SHALLOW FOUNDATION AND SLAB ON GRADE NOTES: <br />SF1. Design Soil Bearing Pressure: <br />Spread Footings: [4000 psf] <br />SF2. Soil to be stripped, compacted and tested in accordance with the <br />recommendations of the soils engineer and project specifications. <br />SF3. Footings shall be placed on firm, undisturbed soil or engineered fill. <br />Engineered Fill: Naturally or artificially graded mixture of natural or <br />crushed gravel, crushed stone, and natural or crushed sand; ASTM D 2940; <br />with at least 90% passing a 1-1/2-inch sieve and not more than 12% passing a <br />No. 200 sieve. <br />SF4. Slabs shall be placed on compacted, free -draining, frost -free drainage <br />course. Drainage Course: Narrowly graded mixture of washed crushed stone, <br />or crushed or uncrushed gravel; ASTM D 448; coarse -aggregate grading Size 57; <br />with 100% passing a 1-1/2-inch sieve and 0% to 5% passing a No. 8 sieve. <br />All fill shall be compacted to a minimum dry density of 95% of the modified <br />Proctor maximum dry density (ASTM-D1557), placed in 6" to 8" lifts. Pea <br />gravel may not be used as fill. Utility trenches and excavations under the <br />foundations or slabs shall meet the same requirements. See soils <br />investigation report for further recommendations. <br />SF5. Undercutting of the soil for foundation and/or slab placement may be <br />req.'d. These drawings do not indicate the entire scope of undercutting, <br />fill or bad soil removal that may be required to attain the design soil <br />bearing pressures. It is the responsibility of the contractor to obtain a <br />soils investigation report, before bidding, to assess the extent of <br />excavation and compaction that may be required to meet the design criteria. <br />The contractor shall retain the services of a soils engineer to monitor all <br />backfilling operations and to inspect footing bearing material. A report <br />certified by the soils engineer shall be furnished to the architect/engineer <br />verifying that all foundations were placed on a material capable of <br />sustaining the design bearing pressures. <br />SF6. If dewatering is req.'d, sumps shall not be placed within foundation <br />excavation. <br />SF7. Maintain a maximum slope between adjacent footing bearing elevations of <br />2 horizontal to 1 vertical. Maintain a 2:1 slope next to existing <br />foundations to avoid undermining foundations. <br />SF8. No horizontal joints permitted in any foundation. Vertical joints <br />permitted only in wall footings. <br />SF9. Shallow foundations may be earth -formed where the excavation permits. <br />If earth -forming is used, add 2" to the width and length of all foundations. <br />SF10. The bottom of all foundations shall be a minimum of 24" below final <br />grade. <br />REINFORCED CONCRETE NOTES: <br />RC1. All concrete shall have the following 28 day compressive strengths: <br />LOCATION STRENGTH AIR ENTRAINMENT <br />Wall Footings, Spread Footings: [4000psi] [6%] <br />IF APPLICABLE <br />All concrete below frost line, exterior [3000 psi] [6%] <br />slabs, piers, walls, columns, grade beams, <br />concrete exposed to freeze/thaw: <br />Interior slabs on grade: <br />[3000 psi] [Non AE] <br />RC2. All reinforcing steel shall be detailed, supplied and placed in <br />accordance with ACI 315-99, ACI 318-99 and CRSI MSP-1-01. <br />RC3. All reinforcing steel shall be shop fabricated and, where applicable, <br />shall be wired together and conform to ASTM A-615, Grade 60. <br />RC4. Chamfer edges of exposed concrete 3/411, unless noted otherwise. <br />RC5. Contractor shall make four, 6"x12" test cylinders for each 50 cubic <br />yards of concrete poured for each days operation. Break 1 at 7 days, 2 at 28 <br />days and retain spare. <br />RC6. All welded wire fabric shall conform to ASTM A185, Fy(MIN.of 65 ksi. <br />All welded wire fabric laps shall be 8". <br />RC7. All finished concrete, concrete formwork and falsework shall be in <br />accordance with ACI 301-99. Contractor is solely responsible for the design <br />and construction of all formwork, falsework and shoring. <br />RC8. Provide the following coverage's over reinforcing: <br />Footings: <br />Bottom and Unformed edges [31 <br />Formed edges and top [2"] <br />Slab on grade: <br />Welded wire fabric [Upper Third] <br />Reinforcing Steel [21 <br />GENERAL NOTES: <br />G1. BUILDING CODES: <br />Model: Florida Building Codes 2004 <br />Local: Manatee County Building and Planning Department <br />Light Gauge Steel: Specifications for cold formed steel design Manual by <br />American Iron Steel Institute. <br />G2. DESIGN LOADS: <br />G2.1 Roof <br />Dead Load: <br />10 <br />pdf <br />Live Load: <br />20 <br />psf <br />G2.2 Mezzanine <br />Dead Load: <br />54 <br />pdf <br />Live Load: <br />125 <br />psf <br />SNOW - N/A <br />Mechanical Mezzanine <br />Dead Load: <br />Live Load: <br />Thermal Fact <br />WIND by Florida Building Code 2004 + 2006 Supplement <br />Basic Wind Speed: 130 mph <br />Wind Importance Factor: 1 <br />Wind Exposure Category: C <br />SEISMIC - N/A <br />G3. Reactions and forces indicated are Allowable Stress Design Service loads. <br />G4. If Drawings and specifications are in conflict, the most stringent <br />restrictions and requirements shall govern. Contractor shall bring all <br />discrepancies to the attention of the engineer and architect immediately. <br />G5. Verify all existing conditions prior to any construction or fabrication. <br />If different than shown, notify engineer/architect immediately for <br />modification of drawings. <br />G6. All contractors are required to coordinate their work with all <br />disciplines to avoid conflicts. The architectural, mechanical, electrical <br />and plumbing aspects are not in the scope of these drawings. Therefore, all <br />required materials and work may not be indicated. It is the contractor's <br />responsibility to coordinate these drawings with all other construction <br />documents. Refer to architectural drawings for all dimensions not shown on <br />these drawings. Locations, sizes and numbers of all openings may not be <br />completely indicated in the structural drawings, the respective contractor <br />shall field verify their work with all other disciplines. <br />G7. The contract documents represent the structure only. They do not <br />indicate the method of construction. The contractor shall provide all <br />measures necessary to protect the structure during construction. Such <br />measures shall include, but not limited to, bracing, shoring, underpinning, <br />etc.. Engineer is not responsible for the contractor's means, methods, <br />techniques, sequences or safety procedures during construction. <br />G8. Notes and details shall take precedence over general structural notes. <br />Where no details or sections are shown, construction shall conform to <br />similar work on the project. Typical sections and details may not be cut on <br />the plans, but apply unless noted otherwise. <br />G9. Provisions for future expansion: <br />Vertical: None <br />Horizontal:None <br />MASONRY AND REINFORCED MASONRY NOTES: <br />M1. Minimum 28 day compressive strength of concrete masonry units shall be <br />3000 p.s.i. based on net area of the unit. Specified design compressive <br />strength of masonry shall be f'm = 3000 p.s.i. All units for exterior walls <br />shall be normal weight block. <br />M2. All mortar shall be Type S. No admixtures may be used unless approved by <br />architect/engineer. Mortar shall not be used for grouting cores or filling <br />bond beams. <br />M3. All block shall be layed in a running bond pattern. <br />M4. Course grout shall be used were grouting is required. Slump shall be <br />8"-11". Minimum grout compressive strength shall be 3000 p.s.i. <br />M5. All reinforcing shall be ASTM A615 Grade 60 (Fy=60 ksi). Lap all <br />reinforcing a minimum of 48 bar diameters. <br />M6. See architectural and specifications for all control joint locations. <br />Reinforcing in bond beams shall be discontinuous at control joints. <br />M7. Provide ladder type horizontal joint reinforcement at 16" o.c. Side rods <br />and cross rods shall be #9 wire, galvanized, see specifications. Cut joint <br />reinforcement at control joints. <br />M8. Provide "L" bars at all bond beam corners as required. <br />M9. Fill cores of block solid with grout two full courses below the bearing <br />of all beams or lintels supported on masonry. <br />M10. See typical schedules for masonry and precast concrete lintels not <br />indicated on plans. <br />M11. All masonry units below grade to be grouted solid. <br />M12. All cores with reinforcing steel shall be grouted solid, full height of <br />wall. <br />SPECIFICATION FOR COLD -FORMED METAL: <br />PRODUCTS <br />METAL STUDS, JOIST AND ACCESSORIES. <br />A. ALL PRODUCTS TO BE MANUFACTURED BY THE CURRENT MEMBERS OF THE STEEL STUD MANUFACTURERS ASSOCIATION. <br />B. ALL GALVANIZED STUDS AND JOISTS SHALL BE FORMED FROM STEEL THAT CORRESPONDS TO THE MINIMUM REQUIREMENTS <br />OF 1996 A.I.S.I. STANDARDS. Fr-50 KSI. <br />C. ALL STRUCTURAL MEMBERS SHALL BE DESIGNED IN ACCORDANCE WITH THE AMERICAN IRON AND STEEL INSTITUTE (AISI) <br />"SPECIFICATION FOR THE DESIGN OF COLD -FORMED STEEL STRUCTURAL MEMBERS" 1996 EDITION. <br />D. PROVIDE ALL ACCESSORIES INCLUDING, BUT NOT LIMITED TO, TRACKS, CLIPS WEB STIFFENERS, ANCHORS, FASTENING, <br />DEVICES, RESILIENT CLIPS AND OTHERS ACCESSORIES REQUIRED FOR A COMPLETE AND PROPER INSTALLATION, AND AS <br />RECOMMENDED BY THE MANUFACTURER FOR THE STEEL MEMBER USED. <br />E. FASTENING OF COMPONENTS SHALL BE WITH SELF -DRILLING SCREWS OR WELDING. SCREWS OR WELDS SHALL BE OF <br />SUFFICIENT SIZE TO INSURE THE STRENGTH OF THE CONNECTION. ALL WELDS OF GALVANIZED STEEL SHALL BE TOUCHED UP <br />WITH A ZINC -RICH PAINT. ALL WELDS OF CARBON SHEET STEEL SHALL BE TOUCHED UP WITH PAINT. WIRE TYING OF <br />COMPONENTS SHALL NOT BE PERMITTED. <br />EXECUTION <br />FABRICATION AND INSTALLATION. <br />A. PRIOR TO FABRICATION OF FRAMING, THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO THE ARCHITECT OR ENGINEER <br />TO OBTAIN APPROVAL. <br />&FRAMING COMPONENTS MAY BE PREASSEMBLED INTO PANELS PRIOR TO ERECTING. PREFABRICATED PANELS SHALL BE <br />SQUARE, WITH COMPONENTS ATTACHED IN A MANNER TO PREVENT RACKING AND TO MINIMIZE DISTORTION WHILE LIFTING AND <br />TRANSPORTING. <br />C. ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO PERPENDICULAR MEMBERS OR AS REQUIRED <br />FOR AN ANGULAR FIT AGAINST ABUTTING MEMBER. <br />D. STUDS SHALL BE PLUMBED, ALIGNED AND SECURELY ATTACHED TO FLANGES OF BOTH UPPER AND LOWER RUNNERS, <br />EXCEPT THAT IN THE CASE OF INTERIOR, NON -LOAD BEARING WALLS, STUDS NEED NOT BE ATTACHED TO UPPER OR LOWER <br />RUNNERS. <br />E. IN ALL DOUBLED JAMB STUDS AND DOUBLED HEADERS NOT ACCESSIBLE TO INSULATION CONTRACTORS, INSULATION EQUAL <br />TO THAT SPECIFIED ELSEWHERE SHALL BE PROVIDES. <br />F. SPLICES IN AXIAL LOAD BEARING MEMBERS OTHER THEN TRACK SHALL NOT BE PERMITTED. <br />G. TEMPORARY BRACING WHERE REQUIRED, SHALL BE PROVIDED UNTIL ERECTION IS COMPLETE. <br />INSTALLATION (NON -LOAD BEARING WALLS) <br />A. TRACKS SHOULD BE SECURELY ANCHORED TO THE SUPPORTING STRUCTURE AS SHOWN ON THE DRAWINGS. <br />B. COMPLETE, UNIFORM AND LEVEL BEARING SUPPORT SHALL BE PROVIDED FOR THE BOTTOM TRACK. <br />C. FRAMING OF WALL OPENINGS SHALL INCLUDE HEADERS AND SUPPORTING STUDS AS SHOWN ON THE DRAWINGS. <br />D. DIAGONALLY BRACED STUD WALLS, AS INDICATED ON THE DRAWINGS, SHALL BE PROVIDED AT LOCATIONS DESIGNATED AS <br />"SHEAR WALLS" FOR FRAME STABILITY AND LATERAL LOAD RESISTANCE. ADDITIONAL STUDS, WHEN NECESSARY, SHALL BE <br />POSITIONED AS INDICATED ON THE DRAWINGS TO RESIST THE VERTICAL COMPONENTS. <br />E. SPLICES IN AXIALLY LOADED STUDS SHALL NOT BE PERMITTED. <br />INSTALLATION (JOISTS) <br />A. JOISTS SHALL BE LOCATED DIRECTLY OVER BEARING STUDS OR A LOAD DISTRIBUTION MEMBER SHALL BE PROVIDED AT THE <br />TOP OF THE BEARING WALL. <br />B. WEB STIFFENERS SHALL BE PROVIDED AT REACTION POINTS AND/OR POINTS OF CONCENTRATED LOADS WHERE INDICATED <br />ON THE DRAWINGS. <br />C. JOIST BRIDGING SHALL BE PROVIDED WHERE INDICATED ON THE DRAWINGS. <br />D. ADDITIONAL JOIST SHALL BE PROVIDED UNDER PARALLEL PARTITIONS WHEN THE PARTITION LENGTH EXCEEDS ONE-HALF <br />THE JOIST SPAN, ALSO AROUND ALL FLOOR AND ROOF OPENINGS, WHICH INTERRUPT ONE OR MORE SPANNING MEMBERS <br />UNLESS OTHERWISE NOTED. <br />E. END BLOCKING SHALL BE PROVIDED WHERE JOIST ENDS ARE NOT OTHERWISE RESTRAINED FROM ROTATION. <br />1. THESE DRAWINGS ARE FOR SCHEMATIC DESIGN ONLY. IT IS UP TO EACH INDIVIDUAL DESIGNER TO SPECIFY AND ENGINEER THESE SYSTEMS <br />FOR SITE SPECIFIC LOCATIONS. <br />2. ALL WORK SHALL COMPLY WITH ALL LOCAL AND STATE CODES AND AUTHORITIES HAVING JURISDICTION. <br />3. PLUMBING CONTRACTOR SHALL SECURE AND PAY FOR ALL REQUIRED PERMITS AND ARRANGE ALL REQUIRED INSPECTIONS. <br />4. ALL CONTRACTORS SHALL EXAMINE THE SITE AND REVIEW THE DRAWINGS AND SPECIFICATIONS PRIOR TO SUBMITTING A PROPOSAL. <br />5. CONTRACTOR SHALL VERIFY DEPTH, SIZE, LOCATION OF ALL EXISTING UTILITIES IN FIELD PRIOR TO STARTING WORK. <br />6. PLUMBING CONTRACTOR SHALL COORDINATE HIS / HER WORK WITH OTHER CONTRACTORS IN ESTABLISHING PIPE RUNS <br />AND SPACE CONDITIONS. <br />7. ALL PIPING TO BE CONCEALED IN HUNG CEILINGS, CHASES AND FURRED SPACES. <br />8. THE DRAWINGS AS PREPARED ARE DIAGRAMMATIC BUT SHALL BE FOLLOWED AS CLOSELY AS CONSTRUCTION OF THE PROJECT AND THE WORK OF <br />THE TRADES WILL PERMIT. EQUIPMENT LOCATIONS INDICATED ARE APPROXIMATE. COORDINATE EXACT LOCATIONS AND REQUIRED CLEARANCES <br />WITH EQUIPMENT SUPPLIER AND ALL TRADES PRIOR TO INSTALLATION. <br />9. REFER TO EQUIPMENT SCHEDULE AND EQUIPMENT SPECIFICATIONS FOR EXACT LOCATIONS OF PLUMBING CONNECTIONS. <br />10. ALL KITCHEN, PREP AREA AND SALES AREA EQUIPMENT WILL BE FURNISHED AND INSTALLED. EQUIPMENT WILL BE FURNISHED WITH TRIM, <br />FAUCETS, ESCUTCHEONS, ETC. PLUMBING CONTRACTOR SHALL PROVIDE ALL ROUGH -IN TRAPS AND MAKE ALL FINAL CONNECTIONS (SEE <br />EQUIPMENT SCHEDULE). <br />11. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL ALL GAS PIPING AND MAKE ALL FINAL CONNECTIONS. <br />12. THIS CONTRACTOR SHALL PROVIDE AND INSTALL ALL PIPE HANGERS, AND SUPPORTS IN ACCORDANCE WITH THE LOCAL <br />APPLICABLE CODES. <br />13. PLUMBING CONTRACTOR TO PROVIDE BACKFLOW PREVENTERS AT ALL COFFEE MAKERS, BAGEL OVEN, DIPPING WELLS, ICE <br />MAKER AND ALL OTHER EQUIPMENT AS REQUIRED BY CODE. <br />14. PLUMBING CONTRACTOR TO PROVIDE TRAP PRIMERS OR TRAP SEAL ON ALL FLOOR DRAINS <br />AS PER APPLICABLE CODE <br />15. ALL ROOF PENETRATIONS SHALL BE AT THE CONTRACTOR'S EXPENSE. COORDINATE WITH OWNER'S ROOFING CONTRACTOR SO AS NOT TO VOID <br />ALL EXISTING ROOF WARRANTIES. <br />16. ANY CUTTING OR PATCHING NECESSARY TO PERMIT THE INSTALLATION OF ANY WORK UNDER THIS CONTRACT SHALL BE THE <br />RESPONSIBILITY OF THIS CONTRACTOR. <br />17. ENTIRE INSTALLATION SHALL BE GUARANTEED FREE OF DEFECTS AND CONTRACTOR SHALL REPAIR AND/OR REPLACE <br />ANY DEFECTIVE MATERIALS OR EQUIPMENT AT NO COST TO THE OWNER FOR A PERIOD OF ONE YEAR FROM THE <br />DATE OF ACCEPTANCE BY ENGINEER. <br />18. ALL WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT / OWNER. <br />CFS (COLD FORMED STEEL) <br />LEGEND: <br />400S 162-54: <br />2X4 STUD 16 GA. <br />600S 162-54: <br />2X6 STUD 16 GA. <br />800S 162-54: <br />2X8 STUD 16 GA. <br />400T162-54: <br />4" TRACK 16 GA. <br />600T162-54: <br />6" TRACK 16 GA. <br />80OT162-54: <br />8" TRACK 16 GA. <br />600T162-43: <br />6" TRACK 18 GA. <br />600T162-68 <br />6" TRACK 14 GA. <br />U o <br />J N � <br />N N <br />O � <br />W M 0 <br />�Z0 ZQM <br />W0 ]ch <br />to WW <br />OQM �?o <br />o O m o <br />VF W I_ LL <br />O CIS Q <br />Z u' 0 J <br />QN a ~� 2 <br />_cf)� z�� <br />H .. Q 2 <br />a- <br />ct) W <br />IX N <br />a <br />°a <br />W <br />L <br />07 <br />�' --_- <br />� <br />W <br />o0 a M <br />y[0 <br />6 ILL <br />U <br />Wn <br />W <br />Z <br />R <br />0 <br />8 <br />m <br />C7 <br />O <br />O� <br />cc cc <br />c <br />- 4) <br />029 <br />UM <br />Jam <br />.� <br />ita <br />U. <br />a <br />�v <br />�< Co <br />0 <br />O <br />a% <br />U <br />LU <br />o 0 <br />ILL <br />ui <br />a <br />N <br />O <br />X <br />W <br />Z <br />Z <br />Z <br />Z <br />Z <br />W <br />CD <br />cn <br />r' <br />Z <br />p <br />° <br />°Y <br />a <br />C9 <br />tL <br />� <br />Q <br />o <br />O <br />Z <br />ui <br />w <br />W <br />Q <br />W <br />F- <br />Z <br />Lu <br />W <br />o <br />UJ <br />O <br />m <br />0 <br />N <br />0 <br />U <br />aa <br />Q <br />Q <br />VJ <br />ZZ <br />00 <br />a <br />U <br />�j <br />w <br />W <br />to <br />to <br />M <br />N <br />O <br />V , <br />W <br />O <br />Z <br />S-4 <br />