Laserfiche WebLink
SYMBOLS <br />& LEGEND <br />BRANCH CIRCUIT CONDUIT CONCEALED IN CEILING AND/OR WALLS, 2#12AWG & 1#12AWG EG <br />UNLESS ❑THERWISE INDICATED, HASHMARKS INDICATE NO. OF WIRES. <br />BRANCH CIRCUIT CONDUIT EXPOSED ON WALL AND OR CEILING, 2#12AWG & 1#12AWG EG UNLESS <br />OTHERWISE INDICATED. HASHMARKS INDICATE NO. OF WIRES. <br />— BRANCH CIRCUIT C❑NDUIT CONCEALED IN OR UNDER FLOOR OR IN FURRED CEILING BELOW, TWO <br />/ \ 2#12AWG & 1#12AWG EG UNLESS ❑THERWISE INDICATED. HASHMARKS INDICATE NO. OF WIRES. <br />H❑MERUN TO PANELB❑ARD. NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS <br />PHASE WIRES <br />NEUTRAL <br />NOTE: ALL C❑NDUITS TO BE 3/4' C — 2#12AWG & 1#12AWG EG UNLESS <br />OTHERWISE INDICATED BY HASH MARKS OR CONDUIT AND WIRE SCHEDULE <br />3—WIRE TIE CONNECTION BETWEEN MASTER/SLAVE LIGHTING FIXTURE C❑MBINATIONS <br />1/2' FLEXIBLE CONDUIT CONNECTION WITH 3#14 & 1#14 E.G. <br />O FLUORESCENT LIGHTING FIXTURE, SURFACE, <br />FLUORESCENT LIGHTING FIXTURE, RECESSED. <br />® WALL OR CEILING MOUNTED EXIT LIGHT. SHADE INDICATES FACE. <br />® RECESSED LIGHTING FIXTURE. <br />SINGLE POLE SWITCH. (SEE M❑UNTING DETAIL) <br />$3 THREE WAY SWITCH. (SEE M❑UNTING DETAIL) <br />$D DIMMER SWITCH EQUAL TO LUTR❑N NOVA SERIES, SIZED FOR LOAD. (SEE M❑UNTING DETAIL) <br />$FD FLUORESCENT DIMMER SWITCH EQUAL TO LUTR❑N NOVA SERIES. (SEE M❑UNTING DETAIL) <br />SIZED FOR LOAD SIZED FOR LOAD, PR❑VIDE POWER PACKS FOR LOAD <br />DUPLEX CONVENIENCE OUTLET. (SEE M❑UNTING DETAIL) <br />CROSSMARK INDICATES 46' A.F.F. <br />SINGLE C❑NVENIENCE OUTLET, MOUNTED AS DETAILED. NEMA TYPE AS NOTED OR REQUIRED. <br />ZQZ <br />EWC ELECTRIC WATER COOLER OUTLET, VERIFY R❑UGH—IN <br />G,T DUPLEX C❑NVENIENCE OUTLET, WP—WITH WEATHER PROOF COVER, G—GFI TYPE, L—LOCKABLE C❑VER, <br />WP T — TAMPER RESISTANT <br />QUAD. CONVENIENCE OUTLET, <br />TELEPHONE, TV, SOUND, ETC., CABINET, AS NOTED. <br />— LIGHTING AND POWER PANELBOARD 120/240 VOLTS. <br />QJ JUNCTION BOX, HEIGHT & SIZE AS NOTED OR REQUIRED. <br />EXHAUST FAN OUTLET, VERIFY ROUGH —IN <br />Eli SAFETY SWITCH, RATING AS INDICATED. <br />WALL MOUNTED INFRARED AND ULTRASONIC OCCUPANCY SENSOR WITH OVERRIDE BUTTON <br />EQUAL TO HUBBELL AT1277 (SELECT COLOR) <br />. TYPICAL TELE/DATA OUTLET; 4' SQ. JB WITH SINGLE GANG PLASTER RING; <br />PROVIDE 3/4' CONDUIT TO ACCESSIBLE LOCATION ABOVE CEILING; SEE DETAIL <br />C❑❑RDINATI❑N NOTES <br />1. MOUNTING HEIGHTS SHOWN ARE FROM THE FINISHED FLOOR TO THE CENTER OF DEVICE UNLESS OTHERWISE NOTED (SEE DETAIL). IF ANY ADDITIONAL <br />CONDUIT IS ADDED, E.C. TO COORDINATE EXACT ROUTING WITH ARCHITECT PRIOR TO INSTALLATION. PROVIDE SKETCH WITH DIMENSIONS AND FITTING FOR <br />APPROVAL <br />2. ELECTRICAL DEVICES SHALL BE ALIGNED WITH THE ARCHITECTURAL FEATURES OF THE BUILDING. DEVICES FOR VARIOUS SYSTEMS (LIGHT SWITCHES, <br />RECEPTACLES, ARE ALARM HORNS, THERMOSTATS, ETC.) LOCATED IN THE SAME GENERAL AREA SHALL BE ALIGNED AT THEIR RESPECTIVE MOUNTING <br />HEIGHTS. THE E.C. SHALL COORDINATE WITH THE OTHER TRADES TO ENSURE ALIGNMENT OF ALL DEVICES, BACK BOXES SHALL BE MOUNTED ON THE <br />SAME SIDE OF THE SAME WALL STUD TO PRESENT AN ALIGNED APPEARANCE. ANY DIMENSIONING SHOWN ON THE DRAWING SHALL SUPERSEDE THIS <br />GUIDANCE. <br />3. WHERE A MULTIPLE GANG BOX HAS CIRCUITS OF DIFFERENT VOLTAGES OR SYSTEMS WHICH ARE REQUIRED TO BE SEPARATED. THE BOX SHALL BE <br />PROVIDED WITH THE CODE REQUIRED SEPARATION USING A FULL HEIGHT AND DEPTH BARRIER PLATE <br />4. MECHANICAL EQUIPMENT WILL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. THE LOCATION SHOWN ON THE ELECTRICAL PLANS <br />ARE APPROXIMATE. THE E.C. SHALL FULLY COORDINATE WITH THE M.C. TO DETERMINE THE EXACT LOCATION OF EACH PIECE OF EQUIPMENT, PRIOR TO <br />ANY INSTALLATION. <br />5. WHERE COVER PLATES FOR LIGHT SWITCHES OR RECEPTACLES CONFLICT WITH CASEWORK OR MILLWORK, THE MOUNTING HEIGHTS OF THE WIRING <br />DEVICES SHALL BE ADJUSTED SLIGHTLY SO THAT THE COVER PLATES CLEAR THE BACK SPLASH BY 1/4". THE ELECTRICAL CONTRACTOR SHALL <br />THOROUGHLY REVIEW THE CASEWORK DRAWINGS AND ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH INS. <br />6. FOR ANY WALL OR FLOOR PENETRATIONS, E.C. TO SHALL PROVIDE FIRE PROOFING TO SEAL ALL THE PENETRATIONS AFTER THE CONDUIT AND WIRING <br />HAS BEEN INSTALLED. E.C. TO USE U.L SYSTEMS PER PENETRATION MADE REFER TO ARCHITECTURAL SHEETS FOR LOCATIONS OF RATED WALLS AND <br />PARTITIONS. <br />7. INSTALL ALL EXPOSED CONDUIT IN AESTHETIC MANNER; RUN TIGHT TO DECK AND INSTALL PULL ELBOWS FOR 90 DEGREE BENDS; ENGINEERS <br />DISCRETION ON INSTALLATION; IN GYM AREA, EXPOSED CONDUIT TO BE KEPT A MINIMUM. ALL RUNS IN SLOPED CEILING TO BE RUN TIGHT ALONG <br />TRUSS AND AT APPROPRIATE HEIGHT TURNED PERPENDICULAR TO THE TRUSS AT PURUN LOCATION. E.C. TO PROVIDE PHOTO OF FIRST INSTALL FOR <br />ARCHITECTURAL APPROVAL PRIOR TO COMPLETING REMAINING CIRCUITRY. <br />8. ALL CUTTING do PATCHING BY G.C. <br />GENERAL NOTES <br />1. CONDUIT RACEWAYS SHOWN ARE DIAGRAMMATIC. CONTRACTOR IS RESPONSIBLE FOR PROVIDING APPROPRIATE WIRE COUNTS WITHIN RACEWAYS TO MAKE <br />SYSTEM FUNCTION AS SHOWN/INDICATED ON PLANS. <br />2. CONTRACTOR MAY COMBINE CIRCUIT HOMERUNS AT THEIR DISCRETION UP TO THREE (3) CIRCUITS PER HOMERUN. IF COMBINING CIRCUITRY, E.C. TO <br />ADJUST CIRCUIT BREAKERS ACCORDINGLY SO THAT ALL SHARED CIRCUITS ARE DISCONNECTED VIA ONE CIRCUIT BREAKER PER NEC 2011. THE NEUTRAL <br />MAY BE SHARED ON CIRCUITS OF DIFFERENT PHASES AT THE CONTRACTORS DISCRETION. IN THESE CASES, THE NEUTRAL SHALL BE INCREASED ONE WIRE <br />SIZE NEUTRALS ON LOAD SIDE OF DIMMERS SHALL NOT BE SHARED UNDER ANY CIRCUMSTANCES. <br />3. ALL EXITS AND EMERGENCY LIGHTING UNITS SHALL BE CONNECTED TO DEDICATED EMERGENCY CIRCUIT AS SHOWN IN PANEL SCHEDULE PROVIDE <br />CIRCUITRY FOR COMPLETE INSTALLATION. <br />4. ALL STAND ALONE WALL BOX DIMMERS TO BE LUTRON NOVA SERIES MATCHED TO LOAD TYPE AND CAPACITY CONTROLLING. <br />5. ALL CABLING ABOVE LAY —IN CEILING TO BE PLENUM RATED. ALL CABLING TO BE IN CONDUIT IN EXPOSED CEILING AREAS. <br />6. ALL 120V HOMERUNS OVER 75 FEET IN LENGTH TO HAVE UPSIZED (ONE SIZE LARGER) WIRE FOR VOLTAGE DROP. <br />7. SEE ARCHITECTURAL SHEETS FOR RATED WALL ASSEMBLIES; E.C. TO PROVIDE PROPER UL APPROVED METHODS FOR MAINTAINING FIRE RATINGS. <br />TO POWER SOURCE; <br />CB IN PANEL OR <br />FUSED DISCONNECT AT <br />WIRING TROUGH <br />DISC. T <br />IF MAIN POWER OVERCURRENT I BY <br />PROTECTION IS NOT WITHIN I E.C. I <br />SIGHT OF STARTER/VSD, <br />E.C. TO PROVIDE AND MOUNT L — — J <br />DISCONNECT AND TO TERMINATE <br />LINE AND LOAD WIRING. <br />=Il <br />CIRCUITRY <br />BY E.C. <br />T <br />J <br />LIQUIDTIGHT FLEX C❑NDUIT <br />STARTER OR VSD AND MOTOR <br />PROVIDED AND MOUNTED BY <br />MC; FINAL WIRING C❑NNECTIONS <br />BY MC. <br />TYPICAL MECHANICAL EQUIPMENT <br />C❑NNECTI❑N C❑❑RDINATI❑N DETAIL <br />NO SCALE <br />KEYED PLAN N❑TES:O <br />1. REMOVE EXISTING TELE/DATA BACKBOARDI EXTENT SERVICE ENTRANCE <br />TELE/COM TO MECH ROOM #110; PROVIDE 2' E.C. TO NEW TELE/DATA <br />CLOSET; COORDINATE INSTALLATION WITH EXISTING CONDITI❑NS, <br />2. EXISTING ELECTRICAL PANEL -A TO REMAIN. COORDINATE WITH <br />EXISTING CONDITIONS. UPDATE PANEL DIRECTORY AFTER UPFIT. <br />3. EXISTING SECURITY ALARM AND ALL DEVICES TO REMOVED IN THEIR <br />ENTIRETY; ALL DEVICES TO BE PATCHED. <br />4. EXISTING FIRE ALARM DEVICE (CONNECTED TO BUILDING FIRE ALARM <br />SYSTEM) TO REMAIN; COORDINATE WITH FIRE MARSHAL. <br />5. E.C. TO PROVIDE LIGHTED SWITCH MOUNTED AT 46' AFF. E.C. TO <br />PR❑VIDE CONTROL TRANSFORMER 120 TO 24V DC FOR SOLENOID VAVLE <br />OPERATIONt VALVES TO SHUTOFF ALL WATER TO UNISEX #109 (USED <br />FOR DRUG TESTING). COORDINATE INSTALLATI❑N WITH P.C.t 120V <br />SOLENOID VALVES ACCEPTABLE IF AVAILABLE; PROVIDE ALL WIRING <br />FOR COMPLETE INSTALLATION. <br />DEM❑LITI❑N NOTES <br />EXISTING ELECTRICAL DEVICES AND CIRCUITRY TO REMAIN AS SHOWN; ALL REMOVED DEVICES TO BE REMOVED BACK TO <br />SOURCE; PATCH AND REPAIR BY G.C.; EXISTING DOWN STREAM DEVICES AFFECTED BY RENOVATION NEED TO BE REFED; <br />E.C. TO THOROUGHLY REVIEW SITE PRIOR TO PLACING BID; COORDINATE WITH EXISTING CONDITIONS; ANY DEVICES OF <br />SALVAGE TO BE TURNED OVER TO BUILDING OWNER. INTENT OF DESIGN IS TO HAVE ALL DEVICES FED FROM EXISTING <br />ELECTRICAL SERVICE (PANEL —A). ALL NEW DEVICES SHOWN TO BE CONNECTED TO THIS EXISTING ELECTRICAL SERVICE. <br />LOAD INF❑RMATI❑N <br />EXISTING ELECTRICAL SERVICE TO REMAIN; EXISTING SERVICE INTENDED FOR SAME RETAIL/BUSINESS OCCUPANCY. <br />EXISTING WAC UNIT TO REMAIN. <br />ELECTRICAL SYSTEM AND EQUIPMENT <br />Method of Compliance: <br />Prescriptive <br />Lighting schedule <br />lamp type required in fixture <br />number of lamps in fixture <br />ballast type used in the fixture <br />number of ballasts in fixture <br />total wattage per fixture <br />total interior wattage specified vs allowed <br />FLOOR <br />See Equipment Schedules <br />See <br />Luminaire <br />Schedule <br />on Sheet <br />E02 <br />See <br />Luminaire <br />Schedule <br />on Sheet <br />E02 <br />See <br />Luminaire <br />Schedule <br />on Sheet <br />E02 <br />See <br />Luminaire <br />Schedule <br />on Sheet <br />E02 <br />See <br />Luminaire <br />Schedule <br />on Sheet <br />E02 <br />1,340 Watts vs. 1,420 <br />Watts <br />Exterior Lighting <br />Minimum Required Exterior Efficacy (45 Lumen/Watt) <br />Specified Exterior Lamps <br />Specified Efficacy <br />Compact Fluorescent 69 <br />Lumens/Watt <br />Metal Halide 71 <br />Lumens/Watt <br />S*_— FIRE ALARM INDICATING <br />DEVICE <br />OUTLET W/HASHMARK <br />MTD. ABV, CABINET <br />90' <br />O TELEPHONE <br />O <br />TELEVISION <br />RECEPTACLE <br />46' Tj <br />O O <br />11}8' <br />SWITCH <br />I <br />46' <br />Fol <br />BASEBOARD <br />OUTLET L❑CATI❑N DETAIL UNLESS NOTED OTHERWISE) <br />NO SCALE D—MOUNT <br />NOTE,=& HASHMARK INDICATES TO BE MTD. AT 46' ABOVE FLOOR <br />EX. PANEL- A <br />MAKE: SQ D <br />TYPE: LOADCENTER <br />RATING: 120/208V 30 4W <br />MOUNTING: FLUSH <br />MLO MAIN CIRCUIT BREAKER (FRAME ) <br />EQUIPMENT GROUND BUS ® YES ❑ NO <br />LOAD <br />SERVED <br />VA PER PHASE <br />CKT <br />BRKR <br />CKT <br />NO. <br />NEUTRAL <br />ABC <br />CKT <br />NO. <br />CKT <br />BRKR <br />VA PER PHASE <br />LOAD <br />SERVED <br />q <br />g <br />t✓ <br />,q <br />B <br />C <br />NOT LABELED <br />- <br />20 1 <br />1 <br />2 <br />20 1 <br />- <br />NOT LABELED <br />NOT LABELED <br />- <br />20 1 <br />3 <br />4 <br />20 1 <br />- <br />NOT LABELED <br />NOT LABELED <br />- <br />20 1 <br />5 <br />6 <br />20 1 <br />720 <br />REC-BREAK RM 109 <br />NOT LABELED <br />- <br />20 1 <br />7 <br />8 <br />20 1 <br />720 <br />REC-BREAK RM 109 <br />SPARE <br />- <br />20 1 <br />9 <br />10 <br />20 1 <br />720 <br />REC-DRAW RM 108 <br />SPARE <br />- <br />20 1 <br />11 <br />12 <br />1 20 1 <br />720 <br />REC-DRAW RM 107 <br />SPARE <br />- <br />20 1 <br />13 <br />14 <br />20 1 <br />720 <br />1 REC-DRAW RM 106 <br />- <br />- <br />- <br />15 <br />16 <br />20 1 <br />720 <br />REC-PROCESS RM 105 <br />RTU-1 <br />- <br />60 3 <br />17 <br />18 <br />- <br />- <br />- <br />- <br />- <br />- <br />19 <br />20 <br />50 3 <br />- <br />SPARE <br />REC-PROCESS RM 105 <br />720 <br />1 20 1 <br />21 <br />22 <br />j - <br />- <br />I - <br />REC-PROCESS RM 105 <br />720 <br />20 1 <br />23 <br />24 <br />30 2 <br />- <br />WATER HEATER <br />REC-DATA 103 <br />- <br />20 1 <br />25 <br />26 <br />- <br />- <br />- <br />REC-RECEPTION 102 <br />720 <br />20 1 <br />27 <br />28 <br />1 - <br />- <br />SPACE ONLY <br />SPARE <br />- <br />20 1 <br />29 <br />30 <br />- <br />- <br />SPACE ONLY <br />REMARKS 0 0 0 SUB -TOTAL "B" <br />UPDATE PANEL DIRECTORY <br />_ <br />- <br />200 BUS <br />SUB -TOTAL "A" <br />0 <br />0 <br />0 <br />MIN. 10,000 A.I.C. <br />SYM. AMPERES <br />LUGS/PHASE <br />LUGS/NEUT. <br />200 LUGS <br />SUB -TOTAL "B" <br />0 <br />0 <br />0 <br />200 S/N <br />GRAND TOTAL <br />0 <br />0 <br />0 <br />BOTT FEED <br />AMPS / PHASE <br />0 <br />0 <br />0 <br />— — — — — — — — <br />MECH. `C BREAK <br />I W H ROOM \\ ROOM <br />110 \\\ 109 <br />I A-25 <br />I I OI I <br />I I TC I I <br />OTS F_ <br />I ROOM I �ETR <br />I i 111 I � I <br />I I <br />II .I 0 <br />I_QJ I <br />L _0 _ J <br />� JFSET- <br />X11 —1 <br />I I_E-T <br />F_ -01 T-1 <br />I I <br />I I I I <br />EXSISTING <br />I ADA RESTROOM I I 05 <br />I I 113 � , <br />I I ETK <br />II � <br />II <br />CORRIDOR <br />I I I I 114 <br />II I <br />I I II <br />II I <br />i L� I EXISTING <br />RECEPTACLES <br />TO REMAIN <br />II <br />II <br />II <br />11 <br />11 <br />11 <br />I� <br />11 <br />II <br />,I <br />I ROOM <br />L 104 _L <br />FAX <br />RECEPTION <br />102 <br />46' 18' <br />11 <br />II <br />II <br />11� DASHED DENOTES <br />EXISTING WALLS <br />II <br />WAITING <br />ROOM <br />101 <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I' - - - - - - - --- ---- <br />L - - - - - - - - - - - - - - - - <br />En- <br />L- — — — — — — — — — — — — — — — — -- <br />I <br />i <br />SUPPLIES <br />1c <br />A-29 <br />ELECTRICAL - <br />POWER & TELE/DATA <br />SCALE 1/4" = 1'-0N <br />0 1' 2' 4' 8' <br />Talmage R. Payne, <br />Architect <br />111 Paisley Street <br />Greensboro, NC <br />27401 <br />336. <br />378.1812 <br />378.1460 fax <br />Charles B. Lackey, <br />Professional Engineer <br />1848 Banking St <br />Greensboro, NC 27408 <br />336.275-6360 <br />336.275-1996 fax <br />info@gsoengineering.com <br />O <br />cc <br />c.� <br />O <br />E <br />O <br />C <br />O <br />0 <br />o �- <br />O <br />G- . <br />O <br />cc <br />Patient Service <br />Center <br />7348 Gall Blvd <br />Zephyrhills, FL <br />ELECTRICAL - SYMBOLS <br />POWER & TELE/DATA <br />PROJECT # <br />DATE: <br />DRAWN BY: <br />SCALE: <br />ISSUED FOR: <br />2/14/14 <br />AS SHOWN <br />PERMITTING <br />TNs drawing is the pp" of PNP Deso Gmup and is not b be <br />wpied ff%Worrdhde w9ate><pmnW wom wnsert.®2013 <br />PNP DWF Gmup <br />El 1 <br />J <br />