SYMBOLS
<br />& LEGEND
<br />BRANCH CIRCUIT CONDUIT CONCEALED IN CEILING AND/OR WALLS, 2#12AWG & 1#12AWG EG
<br />UNLESS ❑THERWISE INDICATED, HASHMARKS INDICATE NO. OF WIRES.
<br />BRANCH CIRCUIT CONDUIT EXPOSED ON WALL AND OR CEILING, 2#12AWG & 1#12AWG EG UNLESS
<br />OTHERWISE INDICATED. HASHMARKS INDICATE NO. OF WIRES.
<br />— BRANCH CIRCUIT C❑NDUIT CONCEALED IN OR UNDER FLOOR OR IN FURRED CEILING BELOW, TWO
<br />/ \ 2#12AWG & 1#12AWG EG UNLESS ❑THERWISE INDICATED. HASHMARKS INDICATE NO. OF WIRES.
<br />H❑MERUN TO PANELB❑ARD. NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS
<br />PHASE WIRES
<br />NEUTRAL
<br />NOTE: ALL C❑NDUITS TO BE 3/4' C — 2#12AWG & 1#12AWG EG UNLESS
<br />OTHERWISE INDICATED BY HASH MARKS OR CONDUIT AND WIRE SCHEDULE
<br />3—WIRE TIE CONNECTION BETWEEN MASTER/SLAVE LIGHTING FIXTURE C❑MBINATIONS
<br />1/2' FLEXIBLE CONDUIT CONNECTION WITH 3#14 & 1#14 E.G.
<br />O FLUORESCENT LIGHTING FIXTURE, SURFACE,
<br />FLUORESCENT LIGHTING FIXTURE, RECESSED.
<br />® WALL OR CEILING MOUNTED EXIT LIGHT. SHADE INDICATES FACE.
<br />® RECESSED LIGHTING FIXTURE.
<br />SINGLE POLE SWITCH. (SEE M❑UNTING DETAIL)
<br />$3 THREE WAY SWITCH. (SEE M❑UNTING DETAIL)
<br />$D DIMMER SWITCH EQUAL TO LUTR❑N NOVA SERIES, SIZED FOR LOAD. (SEE M❑UNTING DETAIL)
<br />$FD FLUORESCENT DIMMER SWITCH EQUAL TO LUTR❑N NOVA SERIES. (SEE M❑UNTING DETAIL)
<br />SIZED FOR LOAD SIZED FOR LOAD, PR❑VIDE POWER PACKS FOR LOAD
<br />DUPLEX CONVENIENCE OUTLET. (SEE M❑UNTING DETAIL)
<br />CROSSMARK INDICATES 46' A.F.F.
<br />SINGLE C❑NVENIENCE OUTLET, MOUNTED AS DETAILED. NEMA TYPE AS NOTED OR REQUIRED.
<br />ZQZ
<br />EWC ELECTRIC WATER COOLER OUTLET, VERIFY R❑UGH—IN
<br />G,T DUPLEX C❑NVENIENCE OUTLET, WP—WITH WEATHER PROOF COVER, G—GFI TYPE, L—LOCKABLE C❑VER,
<br />WP T — TAMPER RESISTANT
<br />QUAD. CONVENIENCE OUTLET,
<br />TELEPHONE, TV, SOUND, ETC., CABINET, AS NOTED.
<br />— LIGHTING AND POWER PANELBOARD 120/240 VOLTS.
<br />QJ JUNCTION BOX, HEIGHT & SIZE AS NOTED OR REQUIRED.
<br />EXHAUST FAN OUTLET, VERIFY ROUGH —IN
<br />Eli SAFETY SWITCH, RATING AS INDICATED.
<br />WALL MOUNTED INFRARED AND ULTRASONIC OCCUPANCY SENSOR WITH OVERRIDE BUTTON
<br />EQUAL TO HUBBELL AT1277 (SELECT COLOR)
<br />. TYPICAL TELE/DATA OUTLET; 4' SQ. JB WITH SINGLE GANG PLASTER RING;
<br />PROVIDE 3/4' CONDUIT TO ACCESSIBLE LOCATION ABOVE CEILING; SEE DETAIL
<br />C❑❑RDINATI❑N NOTES
<br />1. MOUNTING HEIGHTS SHOWN ARE FROM THE FINISHED FLOOR TO THE CENTER OF DEVICE UNLESS OTHERWISE NOTED (SEE DETAIL). IF ANY ADDITIONAL
<br />CONDUIT IS ADDED, E.C. TO COORDINATE EXACT ROUTING WITH ARCHITECT PRIOR TO INSTALLATION. PROVIDE SKETCH WITH DIMENSIONS AND FITTING FOR
<br />APPROVAL
<br />2. ELECTRICAL DEVICES SHALL BE ALIGNED WITH THE ARCHITECTURAL FEATURES OF THE BUILDING. DEVICES FOR VARIOUS SYSTEMS (LIGHT SWITCHES,
<br />RECEPTACLES, ARE ALARM HORNS, THERMOSTATS, ETC.) LOCATED IN THE SAME GENERAL AREA SHALL BE ALIGNED AT THEIR RESPECTIVE MOUNTING
<br />HEIGHTS. THE E.C. SHALL COORDINATE WITH THE OTHER TRADES TO ENSURE ALIGNMENT OF ALL DEVICES, BACK BOXES SHALL BE MOUNTED ON THE
<br />SAME SIDE OF THE SAME WALL STUD TO PRESENT AN ALIGNED APPEARANCE. ANY DIMENSIONING SHOWN ON THE DRAWING SHALL SUPERSEDE THIS
<br />GUIDANCE.
<br />3. WHERE A MULTIPLE GANG BOX HAS CIRCUITS OF DIFFERENT VOLTAGES OR SYSTEMS WHICH ARE REQUIRED TO BE SEPARATED. THE BOX SHALL BE
<br />PROVIDED WITH THE CODE REQUIRED SEPARATION USING A FULL HEIGHT AND DEPTH BARRIER PLATE
<br />4. MECHANICAL EQUIPMENT WILL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. THE LOCATION SHOWN ON THE ELECTRICAL PLANS
<br />ARE APPROXIMATE. THE E.C. SHALL FULLY COORDINATE WITH THE M.C. TO DETERMINE THE EXACT LOCATION OF EACH PIECE OF EQUIPMENT, PRIOR TO
<br />ANY INSTALLATION.
<br />5. WHERE COVER PLATES FOR LIGHT SWITCHES OR RECEPTACLES CONFLICT WITH CASEWORK OR MILLWORK, THE MOUNTING HEIGHTS OF THE WIRING
<br />DEVICES SHALL BE ADJUSTED SLIGHTLY SO THAT THE COVER PLATES CLEAR THE BACK SPLASH BY 1/4". THE ELECTRICAL CONTRACTOR SHALL
<br />THOROUGHLY REVIEW THE CASEWORK DRAWINGS AND ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH INS.
<br />6. FOR ANY WALL OR FLOOR PENETRATIONS, E.C. TO SHALL PROVIDE FIRE PROOFING TO SEAL ALL THE PENETRATIONS AFTER THE CONDUIT AND WIRING
<br />HAS BEEN INSTALLED. E.C. TO USE U.L SYSTEMS PER PENETRATION MADE REFER TO ARCHITECTURAL SHEETS FOR LOCATIONS OF RATED WALLS AND
<br />PARTITIONS.
<br />7. INSTALL ALL EXPOSED CONDUIT IN AESTHETIC MANNER; RUN TIGHT TO DECK AND INSTALL PULL ELBOWS FOR 90 DEGREE BENDS; ENGINEERS
<br />DISCRETION ON INSTALLATION; IN GYM AREA, EXPOSED CONDUIT TO BE KEPT A MINIMUM. ALL RUNS IN SLOPED CEILING TO BE RUN TIGHT ALONG
<br />TRUSS AND AT APPROPRIATE HEIGHT TURNED PERPENDICULAR TO THE TRUSS AT PURUN LOCATION. E.C. TO PROVIDE PHOTO OF FIRST INSTALL FOR
<br />ARCHITECTURAL APPROVAL PRIOR TO COMPLETING REMAINING CIRCUITRY.
<br />8. ALL CUTTING do PATCHING BY G.C.
<br />GENERAL NOTES
<br />1. CONDUIT RACEWAYS SHOWN ARE DIAGRAMMATIC. CONTRACTOR IS RESPONSIBLE FOR PROVIDING APPROPRIATE WIRE COUNTS WITHIN RACEWAYS TO MAKE
<br />SYSTEM FUNCTION AS SHOWN/INDICATED ON PLANS.
<br />2. CONTRACTOR MAY COMBINE CIRCUIT HOMERUNS AT THEIR DISCRETION UP TO THREE (3) CIRCUITS PER HOMERUN. IF COMBINING CIRCUITRY, E.C. TO
<br />ADJUST CIRCUIT BREAKERS ACCORDINGLY SO THAT ALL SHARED CIRCUITS ARE DISCONNECTED VIA ONE CIRCUIT BREAKER PER NEC 2011. THE NEUTRAL
<br />MAY BE SHARED ON CIRCUITS OF DIFFERENT PHASES AT THE CONTRACTORS DISCRETION. IN THESE CASES, THE NEUTRAL SHALL BE INCREASED ONE WIRE
<br />SIZE NEUTRALS ON LOAD SIDE OF DIMMERS SHALL NOT BE SHARED UNDER ANY CIRCUMSTANCES.
<br />3. ALL EXITS AND EMERGENCY LIGHTING UNITS SHALL BE CONNECTED TO DEDICATED EMERGENCY CIRCUIT AS SHOWN IN PANEL SCHEDULE PROVIDE
<br />CIRCUITRY FOR COMPLETE INSTALLATION.
<br />4. ALL STAND ALONE WALL BOX DIMMERS TO BE LUTRON NOVA SERIES MATCHED TO LOAD TYPE AND CAPACITY CONTROLLING.
<br />5. ALL CABLING ABOVE LAY —IN CEILING TO BE PLENUM RATED. ALL CABLING TO BE IN CONDUIT IN EXPOSED CEILING AREAS.
<br />6. ALL 120V HOMERUNS OVER 75 FEET IN LENGTH TO HAVE UPSIZED (ONE SIZE LARGER) WIRE FOR VOLTAGE DROP.
<br />7. SEE ARCHITECTURAL SHEETS FOR RATED WALL ASSEMBLIES; E.C. TO PROVIDE PROPER UL APPROVED METHODS FOR MAINTAINING FIRE RATINGS.
<br />TO POWER SOURCE;
<br />CB IN PANEL OR
<br />FUSED DISCONNECT AT
<br />WIRING TROUGH
<br />DISC. T
<br />IF MAIN POWER OVERCURRENT I BY
<br />PROTECTION IS NOT WITHIN I E.C. I
<br />SIGHT OF STARTER/VSD,
<br />E.C. TO PROVIDE AND MOUNT L — — J
<br />DISCONNECT AND TO TERMINATE
<br />LINE AND LOAD WIRING.
<br />=Il
<br />CIRCUITRY
<br />BY E.C.
<br />T
<br />J
<br />LIQUIDTIGHT FLEX C❑NDUIT
<br />STARTER OR VSD AND MOTOR
<br />PROVIDED AND MOUNTED BY
<br />MC; FINAL WIRING C❑NNECTIONS
<br />BY MC.
<br />TYPICAL MECHANICAL EQUIPMENT
<br />C❑NNECTI❑N C❑❑RDINATI❑N DETAIL
<br />NO SCALE
<br />KEYED PLAN N❑TES:O
<br />1. REMOVE EXISTING TELE/DATA BACKBOARDI EXTENT SERVICE ENTRANCE
<br />TELE/COM TO MECH ROOM #110; PROVIDE 2' E.C. TO NEW TELE/DATA
<br />CLOSET; COORDINATE INSTALLATION WITH EXISTING CONDITI❑NS,
<br />2. EXISTING ELECTRICAL PANEL -A TO REMAIN. COORDINATE WITH
<br />EXISTING CONDITIONS. UPDATE PANEL DIRECTORY AFTER UPFIT.
<br />3. EXISTING SECURITY ALARM AND ALL DEVICES TO REMOVED IN THEIR
<br />ENTIRETY; ALL DEVICES TO BE PATCHED.
<br />4. EXISTING FIRE ALARM DEVICE (CONNECTED TO BUILDING FIRE ALARM
<br />SYSTEM) TO REMAIN; COORDINATE WITH FIRE MARSHAL.
<br />5. E.C. TO PROVIDE LIGHTED SWITCH MOUNTED AT 46' AFF. E.C. TO
<br />PR❑VIDE CONTROL TRANSFORMER 120 TO 24V DC FOR SOLENOID VAVLE
<br />OPERATIONt VALVES TO SHUTOFF ALL WATER TO UNISEX #109 (USED
<br />FOR DRUG TESTING). COORDINATE INSTALLATI❑N WITH P.C.t 120V
<br />SOLENOID VALVES ACCEPTABLE IF AVAILABLE; PROVIDE ALL WIRING
<br />FOR COMPLETE INSTALLATION.
<br />DEM❑LITI❑N NOTES
<br />EXISTING ELECTRICAL DEVICES AND CIRCUITRY TO REMAIN AS SHOWN; ALL REMOVED DEVICES TO BE REMOVED BACK TO
<br />SOURCE; PATCH AND REPAIR BY G.C.; EXISTING DOWN STREAM DEVICES AFFECTED BY RENOVATION NEED TO BE REFED;
<br />E.C. TO THOROUGHLY REVIEW SITE PRIOR TO PLACING BID; COORDINATE WITH EXISTING CONDITIONS; ANY DEVICES OF
<br />SALVAGE TO BE TURNED OVER TO BUILDING OWNER. INTENT OF DESIGN IS TO HAVE ALL DEVICES FED FROM EXISTING
<br />ELECTRICAL SERVICE (PANEL —A). ALL NEW DEVICES SHOWN TO BE CONNECTED TO THIS EXISTING ELECTRICAL SERVICE.
<br />LOAD INF❑RMATI❑N
<br />EXISTING ELECTRICAL SERVICE TO REMAIN; EXISTING SERVICE INTENDED FOR SAME RETAIL/BUSINESS OCCUPANCY.
<br />EXISTING WAC UNIT TO REMAIN.
<br />ELECTRICAL SYSTEM AND EQUIPMENT
<br />Method of Compliance:
<br />Prescriptive
<br />Lighting schedule
<br />lamp type required in fixture
<br />number of lamps in fixture
<br />ballast type used in the fixture
<br />number of ballasts in fixture
<br />total wattage per fixture
<br />total interior wattage specified vs allowed
<br />FLOOR
<br />See Equipment Schedules
<br />See
<br />Luminaire
<br />Schedule
<br />on Sheet
<br />E02
<br />See
<br />Luminaire
<br />Schedule
<br />on Sheet
<br />E02
<br />See
<br />Luminaire
<br />Schedule
<br />on Sheet
<br />E02
<br />See
<br />Luminaire
<br />Schedule
<br />on Sheet
<br />E02
<br />See
<br />Luminaire
<br />Schedule
<br />on Sheet
<br />E02
<br />1,340 Watts vs. 1,420
<br />Watts
<br />Exterior Lighting
<br />Minimum Required Exterior Efficacy (45 Lumen/Watt)
<br />Specified Exterior Lamps
<br />Specified Efficacy
<br />Compact Fluorescent 69
<br />Lumens/Watt
<br />Metal Halide 71
<br />Lumens/Watt
<br />S*_— FIRE ALARM INDICATING
<br />DEVICE
<br />OUTLET W/HASHMARK
<br />MTD. ABV, CABINET
<br />90'
<br />O TELEPHONE
<br />O
<br />TELEVISION
<br />RECEPTACLE
<br />46' Tj
<br />O O
<br />11}8'
<br />SWITCH
<br />I
<br />46'
<br />Fol
<br />BASEBOARD
<br />OUTLET L❑CATI❑N DETAIL UNLESS NOTED OTHERWISE)
<br />NO SCALE D—MOUNT
<br />NOTE,=& HASHMARK INDICATES TO BE MTD. AT 46' ABOVE FLOOR
<br />EX. PANEL- A
<br />MAKE: SQ D
<br />TYPE: LOADCENTER
<br />RATING: 120/208V 30 4W
<br />MOUNTING: FLUSH
<br />MLO MAIN CIRCUIT BREAKER (FRAME )
<br />EQUIPMENT GROUND BUS ® YES ❑ NO
<br />LOAD
<br />SERVED
<br />VA PER PHASE
<br />CKT
<br />BRKR
<br />CKT
<br />NO.
<br />NEUTRAL
<br />ABC
<br />CKT
<br />NO.
<br />CKT
<br />BRKR
<br />VA PER PHASE
<br />LOAD
<br />SERVED
<br />q
<br />g
<br />t✓
<br />,q
<br />B
<br />C
<br />NOT LABELED
<br />-
<br />20 1
<br />1
<br />2
<br />20 1
<br />-
<br />NOT LABELED
<br />NOT LABELED
<br />-
<br />20 1
<br />3
<br />4
<br />20 1
<br />-
<br />NOT LABELED
<br />NOT LABELED
<br />-
<br />20 1
<br />5
<br />6
<br />20 1
<br />720
<br />REC-BREAK RM 109
<br />NOT LABELED
<br />-
<br />20 1
<br />7
<br />8
<br />20 1
<br />720
<br />REC-BREAK RM 109
<br />SPARE
<br />-
<br />20 1
<br />9
<br />10
<br />20 1
<br />720
<br />REC-DRAW RM 108
<br />SPARE
<br />-
<br />20 1
<br />11
<br />12
<br />1 20 1
<br />720
<br />REC-DRAW RM 107
<br />SPARE
<br />-
<br />20 1
<br />13
<br />14
<br />20 1
<br />720
<br />1 REC-DRAW RM 106
<br />-
<br />-
<br />-
<br />15
<br />16
<br />20 1
<br />720
<br />REC-PROCESS RM 105
<br />RTU-1
<br />-
<br />60 3
<br />17
<br />18
<br />-
<br />-
<br />-
<br />-
<br />-
<br />-
<br />19
<br />20
<br />50 3
<br />-
<br />SPARE
<br />REC-PROCESS RM 105
<br />720
<br />1 20 1
<br />21
<br />22
<br />j -
<br />-
<br />I -
<br />REC-PROCESS RM 105
<br />720
<br />20 1
<br />23
<br />24
<br />30 2
<br />-
<br />WATER HEATER
<br />REC-DATA 103
<br />-
<br />20 1
<br />25
<br />26
<br />-
<br />-
<br />-
<br />REC-RECEPTION 102
<br />720
<br />20 1
<br />27
<br />28
<br />1 -
<br />-
<br />SPACE ONLY
<br />SPARE
<br />-
<br />20 1
<br />29
<br />30
<br />-
<br />-
<br />SPACE ONLY
<br />REMARKS 0 0 0 SUB -TOTAL "B"
<br />UPDATE PANEL DIRECTORY
<br />_
<br />-
<br />200 BUS
<br />SUB -TOTAL "A"
<br />0
<br />0
<br />0
<br />MIN. 10,000 A.I.C.
<br />SYM. AMPERES
<br />LUGS/PHASE
<br />LUGS/NEUT.
<br />200 LUGS
<br />SUB -TOTAL "B"
<br />0
<br />0
<br />0
<br />200 S/N
<br />GRAND TOTAL
<br />0
<br />0
<br />0
<br />BOTT FEED
<br />AMPS / PHASE
<br />0
<br />0
<br />0
<br />— — — — — — — —
<br />MECH. `C BREAK
<br />I W H ROOM \\ ROOM
<br />110 \\\ 109
<br />I A-25
<br />I I OI I
<br />I I TC I I
<br />OTS F_
<br />I ROOM I �ETR
<br />I i 111 I � I
<br />I I
<br />II .I 0
<br />I_QJ I
<br />L _0 _ J
<br />� JFSET-
<br />X11 —1
<br />I I_E-T
<br />F_ -01 T-1
<br />I I
<br />I I I I
<br />EXSISTING
<br />I ADA RESTROOM I I 05
<br />I I 113 � ,
<br />I I ETK
<br />II �
<br />II
<br />CORRIDOR
<br />I I I I 114
<br />II I
<br />I I II
<br />II I
<br />i L� I EXISTING
<br />RECEPTACLES
<br />TO REMAIN
<br />II
<br />II
<br />II
<br />11
<br />11
<br />11
<br />I�
<br />11
<br />II
<br />,I
<br />I ROOM
<br />L 104 _L
<br />FAX
<br />RECEPTION
<br />102
<br />46' 18'
<br />11
<br />II
<br />II
<br />11� DASHED DENOTES
<br />EXISTING WALLS
<br />II
<br />WAITING
<br />ROOM
<br />101
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I' - - - - - - - --- ----
<br />L - - - - - - - - - - - - - - - -
<br />En-
<br />L- — — — — — — — — — — — — — — — — --
<br />I
<br />i
<br />SUPPLIES
<br />1c
<br />A-29
<br />ELECTRICAL -
<br />POWER & TELE/DATA
<br />SCALE 1/4" = 1'-0N
<br />0 1' 2' 4' 8'
<br />Talmage R. Payne,
<br />Architect
<br />111 Paisley Street
<br />Greensboro, NC
<br />27401
<br />336.
<br />378.1812
<br />378.1460 fax
<br />Charles B. Lackey,
<br />Professional Engineer
<br />1848 Banking St
<br />Greensboro, NC 27408
<br />336.275-6360
<br />336.275-1996 fax
<br />info@gsoengineering.com
<br />O
<br />cc
<br />c.�
<br />O
<br />E
<br />O
<br />C
<br />O
<br />0
<br />o �-
<br />O
<br />G- .
<br />O
<br />cc
<br />Patient Service
<br />Center
<br />7348 Gall Blvd
<br />Zephyrhills, FL
<br />ELECTRICAL - SYMBOLS
<br />POWER & TELE/DATA
<br />PROJECT #
<br />DATE:
<br />DRAWN BY:
<br />SCALE:
<br />ISSUED FOR:
<br />2/14/14
<br />AS SHOWN
<br />PERMITTING
<br />TNs drawing is the pp" of PNP Deso Gmup and is not b be
<br />wpied ff%Worrdhde w9ate><pmnW wom wnsert.®2013
<br />PNP DWF Gmup
<br />El 1