1.
<br />Wall Assembly —The 1, 2, 3 or 4 hr fire —rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the
<br />manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the
<br />following construction features:
<br />A
<br />Studs —Wall framing may consist of either wood studs (max 2 h fire rated assemblies) or steel channel studs. Wood studs to consist of
<br />nom 2 by 4 in. lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in.
<br />wide by 1-3/8 in. deep channels spaced max 24 in. OC.
<br />B.
<br />Gypsum Board*—Nom 1/2 or 5/8 in. thick, 4 fL wide with square or tapered edges. The gypsum wallboard type, thickness, number of
<br />�A
<br />layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance
<br />3 ®
<br />Directory. Max diam of opening is 13-1/2 in.
<br />2.
<br />Through —Penetrant— One metallic pipe, conduit or tubing installed either concentrically or eccentrically within firestop system. The
<br />annular space between pipe, conduit or tubing
<br />and periphery of opening shall be min of 0 a1.(point contact to max 2 in. Pipe, conduit or tubing to be rigidly supported on both sides
<br />of wall assembly. The following types and sizes of metallic popes, conduits, or tubing may be used:
<br />A.
<br />Steel Pipe—Nom 24 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
<br />B.
<br />Iron Pipe—Nom 24 in. diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in diam (or smaller) or Class 50 (or
<br />heavier) ductle iron pressure pipe.
<br />C.
<br />Conduit—Nom 6 in. diam (or smaller) steel conduit or nom 4 'in diam (or smaller) steel electrical metallic tubing
<br />' Z
<br />D.
<br />Copper Tubing — Nom 6 in. diam (or smaller) Type L (or heavier) copper pipe.
<br />Pipe—Nom 6 in. diam Regular heavier)
<br />A SECTION A —A E.
<br />Copper (or smaller) (or copper pipe.
<br />Through Pentratrating Product�Flexible Metal Piping The following types of steel flexible metal gas piping may be used:
<br />SYSTEM N0. W-L-1001
<br />1. Nom 2 in. diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may not be removed on both sides of floor or wa
<br />assembly.
<br />SEPTEMBER 07, 2004
<br />OMEGA FLEX INC — 2. Nom 1 in. diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may not be removed on both
<br />sides of floor or wall assembly. 11TEWFLEX CORP A BUNDY CO 3 . Nom 2 in. diam (or smaller) steel flexible metal gas piping. Plastic
<br />(FORMERLY SYSTEM NO.147)
<br />covering on piping may not be removed on both sides of floor or wall assembly.
<br />F Ratings-1, 2, 3 and 4 Hr (See Items 2 and 3) 3.
<br />Fill, Void or Cavity Material* —Caulk or Sealant — Min 5/8. 1-1/4, 1-7/8 and 2-1/2 in. thickness of caulk for 1,2,3 and 4 hr rated
<br />T Ratings-0, 1, 2, 3, and 4 Hr (See Item 3)
<br />assemblies, respectively, applied within annulus, flush with both surfaces of wall. Min 1/4 in. diam bead of caulk applied to gypsum
<br />L Rating At Ambient4ess than 1 CFMIsq ft
<br />board/penetrant interface at point contact location on both sides of wall. The hourly F Rating of the firestop system is dependent upon
<br />L Rating At 400 Pess than 1 CFMIsq ft
<br />the hourly fire rating of the wall assembly in which it is installed, as shown in the following table. The hourly T Rating of the firestop
<br />system is dependent upon the type or size of the pipe or conduit and the hourly fire rating of the wall assembly in which it is installed,
<br />as tabulated below: Max Pipe F T
<br />Rename = XHEZ.W—L-1001
<br />or Conduit Rating, Rating,
<br />Diam, In Hr Hr
<br />Copyright September 7, 2004
<br />Reprinted from the UL Online Certifications Directory with
<br />+When copper 1 e g
<br />1 1 or 2 0+, 1 or 2 PP p p is used, T satin is 0 h.
<br />3M COMPANY — CP 25 WB+ or FB-3000WT
<br />permission from Underwriters Laboratories Inc.
<br />1 3 or 4 3 or 4 *Bearing the UL Classification Marking
<br />4 1 or 2 0
<br />6 3or4 0
<br />12 1 or 2 0
<br />GENERAL NOTES
<br />1. CONDUIT RACEWAYS SHOWN ARE DIAGRAMMATIC. CONTRACTOR IS RESPONSIBLE FOR PROVIDING APPROPRIATE WIRE COUNTS WITHIN RACEWAYS TO MAKE
<br />SYSTEM FUNCTION AS SHOWN/INDICATED ON PLANS.
<br />2. CONTRACTOR MAY COMBINE CIRCUIT HOMERUNS AT THEIR DISCRETION UP TO THREE (3) CIRCUITS PER HOMERUN. IF COMBINING CIRCUITRY, E.C. TO
<br />ADJUST CIRCUIT BREAKERS ACCORDINGLY SO THAT ALL SHARED CIRCUITS ARE DISCONNECTED VIA ONE CIRCUIT BREAKER PER NEC 2011. THE NEUTRAL
<br />MAY BE SHARED ON CIRCUITS OF DIFFERENT PHASES AT THE CONTRACTORS DISCRETION. IN THESE CASES, THE NEUTRAL SHALL BE INCREASED ONE WIRE
<br />SIZE. NEUTRALS ON LOAD SIDE OF DIMMERS SHALL NOT BE SHARED UNDER ANY CIRCUMSTANCES.
<br />3. ALL EXITS AND EMERGENCY LIGHTING UNITS SHALL BE CONNECTED TO DEDICATED EMERGENCY CIRCUIT AS SHOWN IN PANEL SCHEDULE. PROVIDE
<br />CIRCUITRY FOR COMPLETE INSTALLATION.
<br />4. ALL STAND ALONE WALL BOX DIMMERS TO BE LUTRON NOVA SERIES MATCHED TO LOAD TYPE AND CAPACITY CONTROLLING.
<br />5. ALL CABLING ABOVE LAY -IN CEILING TO BE PLENUM RATED. ALL CABLING TO BE IN CONDUIT IN EXPOSED CEILING AREAS.
<br />6. ALL 120V HOMERUNS OVER 75 FEET IN LENGTH TO HAVE UPSIZED (ONE SIZE LARGER) WIRE FOR VOLTAGE DROP.
<br />7. SEE ARCHITECTURAL SHEETS FOR RATED WALL ASSEMBLIES; E.C. TO PROVIDE PROPER UL APPROVED METHODS FOR MAINTAINING FIRE RATINGS.
<br />BRANCH CIRCUIT CONDUIT
<br />FOR EACH FIXTURE, PROVIDE TWO STEEL WIRE
<br />SUPPORTS TO STRUCTURE. ONE WIRE AT EACH
<br />CORNER OF THE FIXTURE. THEN SCREW FIXTURE TO
<br />THE MAIN RUNNERS OF THE LAY —IN CEILING TRACK
<br />AT THE FOUR CORNERS WITH SHEET METAL SCREWS,
<br />FOR FIRE —RATED CEILING, FIXTURE SHALL BE SUPPORTED
<br />BY TWO WIRES TO THE BUILDING STRUCTURE. ONE WIRE
<br />SHALL BE USED TO SUPPORT THE FIXTURE AT EACH END.
<br />JUNCTION BOX
<br />ATTACHED TO STRUCTURE
<br />STRUCTURAL CEILING
<br />FLEXIBLE CONDUIT (72' TO ALLOW FOR RELOCATION)
<br />ALL CONDUCTORS TO BE #12 AWG COPPER. INCLUDE
<br />GROUND WIRE. MAXIMUM OF (3) FLEXIBLE CONDUIT
<br />RUNS PER JUNCTION BOX,
<br />LAY —IN FLUORESCENT TROFFER
<br />ACOUSTICAL CEILING PANEL J
<br />LAY -IN LIGHTING FIXTURE MOUNTING DETAIL
<br />NO SCALE
<br />BUSHING
<br />3/4' CONDUIT
<br />TO ACCESSIBLE AREA ABOVE
<br />LAY -IN CEILING
<br />TYPICAL TELE/DATA OUTLET; 4' SQ. JB
<br />WITH SINGLE GANG PLASTER RING;
<br />PR❑VIDE 3/4' CONDUIT TO ACCESSIBLE L❑CATION
<br />ABOVE CEILING; E.C. TO PROVIDE PLENUM
<br />CABLING, JACKS, & FINAL FACE PLATE
<br />KEYED PLAN N❑TESID
<br />1. EXTERIOR TWIN LAMP REMOTE HEAD CONNECTED TO C❑MBINATION
<br />EXIT/EMERGENCY TWIN HEAD UNIT] UPSIZE BATTERY PER MANUFACTURER'S
<br />RECOMMENDATIONS.
<br />2. CONNECT LIGHTING TO EXISTING LIGHTING CIRCUITRY. COORDINATE WITH
<br />EXISTING CONDITIONS. IF REQUIRED PROVIDE NEW 20 AMP HOMERUN
<br />BACK TO PANEL —A. CIRCUITRY TO BE 3/4'C — 2#12 + 1#12 E.G.
<br />ROUTE CABLING THROUGH CORRIDORS AND PR❑VIDE
<br />'J' HOOKS FOR CLEAN INSTALLATION, INSTALL PER MANUFACUTER'S INSTRUCTIONS
<br />MANUFACUTER'S INSTRUCTIONS
<br />EMT
<br />TYPICAL 3-PORT TELE/DATA
<br />OUTLET CONFIGURATION
<br />#XX DENOTES NUMBER OF CABLES/PORTS
<br />C
<br />1/2'C - 1#6 SG
<br />SEE GROUND DETAIL
<br />:�,
<br />CAT 6 PLENUM CABLING
<br />(1) 2' E.C. TO UTILITY SERVICE PROVIDER
<br />COORDINATE EXACT LOCATION WITH UTILITY
<br />LAY -IN CEILING
<br />�— 4' X 8' X 3/4' PLYWOOD
<br />WITH (2) COATS OF
<br />GRAY PAINT; TYPICAL
<br />TYPICAL TELE/DATA RISER
<br />NO SCALE
<br />LUMINAIRE SCHEDULE
<br />MARK
<br />MANUFACTURER
<br />CATALOG NUMBER
<br />LAMP(S)
<br />BALLAST(S)
<br />FIXTURE
<br />MOUNTING
<br />REMARKS
<br />#
<br />TYPE
<br />WATT.
<br />#
<br />TYPE
<br />WATT.
<br />WATT.
<br />VOLTAGE
<br />A2
<br />LITHONIA
<br />GT8 SERIES
<br />2
<br />32 WATT T8, 3100
<br />LUMENS, FLUORESCENT
<br />3500' K
<br />MINIMUM 85 CRI
<br />32
<br />1
<br />2—LAMP ELECTRONIC
<br />58
<br />58
<br />120/277
<br />CEILING RECESSED
<br />2' X 4' ACRYLIC LAY —IN TROUFFER; .125 Al2 ACRYLIC LENS;
<br />PROGRAM START; 120/277V BALLAST;
<br />80+ CRI LAMPS
<br />—
<br />DAY BRITE
<br />EQUAL
<br />CRAMER
<br />EQUAL
<br />A
<br />LITHONIA
<br />GT8 SERIES
<br />3
<br />32 WATT T8, 3100
<br />LUMENS, FLUORESCENT
<br />3500' K
<br />MINIMUM 85 CRI
<br />32
<br />1
<br />3—LAMP ELECTRONIC
<br />88
<br />88
<br />120/277
<br />CEILING RECESSED
<br />2' X 4' ACRYLIC LAY —IN TROUFFER; .125 Al2 ACRYLIC LENS;
<br />PROGRAM START; 120/277V BALLAST; INBOARD/OUTBOARD WIRING;
<br />80+ CRI LAMPS
<br />—
<br />DAY BRITE
<br />EQUAL
<br />CRAMER
<br />EQUAL
<br />B
<br />UTHONIA
<br />GT8 SERIES
<br />3
<br />17 WATT T8, 3100
<br />LUMENS, FLUORESCENT
<br />3500' K
<br />MINIMUM 85 CRI
<br />17
<br />1
<br />3—LAMP ELECTRONIC
<br />88
<br />88
<br />120/277
<br />CEILING RECESSED
<br />2' X 2' ACRYLIC LAY —IN TROUFFER; .125 Al2 ACRYLIC LENS;
<br />PROGRAM START, 120/277V BALLAST; INBOARD/OUTBOARD WIRING;
<br />80+ CRI LAMPS
<br />—
<br />DAY BRITE
<br />EQUAL
<br />CRAMER
<br />EQUAL
<br />gEELLp
<br />u
<br />UTHONIA
<br />ELM2 SERIES
<br />2
<br />6 VOLT
<br />SEALED BEAM
<br />HALOGEN
<br />6
<br />—
<br />—
<br />—
<br />15
<br />120/277
<br />WALL MOUNTED
<br />8'-0' AFF
<br />TWO HEADED, SELF—CONTAINED EMERGENCY LIGHTING UNIT;
<br />120/277 DUAL VOLTAGE INPUT; 6 VOLT, 6 WATT SEALED BEAM
<br />HALOGEN LAMPS; HIGH —IMPACT POLYCARBONATE HOUSING;
<br />MAINTENANCE FREE LEAD CALCIUM BATTERY; WHITE;
<br />DAY BRITE
<br />EQUAL
<br />EXITRON►CS
<br />EQUAL
<br />®
<br />LITHONIA
<br />QUANTUM SERIES
<br />—
<br />GREEN LED
<br />—
<br />—
<br />—
<br />—
<br />1
<br />120/277
<br />CEILING SURFACE
<br />OR WALL MOUNTED
<br />12" ABOVE DOOR
<br />UNIVERSAL MOUNTING POLYCARBONATE EXIT SIGN;
<br />120/277 DUAL VOLTAGE INPUT, GREEN STENCIL FACE;
<br />GREEN LED'S; MAINTENANCE FREE LEAD CALCIUM
<br />BATTERY, WHITE HOUSING
<br />12 WATT HALOGEN LAMPS ON COMBINATION SIGN — LITHONIA LHQM
<br />SURE—LITES
<br />EQUAL
<br />MCPHILBEN
<br />EQUAL
<br />COMBINATION EXIT/EMERGENCY UNIT
<br />FLOOR
<br />F
<br />MECH. I
<br />ROOM
<br />110 �
<br />I
<br />OTS
<br />ROOM
<br />111 I
<br />I
<br />EXISTING
<br />CLOSETI
<br />112 I
<br />EXISTING
<br />ADA RESTRd)f
<br />1-137 1
<br />I
<br />I
<br />CORRIDOR
<br />115
<br />BREAK
<br />ROOM 0
<br />109
<br />•0
<br />0
<br />1 L11
<br />0
<br />e
<br />INW1
<br />EMI
<br />I 71LI
<br />Fi
<br />E
<br />I�
<br />1110
<br />&1
<br />E
<br />E
<br />LTViml,
<br />!
<br />WAI,
<br />FM
<br />I
<br />L*A
<br />NINE
<br />Inv
<br />I
<br />NEff
<br />IEEE.
<br />111C
<br />FMOOME
<br />0
<br />1,
<br />E-N�
<br />-
<br />IOWA
<br />FkIN
<br />EMINI(I)ENNIN
<br />ErLVA
<br />_1EEEErLV4
<br />10
<br />NONE
<br />0
<br />.o
<br />I
<br />I
<br />DRAW
<br />ROOM
<br />108
<br />I
<br />DRAW
<br />ROOM
<br />107
<br />I
<br />i
<br />I
<br />I
<br />I
<br />DRAW
<br />ROOM
<br />I 106
<br />I
<br />I
<br />I
<br />I
<br />I
<br />PROCESSING
<br />ROOM
<br />1E 105
<br />I
<br />SUPPLIES
<br />I 103
<br />I
<br />i
<br />WAITING
<br />ROOM
<br />101
<br />ELECTRICAL — LIGHTING PLAN
<br />SCALE 1/4" = 1'-0"
<br />Talmage R. Payne,
<br />Architect
<br />111 Paisley Street
<br />Greensboro, NC
<br />27401
<br />336.
<br />378.1812
<br />378.1460 fax
<br />S B.
<br />�CE�
<br />�,��j 1%N
<br />s • ...I.j...••'
<br />��,S70NA L �..,•��.
<br />Charles B. Lackey,
<br />Professional Engineer
<br />1848 Banking St
<br />Greensboro, NC 27408
<br />336.275-6360
<br />336.275-1996 fax
<br />info@gsoengineering.com
<br />2�=
<br />Patient Service
<br />Center
<br />7348 Gall Blvd
<br />Zephyrhills, FL
<br />ELECTRICAL —
<br />LIGHTING PLAN
<br />PROJECT #
<br />DATE: 2/14/14
<br />DRAWN BY:
<br />SCALE: AS SHOWN
<br />ISSUED FOR: PERMITTING
<br />T* drawing is the p oWtyd PNP Design Group W 4 not b W
<br />w* irW or while wOmt w pr=W wdm emo t (D2013
<br />PNP Desgn GmW