1. <br />Wall Assembly —The 1, 2, 3 or 4 hr fire —rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the <br />manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the <br />following construction features: <br />A <br />Studs —Wall framing may consist of either wood studs (max 2 h fire rated assemblies) or steel channel studs. Wood studs to consist of <br />nom 2 by 4 in. lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in. <br />wide by 1-3/8 in. deep channels spaced max 24 in. OC. <br />B. <br />Gypsum Board*—Nom 1/2 or 5/8 in. thick, 4 fL wide with square or tapered edges. The gypsum wallboard type, thickness, number of <br />�A <br />layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance <br />3 ® <br />Directory. Max diam of opening is 13-1/2 in. <br />2. <br />Through —Penetrant— One metallic pipe, conduit or tubing installed either concentrically or eccentrically within firestop system. The <br />annular space between pipe, conduit or tubing <br />and periphery of opening shall be min of 0 a1.(point contact to max 2 in. Pipe, conduit or tubing to be rigidly supported on both sides <br />of wall assembly. The following types and sizes of metallic popes, conduits, or tubing may be used: <br />A. <br />Steel Pipe—Nom 24 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. <br />B. <br />Iron Pipe—Nom 24 in. diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in diam (or smaller) or Class 50 (or <br />heavier) ductle iron pressure pipe. <br />C. <br />Conduit—Nom 6 in. diam (or smaller) steel conduit or nom 4 'in diam (or smaller) steel electrical metallic tubing <br />' Z <br />D. <br />Copper Tubing — Nom 6 in. diam (or smaller) Type L (or heavier) copper pipe. <br />Pipe—Nom 6 in. diam Regular heavier) <br />A SECTION A —A E. <br />Copper (or smaller) (or copper pipe. <br />Through Pentratrating Product�Flexible Metal Piping The following types of steel flexible metal gas piping may be used: <br />SYSTEM N0. W-L-1001 <br />1. Nom 2 in. diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may not be removed on both sides of floor or wa <br />assembly. <br />SEPTEMBER 07, 2004 <br />OMEGA FLEX INC — 2. Nom 1 in. diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may not be removed on both <br />sides of floor or wall assembly. 11TEWFLEX CORP A BUNDY CO 3 . Nom 2 in. diam (or smaller) steel flexible metal gas piping. Plastic <br />(FORMERLY SYSTEM NO.147) <br />covering on piping may not be removed on both sides of floor or wall assembly. <br />F Ratings-1, 2, 3 and 4 Hr (See Items 2 and 3) 3. <br />Fill, Void or Cavity Material* —Caulk or Sealant — Min 5/8. 1-1/4, 1-7/8 and 2-1/2 in. thickness of caulk for 1,2,3 and 4 hr rated <br />T Ratings-0, 1, 2, 3, and 4 Hr (See Item 3) <br />assemblies, respectively, applied within annulus, flush with both surfaces of wall. Min 1/4 in. diam bead of caulk applied to gypsum <br />L Rating At Ambient4ess than 1 CFMIsq ft <br />board/penetrant interface at point contact location on both sides of wall. The hourly F Rating of the firestop system is dependent upon <br />L Rating At 400 Pess than 1 CFMIsq ft <br />the hourly fire rating of the wall assembly in which it is installed, as shown in the following table. The hourly T Rating of the firestop <br />system is dependent upon the type or size of the pipe or conduit and the hourly fire rating of the wall assembly in which it is installed, <br />as tabulated below: Max Pipe F T <br />Rename = XHEZ.W—L-1001 <br />or Conduit Rating, Rating, <br />Diam, In Hr Hr <br />Copyright September 7, 2004 <br />Reprinted from the UL Online Certifications Directory with <br />+When copper 1 e g <br />1 1 or 2 0+, 1 or 2 PP p p is used, T satin is 0 h. <br />3M COMPANY — CP 25 WB+ or FB-3000WT <br />permission from Underwriters Laboratories Inc. <br />1 3 or 4 3 or 4 *Bearing the UL Classification Marking <br />4 1 or 2 0 <br />6 3or4 0 <br />12 1 or 2 0 <br />GENERAL NOTES <br />1. CONDUIT RACEWAYS SHOWN ARE DIAGRAMMATIC. CONTRACTOR IS RESPONSIBLE FOR PROVIDING APPROPRIATE WIRE COUNTS WITHIN RACEWAYS TO MAKE <br />SYSTEM FUNCTION AS SHOWN/INDICATED ON PLANS. <br />2. CONTRACTOR MAY COMBINE CIRCUIT HOMERUNS AT THEIR DISCRETION UP TO THREE (3) CIRCUITS PER HOMERUN. IF COMBINING CIRCUITRY, E.C. TO <br />ADJUST CIRCUIT BREAKERS ACCORDINGLY SO THAT ALL SHARED CIRCUITS ARE DISCONNECTED VIA ONE CIRCUIT BREAKER PER NEC 2011. THE NEUTRAL <br />MAY BE SHARED ON CIRCUITS OF DIFFERENT PHASES AT THE CONTRACTORS DISCRETION. IN THESE CASES, THE NEUTRAL SHALL BE INCREASED ONE WIRE <br />SIZE. NEUTRALS ON LOAD SIDE OF DIMMERS SHALL NOT BE SHARED UNDER ANY CIRCUMSTANCES. <br />3. ALL EXITS AND EMERGENCY LIGHTING UNITS SHALL BE CONNECTED TO DEDICATED EMERGENCY CIRCUIT AS SHOWN IN PANEL SCHEDULE. PROVIDE <br />CIRCUITRY FOR COMPLETE INSTALLATION. <br />4. ALL STAND ALONE WALL BOX DIMMERS TO BE LUTRON NOVA SERIES MATCHED TO LOAD TYPE AND CAPACITY CONTROLLING. <br />5. ALL CABLING ABOVE LAY -IN CEILING TO BE PLENUM RATED. ALL CABLING TO BE IN CONDUIT IN EXPOSED CEILING AREAS. <br />6. ALL 120V HOMERUNS OVER 75 FEET IN LENGTH TO HAVE UPSIZED (ONE SIZE LARGER) WIRE FOR VOLTAGE DROP. <br />7. SEE ARCHITECTURAL SHEETS FOR RATED WALL ASSEMBLIES; E.C. TO PROVIDE PROPER UL APPROVED METHODS FOR MAINTAINING FIRE RATINGS. <br />BRANCH CIRCUIT CONDUIT <br />FOR EACH FIXTURE, PROVIDE TWO STEEL WIRE <br />SUPPORTS TO STRUCTURE. ONE WIRE AT EACH <br />CORNER OF THE FIXTURE. THEN SCREW FIXTURE TO <br />THE MAIN RUNNERS OF THE LAY —IN CEILING TRACK <br />AT THE FOUR CORNERS WITH SHEET METAL SCREWS, <br />FOR FIRE —RATED CEILING, FIXTURE SHALL BE SUPPORTED <br />BY TWO WIRES TO THE BUILDING STRUCTURE. ONE WIRE <br />SHALL BE USED TO SUPPORT THE FIXTURE AT EACH END. <br />JUNCTION BOX <br />ATTACHED TO STRUCTURE <br />STRUCTURAL CEILING <br />FLEXIBLE CONDUIT (72' TO ALLOW FOR RELOCATION) <br />ALL CONDUCTORS TO BE #12 AWG COPPER. INCLUDE <br />GROUND WIRE. MAXIMUM OF (3) FLEXIBLE CONDUIT <br />RUNS PER JUNCTION BOX, <br />LAY —IN FLUORESCENT TROFFER <br />ACOUSTICAL CEILING PANEL J <br />LAY -IN LIGHTING FIXTURE MOUNTING DETAIL <br />NO SCALE <br />BUSHING <br />3/4' CONDUIT <br />TO ACCESSIBLE AREA ABOVE <br />LAY -IN CEILING <br />TYPICAL TELE/DATA OUTLET; 4' SQ. JB <br />WITH SINGLE GANG PLASTER RING; <br />PR❑VIDE 3/4' CONDUIT TO ACCESSIBLE L❑CATION <br />ABOVE CEILING; E.C. TO PROVIDE PLENUM <br />CABLING, JACKS, & FINAL FACE PLATE <br />KEYED PLAN N❑TESID <br />1. EXTERIOR TWIN LAMP REMOTE HEAD CONNECTED TO C❑MBINATION <br />EXIT/EMERGENCY TWIN HEAD UNIT] UPSIZE BATTERY PER MANUFACTURER'S <br />RECOMMENDATIONS. <br />2. CONNECT LIGHTING TO EXISTING LIGHTING CIRCUITRY. COORDINATE WITH <br />EXISTING CONDITIONS. IF REQUIRED PROVIDE NEW 20 AMP HOMERUN <br />BACK TO PANEL —A. CIRCUITRY TO BE 3/4'C — 2#12 + 1#12 E.G. <br />ROUTE CABLING THROUGH CORRIDORS AND PR❑VIDE <br />'J' HOOKS FOR CLEAN INSTALLATION, INSTALL PER MANUFACUTER'S INSTRUCTIONS <br />MANUFACUTER'S INSTRUCTIONS <br />EMT <br />TYPICAL 3-PORT TELE/DATA <br />OUTLET CONFIGURATION <br />#XX DENOTES NUMBER OF CABLES/PORTS <br />C <br />1/2'C - 1#6 SG <br />SEE GROUND DETAIL <br />:�, <br />CAT 6 PLENUM CABLING <br />(1) 2' E.C. TO UTILITY SERVICE PROVIDER <br />COORDINATE EXACT LOCATION WITH UTILITY <br />LAY -IN CEILING <br />�— 4' X 8' X 3/4' PLYWOOD <br />WITH (2) COATS OF <br />GRAY PAINT; TYPICAL <br />TYPICAL TELE/DATA RISER <br />NO SCALE <br />LUMINAIRE SCHEDULE <br />MARK <br />MANUFACTURER <br />CATALOG NUMBER <br />LAMP(S) <br />BALLAST(S) <br />FIXTURE <br />MOUNTING <br />REMARKS <br /># <br />TYPE <br />WATT. <br /># <br />TYPE <br />WATT. <br />WATT. <br />VOLTAGE <br />A2 <br />LITHONIA <br />GT8 SERIES <br />2 <br />32 WATT T8, 3100 <br />LUMENS, FLUORESCENT <br />3500' K <br />MINIMUM 85 CRI <br />32 <br />1 <br />2—LAMP ELECTRONIC <br />58 <br />58 <br />120/277 <br />CEILING RECESSED <br />2' X 4' ACRYLIC LAY —IN TROUFFER; .125 Al2 ACRYLIC LENS; <br />PROGRAM START; 120/277V BALLAST; <br />80+ CRI LAMPS <br />— <br />DAY BRITE <br />EQUAL <br />CRAMER <br />EQUAL <br />A <br />LITHONIA <br />GT8 SERIES <br />3 <br />32 WATT T8, 3100 <br />LUMENS, FLUORESCENT <br />3500' K <br />MINIMUM 85 CRI <br />32 <br />1 <br />3—LAMP ELECTRONIC <br />88 <br />88 <br />120/277 <br />CEILING RECESSED <br />2' X 4' ACRYLIC LAY —IN TROUFFER; .125 Al2 ACRYLIC LENS; <br />PROGRAM START; 120/277V BALLAST; INBOARD/OUTBOARD WIRING; <br />80+ CRI LAMPS <br />— <br />DAY BRITE <br />EQUAL <br />CRAMER <br />EQUAL <br />B <br />UTHONIA <br />GT8 SERIES <br />3 <br />17 WATT T8, 3100 <br />LUMENS, FLUORESCENT <br />3500' K <br />MINIMUM 85 CRI <br />17 <br />1 <br />3—LAMP ELECTRONIC <br />88 <br />88 <br />120/277 <br />CEILING RECESSED <br />2' X 2' ACRYLIC LAY —IN TROUFFER; .125 Al2 ACRYLIC LENS; <br />PROGRAM START, 120/277V BALLAST; INBOARD/OUTBOARD WIRING; <br />80+ CRI LAMPS <br />— <br />DAY BRITE <br />EQUAL <br />CRAMER <br />EQUAL <br />gEELLp <br />u <br />UTHONIA <br />ELM2 SERIES <br />2 <br />6 VOLT <br />SEALED BEAM <br />HALOGEN <br />6 <br />— <br />— <br />— <br />15 <br />120/277 <br />WALL MOUNTED <br />8'-0' AFF <br />TWO HEADED, SELF—CONTAINED EMERGENCY LIGHTING UNIT; <br />120/277 DUAL VOLTAGE INPUT; 6 VOLT, 6 WATT SEALED BEAM <br />HALOGEN LAMPS; HIGH —IMPACT POLYCARBONATE HOUSING; <br />MAINTENANCE FREE LEAD CALCIUM BATTERY; WHITE; <br />DAY BRITE <br />EQUAL <br />EXITRON►CS <br />EQUAL <br />® <br />LITHONIA <br />QUANTUM SERIES <br />— <br />GREEN LED <br />— <br />— <br />— <br />— <br />1 <br />120/277 <br />CEILING SURFACE <br />OR WALL MOUNTED <br />12" ABOVE DOOR <br />UNIVERSAL MOUNTING POLYCARBONATE EXIT SIGN; <br />120/277 DUAL VOLTAGE INPUT, GREEN STENCIL FACE; <br />GREEN LED'S; MAINTENANCE FREE LEAD CALCIUM <br />BATTERY, WHITE HOUSING <br />12 WATT HALOGEN LAMPS ON COMBINATION SIGN — LITHONIA LHQM <br />SURE—LITES <br />EQUAL <br />MCPHILBEN <br />EQUAL <br />COMBINATION EXIT/EMERGENCY UNIT <br />FLOOR <br />F <br />MECH. I <br />ROOM <br />110 � <br />I <br />OTS <br />ROOM <br />111 I <br />I <br />EXISTING <br />CLOSETI <br />112 I <br />EXISTING <br />ADA RESTRd)f <br />1-137 1 <br />I <br />I <br />CORRIDOR <br />115 <br />BREAK <br />ROOM 0 <br />109 <br />•0 <br />0 <br />1 L11 <br />0 <br />e <br />INW1 <br />EMI <br />I 71LI <br />Fi <br />E <br />I� <br />1110 <br />&1 <br />E <br />E <br />LTViml, <br />! <br />WAI, <br />FM <br />I <br />L*A <br />NINE <br />Inv <br />I <br />NEff <br />IEEE. <br />111C <br />FMOOME <br />0 <br />1, <br />E-N� <br />- <br />IOWA <br />FkIN <br />EMINI(I)ENNIN <br />ErLVA <br />_1EEEErLV4 <br />10 <br />NONE <br />0 <br />.o <br />I <br />I <br />DRAW <br />ROOM <br />108 <br />I <br />DRAW <br />ROOM <br />107 <br />I <br />i <br />I <br />I <br />I <br />DRAW <br />ROOM <br />I 106 <br />I <br />I <br />I <br />I <br />I <br />PROCESSING <br />ROOM <br />1E 105 <br />I <br />SUPPLIES <br />I 103 <br />I <br />i <br />WAITING <br />ROOM <br />101 <br />ELECTRICAL — LIGHTING PLAN <br />SCALE 1/4" = 1'-0" <br />Talmage R. Payne, <br />Architect <br />111 Paisley Street <br />Greensboro, NC <br />27401 <br />336. <br />378.1812 <br />378.1460 fax <br />S B. <br />�CE� <br />�,��j 1%N <br />s • ...I.j...••' <br />��,S70NA L �..,•��. <br />Charles B. Lackey, <br />Professional Engineer <br />1848 Banking St <br />Greensboro, NC 27408 <br />336.275-6360 <br />336.275-1996 fax <br />info@gsoengineering.com <br />2�= <br />Patient Service <br />Center <br />7348 Gall Blvd <br />Zephyrhills, FL <br />ELECTRICAL — <br />LIGHTING PLAN <br />PROJECT # <br />DATE: 2/14/14 <br />DRAWN BY: <br />SCALE: AS SHOWN <br />ISSUED FOR: PERMITTING <br />T* drawing is the p oWtyd PNP Design Group W 4 not b W <br />w* irW or while wOmt w pr=W wdm emo t (D2013 <br />PNP Desgn GmW <br />