<br />MECHANICAL / PLUMBING DEMOLITION PLAN
<br />1/8" = V-0"
<br />PLUMBING LEGEND
<br />ALL SYBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.
<br />SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
<br />SYMBOL
<br />DESCRIPTION
<br />—
<br />DOMESTIC COLD WATER PIPING (CW)
<br />— — —
<br />DOMESTIC HOT WATER PIPING (HW)
<br />— — — — —
<br />DOMESTIC HOT WATER RETURN PIPING (HWR)
<br />—Q
<br />PIPING UP
<br />PIPING DOWN
<br />�—
<br />DIRECTION OF FLOW
<br />04
<br />GATE VALVE (GV)
<br />BALL VALVE
<br />TEMPERATURE AND PRESSURE RELIEF VALVE (T&P)
<br />►Pi
<br />PRESSURE REDUCING VALVE (PRV)
<br />SS
<br />SANITARY SEWER PIPING
<br />— — — — — — —
<br />SANITARY VENT PIPING
<br />-00
<br />P-TRAP
<br />FLOOR DRAIN OR FLOOR SINK W/ P-TRAP (FD)
<br />—30
<br />HUB DRAIN W/ P-TRAP (HD)
<br />tr,l FCO/
<br />FLOOR CLEANOUT OR GRADE CLEANOUT
<br />WOO
<br />CLEANOUT OR WALL CLEANOUT
<br />NEW CONNECTION TO EXISTING
<br />PLUMBING ABBREVIATIONS
<br />AAV AIR ADMITTANCE VALVE DS DOWNSPOUT
<br />AFF ABOVE FINISH FLOOR GC GENERAL CONTRACTOR
<br />AFG ABOVE FINISH GRADE PRV PRESSURE REDUCING VALVE
<br />A/C ABOVE CEILING RPZ-BFP REDUCED PRESSURE ZONE BFP
<br />B/F BELOW FLOOR SS SANITARY SEWER
<br />BFF BELOW FINISH FLOOR TP TRAP PRIMER
<br />BFP BACKFLOW PREVENTER V PLUMBING VENT
<br />B/G BELOW GRADE VTR VENT THRU ROOF
<br />DCV-BFP DUAL CHECK VALVE BFP W WASTE
<br />r�
<br />EXISTING
<br />VTR I
<br />I � j
<br />I 13"V
<br />I I �''3"V
<br />I Ii�
<br />y LAV
<br />i
<br />i
<br />3"V
<br />I � •
<br />I
<br />I
<br />311V� <'4
<br />STING
<br />S
<br />4"SS
<br />3"W
<br />3"FD
<br />W/TP
<br />/_ EXISTING
<br />4 SANITARY RISER DIAGRAM
<br />M1-1 NTS
<br />PLUMBING FIXTURE SCHEDULE
<br />ROUGH -IN SIZE
<br />ITEM
<br />DESCRIPTION
<br />FIXTURE MANUFACTURER
<br />FITTING MANUFACTURER
<br />REMARKS
<br />AND MODEL NUMBER
<br />AND MODEL NUMBER
<br />CW
<br />HW
<br />SAN
<br />HWC
<br />WATER CLOSET (HANDICAP)
<br />ZURN Z5562
<br />ZURN Z5955SS-EL SEAT
<br />1/2"
<br />-
<br />4"
<br />1, 2, 4
<br />WC
<br />WATER CLOSET
<br />ZURN Z5572
<br />ZURN Z5955SS-EL SEAT
<br />1/2"
<br />-
<br />4"
<br />2,4
<br />LAV
<br />LAVATORY (WALL -HUNG)
<br />AMERICAN STANDARD COMRADE 0124
<br />ZURN Z7440-FC FAUCET
<br />1/2"
<br />1/2"
<br />1-1/4"
<br />1, 3, 4, 5, 6, 7
<br />REMARKS:
<br />1. ADA COMPLIANT.
<br />2. DUAL FLUSH (1.6/1.0 GPF), PRESSURE ASSISTED, TANK TYPE.
<br />3. FAUCET: ADA COMPLIANT, SINGLE LEVER HANDLE, 0.5 GPM VANDAL RESISTANT AERATOR.
<br />4. SUPPLIES: CHROME PLATED BRASS ANGLE TYPE SUPPLY KIT WITH WHEEL HANDLE & 12" RISER.
<br />5. P-TRAP: 17 GAUGE CHROME PLATED CAST BRASS, ADJUSTABLE, WITH CLEANOUT PLUG.
<br />6. DRAIN & SUPPLY COVERS: TRUEBRO LAV GUARD.
<br />7. PROVIDE WITH LAVATORY CARRIER.
<br />i"HW DOWN Y2"HW DOWN
<br />Yz"CW DOWN iz"CW DOWN
<br />�/z"CW
<br />f
<br />T� I _gip Iro
<br />LAV WCHWC LAV
<br />2 PLUMBING PLAN - WATER
<br />M1-1 1/4" = V-0"
<br />EXIST. 4"SS B/G
<br />(FIELD VERIFY)
<br />30*0"�PLUMBING PLAN - SANITARY
<br />M1-1 1/4" = V-0"
<br />FAN SCHEDULE
<br />ITEM
<br />TYPE
<br />SERVICE
<br />CFM
<br />ESP
<br />DRIVE
<br />RPM
<br />HP
<br />VOLT/0
<br />MANUFACTURER
<br />REMARKS
<br />IN WC
<br />TYPE
<br />AND MODEL NUMBER
<br />EF-1 & EF-2
<br />CEILING EXHAUST
<br />TOILET ROOM
<br />75
<br />0.250
<br />DIRECT
<br />700
<br />50W
<br />120/1
<br />GREENHECK SP-690
<br />1, 2, 3
<br />REMARKS:
<br />1. INTEGRAL BACKDRAFT DAMPER.
<br />2. INTEGRAL DISCONNECT.
<br />3. INTERLOCK FAN WITH TOILET ROOM LIGHT; SEE ELECTRICAL DRAWING.
<br />KEYED NOTES:
<br />OREMOVE AND DISPOSE OF THE EXISITNG WATER CLOSETS, LAVATORIES, AND
<br />ASSOCIATED PIPING & FITTINGS. CAP PIPING BELOW FLOOR AND ABOVE CEILING.
<br />0 REMOVE AND DISPOSE OF THE EXISITNG EXHAUST FANS; DUCTWORK SHALL REMAIN
<br />FOR USE WITH THE NEW FANS. LOCATE THE NEW EXHAUST FANS (EF-1 & EF-2)
<br />ABOVE THE NEW WATER CLOSETS, AND CONNECT THE 6"0 EXHAUST DUCTS TO
<br />EXISTING (ABOVE THE CEILING) - FIELD VERIFY LOCATION.
<br />OCONNECT NEW 1/2" HOT & COLD WATER LINES (ABOVE CEILING) TO EXISTING.
<br />FIELD VERIFY EXACT LOCATION PRIOR TO CONSTRUCTION.
<br />OCONNECT THE NEW 4"SS LINES TO EXISTING. FIELD VERIFY EXACT LOCATION PRIOR
<br />TO CONSTRUCTION.
<br />OCONNECT 3"V (ABOVE CEILING) TO EXISTING VENT STACK. FIELD VERIFY EXACT
<br />LOCATION.
<br />SPECIFICATIONS:
<br />GENERAL
<br />SCOPE: THE INTENT OF THE SPECIFICATIONS AND THE DRAWINGS IS TO PROVIDE
<br />COMPLETE AND FULLY OPERATIONAL SYSTEMS. FURNISH AND INSTALL ALL LABOR,
<br />MATERIAL AND EQUIPMENT NECESSARY TO COMPLETE THE WORK.
<br />SITE EXAMINATION: THOROUGHLY EXAMINE ALL AREAS WHERE EQUIPMENT, DUCTWORK
<br />AND PIPING WILL BE INSTALLED, AND REPORT ANY CONDITION THAT, IN THE
<br />CONTRACTOR'S OPINION, PREVENTS THE PROPER INSTALLATION OF THE WORK.
<br />STANDARDS: EQUIPMENT AND MATERIALS SHALL CONFORM WITH APPROPRIATE
<br />PROVISIONS OF ARL, ASME, ASTM, UL, ASHRAE, SMACNA, NEMA, ANSI, NFPA, AS
<br />APPLICABLE TO EACH INDIVIDUAL UNIT, ASSEMBLY OR SYSTEM.
<br />CODES: ALL WORK PERFORMED SHALL BE IN COMPLIANCE WITH THE FLORIDA BUILDING
<br />CODE AND ALL OTHER APPLICABLE LOCAL CODES AND ORDINANCES OF THE AUTHORITY
<br />HAVING JURISDICTION. IN CASE OF CONFLICT BETWEEN THE DRAWINGS/SPECIFICATIONS
<br />AND THE CODES AND ORDINANCES, THE HIGHEST STANDARD SHALL APPLY.
<br />PROVIDE ELECTRIC DISCONNECT SWITCHES FOR EACH PIECE OF POWERED EQUIPMENT IF
<br />NOT SHOWN TO BE PROVIDED ON THE ELECTRICAL DRAWINGS. FUSED OR NON -FUSED
<br />TYPE SHALL BE INSTALLED BASED UPON EQUIPMENT CHARACTERISTICS, MANUFACTURER'S
<br />RECOMMENDATIONS, AND THE ELECTRICAL DRAWINGS.
<br />SUBMITTALS: SUBMIT SHOP DRAWINGS AND PRODUCT DATA FOR ALL MATERIAL AND
<br />EQUIPMENT SPECIFIED AND SCHEDULED ON THE DRAWINGS. PURCHASING AND
<br />FABRICATION SHALL NOT OCCUR UNTIL SUBMITTALS HAVE BEEN REVIEWED. INCLUDE ALL
<br />REQUIRED PRODUCT & MATERIAL DATA.
<br />PERMITS AND FEES: CONTRACTOR(S) SHALL PROCURE AND PAY FOR ALL PERMITS, FEES
<br />AND INSPECTIONS NECESSARY TO COMPLETE THE WORK.
<br />WARRANTY: CONTRACTOR(S) SHALL UNCONDITIONALLY WARRANT ALL WORK TO BE FREE
<br />OF DEFECTS IN MATERIAL AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR FROM THE
<br />DATE OF FINAL ACCEPTANCE BY THE OWNER AND SHALL REPAIR OR REPLACE ANY
<br />DEFECTIVE WORK PROMPTLY AND WITHOUT CHARGE AND RESTORE ANY OTHER EXISTING
<br />WORK DAMAGED IN THE COURSE OF REPAIRING DEFECTIVE MATERIALS AND
<br />WORKMANSHIP.
<br />1I4 UM1.300,
<br />WATER PIPING ABOVE GROUND SHALL BE TYPE "L" HARD DRAWN COPPER TUBE PER ASTM
<br />B88, WITH SOLDER TYPE WROUGHT COPPER FITTINGS.
<br />WASTE & VENT PIPING ABOVE GROUND SHALL BE NO -HUB CAST IRON SOIL PIPE PER CISPI
<br />STANDARD 301, OR DWV COPPER TUBE PER ASTM B306.
<br />WASTE & VENT PIPING BELOW GROUND SHALL BE HUB -AND -SPIGOT CAST IRON SOIL PIPE
<br />AND FITTINGS PER ASTM A74. JOINTS SHALL HAVE RUBBER GASKETS CONFORMING TO
<br />ASTM C564.
<br />WASTE & VENT PIPING MAY BE SCHEDULE 40 PVC-DWV PIPE WITH SOLVENT WELD DWV
<br />FITTINGS PER ASTM D2665 & D1785, IF ACCEPTABLE TO THE LOCAL AUTHORITY HAVING
<br />JURISDICTION.
<br />FLOOR DRAIN: ZURN Z4156, POLISHED NICKEL BRONZE STRAINER, 1/2" TRAP PRIMER
<br />CONNECTION.
<br />FLOOR CLEANOUT: ZURN Z1400 ADJUSTABLE CLEANOUT, CAST IRON BODY, POLISHED
<br />BRONZE HEAVY DUTY TOP.
<br />0191"KNIT01111
<br />DUCTWORK SHALL BE RIGID SHEETMETAL CONSTRUCTED FROM GALVANIZED SHEET
<br />STEEL. DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH THE
<br />CURRENT SMACNA DUCT CONSTRUCTION STANDARDS. DUCTWORK SHALL BE ROUND OR
<br />RECTANGULAR, AS SHOWN ON THE PLAN. PROVIDE ALL REQUIRED TRANSITIONS,
<br />CONNECTIONS, AND OTHER ACCESSORIES NECESSARY FOR A COMPLETE OPERATING
<br />SYSTEM.
<br />DUCT SEALANT: SEAL ALL LONGITUDINAL AND TRANSVERSE JOINTS WITH A
<br />NON -HARDENING, NOWMIGRATING MASTIC OR LIQUID ELASTIC SEALANT OF A TYPE
<br />RECOMMENDED BY THE MANUFACTURER FOR SEALING JOINTS AND SEAMS IN SHEET
<br />METAL DUCTWORK. COVER ALL FIELD JOINTS AND FASTENING SCREWS WITH MASTIC.
<br />tJE1S
<br />Florida Certificate of Authorization #28010
<br />1349 West Peachtree Street, NE
<br />Atlanta, GA 30309
<br />Phone: (404) 873-3697
<br />Fax: (678)904-1510
<br />�a pAVt �•
<br />a -
<br />• • w
<br />• • w
<br />• • w
<br />S A► A OP
<br />' v►�,r
<br />•
<br />John David AddisonAL E
<br />Seal: PE #59239 Seal: •iq���
<br />Consultant:
<br />CBRE BANK OF AMERICA
<br />CEI RICHARD ELLIS
<br />BU* 0f 6700 Lakeview Center
<br />41WDrive
<br />Second Floor
<br />Client: Tampa, Florida 33619
<br />Permit Set _ 11 25 09
<br />Client Review__Set_ ____ 11 13 09
<br />Description: No: I By: Date:
<br />BANK OF AMERICA ADA REMEDIATION
<br />Zephyrhills Location
<br />5632 Gall Boulevard
<br />Zephyrhills, Florida 33539
<br />Project Title & Address:
<br />MECHANICAL / PLUMBING
<br />PLAN
<br />Sheet Title:
<br />Proj. No.
<br />09.00683.80
<br />Drawn By:
<br />_ JC
<br />M 1 _
<br />Checked By:
<br />MC
<br />SARAH ROLAND
<br />_
<br />LL DI AMENSIONS AND CONDITIONS MUST BE CHECKED AND VERIFIED ON
<br />SITE BY THE CONTRACTOR AND SUB -CONTRACTORS. THE PROJECT
<br />MANAGER SHALL BE NOTIFIED IN WRITING OF ANY DISCREPANCIES PRIOR
<br />TO PROCEEDING WITH THE WORK.
<br />© NELSON
<br />ALL RIGHTS RESERVED