PANEL 'HP' SURFACE MOUNTED, NEMA 3R <br />120/208 VOLT, 3 PHASE, 4 WARE REFER TO FAULT CURRENT STUDY (BUS AFC) FOR MIN. AIC REQUIREMENT <br />100A MCB PROVIDE WITH GROUND BAR. <br />CKT <br />DESCRIPTION <br />BREAKER <br />VOLT <br />KVA <br />LOAD <br />CODE <br />CKT <br />DESCRIPTION <br />BREAKER <br />VOLT <br />KVA <br />LOAD <br />CODE <br />TRIP <br />POLE <br />TRIP <br />POLE <br />1 <br />SITE LIGHTING <br />20 <br />2 <br />208 <br />2.8 <br />1 <br />2 <br />CONTACTORS/TC/PC <br />20 <br />1 <br />120 <br />0.7 <br />7 <br />3 <br />4 <br />SPARE <br />20 <br />1 <br />120 <br />5 <br />SIGN <br />20 <br />1 <br />120 <br />1.2 <br />1 <br />6 <br />SPARE <br />20 <br />1 <br />120 <br />7 <br />EXTERIOR LIGHTING <br />20 <br />1 <br />120 <br />0.4 <br />1 <br />8 <br />SPARE <br />20 <br />1 <br />120 <br />9 <br />SPARE <br />20 <br />1 <br />120 <br />10 <br />SPARE <br />20 <br />1 <br />120 <br />11 <br />SPARE <br />20 <br />1 <br />120 <br />12 <br />SPARE <br />20 <br />1 <br />120 <br />13 <br />SPARE <br />20 <br />1 <br />120 <br />14 <br />SPACE <br />1 <br />15 <br />SPARE <br />20 <br />1 <br />120 <br />16 <br />SPACE <br />1 <br />17 <br />SPACE <br />1 <br />18 <br />SPACE <br />1 <br />19 <br />SPACE <br />1 <br />20 <br />SPACE <br />1 <br />21 <br />SPACE <br />1 <br />22 <br />SPACE <br />1 <br />23 <br />SPACE <br />1 <br />24 <br />SPACE <br />1 <br />25 <br />SPACE <br />1 <br />26 <br />SPACE <br />1 <br />27 <br />SPACE <br />1 <br />28 <br />SPACE <br />1 <br />29 <br />SPACE <br />1 <br />30 <br />SPACE <br />1 <br />LOAD CODES <br />CONNECTED <br />DEMAND <br />LOAD (KVA) <br />FACTOR <br />1. LIGHTING <br />4 <br />1:25 <br />2. HEAT <br />0 <br />1.00 <br />3. AIR CONDITIONING <br />0 <br />1.00 <br />4. MOTORS <br />0 <br />25% OF LARGEST MOTOI <br />5. RECEPTACLES <br />0 <br />NEC 220.44 <br />6. MISC. CONTINUOUS LOADS <br />0 <br />1.25 <br />7. MISC. NON -CONTINUOUS LOADS <br />1 <br />1.00 <br />8. KITCHEN EQUIPMENT (6 PIECES) <br />0 <br />0.65 <br />9. HOTEL ROOM LOADS <br />0 <br />NEC 220.42 <br />xxxxxxxx <br />5 <br />xxxxxxxx <br />NOTES: <br />(1) PROVIDE GFI RECEPTACLE ADJACENT TO PANEL <br />WITH WP WHILE IN USE COVER SUFFICIENT FOR <br />IRRIGATION CONTROLLER USE_ <br />v3i1 <br />2" NIPPLE <br />PANEL <br />'HP' <br />14 13 111 � L_ 11 � <br />I <br />I I <br />15 L_0__j L- 1©__j <br />16 21 2' <br />PANEL 4 <br />'L1' <br />5.4 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.0 <br />0.7 <br />0.0 <br />0.0 <br />xxxxx <br />6.1 <br />0.0 LESS SMALLEST OF HEAT/AC <br />xxxxx <br />6.1 TOTAL DEMAND LOAD <br />VOLTAGE 208 <br />xxxxxxxx <br />PHASE 3 <br />xxxxxxxx <br />17 AMPS <br />LOAD SUMMARY <br />PANEL'L1' SURFACE MOUNTED, NEMA 1 <br />120/208 VOLT, 3 PHASE, 4 WIRE REFER TO FAULT CURRENT STUDY (BUS AFC) FOR MIN. AIC REQUIREMENT <br />225 A MLO (VIA 200A FUSE) PROVIDE WITH GROUND BAR. <br />CKT <br />DESCRIPTION <br />BREAKER <br />VOLT <br />KVA <br />LOAD <br />CODE <br />CKT <br />DESCRIPTION <br />BREAKER <br />VOLT <br />KVA <br />LOAD <br />CODE <br />TRIP <br />POLE <br />TRIP <br />POLE <br />1 <br />LIGHTING <br />20 <br />1 <br />120 <br />1.4 <br />1 <br />2 <br />RECEPTACLES <br />20 <br />1 <br />120 <br />0.7 <br />5 <br />3 <br />LIGHTING <br />20 <br />1 <br />120 <br />1.1 <br />1 <br />4 <br />RECEPTACLES <br />20 <br />1 <br />120 <br />0.9 <br />5 <br />5 <br />LIGHTING <br />20 <br />1 <br />120 <br />1.1 <br />1 <br />6 <br />RECEPTACLES <br />20 <br />1 <br />120 <br />0.9 <br />5 <br />7 <br />LIGHTING <br />20 <br />1 <br />120 <br />1.1 <br />1 <br />8 <br />EWC <br />20 <br />1 <br />120 <br />0.5 <br />7 <br />9 <br />LIGHTING <br />20 <br />1 <br />120 <br />0.8 <br />1 <br />10 <br />TELEPHONE RECEPTACLES <br />20 <br />1 <br />120 <br />0.7 <br />7 <br />11 <br />RTU-1 <br />100 <br />3 <br />208 <br />20.3 <br />2 <br />12 <br />SPARE <br />20 <br />1 <br />120 <br />13 <br />11.9 <br />3 <br />14 <br />SPARE <br />20 <br />1 <br />120 <br />15 <br />1.3 <br />4 <br />16 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />17 <br />RTU-2 <br />100 <br />3 <br />208 <br />20.3 <br />2 <br />18 <br />SIGN <br />20 <br />1 <br />120 <br />1.2 <br />1 <br />19 <br />11 9.5 <br />3 <br />20 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />21 <br />1.8 <br />4 <br />22 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />23 <br />ROOF TOP RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />24 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />25 <br />SPARE <br />20 <br />1 <br />120 <br />26 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />27 <br />SPARE <br />20 <br />1 <br />120 <br />28 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />29 <br />GONTACTORIrC <br />20 <br />1 <br />120 <br />0.7 <br />7 <br />30 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />31 <br />SPARE <br />20 <br />1 <br />120 <br />32 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />33 <br />SPARE <br />20 <br />1 <br />120 <br />34 <br />SIGN <br />20 <br />1 <br />120 <br />1.2 <br />1 <br />35 <br />SPARE <br />20 <br />1 <br />120 <br />36 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />37 <br />SPARE <br />20 <br />1 <br />120 <br />38 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />39 <br />EWH <br />30 <br />2 <br />208 <br />4.5 <br />7 <br />40 <br />SHOW WINDOW RECEPTACLE <br />20 <br />1 <br />120 <br />0.2 <br />5 <br />41 <br />42 <br />SIGN <br />20 <br />1 <br />1 120 <br />1 1.2 <br />1 <br />LOAD CODES <br />1. LIGHTING <br />2. HEAT <br />3. AIR CONDITIONING <br />4. MOTORS <br />5. RECEPTACLES <br />6. MISC. CONTINUOUS LOADS <br />7. MISC. NON -CONTINUOUS LOADS <br />8. KITCHEN EQUIPMENT (6 PIECES ) <br />9. HOTEL ROOM LOADS <br />CONNECTED <br />DEMAND <br />LOAD (KVA) <br />FACTOR <br />9 <br />1.25 <br />41 <br />1.00 <br />21 <br />1.00 <br />3 <br />25% OF LARGEST MOTOI <br />5 <br />NEC 220.44 <br />0 <br />1.25 <br />6 <br />1.00 <br />0 <br />0.65 <br />0 <br />NEC 220.42 <br />xxxxxxxx <br />85 <br />xxxxxxxx <br />GENERAL NOTES <br />1) PROVIDE A BREAKER TIE FOR ALL BRANCH CIRCUITS THAT ARE PART OF A MULTI -CIRCUIT <br />HOMERUN, SHARING THE SAME NEUTRAL <br />9601 Sq. Ft. x 25 Wats/Sq. Ft. = 240.OKVA <br />House Panel KVA = 6.9KVA <br />Total KVA = 246.9KVA <br />Total amps @ 208 Volt, 3 Phase = 686.2AMPS <br />Spare = 313.8AMPS <br />208V Three-phase minimum service size IOOOAmps <br />Main 11 1000Amps <br />L 11 _ L 11 I L 11 <br />F_ - - -i <br />I I I i t I I I I <br />I I I I I I I <br />10 1 I C I 10 1 I 10 <br />POWER RISER DIAGRAM <br />SCALE: NONE <br />L20' <br />DEMANDLOAD <br />11.4 <br />40.6 <br />21.3 <br />3.5 <br />4.7 <br />0.0 <br />6.4 <br />0.0 <br />0.0 <br />xxxxx <br />87.9 <br />21.3 LESS SMALLEST OF HEAT/AC <br />xxxxx <br />66.6 TOTAL DEMAND LOAD <br />VOLTAGE 208 <br />xxxxxxxx <br />PHASE 3 <br />xxxxxxxx <br />REVISED: 16-Jul-13 <br />FAULT CURRENT <br />CABLE IMPEDANCE VALUES BASED ON IEEE STD. 241-1990, TABLE 65. <br />PROJECT: MATRESS FIRM do RETAIL <br />ZEPHYRHILLS, FL <br />SYSTEM VOLTAGE: <br />ASSUMED BASE KVA: <br />UTILITY COMPANY AFC: <br />UTILITY COMPANY X/R RATIO: <br />185 AMPS <br />208 WIRE TYPE CU=1 <br />225 WIRE TYPE AL=2 <br />48792 PVC CONDUIT <br />12 <br />SOURCE SOURCE WIRE WIRE I OF <br />BUS AFC X/R SIZE TYPE RUNS <br />BUS <br />X/R <br />BUS <br />AFC <br />MAIN 48792 12.00 400 1 3 <br />2.73 <br />29773 <br />PANEL HP 29773 2.73 1 1 1 <br />1.95 <br />26988 <br />PANEL L1 29773 2.73 3/0 1 1 <br />2.02 <br />26210 <br />NOTE: <br />THE FAULT CURRENT STUDY ABOVE IS BASED UPON A 225 KVA UTILITY TRANSFORMER. <br />ELECTRICAL CONTRACTOR SHALL CONFIRM UTILITY TRANSFORMER SIZE AND <br />AVAILABLE FAULT CURRENT PRIOR TO ORDERING GEAR. IF UTILITY TRANSFORMER IS <br />DIFFERENT THAN AS INDICATED ABOVE, THE ELECTRICAL CONTRACTOR SHALL CONTACT <br />THE ENGINEER PRIOR TO PROCEEDING FOR SUITABLE AIC RATING. INTEGRATED <br />SERIES RATINGS OF CIRCUIT BREAKERS IS PERMITTED. EC OBTAIN SITE SPECIFIC <br />AIC RATING FOR INSTALLED TRANSFORMER FROM THE UTILITY PROVIDER AND MAKE <br />AVAILABLE FOR INSPECTOR PRIOR TO INITIAL ELECTRICAL INSPECTION. <br />L <br />TO REBAR IN BUILDING <br />FOOTING & BUILDING STEEL <br />METALLIC COLD WATER <br />3/4" DIA X 10' LONG COPPER <br />CLAD DRIVEN GROUND ROD. <br />GRADE <br />NOTES O <br />1. UTILITY COMPANY PAD MOUNTED TRANSFORMER WITH 120/208 VOLT <br />SECONDARY. <br />2. SERVICE LATERAL CONSISTING OF (3) PARALLEL RUNS OF 4" C WITH (4) #400 <br />KCMIL COPPER EACH. <br />3. 1200 AMP HEAVY-DUTY, 3 POLE, 600 VOLT, SERVICE ENTRANCE RATED, NEMA <br />3R, DISCONNECT WITH SOLID NEUTRAL, FUSED AT 1000 AMPS WITH L CURRENT <br />LIMITING FUSES. PROVIDE PLAQUE INDICATING "SERVICE MAIN #1" IN <br />ACCORDANCE WITH NEC 230.70. <br />4, TYPE 1 SURGE PROTECTIVE DEVICE (SPD) PER NEC 285. <br />5. GROUNDING ELECTRODE CONDUCTOR TO CONSIST OF #3/0 FROM N-G BOND IN <br />'MAIN' AND EXTENDED UNBROKEN TO TWO (2) 3/4" X 10'L COPPER CLAD STEEL <br />VERTICALLY DRIVEN GROUND RODS, NEAREST BUILDING STEEL BEAM, <br />FOUNDATION STEEL (BELOW MAIN), COLD WATER PIPE (WITHIN 5FT, OF BUILDING <br />ENTRY) IN ACCORDANCE WITH NEC 250.104. ROUTE EXTERIOR EXPOSED <br />PORTIONS OF GEC IN PVC. ALL CONCEALED CONNECTIONS SHALL BE BY <br />IRREVERSIBLE CONNECTION FOR THE INSTALLED USE, <br />6. EXTEND #6 COPPER CONDUCTOR TO TELEPHONE BOARD IN TELEPHONE CABINET <br />ROUTE EXTERIOR EXPOSED PORTIONS OF CONDUCTOR IN PVC. EC SHALL <br />PROVIDE AN ADDITIONAL 2' OF CONDUCTOR COILED IN TELEPHONE BOX. <br />7. 3 PARALLEL 4"C WITH 4 #400 KCMIL, 1 #2/0 EG EACH. <br />8, 18'%18'X16' NEMA 3R WIREWAY WITH LOCKABLE COVER. BOND WIREWAY TO EG. <br />EXTEND CONDUCTORS FULL LENGTH OF THE WIREWAY AND TAP IN A STAGGERED <br />FASHION. <br />9. EC SHALL ENSURE SUFFICIENT SPACE IS PROVIDED FOR FUTURE 400AMP METER <br />SOCKET. <br />10. EC SHALL ENSURE SUFFICIENT SPACE IS PROVIDED FOR FUTURE 400AMP- <br />DISCONNECT. <br />11. EC SHALL ENSURE SUFFICIENT SPACE IS PROVIDED FOR FUTURE 200AMP METER <br />SOCKET. <br />12. EC SHALL ENSURE SUFFICIENT SPACE IS PROVIDED FOR FUTURE 200AMP <br />DISCONNECT <br />13. PROVIDE 200AMP SELF-CONTAINED METER SOCKET. COORDINATE INSTALLATION <br />WITH UTILITY COMPANY. <br />14. PROVIDE 100AMP SELF-CONTAINED METER SOCKET. COORDINATE INSTALLATION <br />WITH UTILITY COMPANY. <br />15. 200 AMP HEAVY-DUTY, NEMA 3R, 3 POLE, 250 VOLT, DISCONNECT, FUSED AT <br />200 AMPS WITH CLASS RK1 CURRENT LIMITING FUSES. <br />16. (1) 2-1/2"C WITH 4 #3/0, 1 #6 EG. EXTENDED TO APPROPRIATE PANEL. <br />PROVIDE (1) ADDITIONAL PARALLEL 2-1/2" EMPTY SPARE CONDUIT WITH <br />PULLSTRING. STUB -UP AND CAP AT BOTH ENDS FOR FUTURE USE. <br />17. 2-1 /2"C WITH 4 #3/0, 1 #3/0 EG. <br />18. 1-1 /2"C WITH 4 #1, 1 #1 EG. <br />19. 120 VOLT PHOTO CELL (INTERMATIC # K1100 OR EQUIVALENT) MOUNTED ON <br />WEATHERPROOF BOX ON ROOF FACING NORTH. <br />20. 24"X24'X6" DEEP, NEMA 3R, HINGED COVER BOX WITH CONTACTORS IN <br />ACCORDANCE WITH SCHEDULE ON THIS SHEET AND 24-HR, 7-DAY, TIME CLOCK <br />(INTERMATIC # ET8215C OR EQUIVALENT). REFER TO CONTROL DIAGRAM ON <br />SHEET ES-0.0, <br />21. EXTEND (2) 2-1/2" CONDUITS TO TENANT SPACE AS SHOWN ON SHEET E2.1 <br />FOR FUTURE TENANT SERVICE. REFER TO CORRESPONDING DIAMOND NOTE FOR <br />STUB -UP LOCATION. STUB -UP AND CAP AT BOTH ENDS. <br />GENERAL NOTES <br />1. REFER TO FAULT CURRENT STUDY THIS SHEET FOR AVAILABLE FAULT CURRENT <br />AT EACH PANEL (BUS AFC). EC TO ENSURE PANELBOARDS ARE SUITABLE FOR <br />FAULT CURRENT ENVIRONMENT (BUS AFC). SERIES RATINGS WITH UPSTREAM <br />DEVICES WILL BE ACCEPTED. <br />2. PROVIDE ENGRAVED PLASTIC LAMINATED SIGNS TO IDENTIFY MAINS AND SUITE <br />NUMBERS. <br />Job Number: 65173 <br />E; Tec;. <br />y aY o n <br />N <br />Associates, Inc. AA26001933 <br />Architecture • Planning • Interior Design <br />14125 N.W. 80th Ave. Suite 303 <br />Miami Lakes, FI. 33016 <br />T. 786-235-9097 <br />F. 305-362-4420 <br />dtiinfo@dtiarchitect.com <br />www.dtiarchitect.com <br />♦♦♦1%111111/II/ I <br />�� �\•� • •E N g �� ��i <br />50W <br />�cc <br />ST 44,1' <br />�0••. •�: <br />,,,�1/1I11111 <br />Phillip L. Cochran, <br />P.E. No.50716 <br />Revisions: <br />Date Description <br />N M <br />M <br />O� <br />WWo <br />� U <br />w <br />Q <br />W <br />L <br />Ua <br />0 <br />U <br />o <br />CD <br />H <br />A <br />O <br />H <br />P-� <br />m <br />0 <br />� <br />0 <br />o <br />H <br />P� <br />W <br />Job Number: <br />12049.01 <br />File name: <br />Issued Date: <br />07.17.13 <br />Drawn by: <br />AS/PK <br />Checked by: <br />DAS <br />'SHEET NAME <br />POWER RISER & <br />PANEL <br />SCHEDULES <br />' Colwill Engineering <br />Consulting Engineers, Inc. SHEET NUMBER <br />Engineering Business No. 9021 <br />4750 East Adamo Drive Tampa, Florida 33805 E-3.00 <br />Tel: 813-241-2525 Fax: 813-241-2424 <br />© 2013 ALL RIGHTS RESERVED <br />