SPLIT DX SCHEDULE (TYPICAL APARTMENT TYPE)
<br />AIR HANDLING UNIT NO.
<br />AHU-UNIT NUMBER
<br />AHU-UNIT NUMBER
<br />AHU-UNIT NUMBER
<br />LOCATION `UNIT TYPE'
<br />-
<br />R/A SUITE APARTMENT
<br />1-BEDROOM APARTMENT
<br />2-BEDROOM APARTMENT
<br />TOTAL COOLING CAPACITY
<br />BTUH
<br />7,800
<br />17,500
<br />28,400
<br />SENSIBLE COOLING CAPACITY
<br />BTUH
<br />6,400
<br />14,000
<br />19,200
<br />TOTAL SUPPLY AIR
<br />CFM
<br />280
<br />615
<br />900
<br />OUTSIDE AIR
<br />CFM
<br />20 CFM (NOTE 8)
<br />40 CFM (NOTE 8)
<br />60 CFM (NOTE 8)
<br />COOLING COIL ENTERING AIR (DB/WB)
<br />'F
<br />76.0/63.5
<br />76.0/63.5
<br />76.0/63.5
<br />COOLING COIL LEAVING AIR (DB/WB)
<br />-F
<br />55.0/55.0
<br />55.0/55.0
<br />55.0/55.0
<br />STATIC PRESSURE (EXT)
<br />IN. WG
<br />0.5
<br />0.5
<br />0.5
<br />FILTERS
<br />-
<br />2- MERV 11 (THROWAWAY)
<br />2- MERV 11 (THROWAWAY)
<br />2- MERV 11 (THROWAWAY)
<br />FAN MOTOR
<br />HP
<br />-
<br />1/5
<br />1/3
<br />ELECTRIC HEATER/STAGES
<br />KW/STAG
<br />3.0/1
<br />5.0/1
<br />5.0/1
<br />UNIT MCA/MOP
<br />AMPS
<br />NOTE 8
<br />23.0 / 25
<br />23.6 / 25
<br />ELECTRICAL
<br />V/0/Hz
<br />208/1/60
<br />208/1/60
<br />208/1/60
<br />MANUFACTURER
<br />-
<br />DAIKIN
<br />GOODMAN
<br />GOODMAN
<br />MODEL NO.
<br />-
<br />FDMQ09RVJU
<br />AWUT240514
<br />AWUT300514
<br />NOTES
<br />-
<br />1,2,3,4,5,6,7,8
<br />1,2,3,4,5,6,7,8
<br />1,2,3,4,5,6,7,8
<br />HEAT PUMP UNIT NO.
<br />CU-UNIT NUMBER
<br />CU-UNIT NUMBER
<br />CU-UNIT NUMBER
<br />OUTDOOR TEMPERATURE
<br />•F
<br />95
<br />95
<br />95
<br />ELECTRICAL
<br />V/O/Hz
<br />208/1/60
<br />208/1/60
<br />208/1/60
<br />UNIT MCA/MOP
<br />AMPS
<br />9 / 15
<br />21.9 / 30
<br />23.2 / 35
<br />ARI SEER/EER RATING
<br />-
<br />14.0/11.0
<br />14.0/12.0
<br />14.0/12.0
<br />MANUFACTURER
<br />-
<br />DAIKIN
<br />GOODMAN
<br />GOODMAN
<br />MODEL NUMBER
<br />-
<br />RX09RMVJU9
<br />GPH1424H41
<br />GPH143OH41
<br />NOTES
<br />-
<br />1,2,3,4,5,6,7,8
<br />1,2,3,4,5,6,7
<br />1,2,3,4,5,6,7
<br />NOTES:
<br />1. PROVIDE FACTORY MOUNTED STARTER, DISCONNECT BY DIVISION 16.
<br />2. PROVIDE THERMAL OVERLOAD PROTECTION.
<br />3. PROVIDE SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED STARTER AND MAGNETIC CONTACTOR FOR HEAT.
<br />4. PROVIDE LONG LINE SET FOR REFRIGERANT PIPING WHEN REQUIRED.
<br />5. PROVIDE LIQUID LINE SPECIALTIES INCLUDING FILTER DRIER, SIGHT GLASS TXV, SOLENOID VALVE, 24V 1 ph CONTROL WIRE BY CONTROLS CONTRACTOR.
<br />6. PROVIDE REFRIGERANT PIPING SIZED AS PER MANUFACTURER'S RECOMMENDATIONS. -ACR- COPPER ONLY.
<br />7. OUTSIDE AIR PROVIDED DUCTED DIRECTLY TO EACH APARTMENT AIR HANDLER PER CODE.
<br />8. UNIT POWER SHALL BE FEED TO CONDENSING UNIT AND THEN ROUTED INTERIOR TO THE AIR HANDLER MOUNTED IN THE CLOSET
<br />SPLIT DX SCHEDULE (1ST FLOOR AMENITY AREA)
<br />AIR HANDLING UNIT, NO.
<br />AHU-1
<br />AHU-2
<br />MU-3
<br />LOCATION 'UNIT TYPE'
<br />-
<br />FLEX ROOM 114
<br />ACTIVITY ROOM 115
<br />LOUNGE 118
<br />TOTAL COOLING CAPACITY
<br />BTUH
<br />19,800
<br />23,800
<br />89,200
<br />SENSIBLE COOLING CAPACITY
<br />BTUH
<br />12,200
<br />14,100
<br />57,300
<br />TOTAL SUPPLY AIR
<br />CFM
<br />480
<br />540
<br />2,265
<br />OUTSIDE AIR -
<br />CFM
<br />100
<br />130
<br />440
<br />COOLING COIL ENTERING AIR (DB/WB)
<br />-F
<br />79.6/66.3
<br />80.2/66.6
<br />79.4/66.0
<br />COOLING COIL LEAVING AIR (DB/WB)
<br />-F
<br />56.0/55.0
<br />56.0/55.0
<br />56.0/55.0
<br />STATIC PRESSURE (EXT)
<br />IN. WG
<br />0.5
<br />0.5
<br />0.5
<br />FILTERS
<br />-
<br />2' MERV 11 (THROWAWAY)
<br />2- MERV 11 (THROWAWAY)
<br />2- MERV 11 (THROWAWAY)
<br />FAN MOTOR
<br />HP
<br />3/4
<br />3/4
<br />2.0
<br />ELECTRIC HEATER/STAGES
<br />KW/STAGE
<br />4.5 / 1
<br />6.0 / 1
<br />20 / 2
<br />UNIT MCA/MOP
<br />AMPS
<br />27.0 / 30
<br />32.0 / 35
<br />59.6 / 60
<br />ELECTRICAL
<br />V/O/Hz
<br />208/1/60
<br />208/1/60
<br />208/1/60
<br />MANUFACTURER
<br />-
<br />GOODMAN
<br />GOODMAN
<br />DARIN
<br />MODEL NO.
<br />-
<br />AEPT33C14
<br />AEPT33C14
<br />DAT09043A
<br />NOTES
<br />-
<br />1,2,3,4,5,6,7
<br />1,2,3,4,5,6,7
<br />1,2,3,4,5,6,7
<br />HEAT PUMP UNIT NO.
<br />CU-1
<br />CU-2
<br />CU-3
<br />OUTDOOR TEMPERATURE
<br />-F
<br />95
<br />95
<br />95
<br />ELECTRICAL
<br />V/O/Hz
<br />208/1/60
<br />208/1/60
<br />208/1/60
<br />UNIT MCA/MOP
<br />AMPS
<br />14.6 / 25
<br />14.6 / 25
<br />39.2 / 60
<br />ARI SEER/EER RATING
<br />-
<br />14.0
<br />14.0
<br />14.0
<br />MANUFACTURER
<br />-
<br />GOODMAN
<br />GOODMAN
<br />DAIKIN
<br />MODEL NUMBER
<br />-
<br />GSZ140241
<br />GSZ140241
<br />DZ11TA0903M
<br />NOTES
<br />-
<br />1,2,3,4,5,6,7
<br />1,2,3,4,5,6,7
<br />1,2,3,4,5,6,7
<br />NOTES:
<br />1. PROVIDE FACTORY MOUNTED STARTER, DISCONNECT BY DIVISION 16.
<br />2. PROVIDE THERMAL OVERLOAD PROTECTION.
<br />3. PROVIDE SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED STARTER AND MAGNETIC CONTACTOR FOR HEAT.
<br />4. PROVIDE LONG LINE SET FOR REFRIGERANT PIPING WHEN REQUIRED.
<br />5. PROVIDE UNIT WITH INTERNAL SPRING ISOLATION.
<br />0 VALVE, 24V 1 h CONTROL WIRE BY CONTROLS CONTRACTOR.
<br />6. PROVIDE LIQUID LINE SPECIALTIES .INCLUDING FILTER DRIER, SIGHT GLASS TXV, SOLENOID VE, p
<br />7. PROVIDE REFRIGERANT PIPING SIZED AS PER MANUFACTURER'S RECOMMENDATIONS. -ACR- COPPER ONLY.
<br />SPLIT DX AIR HANDLING UNIT BREAKOUT
<br />(PER TYPICAL APARTMENT TYPE)
<br />1ST
<br />2ND
<br />3RD
<br />FLOOR
<br />FLOOR
<br />FLOOR.
<br />APARTMENT
<br />(R/A SUITE)
<br />117
<br />208
<br />308
<br />APARTMENT
<br />(1-BEDROOM)
<br />102
<br />202
<br />2
<br />210
<br />302
<br />3
<br />310
<br />APARTMENT
<br />(2-BEDROOM)
<br />103
<br />121
<br />203
<br />204
<br />209
<br />303
<br />304
<br />306
<br />309
<br />122
<br />211
<br />311
<br />123
<br />212
<br />213
<br />312
<br />313
<br />AIR DEVICE SCHEDULE
<br />MARK
<br />TYPE
<br />MATERIAL
<br />FINISH
<br />ACCESSORIES
<br />MANUFACTURER
<br />MODEL
<br />NOTES
<br />A
<br />CEILING SUPPLY
<br />ALUMINUM
<br />WHITE
<br />O.B.D.
<br />TITUS
<br />TMS-AA
<br />1 2 3
<br />4
<br />B
<br />CEILING RETURN EXHAUST
<br />ALUMINUM
<br />WHITE
<br />-
<br />TITUS
<br />PAR -AA
<br />1 2 3
<br />4
<br />C
<br />EA OA LOUVER
<br />ALUMINUM
<br />ALUMINUM
<br />-
<br />RUSKIN
<br />ELF6375DXD
<br />(2)(4)
<br />D
<br />SIDEWALL SUPPLY GRILLE
<br />ALUMINUM
<br />WHITE
<br />O.B.D.
<br />TITUS
<br />272 FS
<br />(1)(2) 3
<br />4
<br />E
<br />TRANSFER AIR
<br />ALUMINUM
<br />WHITE
<br />-
<br />TINS
<br />4F
<br />1 (2)(3 5
<br />F
<br />TRANSFER AIR
<br />ALUMINUM
<br />WHITE
<br />-
<br />TINS
<br />4F
<br />1 2 3
<br />6
<br />NOTES:
<br />1. COORDINATE WITH LIGHTS FOR EXACT LOCATIONS OF ALL DIFFUSERS, GRILLES AND REGISTERS.
<br />2. COORDINATE FRAME STYLES WITH CEILING OR WALL SYSTEM.
<br />3. N.C. VALUES FOR DIFFUSERS, GRILLES AND REGISTERS SHALL NOT EXCEED 25, WITH A ROOM
<br />ABSORPTION RATE OF
<br />1ODB I.E. 10-12 WATTS.
<br />4. FINAL COLOR SELECTION AS DIRECTED BY ARCHITECT. MUST HAVE ARCHITECTS APPROVAL PRIOR TO ORDERING.
<br />5. TRANSFER GRILLE MTD. 2-t BELOW CEILING.
<br />6. TRANSFER GRILLE MTD. 4-f ABOVE FINISHED FLOOR.
<br />EXHAUST FAN SCHEDULE
<br />MARK
<br />-
<br />EF-1
<br />EF-2
<br />EF-3
<br />EF-4
<br />EF-APRTMNT
<br />EF-APRTMNT I
<br />EF-APRTMNT # (A/B)
<br />LOCATION
<br />-
<br />CUSTODIAL 105
<br />RESTROOM 107
<br />RESTROOM 108
<br />RESTROOM 109
<br />R/A SUITE
<br />1-BEDROOM
<br />2-BEDROOM
<br />SERVICE
<br />-
<br />GENERAL
<br />RESTROOM
<br />RESTROOM
<br />RESTROOM
<br />BATHROOM
<br />BATHROOM
<br />BATHROOM
<br />TOTAL AIR
<br />CFM
<br />100
<br />70
<br />70
<br />70
<br />50
<br />50
<br />50
<br />TYPE
<br />-
<br />CEILING
<br />COUNG
<br />CEILING
<br />CEILING
<br />CEILING
<br />CEILING
<br />CEILING
<br />EXT. STATIC PRESS.
<br />IN H2O
<br />0.3
<br />0.25
<br />0.25
<br />0.25
<br />0.25
<br />0.25
<br />0.25
<br />MAX RPM
<br />-
<br />718
<br />688
<br />688
<br />688
<br />652
<br />652
<br />652
<br />HP
<br />-
<br />128 WATTS
<br />20 WATTS
<br />20 WATTS
<br />20 WATTS
<br />15 WATTS
<br />15 WATTS
<br />15 WATTS
<br />SONES
<br />-
<br />1.6
<br />1.8
<br />1.8
<br />1.8
<br />1.4
<br />1.4
<br />1.4
<br />DRIVE TYPE
<br />-
<br />DIRECT
<br />DIRECT
<br />DIRECT
<br />DIRECT
<br />DIRECT
<br />DIRECT
<br />DIRECT
<br />ELECTRICAL
<br />V/0/Hz
<br />120-1-60
<br />120-1-60
<br />120-1-60
<br />120-1-60
<br />120-1-60
<br />120-1-60
<br />120-1-60
<br />MANUFACTURER
<br />-
<br />GREENHECK
<br />GREENHECK
<br />GREENHECK
<br />GREENHECK
<br />GREENHECK
<br />GREENHECK
<br />GREENHECK
<br />MODEL
<br />-
<br />SP-B150
<br />SP-B90
<br />SP-1390
<br />SP-1390
<br />SP-B70
<br />SP-B70
<br />SP-1370
<br />NOTES
<br />-
<br />1,2,3,4
<br />1,2,3,4
<br />1,2,3,4
<br />1,2,3,4
<br />1,2,3,4
<br />1,2,3,4
<br />1,2,3,4
<br />NOTES:
<br />1. PROVIDE VARIABLE SPEED CONTROLLER FOR ALL DIRECT DRIVE FANS. T do B CONTRACTOR SHALL MARK BALANCED POSITION ON CONTROLLER.
<br />2. FAN SHALL BE INTERLOCKED WITH LIGHT SWITCH. SEE ELECTRICAL DRAWINGS FOR INTERCONNECTION.
<br />3. PROVIDE FACTORY WIRED DISCONNECT SWITCH.
<br />4. PROVIDE THERMAL OVERLOAD PROTECTION.
<br />CORRIDOR ROOFTOP UNIT SCHEDULE
<br />MARK
<br />-
<br />RTU-1
<br />COOLING CAPACITY
<br />MBH
<br />34,179
<br />SENSIBLE COOLING CAPACITY
<br />MBH
<br />24,915
<br />ENTERING AIR TEMPERATURE
<br />DB'F/WB'F
<br />79.2/65.9
<br />LEAVING AIR TEMPERATURE
<br />DI T/YYB'F
<br />56.6/55.2
<br />SUPPLY AIR
<br />CFM
<br />970
<br />OUTSIDE AIR
<br />CFM
<br />180
<br />STATIC PRESSURE (EXTERNAL)
<br />IN. WG
<br />0.5
<br />FAN MOTOR
<br />HP
<br />0.5
<br />HEATING CAPACITY
<br />BTUH
<br />34,130
<br />ELECTRIC HEATER
<br />KW
<br />10
<br />STEPS OF CAPACITY
<br />-
<br />1
<br />NUMBER OF COMPRESSORS
<br />-
<br />1
<br />FILTERS
<br />-
<br />2' MERV 11 (14-x20-X2' - QTY OF 4)
<br />ELECTRICAL
<br />V/b/Hz
<br />208/1/60
<br />EER (COOLING)
<br />-
<br />14.0
<br />IEER (COOLING)
<br />-
<br />11.5
<br />MCA/MOCP
<br />-
<br />72.6 / 80
<br />WEIGHT
<br />LBS.
<br />741
<br />LOCATION
<br />-
<br />ROOF
<br />MANUFACTURER
<br />-
<br />DAIKIN
<br />MODEL
<br />-
<br />DBH MODEL 036
<br />NOTES
<br />-
<br />1,2,3,4.5
<br />NOTES:
<br />1. PROVIDE THERMAL. OVERLOAD PROTECTION.
<br />2. PROVIDE SLOPED STAINLESS STEEL DRAIN PANS.
<br />3. PROVIDE SINGLE POINT POWER CONNECTION WITH FACTORY MOUNTED STARTER. SEE ELECTRICAL DRAWINGS FOR
<br />OTHER REQUIREMENTS.
<br />4. PROVIDE UNIT WITH SINGLE POINT POWER WITH INTERNAL ELECTRIC HEATER.
<br />5. PROVIDE MANUFACTURER PROVIDED 14- DEEP ROOF CURB, MOTORIZED FRESH AIR DAMPER AND HAIL GUARDS.
<br />Furr,
<br />Wegman &
<br />Banks
<br />Architects, P.A. AR0006480
<br />625 EAST ORANGE ST.
<br />LAKELAND, FL 33801
<br />E-MAIL: INFOQFWBARCHITECTS.COM
<br />W W W.FWBARCHITECTS.COM
<br />PH. 863.688.1211
<br />® COPYRIGHr 2021
<br />FURR, WEGMAN & BANKS ARCHITECTS, PA
<br />THE DESIGN AND CONCEPTS DEPICTED HEREWITH ARE THE SOLE
<br />PROPERTY OF R1RR, WEGMAN & BANKS ARCHITECTS. PA.
<br />NO REPRODUCTION. REVISION OR REUSE OF THISDRAWING IS
<br />AUTHORED WITHOUT SPECIFIC WRITTEN PERMISSION.
<br />ALL RIGHTS RESERVED.
<br />B ERr
<br />\.���0� • C E NSF•
<br />- No.86539
<br />STATE OF
<br />Gn
<br />Sfl�l�,\P.E.
<br />ScOl/
<br />P53
<br />FL. UC. 8t'�P.�+02�-28-2023
<br />=o
<br />V \
<br />w ,Z,,
<br />0 o
<br />0�
<br />S N "
<br />Ram� IL
<br />s
<br />my=j�MMhci
<br />m
<br />_s
<br />..,,, aca
<br />IL Z
<br />CL
<br />z
<br />z
<br />O
<br />W
<br />w
<br />I-
<br />z
<br />O
<br />H
<br />o_
<br />U
<br />U)
<br />W
<br />0
<br />z
<br />O
<br />w
<br />w
<br />H
<br />a
<br />0
<br />aN
<br />C)
<br />In
<br />CO
<br />n
<br />N
<br />O
<br />N
<br />ti
<br />N
<br />co
<br />O
<br />L LI
<br />Q
<br />rn
<br />Z
<br />(n
<br />W
<br />W
<br />J
<br />D
<br />O
<br />0
<br />Z
<br />0
<br />w
<br />Up
<br />o
<br />=
<br />U
<br />_j
<br />J
<br />W
<br />m
<br />0
<br />Q
<br />Z F-
<br />Z
<br />U
<br />-Z
<br />o
<br />D
<br />Z
<br />aLL
<br />0,
<br />o
<br />o I
<br />U
<br />m Q 2�
<br />w
<br />rna
<br />Q ifo N
<br />=
<br />0-
<br />PROJ MGR:
<br />CKD BY:
<br />MC/DB
<br />SN
<br />JOB NUMBER:
<br />21-19
<br />SHEET NUMBER:
<br />M30 1
<br />Z:\Furr Wegman & Banks Architects\211036 - Healthier Stay Pasco Dormitory\Desgn\211036 M301 - Schedules.dwg, August 27, 2021 4:06 PM, SHAWN JEFFREY,
<br />
|