilation air damper -and operate the indoor fan and heat <br />t ucondenser and/or electric heat strip until the space conditions are <br />satisfied - use a 72 degree thermostat setting during the heating season. Upon a call for cooling, the air handler fan interlock will open the ventilation air damper and operate the indoor fan and heat <br />pump condenser until the space conditions are satisfied - use a 75 degree thermostat setting during the cooling season. During favorable outdoor conditions, when the temperature and humidity is <br />low - the thermostat may be set to "fan on" for continuous air circulation and introduction of ventilation air. For newly constructed homes to be energy code compliant (FEC403.1), the HVAC installer <br />must set the programmable thermostat to provide heating up to 70 degrees and cooling down to 78 degrees. Be sure not to overcool the conditioned space - overcooling a building is defined as a <br />temperature lower than the dew point temperature for the interior conditioned space - most buildings can easily be driven to dew point temperatures during part load conditions. Overcooling a <br />building successfully requires specialized HVAC equipment and controls. The heat removal (sensible heat) and moisture removal (latent heat) must be de -coupled and independently controlled for <br />buildings to achieve temperature's lower than the "dew point safe" energy code set point of 78 degrees. <br />HVAC SYMBOLS - FLORIDA BUILDING CODE 6TH <br />EDITION (2017-2020) <br />-'� <br />CEILING REGISTER <br />1 WAY THROW SHOWN <br />RECTANGULAR <br />DUCTWORK <br />FMC 603 <br />CONDENSING UNiT <br />HORIZONTAL AIR <br />1 <br />FTC 603.18 <br />59 HVAC NOTES 3 <br />HVAC NOTES 5,9 <br />ON SLAB RAISED <br />I HANDLER MOUNT <br />0 <br />STAND OR ROOF <br />FMC SECTIONS <br />HVACNO S 3,44,9,10 <br />FROM STRUCTURE <br />IFMC SECTIONS <br />LE HVAC NOTES 3,8,10 <br />.1W WALL REGISTER U2 WAY THROW <br />� DUCTWORK FLEXIBLE <br />FMC 603.18 <br />FMC 603 <br />_..._.... <br />HVAC NOTES 3,5,9 <br />. _. <br />HVAC NOTES 5,9 <br />FLOOR REGISTER <br />2 WAY THROW <br />FLEX DUCT <br />JUNCTION BOXES <br />FMC 603 <br />______4P1 <br />DUCTLESS AIR <br />FMC 603.18.1 <br />HVAC MOTES 3 5 9 <br />,aA <br />HVAC NOTES 5 9 <br />. <br />. . <br />VERTICAL AIR <br />HANDLER ON <br />�.� HANDLER <br />'��-� HIGH WALL OR <br />•e. <br />STAND/OR ATTIC <br />FMC SECTIONS <br />303, 304, 306 <br />HVAC NOTES 3,8,9,10 <br />0 �-� CEILING MOUNT <br />FMC SECTIONS <br />3 4 <br />-�--�!• C NOTES <br />HVAC NOTES 3,4,9,10 <br />FLOOR OR CEILING <br />Z*v FILTER GRILLE <br />��, <br />RETURN AIR <br />PLENUM TRUNK <br />FMC 603.18 <br />FMC 602 <br />r <br />HVAC NOTES 3,5,7,9 <br />HVAC NOTES 5,9 <br />0 <br />WALL <br />FILTER GRILLE <br />SUPPLY AIR <br />PLENUM TRUNK <br />AFF = ABOVE FINISH FLOOR <br />AHU = AIR HANDLING UNIT <br />603.18 <br />Ell <br />FMC 602�AFMC <br />DEDK:ATEQP <br />= YPA P <br />B BYPASS DAMPER <br />HVAC NOTES 3,5,7,9 <br />HVAC NOTES 5 9 <br />BD BAROMETRIC DAMPER <br />VENTILATROfl-(4)6Y <br />FLEXIBLE DUCTS <br />= <br />CFM = CUBIC FEET / MINUTE <br />CEILING GRILLE <br />+,- -J' DUCTED T/A <br />*.- <br />REFRIGERANT + <br />CONTROL PIPING <br />SEE FLOOR PLAN <br />FOR CONFIGURATION <br />CU = CONDENSING UNIT <br />DH=DE <br />FMC 601.6 + 603.18 <br />FMC 306 + 1107 <br />FMC 303, 304, 306 <br />-HUMIDIFIER <br />HVAC NOTES 3,5,7,9 <br />HVAC NOTES 3,6,9 <br />HVAC NOTES 3,8,9,10 <br />E/A = EXHAUST AIR <br />EER = ENERGY EFFICIENCY RATIO <br />EF = EXHAUST FAN <br />FPM =FEET PER MINUTE <br />WALL GRILLE <br />-i- H -Ir DIRECT Tt A <br />CONDENSATE <br />------•---- DRAIN LINES <br />9 I%- <br />FMC so1.s +s03.18 <br />FMC 306 + 307 <br />DEDICATED <br />HSPF =HEATING SEASON PERFORMACE FACTOR <br />HVAC NOTES 3 5 7 9 <br />HVAC NOTES 3,6,8,9 <br />VENTILATING <br />HP = HORSE POWER <br />= <br />DEHUMDiFIER <br />DEWPOINT CONTROL <br />MOP = MAXIMUM OVER CURRENT PROTECTION <br />e•e <br />CONDENSATE <br />o <br />SEE FLOOR PLAN <br />MTR = MOTORIZED DAMPER <br />1" UNQERCUT QOOR <br />°e• °• <br />- ' - - - - - • e � ° <br />DRAIN <br />FOR CONFIGURATION <br />MUA =MAKE UP AIR <br />TYPICAL ALL INTERIOR <br />DOORS FMC <br />ease a <br />06 +DRYWELL <br />FMC 305 + 307 <br />HVAC NOTE 6 <br />FMC 303, 304, 306 <br />HVAC NOTES 2,3,8,9,10 <br />KW = KILO WATTS <br />E 7 <br />HVAC NOTE 7 <br />O/A =OUTSIDE AIR <br />PKG = PACKAGE UNIT <br />_J <br />BRANCH DUCT VOLUME <br />CONTROL DAMPER <br />'�' H S <br />EQUIP. CONTROLS <br />FECC4032.4+ <br />FECR403.1 <br />DEDICATED <br />R/A = RETURN AIR <br />RTU = ROOFTOP UNIT <br />FMC 603.18 <br />HVAC NOTES 2,5,10 <br />HVAC NOTES 3 10 <br />E <br />2' `�' <br />� <br />DE -HUMIDIFIER <br />EXPOSED SHOWN <br />CONCEALED WITH <br />SlA =SUPPLY AIR <br />SEER =SEASONAL ENERGY EFFICIENCY RATIO <br />DUCT MOUNTED <br />FIRE DAMPER <br />° - ° <br />Ef <br />DUCT MOUNTED <br />SMOKE DETECTOR <br />DUCTWORK OPTION <br />FMC 303, 304, 306 <br />HVAC NOTES 3,8,9,10 <br />SF = SUPPLY FAN <br />SP = STATIC PRESSURE <br />FMC 607 <br />FMC 606 <br />I T/A = TRANSFER AIR <br />HVAC NOTE 3,6 <br />HVAC NOTE 9 <br />TSP =TOTAL STATIC PRESSURE <br />7YP = TYPICAL <br />✓"J\" EXHAUST VENT <br />; ROOF/ WALL <br />ZD BP <br />ZONE I BYPASS <br />FMC DAMPER <br />_ _ _ _ - - _ <br />; . , <br />V/A = VENTILATION AIR <br />VDH =VENTILATING DEHUMIDIFIER <br />FMC 504, 605 <br />HVAC NOTES 3,4 <br />HVAC NOTE 9 <br />. ° . 1 <br />VTE =VENT TO EXTERIOR <br />- _ -1-41 <br />: -� <br />PACKAGE uNtr <br />ZD = ZONE DAMPER <br />- <br />r I INTAKE VENT <br />1�1 ROOF / WALL <br />MTR <br />MOTOR FOR <br />AIR DAMPER <br />1,- <br />� : <br />t , 4 <br />SLAB OR ROOF <br />MOUNTED <br />� . + <br />1 FMC 401.5 <br />FMC 3D3 304 306 <br />-.. <br />, °.­ 1 .0. <br />FMC SECTIONS <br />HVAC NOTES 2,3,4 <br />HVAC NOTES 2 9 10 <br />> > <br />. l <br />303,304,306 <br />4 .• <br />4 - �• <br />HVAC NOTES 3,4,9,1 0 <br />EQUIPMENT <br />EXHAUST FAN <br />ACCESS PANEL <br />O <br />EF-1 or as NOTED <br />4� <br />E�] <br />FMC 306 <br />FMC 601 <br />- - - - - - - - <br />HVAC NOTE $ <br />HVAC NOTES3,5,9,10 <br />HVAC BASIS OF DESIGN - BUILDING ENVELOPE COMPONENTS - FECC103.2 + FECR103.2 <br />BUILDING ENVELOPE COMPONENTS SHOWN ON THIS REPORT ARE DATA LINKED TO THE 3D SMART CAD HVAC FLOOR PLAN(S) SMART <br />FIGURES. ANY CHANGES TO THE BUILDING ENVELOPE COMPONENT TYPES, COMPONENT AMOUNTS, BUILDING USAGE, INTERIOR <br />ROOM LAYOUTS, OR BUILDING COMPASS ORIENTATION (NORTH ARROW) MUST BE COMMUNICATED TO THE ORIGINAL DESIGNER. <br />CONDUCT AN OWNER SURVEY PER APPENDIX 1 "SURVEY", PAGE A1-1 TO ESTABLISH THE LISTED ITEMS ON THIS SUMMARY PAGE <br />MEETS THE BUILDING OWNERS NEEDS. SEE "PROJECT REPORT" FOR BUILDING SITE CLIMATIC CONDITIONS AND INDOOR DESIGN <br />CONDITIONS. ALSO SEE MANUAL D DUCT DESIGN REPORT(S) + "MANUAL S EQUIPMENT SELECTION" REPORT(S) FOR MORE DETAILED <br />INFORMATION. SEE ENERGY FORMS FOR MINIMUM REQUIREMENTS OF ALL ITEMS. <br />DOOR U VALUES USED iN THE CALCULATIONS =11 D WOOD .39 (R=2.564) 11 N METAL .35 (R=2.857) 11J FIBERGLASS .40 (R=2.5) <br />Rhvac - Residential & Light Commercial HVAC Loads Elite Software Development, Inc. <br />HVAC Designs Kennedy Avenue A2M2 SFR 2155 n <br />0 <br />Tam a, FL 33615 Page 9 <br />Total Building Summary Loads <br />Component Area Sen Lat Sen Total <br />Description Quan Lass Gain Gain Gain <br />R405 FD: Glazing-FECR405.5.2 Two Pane Low E Glass 40 512 0 380 380 <br />Door, ground reflectance = 0.32, medium color <br />blinds at 450 with 25% coverage, U-value 0.4, SHGC <br />0.25 <br />R405 OP: Glazing-FECR405.5.2 Two Pane Low E 179.3 2,295 0 3,410 3,410 <br />Window Operable, ground reflectance = 0.23, <br />outdoor insect screen with 50% coverage, medium <br />color blinds at 45' with 25% coverage, U-value 0.4, <br />SHGC 0.25 <br />R405 OP: Glazing-FECR405.5.2 Two Pane Low E 16.2 207 0 138 138 <br />Window Operable, ground reflectance = 0.32, <br />outdoor insect screen with 50% coverage, medium <br />color blinds at 45° with 25% coverage, U-value 0.4, <br />SHGC 0.25 <br />WCB4: Wall -Block, Custom, R-4 continuous + any 1683.3 7,702 0 3,921 3,921 <br />finish, U-value 0.143 <br />WGE20: Wall -Frame, Custom, Gable up + R-20 + any 60 123 0 53 53 <br />finish, U-value 0.064 <br />RUA20DS-ad: Roof/Ceiling-Roof Joists Between Roof 2327 3,723 0 4,771 4,771 <br />Deck and Ceiling or Foam Encapsulated Roof <br />Joists, Custom, Unvent + R-20 @ roof, dark <br />asphalt, U-value 0.05 <br />RUABW20: Roof/Ceilin -Roof Joists Between Roof 62 g 113 0 145 145 <br />Deck and Ceiling or Foam Encapsulated Roof <br />Joists, Custom, Unvent Attic Break Wall + R-20, U- <br />value 0.057 <br />FSOGO: Floor -Slab on grade, Custom, R-0 edge + any 216 8,158 0 0 0 <br />finish, U-value 1.18 <br />Subtotals for structure: 22,833 0 12,818 12,818 <br />People: 5 1,150 1,500 2,650 <br />Equipment: 770 2,810 3,580 <br />Lighting: 0 0 0 <br />Ductwork: 2,213 1,889 711 2,600 <br />Infiltration: Winter CFM: 0 Summer CFM: 0 0 0 0 Q <br />Ventilation: Winter CFM: 75, Summer CFM: 75 2,638 2,698 1,319 4,018 <br />Total Building Load Totals: 27,684 6,508 19,158 25,666 <br />Check Fi ures <br />Total Building Supply CFM: 1,000 CFM Per Square ft.: 0.464 <br />Square ft. of Room Area: 2,155 Square ft. Per Ton: 985 <br />Volume (1`1:3): 20,106 <br />Buildina Loads <br />Total Heating Required Including Ventilation Air: 27,684 Btuh 27.684 MBH <br />Total Sensible Gain: 19,158 Btuh 75 % <br />Total Latent Gain: 6,508 Btuh 25 % <br />Total Cooling Required Including Ventilation Air: 25,666 Btuh 2.19 Tons (Based On 73% Sensible Capacity) <br />Notes <br />Rhvac is an ACCA approved Manual J, D and S computer program. <br />Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. <br />All computed results are estimates as building use and weather may vary. <br />Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design <br />conditions. <br />INTELLIGENT CAD DUCT FIGURES - GRAPHIC MANUAL D DUCT FITTINGS <br />- - <br />10: <br />- -- <br />$!�f <br />- i <br />1,4],Vr1_,4,,,.,, <br />: -- - <br />HEATER i <br />IL <br />- _Pi INCLUDES PE1 r `, - / <br />• I SUPPLY AIR :11 <br />L PLENUMS RETURN AIR t • <br />I MAIN SUPPLY AIR PLENUMS i t DEVICES <br />I <br />V 2-A <br />EL35-80 2-D 2-E <br />EL40-85 EL25-50 <br />SUPPLY BRANCH DUCT TAKEOFF <br />6-C 1#7 6 BYy <br />6 A <br />EL10-115 EL10-110 ELtO-75 <br />RETURN BRANCH DUCT TAKEOFF <br />8-A 6-A 3PC 8-B ES 8-D <br />EL10-20 EL20-35 EL10-65 EL65 <br />SUPPLY + RETURN ELBOWS <br />2-O 2-P 2- <br />0 <br />EL55.100 EL50-75 ELIO-25 <br />. r • <br />45 DEGREES 90 DEGREES <br />6-E <br />6-D EL1540 <br />EL10-30 <br />RETURN BRANCH DUCT TAKEOFF <br />rn),%% 12-1 <br />12-H EL10-35 <br />12-C EL15-40 <br />EL20-40 <br />S/A + RIA DIVERGING TRANSITIONS <br />I?b VL <br />4Z 9 B 9-E 9 K <br />4..-A or 4-AD <br />EL60 EL80 EL50 EL65 <br />EL35 <br />; ,. I <br />:•._ <br />-...6_ <br />1►Cr %��', �k __:�. <br />4 <br />I I <br />r <br />CONVERGING• <br />DUCT VELOCITY <br />SHOWN IS FEET <br />PER MINUTE <br />SUPPLY AIR SIDE <br />RETURN AIR SIDE <br />RIGID <br />FLEX <br />RIGID <br />FLEX <br />TRUNK DUCT <br />700 - 900 <br />600-700 <br />600-700 <br />600-700 <br />BRANCH DUCT <br />600 - 700 <br />1 600 - 700 <br />400 - 700 <br />600-700 <br />RETURN TRUNK JUNCTION FITTINGS <br />LI A9-O <br />9-M EL85 EL15 <br />EL20 <br />SUPPLY TRUNK JUNCTION FITTINGS <br />e 1!2) , <br />TRAPEZOID <br />TRIANGLE <br />11A FLEX ELBOW <br />11A EXACT DEGREE <br />EL10-95 EL10-95 11 B <br />EL5-20 <br />S/A + R/A FLEXIBLE DUCT JUNCTION BOX <br />DUCT DESIGN SHOWNDATA i TO THE MANUALi DUCT i REPORTS. -•'EVERY DUCT <br />SECTION SHOWN INCLUDED <br />THE CALCULATIONS TO DETERMINE THE MOST RESTRICTIVE AIR PATH. MANUAL D DUCT DESIGN DATA IS USED FOR AIR HANDLING EQUIPMENT I <br />� SELECTION. THE MAXIMUM VELOCITIES USED ARE BASED ON MANUAL D SECTION 3 (PAGE 3-6) OF ACCA MANUAL D DUCT DESIGN. <br />HEAT PUMP SCHEDULE <br />AIR HANDLER MARK: <br />AHU-1 <br />UNIT MANUFACTURER: <br />AMERICAN STND <br />UNIT MODEL NUMBER: <br />TAM7A0B30H <br />UNIT DIMEN H/W/D: <br />55.7x21.3x21.8 <br />UNIT WEIGHT: <br />138 <br />SUPPLY PLENUM SIZE: <br />18AX14.35 <br />RETURN PLENUM SIZE: <br />18AX117.15 <br />MANUAL D DUCT CFM: <br />1000 / .412 <br />SUPPLY FAN CFM / SP : <br />1003 / A to .9 <br />SUPPLY FAN H/P : <br />1/2 <br />VENTILATION AIR CFM: <br />75 <br />AHU OFF / INFILTRATION: <br />34 <br />UNIT PHASE / HERTZ: <br />1/60 <br />UNIT VOLTAGE: <br />208 / 240 <br />HEATER KW: <br />3.6 / 4.8 <br />AHU + HEAT MOP: <br />25 / 30 <br />CONDENSER MARK: <br />CU-1 <br />NOMINAL A/C TONS: <br />2.5 <br />UNIT MODEL NUMBER: <br />4A61­14030131 <br />UNIT VOLTAGE: <br />208/230/ 1 / 60 <br />UNIT MCA / MOP: <br />15 / 25 <br />UNIT DIMEN H/W/D: <br />33x37x34 <br />UNIT WEIGHT: <br />193 <br />COOL / OUTDOOR TEMP: <br />91 <br />92 <br />93 <br />TOTAL COOLING KBTUH: <br />32.6 <br />32.3 <br />32.1 <br />SENS. COOLING KBTUH: <br />23.8 <br />23.6 <br />23.4 <br />LAT. COOLING KBTUH: <br />8.8 <br />8.7 <br />8.7 <br />SENSIBLE HEAT RATIO: <br />0.73 <br />AHRI C?a 95: TC,SC,LC <br />31.6 <br />23.7 <br />79 <br />AHRi # : <br />7422207 <br />TOTAL HEATING KBTUH: <br />30.0 <br />SEER / HSPF: <br />14.5 / 8.5 <br />THERMOSTAT MODEL: I <br />PROGRAM <br />ALTERNATE BRAND EQUIPMENT WITH EQUAL <br />CAPACITY + EFFICIENCY IS ACCEPTABLE - <br />VIEW ENERGY FORMS FOR MIN EFFICIENCIES <br />ACCU CLEAN FILTRATION IS RECOMMENDED. <br />HVAC CONTRACTOR TO PROVIDE EQUIPMENT <br />TIE DOWN AND INSTALL INSTRUCTIONS + <br />MATCHED EQUIPMENT AHRI RATINGS <br />ON SITE FOR FIELD INSPECTORS APPROVAL. <br />.(2833) <br />y �. . . • " <br />VAC <br />■TEM <br />a - <br />EXHAUST FAN SCHEDULE <br />FAN MARK: <br />EF-1 <br />MANUFACTURER: <br />NUTONE <br />MODEL NUMBER: <br />QT-80 <br />FAN TYPE: <br />CEILING <br />FAN CFM: <br />70 <br />TOTAL PRESSURE: <br />•3 <br />FAN VOLTAGE: <br />120/1/60 <br />FAN AMPERAGE: <br />•7 <br />FAN DIMEN LWH: <br />9X9X6 <br />DUCT OUTLET SIZE: <br />4 <br />DUCT INLET SIZE: <br />10X10 <br />FAN WEIGHT: <br />12 <br />NOTES: <br />1 1,2 <br />1 = VENT TO EXTERIOR <br />2 = INTERLOCK WITH LIGHTS <br />3 = THERMOSTAT CONTROL <br />4 = INTERLOCK WITH SAME ZONE HVAC <br />5 = VARIABLE SPEED CONTROLLER <br />6 = ADJUSTABLE EXTENDED OPERATION <br />RESIDENTIAL OPTION: A 50 CFM MINIMUM <br />EXHAUST FAN MAY BE USED // FMC403.3.1.1 <br />EACH ROOM I I EACH ZONE II DUCT <br />HEAT LOAD I I HEAT LOAD TYPE TYPE <br />FE-CC403.2.1 + FECR403.71 <br />EQUIPMENT <br />SELECTION <br />MANUAL S <br />FECR403.7.1 <br />mmnrrl <br />ENERGY CODE CALCULATIONS <br />FECC402,407+ FECR402,405,406 FINISH <br />HEATING AND COOLING SYSTEM SELECTION, OR "REQUIRED TONS" IS NOT BASED ON THE <br />CONDITIONED AREA SQUARE FEET DIVIDED BY SOME "MAGIC" NUMBER. ABSURD DESIGN <br />PRACTICE ("SQUARE FEET PER TON") IS FORBIDDEN BY THE FLORIDA BUILDING CODES. <br />SELECTION OF HVAC EQUIPMENT, DUCT SIZES, AND AIR DEVICE SIZES ARE BASED ON EACH <br />ROOMS HEAT LOAD DEMAND. CALCULATIONS ARE COMPASS ORIENTATION + CITY SPECIFIC. <br />HVAC EQUIPMENT SHOWN THIS PAGE IS FOR SINGLE STAGE <br />CAPACITY SELECTED ED IN COMPLIANCE WITH MANUAL J 8TH <br />T <br />EDITION HEAT LOAD CALCULATION PROCEDURE + MANUAL <br />D DUCT DESIGN PROCEDURE + MANUAL S HVAC EQUIPMENT <br />SELECTION PROCEDURE AS REQUIRED BY FLORIDA ENERGY <br />CONSERVATION CODE SECTION R403.7. SINGLE STAGE CAPACITY <br />EQUIPMENT CAN NOT BE UNDERSIZED BELOW THE MANUAL J <br />HEAT LOAD CALCULATIONS OR OVERSIZED BY MORE THAN 15% <br />OF THE MANUAL J HEAT LOAD CALCULATIONS (OR NEXT SIZE AVAIL). <br />SEE HVAC BASIS OF DESIGN NOTES ON THIS PAGE FOR CODE SET <br />HVAC DESIGN PARAMETERS AND FECC CODES FECC403.7.1.1 + <br />FECC403.7.1.2. SEE ENERGY FORMS FOR MINIMUM EFFICIENCIES <br />REQUIRED FOR THIS PARTICULAR PROJECT TO COMPLY WITH FECC. <br />VIEW HVAC "OPTIONS" DRAWING FOR UPGRADE TO THE OVERSIZED <br />VARIABLE CAPACITY HVAC EQUIPMENT AS ALLOWED BY FECC CODE <br />SECTION FECC403.7.1.3. OPTIONAL HVAC EQUIPMENT SHOWN ON <br />THE OPTIONS PAGE WILL REQUIRE THE HVAC INSTALLER TO INSTALL <br />A LARGER DUCT SYSTEM AS REQUIRED FOR THE INCREASED AIRFLOW <br />AMOUNT ASSOCIATED WITH THE OPTIONAL OVERSIZED STAGED <br />CAPACITY EQUIPMENT. CONTACT THE ORIGINAL HVAC DESIGNER <br />FOR AN OPTIONAL UPGRADE DESIGN PACKAGE. <br />1-11 <br />1 <br />M <br />i`- <br />In <br />In <br />n <br />1'.0 <br />I <br />Q <br />Ln <br />i-- <br />Q_� <br />O <br />,--. <br />� <br />J <br />II <br />5• <br />Q <br />U <br />� <br />'Q <br />iZ <br />O <br />tY <br />CN <br />r- <br />< <br />{) <br />( <br />I <br />Q <br />(n(-.4 O <br />r- <br />I-_ <br />Z <br />O <br />_ <br />OU <br />v <br />F__ <br />W <br />O <br />= <br />cfl <br />O <br />I <br />�} <br />Q- <br />0 <br />U <br />n-,,, <br />r� <br />V 1 <br />��7 <br />U <br />Q <br />r-) <br />CL <br />O <br />__J <br />(-) <br />U-) <br />n-- <br />I <br />= <br />< <br />= <br />CD <br />Q <br />= <br />a_ <br />W <br />U <br />Q <br />r--� <br />e <br />W <br />• <br />= <br />VV/ <br />W <br />Q <br />0 <br />W <br />Z <br />lW <br />DRAWN: <br />C.T. D <br />SCALE: <br />1 /4" = 1 '-0" <br />GHECkEO &APPROVED <br />SHEET M.1 <br />li -r T-----7--__7-__7T - T <br />