MAIN DISTRIBUTION
<br />Three Phase, 4 Wires, 120/208 Volts, Solid Neutral, Grounding Bar, 400 Amps MB Adjusted at 300 Amps
<br />Trip, 42 Poles, Indoor, Surface Mounted.
<br />PANEL "B„
<br />SQUARE D N0442L4C+MQMB4LA+MH62+NC62V(S). Main Breaker LAL36400MC
<br />Kw per Phase
<br />Pole
<br />ole
<br />Brk
<br />Wiring
<br />Load Description
<br />Load Description
<br />Wiring
<br />Brk
<br />Pole
<br />A
<br />B
<br />C
<br />1
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Small AC Unit Server Room 117
<br />Southeast Area
<br />1.10
<br />Water Cooler Hall 140
<br />South Central Area
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />2
<br />3
<br />1.10
<br />4
<br />5
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Purpose Receptacles Rooms 115, 116
<br />2.70
<br />General Purpose Receptacles Hall, Electrical,
<br />(2) #12 AWG, (1) 414 G
<br />20
<br />6
<br />South Central Area
<br />Storage and Mechanical Rooms South Central Area
<br />7
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />IT Server Equipment Room 117
<br />1.80
<br />General Purpose Receptacles Open Office 120
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />8
<br />South Central Area
<br />South Central Area
<br />9
<br />20
<br />(2) #12 AWG, (i) #14 G
<br />General Purpose Receptacles Rooms 129, 130
<br />2.52
<br />General Purpose Receptacles Open Office 120
<br />(2) #12 AWG, (1 } #14 G
<br />20
<br />10
<br />South Central Area
<br />South Central Area
<br />11
<br />20
<br />(2) #12 AWG. (1) #14 G
<br />Flushometers Restrooms 113 and 114. Service WP
<br />-
<br />1.80
<br />General Purpose Receptacles Restroom 113,114,
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />12
<br />Receptacle Condensing Unit #2 South Central Area
<br />Rooms 115, 116 and Hall 140 South Central Area
<br />13
<br />80
<br />(3) #4 AWG,
<br />Air Handling Unit #2
<br />18.71 kW Heater
<br />7.00
<br />Air Handling Unit #2
<br />(2) 4.2 HP Compressor
<br />(3) #8 AWG,
<br />45
<br />14
<br />15
<br />7.00'
<br />16
<br />(1) #8 G
<br />(1) 2 HP Motor
<br />(1) 1 HP Motor
<br />(1) #8 G
<br />17
<br />7.00"
<br />18
<br />19
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Emergency Lighting
<br />1.74
<br />General Purpose Receptacles Conference Room 121
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />20
<br />South Central Area
<br />South Central Area
<br />21
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Emergency Lighting
<br />1.60
<br />General Purpose Receptacles Conference Room
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />22
<br />North Central Area
<br />122 South Central Area
<br />23
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Lighting Open Office Space 120
<br />2.40
<br />General Lighting Restrooms 113 and 114
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />24
<br />South Central Area
<br />South Central Area
<br />25
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Lighting Copy Room 127, Halls 137 and 139
<br />2.30
<br />General Lighting Rooms 115, 116, 117, 118a, 118b
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />26
<br />North -South Central Area
<br />and 119 South Central Area
<br />27
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Lighting Conference Rooms 121 and 122
<br />South Central Area
<br />1.60
<br />VAV Boxes 2-1 Thru BP Actuators
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />26
<br />29
<br />15.86
<br />30
<br />150
<br />See Single Line
<br />Load Center "A"
<br />Load Center "BR"
<br />See Single Line
<br />100
<br />31
<br />11.82
<br />32
<br />Diagram this Sheet
<br />Diagram this Sheet
<br />33
<br />15.72
<br />34
<br />35
<br />4.32
<br />36
<br />100
<br />See Single Line
<br />Load Center "C"
<br />-
<br />37
<br />7.54
<br />38
<br />Diagram this Sheet
<br />39
<br />8-53
<br />40
<br />41
<br />42
<br />Total Connected Load per Phase in kiloWatts
<br />33.30
<br />38.07
<br />34.38
<br />Connected Average amperes per phase 294.0 Amperes
<br />Estimated Demand Factor = 70% Average Demand Current per Phase : 0.7 x 294 = 206 Amperes
<br />u
<br />SINGLE LINE DIAGRAM
<br />Existing Underground Service Drop to Remain C 4" (3) 350
<br />KMill THHN (1) 4/0 AWG THHN (N). Aluminum.
<br />New Service Service Extension C 4" (3) 350 KMill THHN (1)
<br />4/0 AWG THHN (N), 1/0 (G) Aluminum
<br />New Service Grounding Conductor (1) #1/0 AWG Aluminum.
<br />Bond It to the Cold Water Grid.
<br />New Grounding Electrodes: (3) 3/4" x 10' Copper Clad Steel
<br />Grounding Bars one on each Corner of a 10" Side Equilateral
<br />Triangle Tied with a 1/0 Aluminun Grounding Conductor
<br />101
<br />3uilding
<br />isting Grade
<br />C
<br />Room
<br />136
<br />5 } is C 1-1/2", (3) # 2 AWG THW, (1) # 6 (N), (1) # 8 AWG (G)
<br />6 C 1-1 /4", (3) # 4 AWG THW, (1) # 8 (N), (1) # 8 AWG (G)
<br />400 Amperes, Three Phase, 208 Volts, Feed Only, Meter Pak
<br />Center, Rainproof, UL Listed, 100KA, Bolt Lugs, Neutral and
<br />SB Grounding Bars, for Aluminun Conductors Only. Coordinate
<br />Installation with Utility Company.
<br />Square D Catalog No. EZ M340OTBU
<br />LOAD CENTER "A"
<br />Three Phase, 4 Wires, 120/208 Volts, Floating Neutral, Grounding Bar, 200 Amps MLO, 24 Poles, Indoor,
<br />Surface Mounted, With Door.
<br />SQUARE D Q0324L200G+QOC24US
<br />Kw per Phase
<br />Pole
<br />Brk
<br />Wiring
<br />Load Description
<br />Load Description
<br />Wiring
<br />g
<br />Brk
<br />Pole
<br />A
<br />B
<br />C
<br />1
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Hallways and Mechanical Room General Purpose
<br />2.52
<br />General Purpose Receptacles Rooms 106 and 107
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />2
<br />Receptacles Southwest Area
<br />Northwest Area
<br />3
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Purpose Receptacles Rooms 101 and 102
<br />2 52
<br />(general Purpose Receptacles Rooms 107 and 108
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />4
<br />Southwest Area
<br />Southwest Area
<br />5
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Purpose Receptacles Rooms 102 and 103
<br />Southwest Area
<br />3.06
<br />Copier of Hall 139
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />6
<br />7
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Purpose Receptacles Rooms 104 and 105
<br />. L 70
<br />General Purpose Receptacles Rooms 109 and 110
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />8
<br />Southwest Area
<br />Southwest Area
<br />9
<br />50
<br />() #AWG,
<br />AIR HANDLER UNIT # 1 :
<br />4.50*
<br />CONDENSING UNIT # 1:
<br />(3) #8 AWG,
<br />10
<br />11
<br />(1) 2 HP BLOWER
<br />4.50*
<br />(1) 5.6 HP COMPRESSOR
<br />40
<br />12
<br />(1)#10G
<br />(1) 1 1.25 kW HEATER
<br />(2) 112 HP FAN MOTOR
<br />(1)#10G
<br />13
<br />4 50*
<br />14
<br />15
<br />(2 #8 AWG,
<br />)
<br />Tankless Instantaneous Water Heater
<br />i-E;O
<br />General Lighting Rooms 105, 106 and 107
<br />Northwest Area
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />16
<br />40
<br />(1) #10 G
<br />Nominal Load 6,000 Watts
<br />17
<br />7.6
<br />General Purpose Lighting Rooms 101, 102, 103, and
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />18
<br />104 West Area
<br />19
<br />20
<br />2 #12 AWG, 1 #14 G
<br />O O
<br />General Lighting Halls 133, 136 and 137, Storage,
<br />1.60
<br />Emer enc Lighting Southwest Area
<br />g y g 9
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />20
<br />Janitor and Mechanical Rooms Southwest Area
<br />21
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Purpose Lighting Roorns 108, 109 and 110
<br />0.60
<br />Spare
<br />20
<br />22
<br />Southwest Area
<br />23
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />VAV Boxes 1-1 thru BP Actuators
<br />20
<br />24
<br />25
<br />26
<br />27
<br />28
<br />29
<br />30
<br />Total Connected Load per Phase in kiloWatts
<br />11.32
<br />15.22
<br />15.36
<br />Average amperes per phase 116.0 Amperes
<br />(') Since the Heating Elements (8,000 Watts) of the AHU and the Compressors of the Condensing Unit will not operate simultaneously only the largest of the two electrical loads is
<br />considered in the Total Load Calculations.
<br />LOAD CENTER 11Cif
<br />Three Phase, 4 Wires, 120/208 Volts, Floating Neutral, Grounding Bar, 125 Amps MLO, 24 Poles, Indoor,
<br />Surface Mounted, With Door.
<br />SQUARE D Q0324L125G+QOC24US
<br />Kw per Phase
<br />Pole
<br />Brk
<br />Wiring
<br />Load Description
<br />Load Description
<br />Wiring
<br />Brk
<br />Pole
<br />A
<br />B
<br />C
<br />1
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Hallways and Mechanical Room General Purpose
<br />3.68
<br />Tankless Instantaneous Water Heater
<br />(2) #10 AWG, (1) #10 G
<br />20
<br />2
<br />Receptacles Northeast Area
<br />Nominal Load 2,600 Watts
<br />3
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Accounting Room 134 General Purpose Receptacles
<br />3 68
<br />Rooms 127 and 128 General Purpose Receptacles
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />4
<br />Northeast Area
<br />Northeast Area
<br />5
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Accounting Room 134 General Purpose Receptacles
<br />1.22
<br />Plotter, Room 127
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />6
<br />Northeast Area
<br />Northeast Area
<br />7
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Offices 135 and 136 General Purpose Receptacles
<br />Northeast Area
<br />1 ^46
<br />Emergency Lights NE Section
<br />(2) #12 AWG, (1) #14 G
<br />10
<br />8
<br />9
<br />30
<br />AWG,
<br />(1) #)#1
<br />AIR HANDLER UNIT_ # 3:
<br />(1) 1/2 HP BLOWER
<br />2-40
<br />CONDENSING UNIT # 3:
<br />(1) 3 HP COMPRESSOR
<br />(3) #10 AWG,
<br />25
<br />10
<br />11
<br />2.40'
<br />12
<br />( 0G
<br />(1) 7.2 kW HEATER
<br />(1) 1 /8 HP FAN MOTOR
<br />(1)#10G
<br />13
<br />2 40'
<br />14
<br />15
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Lighting Rooms 128 and 134
<br />2.45
<br />General Lighting Rooms 131, 132, 133 and 135
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />16
<br />Northeast Area
<br />Northeast Area
<br />17
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Lighting Room 134 Work Area
<br />Northeast Area
<br />1.0
<br />VAV Boxes 2-1 Thru BP Actuators
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />18
<br />19
<br />20
<br />SPARE
<br />20
<br />21
<br />22
<br />23
<br />24
<br />Total Connected Load per Phase in kiloWatts
<br />7.54
<br />8.53
<br />4.62
<br />Average amperes per phase 57.0 Amperes
<br />() Since the Heating Elements (8,000 Watts) of the AHU and the Compressors of the Condensing Unit will not operate simultaneously only the largest of the two electrical loads is
<br />considered in the Total Load Calculations.
<br />Three Phase, 4 Wires, 120/208 Volts, Floating Neutral, Grounding Bar, 125 Amps MLO, 20 Poles, Indoor,
<br />�� ��
<br />LOAD CENTER "BR"
<br />Flush Mounted, With Door.
<br />SQUARE D Q0320L125G+QOC20US
<br />Kw per Phase
<br />Pole
<br />Brk
<br />Wiring
<br />Load Description
<br />Load Description
<br />Wiring
<br />Brk
<br />Pole
<br />A
<br />B
<br />C
<br />1
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Break Room 125 General Purpose Receptacles
<br />2.16
<br />Break Room 125 East Countertop Receptacles
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />2
<br />North-Central Area
<br />North-Central Area
<br />3
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Break Room 125 North Countertop Receptacles
<br />4.40
<br />l ankless Instantaneous Water Heater
<br />(2) #10 AWG, (1) #10 G
<br />30
<br />4
<br />North-Central Area
<br />Nominal Load 2,600 Watts
<br />5
<br />20
<br />(2) #10 AWG, (1) #10 G
<br />Break Room Sink Tankless Instantaneous Water
<br />3.30
<br />Break Room 125 Refrigerator
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />6
<br />Heater North-Central Area 2,600 Watts
<br />North Central Area
<br />7
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Reception/Lobby 126 General Purpose Receptacles
<br />1.80
<br />Copy Room 127 General Purpose Receptacles
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />8
<br />North-Central Area
<br />North Central Area
<br />9
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />Copy Room 127 Copier
<br />3.20
<br />General Lighting Outdoor Porch and Lobby 126
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />10
<br />North Central Area
<br />North Central Area
<br />11
<br />20
<br />(2) #12 AWG, (1) #14 G
<br />General Lighting Hall 123, Lobby 126, Reception
<br />2.15
<br />General Lighting Break Room 125 and Restroom
<br />(2) #12 AWG, (1) #14 G
<br />20
<br />12
<br />North Central Area
<br />124 North Central Area
<br />13
<br />20
<br />(3) #12 AWG, (1) #14 G
<br />2 HP Electric Motor of the SKYFOLD Retractable
<br />0.50
<br />Spare
<br />20
<br />14
<br />15
<br />0.50
<br />16
<br />Partition.
<br />17
<br />0.50
<br />18
<br />19
<br />20
<br />Total Connected Load per Phase in kiloWatts
<br />4.46
<br />8.10
<br />5.95
<br />Average amperes per phase 52-0 Amperes
<br />PROPOSED
<br />1 ELEC PANELS
<br />architect
<br />SONIA FUEREDI DESIGN
<br />2860 WILTSHIRE DRIVE
<br />DECATUR, GA 30030
<br />plumbing & electrical
<br />HUGO MADRIGAL, PE
<br />4911 Molokai Drive
<br />Naples, FL 33412
<br />Florida Registration 39560
<br />mechanical
<br />CONSULTING ENG.
<br />ASSOCIATES, INC.
<br />8365 Gunn Highway
<br />Tampa, Florida 33626
<br />GENERAL CONTRACTOR
<br />general contractor
<br />RTD CONSTRUCTION, Inc
<br />5344 9th Street
<br />Zephyrhills, Florida 33542
<br />OC
<br />U
<br />Z
<br />J
<br />O
<br />LL
<br />V)
<br />J
<br />_J
<br />zz�
<br />00
<br />=
<br />UJ
<br />Q
<br />N
<br />O
<br />oC
<br />Imo;
<br />z
<br />zF
<br />-
<br />LLI
<br />W
<br />Cn
<br />Q
<br />cr
<br />Z
<br />=
<br />W
<br />O�
<br />U
<br />U
<br />0
<br />z
<br />L
<br />Q
<br />00
<br />L
<br />0
<br />CC
<br />0c0
<br />rn
<br />PROJECT NO: 2014-001
<br />DATE 2014_0327
<br />REVISIONS
<br />i 1Uu0, MAD: L PF
<br />PE 39560
<br />E-3
<br />
|