PANEL 'HP' SURFACE MOUNTED, NEMA 3R
<br />120/208 VOLT, 3 PHASE, 4 WARE REFER TO FAULT CURRENT STUDY (BUS AFC) FOR MIN. AIC REQUIREMENT
<br />100A MCB PROVIDE WITH GROUND BAR.
<br />CKT
<br />DESCRIPTION
<br />BREAKER
<br />VOLT
<br />KVA
<br />LOAD
<br />CODE
<br />CKT
<br />DESCRIPTION
<br />BREAKER
<br />VOLT
<br />KVA
<br />LOAD
<br />CODE
<br />TRIP
<br />POLE
<br />TRIP
<br />POLE
<br />1
<br />SITE LIGHTING
<br />20
<br />2
<br />208
<br />2.8
<br />1
<br />2
<br />CONTACTORS/TC/PC
<br />20
<br />1
<br />120
<br />0.7
<br />7
<br />3
<br />4
<br />SPARE
<br />20
<br />1
<br />120
<br />5
<br />SIGN
<br />20
<br />1
<br />120
<br />1.2
<br />1
<br />6
<br />SPARE
<br />20
<br />1
<br />120
<br />7
<br />EXTERIOR LIGHTING
<br />20
<br />1
<br />120
<br />0.4
<br />1
<br />8
<br />SPARE
<br />20
<br />1
<br />120
<br />9
<br />SPARE
<br />20
<br />1
<br />120
<br />10
<br />SPARE
<br />20
<br />1
<br />120
<br />11
<br />SPARE
<br />20
<br />1
<br />120
<br />12
<br />SPARE
<br />20
<br />1
<br />120
<br />13
<br />SPARE
<br />20
<br />1
<br />120
<br />14
<br />SPACE
<br />1
<br />15
<br />SPARE
<br />20
<br />1
<br />120
<br />16
<br />SPACE
<br />1
<br />17
<br />SPACE
<br />1
<br />18
<br />SPACE
<br />1
<br />19
<br />SPACE
<br />1
<br />20
<br />SPACE
<br />1
<br />21
<br />SPACE
<br />1
<br />22
<br />SPACE
<br />1
<br />23
<br />SPACE
<br />1
<br />24
<br />SPACE
<br />1
<br />25
<br />SPACE
<br />1
<br />26
<br />SPACE
<br />1
<br />27
<br />SPACE
<br />1
<br />28
<br />SPACE
<br />1
<br />29
<br />SPACE
<br />1
<br />30
<br />SPACE
<br />1
<br />LOAD CODES
<br />CONNECTED
<br />DEMAND
<br />LOAD (KVA)
<br />FACTOR
<br />1. LIGHTING
<br />4
<br />1:25
<br />2. HEAT
<br />0
<br />1.00
<br />3. AIR CONDITIONING
<br />0
<br />1.00
<br />4. MOTORS
<br />0
<br />25% OF LARGEST MOTOI
<br />5. RECEPTACLES
<br />0
<br />NEC 220.44
<br />6. MISC. CONTINUOUS LOADS
<br />0
<br />1.25
<br />7. MISC. NON -CONTINUOUS LOADS
<br />1
<br />1.00
<br />8. KITCHEN EQUIPMENT (6 PIECES)
<br />0
<br />0.65
<br />9. HOTEL ROOM LOADS
<br />0
<br />NEC 220.42
<br />xxxxxxxx
<br />5
<br />xxxxxxxx
<br />NOTES:
<br />(1) PROVIDE GFI RECEPTACLE ADJACENT TO PANEL
<br />WITH WP WHILE IN USE COVER SUFFICIENT FOR
<br />IRRIGATION CONTROLLER USE_
<br />v3i1
<br />2" NIPPLE
<br />PANEL
<br />'HP'
<br />14 13 111 � L_ 11 �
<br />I
<br />I I
<br />15 L_0__j L- 1©__j
<br />16 21 2'
<br />PANEL 4
<br />'L1'
<br />5.4
<br />0.0
<br />0.0
<br />0.0
<br />0.0
<br />0.0
<br />0.7
<br />0.0
<br />0.0
<br />xxxxx
<br />6.1
<br />0.0 LESS SMALLEST OF HEAT/AC
<br />xxxxx
<br />6.1 TOTAL DEMAND LOAD
<br />VOLTAGE 208
<br />xxxxxxxx
<br />PHASE 3
<br />xxxxxxxx
<br />17 AMPS
<br />LOAD SUMMARY
<br />PANEL'L1' SURFACE MOUNTED, NEMA 1
<br />120/208 VOLT, 3 PHASE, 4 WIRE REFER TO FAULT CURRENT STUDY (BUS AFC) FOR MIN. AIC REQUIREMENT
<br />225 A MLO (VIA 200A FUSE) PROVIDE WITH GROUND BAR.
<br />CKT
<br />DESCRIPTION
<br />BREAKER
<br />VOLT
<br />KVA
<br />LOAD
<br />CODE
<br />CKT
<br />DESCRIPTION
<br />BREAKER
<br />VOLT
<br />KVA
<br />LOAD
<br />CODE
<br />TRIP
<br />POLE
<br />TRIP
<br />POLE
<br />1
<br />LIGHTING
<br />20
<br />1
<br />120
<br />1.4
<br />1
<br />2
<br />RECEPTACLES
<br />20
<br />1
<br />120
<br />0.7
<br />5
<br />3
<br />LIGHTING
<br />20
<br />1
<br />120
<br />1.1
<br />1
<br />4
<br />RECEPTACLES
<br />20
<br />1
<br />120
<br />0.9
<br />5
<br />5
<br />LIGHTING
<br />20
<br />1
<br />120
<br />1.1
<br />1
<br />6
<br />RECEPTACLES
<br />20
<br />1
<br />120
<br />0.9
<br />5
<br />7
<br />LIGHTING
<br />20
<br />1
<br />120
<br />1.1
<br />1
<br />8
<br />EWC
<br />20
<br />1
<br />120
<br />0.5
<br />7
<br />9
<br />LIGHTING
<br />20
<br />1
<br />120
<br />0.8
<br />1
<br />10
<br />TELEPHONE RECEPTACLES
<br />20
<br />1
<br />120
<br />0.7
<br />7
<br />11
<br />RTU-1
<br />100
<br />3
<br />208
<br />20.3
<br />2
<br />12
<br />SPARE
<br />20
<br />1
<br />120
<br />13
<br />11.9
<br />3
<br />14
<br />SPARE
<br />20
<br />1
<br />120
<br />15
<br />1.3
<br />4
<br />16
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />17
<br />RTU-2
<br />100
<br />3
<br />208
<br />20.3
<br />2
<br />18
<br />SIGN
<br />20
<br />1
<br />120
<br />1.2
<br />1
<br />19
<br />11 9.5
<br />3
<br />20
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />21
<br />1.8
<br />4
<br />22
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />23
<br />ROOF TOP RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />24
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />25
<br />SPARE
<br />20
<br />1
<br />120
<br />26
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />27
<br />SPARE
<br />20
<br />1
<br />120
<br />28
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />29
<br />GONTACTORIrC
<br />20
<br />1
<br />120
<br />0.7
<br />7
<br />30
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />31
<br />SPARE
<br />20
<br />1
<br />120
<br />32
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />33
<br />SPARE
<br />20
<br />1
<br />120
<br />34
<br />SIGN
<br />20
<br />1
<br />120
<br />1.2
<br />1
<br />35
<br />SPARE
<br />20
<br />1
<br />120
<br />36
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />37
<br />SPARE
<br />20
<br />1
<br />120
<br />38
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />39
<br />EWH
<br />30
<br />2
<br />208
<br />4.5
<br />7
<br />40
<br />SHOW WINDOW RECEPTACLE
<br />20
<br />1
<br />120
<br />0.2
<br />5
<br />41
<br />42
<br />SIGN
<br />20
<br />1
<br />1 120
<br />1 1.2
<br />1
<br />LOAD CODES
<br />1. LIGHTING
<br />2. HEAT
<br />3. AIR CONDITIONING
<br />4. MOTORS
<br />5. RECEPTACLES
<br />6. MISC. CONTINUOUS LOADS
<br />7. MISC. NON -CONTINUOUS LOADS
<br />8. KITCHEN EQUIPMENT (6 PIECES )
<br />9. HOTEL ROOM LOADS
<br />CONNECTED
<br />DEMAND
<br />LOAD (KVA)
<br />FACTOR
<br />9
<br />1.25
<br />41
<br />1.00
<br />21
<br />1.00
<br />3
<br />25% OF LARGEST MOTOI
<br />5
<br />NEC 220.44
<br />0
<br />1.25
<br />6
<br />1.00
<br />0
<br />0.65
<br />0
<br />NEC 220.42
<br />xxxxxxxx
<br />85
<br />xxxxxxxx
<br />GENERAL NOTES
<br />1) PROVIDE A BREAKER TIE FOR ALL BRANCH CIRCUITS THAT ARE PART OF A MULTI -CIRCUIT
<br />HOMERUN, SHARING THE SAME NEUTRAL
<br />9601 Sq. Ft. x 25 Wats/Sq. Ft. = 240.OKVA
<br />House Panel KVA = 6.9KVA
<br />Total KVA = 246.9KVA
<br />Total amps @ 208 Volt, 3 Phase = 686.2AMPS
<br />Spare = 313.8AMPS
<br />208V Three-phase minimum service size IOOOAmps
<br />Main 11 1000Amps
<br />L 11 _ L 11 I L 11
<br />F_ - - -i
<br />I I I i t I I I I
<br />I I I I I I I
<br />10 1 I C I 10 1 I 10
<br />POWER RISER DIAGRAM
<br />SCALE: NONE
<br />L20'
<br />DEMANDLOAD
<br />11.4
<br />40.6
<br />21.3
<br />3.5
<br />4.7
<br />0.0
<br />6.4
<br />0.0
<br />0.0
<br />xxxxx
<br />87.9
<br />21.3 LESS SMALLEST OF HEAT/AC
<br />xxxxx
<br />66.6 TOTAL DEMAND LOAD
<br />VOLTAGE 208
<br />xxxxxxxx
<br />PHASE 3
<br />xxxxxxxx
<br />REVISED: 16-Jul-13
<br />FAULT CURRENT
<br />CABLE IMPEDANCE VALUES BASED ON IEEE STD. 241-1990, TABLE 65.
<br />PROJECT: MATRESS FIRM do RETAIL
<br />ZEPHYRHILLS, FL
<br />SYSTEM VOLTAGE:
<br />ASSUMED BASE KVA:
<br />UTILITY COMPANY AFC:
<br />UTILITY COMPANY X/R RATIO:
<br />185 AMPS
<br />208 WIRE TYPE CU=1
<br />225 WIRE TYPE AL=2
<br />48792 PVC CONDUIT
<br />12
<br />SOURCE SOURCE WIRE WIRE I OF
<br />BUS AFC X/R SIZE TYPE RUNS
<br />BUS
<br />X/R
<br />BUS
<br />AFC
<br />MAIN 48792 12.00 400 1 3
<br />2.73
<br />29773
<br />PANEL HP 29773 2.73 1 1 1
<br />1.95
<br />26988
<br />PANEL L1 29773 2.73 3/0 1 1
<br />2.02
<br />26210
<br />NOTE:
<br />THE FAULT CURRENT STUDY ABOVE IS BASED UPON A 225 KVA UTILITY TRANSFORMER.
<br />ELECTRICAL CONTRACTOR SHALL CONFIRM UTILITY TRANSFORMER SIZE AND
<br />AVAILABLE FAULT CURRENT PRIOR TO ORDERING GEAR. IF UTILITY TRANSFORMER IS
<br />DIFFERENT THAN AS INDICATED ABOVE, THE ELECTRICAL CONTRACTOR SHALL CONTACT
<br />THE ENGINEER PRIOR TO PROCEEDING FOR SUITABLE AIC RATING. INTEGRATED
<br />SERIES RATINGS OF CIRCUIT BREAKERS IS PERMITTED. EC OBTAIN SITE SPECIFIC
<br />AIC RATING FOR INSTALLED TRANSFORMER FROM THE UTILITY PROVIDER AND MAKE
<br />AVAILABLE FOR INSPECTOR PRIOR TO INITIAL ELECTRICAL INSPECTION.
<br />L
<br />TO REBAR IN BUILDING
<br />FOOTING & BUILDING STEEL
<br />METALLIC COLD WATER
<br />3/4" DIA X 10' LONG COPPER
<br />CLAD DRIVEN GROUND ROD.
<br />GRADE
<br />NOTES O
<br />1. UTILITY COMPANY PAD MOUNTED TRANSFORMER WITH 120/208 VOLT
<br />SECONDARY.
<br />2. SERVICE LATERAL CONSISTING OF (3) PARALLEL RUNS OF 4" C WITH (4) #400
<br />KCMIL COPPER EACH.
<br />3. 1200 AMP HEAVY-DUTY, 3 POLE, 600 VOLT, SERVICE ENTRANCE RATED, NEMA
<br />3R, DISCONNECT WITH SOLID NEUTRAL, FUSED AT 1000 AMPS WITH L CURRENT
<br />LIMITING FUSES. PROVIDE PLAQUE INDICATING "SERVICE MAIN #1" IN
<br />ACCORDANCE WITH NEC 230.70.
<br />4, TYPE 1 SURGE PROTECTIVE DEVICE (SPD) PER NEC 285.
<br />5. GROUNDING ELECTRODE CONDUCTOR TO CONSIST OF #3/0 FROM N-G BOND IN
<br />'MAIN' AND EXTENDED UNBROKEN TO TWO (2) 3/4" X 10'L COPPER CLAD STEEL
<br />VERTICALLY DRIVEN GROUND RODS, NEAREST BUILDING STEEL BEAM,
<br />FOUNDATION STEEL (BELOW MAIN), COLD WATER PIPE (WITHIN 5FT, OF BUILDING
<br />ENTRY) IN ACCORDANCE WITH NEC 250.104. ROUTE EXTERIOR EXPOSED
<br />PORTIONS OF GEC IN PVC. ALL CONCEALED CONNECTIONS SHALL BE BY
<br />IRREVERSIBLE CONNECTION FOR THE INSTALLED USE,
<br />6. EXTEND #6 COPPER CONDUCTOR TO TELEPHONE BOARD IN TELEPHONE CABINET
<br />ROUTE EXTERIOR EXPOSED PORTIONS OF CONDUCTOR IN PVC. EC SHALL
<br />PROVIDE AN ADDITIONAL 2' OF CONDUCTOR COILED IN TELEPHONE BOX.
<br />7. 3 PARALLEL 4"C WITH 4 #400 KCMIL, 1 #2/0 EG EACH.
<br />8, 18'%18'X16' NEMA 3R WIREWAY WITH LOCKABLE COVER. BOND WIREWAY TO EG.
<br />EXTEND CONDUCTORS FULL LENGTH OF THE WIREWAY AND TAP IN A STAGGERED
<br />FASHION.
<br />9. EC SHALL ENSURE SUFFICIENT SPACE IS PROVIDED FOR FUTURE 400AMP METER
<br />SOCKET.
<br />10. EC SHALL ENSURE SUFFICIENT SPACE IS PROVIDED FOR FUTURE 400AMP-
<br />DISCONNECT.
<br />11. EC SHALL ENSURE SUFFICIENT SPACE IS PROVIDED FOR FUTURE 200AMP METER
<br />SOCKET.
<br />12. EC SHALL ENSURE SUFFICIENT SPACE IS PROVIDED FOR FUTURE 200AMP
<br />DISCONNECT
<br />13. PROVIDE 200AMP SELF-CONTAINED METER SOCKET. COORDINATE INSTALLATION
<br />WITH UTILITY COMPANY.
<br />14. PROVIDE 100AMP SELF-CONTAINED METER SOCKET. COORDINATE INSTALLATION
<br />WITH UTILITY COMPANY.
<br />15. 200 AMP HEAVY-DUTY, NEMA 3R, 3 POLE, 250 VOLT, DISCONNECT, FUSED AT
<br />200 AMPS WITH CLASS RK1 CURRENT LIMITING FUSES.
<br />16. (1) 2-1/2"C WITH 4 #3/0, 1 #6 EG. EXTENDED TO APPROPRIATE PANEL.
<br />PROVIDE (1) ADDITIONAL PARALLEL 2-1/2" EMPTY SPARE CONDUIT WITH
<br />PULLSTRING. STUB -UP AND CAP AT BOTH ENDS FOR FUTURE USE.
<br />17. 2-1 /2"C WITH 4 #3/0, 1 #3/0 EG.
<br />18. 1-1 /2"C WITH 4 #1, 1 #1 EG.
<br />19. 120 VOLT PHOTO CELL (INTERMATIC # K1100 OR EQUIVALENT) MOUNTED ON
<br />WEATHERPROOF BOX ON ROOF FACING NORTH.
<br />20. 24"X24'X6" DEEP, NEMA 3R, HINGED COVER BOX WITH CONTACTORS IN
<br />ACCORDANCE WITH SCHEDULE ON THIS SHEET AND 24-HR, 7-DAY, TIME CLOCK
<br />(INTERMATIC # ET8215C OR EQUIVALENT). REFER TO CONTROL DIAGRAM ON
<br />SHEET ES-0.0,
<br />21. EXTEND (2) 2-1/2" CONDUITS TO TENANT SPACE AS SHOWN ON SHEET E2.1
<br />FOR FUTURE TENANT SERVICE. REFER TO CORRESPONDING DIAMOND NOTE FOR
<br />STUB -UP LOCATION. STUB -UP AND CAP AT BOTH ENDS.
<br />GENERAL NOTES
<br />1. REFER TO FAULT CURRENT STUDY THIS SHEET FOR AVAILABLE FAULT CURRENT
<br />AT EACH PANEL (BUS AFC). EC TO ENSURE PANELBOARDS ARE SUITABLE FOR
<br />FAULT CURRENT ENVIRONMENT (BUS AFC). SERIES RATINGS WITH UPSTREAM
<br />DEVICES WILL BE ACCEPTED.
<br />2. PROVIDE ENGRAVED PLASTIC LAMINATED SIGNS TO IDENTIFY MAINS AND SUITE
<br />NUMBERS.
<br />Job Number: 65173
<br />E; Tec;.
<br />y aY o n
<br />N
<br />Associates, Inc. AA26001933
<br />Architecture • Planning • Interior Design
<br />14125 N.W. 80th Ave. Suite 303
<br />Miami Lakes, FI. 33016
<br />T. 786-235-9097
<br />F. 305-362-4420
<br />dtiinfo@dtiarchitect.com
<br />www.dtiarchitect.com
<br />♦♦♦1%111111/II/ I
<br />�� �\•� • •E N g �� ��i
<br />50W
<br />�cc
<br />ST 44,1'
<br />�0••. •�:
<br />,,,�1/1I11111
<br />Phillip L. Cochran,
<br />P.E. No.50716
<br />Revisions:
<br />Date Description
<br />N M
<br />M
<br />O�
<br />WWo
<br />� U
<br />w
<br />Q
<br />W
<br />L
<br />Ua
<br />0
<br />U
<br />o
<br />CD
<br />H
<br />A
<br />O
<br />H
<br />P-�
<br />m
<br />0
<br />�
<br />0
<br />o
<br />H
<br />P�
<br />W
<br />Job Number:
<br />12049.01
<br />File name:
<br />Issued Date:
<br />07.17.13
<br />Drawn by:
<br />AS/PK
<br />Checked by:
<br />DAS
<br />'SHEET NAME
<br />POWER RISER &
<br />PANEL
<br />SCHEDULES
<br />' Colwill Engineering
<br />Consulting Engineers, Inc. SHEET NUMBER
<br />Engineering Business No. 9021
<br />4750 East Adamo Drive Tampa, Florida 33805 E-3.00
<br />Tel: 813-241-2525 Fax: 813-241-2424
<br />© 2013 ALL RIGHTS RESERVED
<br />
|