Laserfiche WebLink
AIR DEVICE SCHEDULE <br />MARK <br />FACE SIZE <br />NECK SIZE <br />MATERIAL <br />ACCESSORIES <br />I <br />FINISH <br />MANUFACTURER <br />AND MODEL I <br />NOTES <br />A <br />24X24 <br />600 <br />ALUMINUM <br />— <br />— <br />TITUS—PAS—AA <br />B <br />24X24 <br />8wo <br />ALUMINUM <br />— <br />— <br />TITUS—PAS—AA <br />C <br />24X24 <br />1000 <br />ALUMINUM <br />— <br />— <br />TITUS—PAS—AA <br />F <br />12X12 <br />6NO <br />ALUMINUM <br />— <br />— <br />TITUS—TDC—AA <br />00 <br />L <br />24X24 <br />22X22 <br />ALUMINUM <br />— <br />— <br />TITUS-50F <br />(DW <br />Li <br />16X16 <br />16X16 <br />ALUMINUM <br />BIRDSCREEN <br />KYNAR <br />RUSKIN—ELF6375DXD <br />00 <br />L2 <br />12X12 <br />12X12 <br />ALUMINUM <br />BIRDSCREEN <br />KYNAR <br />RUSKIN—ELF6375DXD <br />M <br />12X12 <br />loxio <br />ALUMINUM <br />TITUS-50F <br />16X16 <br />14X14 <br />ALUMINUM <br />TMS-300FL <br />(D FLEX DUCT SIZE TO MATCH NECK SIZE. MINIMUM LENGTH OF FLEX SHALL BE 6'-0- TO MAXIMUM LENGTH OF <br />10'-0", BALANCE OF DUCT SHOWN ON PLAN SHALL BE RIGID STEEL DUCT SAME SIZE AS NECK SIZE, EXTERNALLY <br />INSULATED. <br />PROVIDE RUNOUT BRANCH DUCT TO AIR DEVICE SAME SIZE AS AIR DEVICE NECK UNLESS OTHERWISE NOTED ON <br />PLANS. PROVIDE O.B.D. MODEL # AG-15—AA FOR AIR DEVICES IN HARD CEILING. <br />PERFORATED FACE AIR DEVICE. <br />ALUMINUM A X A X Vt GRID <br />HORIZONTAL RUNOUT BRANCH DUCTS SERVING A SINGLE AIR DEVICE WITH: <br />95 C.F.M. OR LESS SHALL BE 6*0 RIGID STEEL DUCT AND TRANSITION TO 6*0 FLEX DUCT PRIOR TO AIR DEVICE, <br />100 TO 200 C.F.M. SHALL BE 8"0 RIGID STEEL DUCT AND TRANS11ION TO 8"0 FLEX DUCT PRIOR TO AIR DEVICE, <br />205 TO 370 C.F.M. SHALL BE 10*0 RIGID STEEL DUCT AND TRANS11ION TO 1000 FLEX DUCT PRIOR TO AIR DEVICE, <br />375 TO 600 C.F.M. SHALL BE 12*0 RIGID STEEL DUCT AND TRANSITION TO 12"0 FLEX DUCT PRIOR TO AIR DEVICE, <br />605 TO 900 C.F.M. SHALL BE 14"0 RIGID STEEL DUCT AND TRANSITION TO 14*0 FLEX DUCT PRIOR TO AIR DEVICE, <br />ALL ELSE SHALL BE 22XlO AND TRANSITION TO 22X22, UNLESS OTHERWISE NOTED. MINIMUM LENGTH OF FLEX <br />SHALL BE 6'-0* TO MAXIMUM LENGTH OF 10'-0'. <br />AIR DEVICES USED FOR THE TRANSFER OF AIR DO NOT REQUIRE O.B.D. OR FILTER. <br />Q) PROVIDE WITH SHEETMETAL PLENUM 12 INCHES DEEP (UNLESS OTHERWISE NOTED) X FACE DIMENSION FOR <br />TRANSITION OF LOUVER TO DUCT. REFER TO MECHANICAL DETAILS FOR MORE INFORMATION. <br />LOUVER IS MIAMI—DADE COUNTY, FLORIDA APPROVED FOR MAXIMUM WINDLOAD OF :L148 PSF. ASSEMBLE <br />ACCORDING TO MANUFACTURERS INSTRUCTIONS TO MAINTAIN RATING. <br />AIR DEVICE GENERAL NOTES: <br />1. ALL UNITS FOR LAY —IN T—BAR GRILLE SHALL BE PROVIDED WITH TYPE 3 BORDER CEILING MODULE (24X24). <br />2. ALL AIR DEVICES SHALL HAVE PAINTED WHITE FINISH UNLESS COLOR COORDINATED WITH ARCHITECT. <br />3. PROVIDE SQUARE TO ROUND TRANSITIONS AS REQUIRED FOR COORDINATION OF DUCT AND AIR DEVICE NECK. <br />4. COORDINATE FRAME TYPE NTH LATEST ARCHITECTURAL REFLECTED CEILING PLAN. <br />5. INSULATE THE TOPS OF ALL SUPPLY AIR DEVICES, REFER TO SPECIFICATIONS. <br />6. AIR DEVICES LOCATED IN HARD CEILINGS, SOFFITS, OR SIDE WALLS NTH INACCESSIBLE BRANCH DUCTS, SHALL BE <br />EQUIPPED WITH AN OPPOSED BLADE DAMPER ADJUSTABLE FROM FACE OF DEVICE. <br />VENTILATIOIN SCHEDULE <br />OUTDOOR AIR <br />EXHAUST AND PRESSURIZATION <br />UNIT NUMBER <br />NUMBER OF <br />AREA <br />PEOPLE+AREA <br />EXHAUST <br />PRESS. <br />PRESS. & <br />TOTAL DESIGN OUTDOOR <br />RELIEF <br />PEOPLE <br />CFM (D <br />AIR CFM <br />AIR CFM <br />EX. CFM <br />INTAKE CFM <br />CFM <br />I <br />(CORRECTED) <br />AH-3 <br />1 32 <br />1,407 <br />190 <br />120 <br />70 <br />190 <br />190 <br />0 <br />(DOUTDOOR AIR CALCULATION BASED ON ASHRAE 62.1-2004. VALUE LISTED IN TABLE IS THE CORRECTED OA VALUE. VALUE LISTED <br />INCLUDES A 50% POPULATION DIVERSITY. <br />GRAVITY VENT SCHEDULE <br />MARK <br />GV-1 <br />MANUFACTURER <br />GREENHECK <br />MODEL NUMBER <br />FGR <br />SIZE <br />WXLXH <br />18X24X14 <br />THROAT DIMENSIONS <br />WXL <br />8X8 <br />AIR QUANTITY <br />CFM <br />170 <br />EXT. STA11C PRESSURE <br />IN. H20 <br />.05 <br />LOCATION <br />ROOF <br />NOTES <br />(D 00 <br />(3)PROVIDE NTH FACTORY SUPPLIED ROOF CURB TO MATCH SLOPE OF <br />ROOF AND RATING OF GRAVITY VENT AND BACK DRAFT DAMPER. <br />(2) GRAVITY VENT SHALL HU INCLUDE ANY ALUMINUM BIRDSCREEN OR <br />INSECT SCREEN. <br />RATED FOR 150 MPH WINDS AND IMPACT RESISTANT. ASSEMBLE <br />ACCORDING TO MANUFACTURER INSTRUCTIONS TO MAINTAIN RATING. <br />FANSCHEDULE <br />MARK <br />EF-1 <br />MANUFACTURER <br />GREENHECK <br />MODEL NUMBER <br />CSP—A200 <br />SERVICE <br />EXHAUST <br />AIR QUANTITY <br />CFMI <br />120 <br />EXT. STATIC PRESSURE <br />IN H 20 <br />0.4 <br />FAN TYPE <br />FC <br />DRIVE TYPE <br />DIRECT <br />MAXIMUM GENERATED NOISE <br />SONES <br />0.4 <br />MAXIMUM FAN SPEED <br />RPM <br />784 <br />MOTOR SIZE <br />48 WATTS <br />CONTROLS <br />Kmum W/ <br />ASSOCIAIM M <br />LOCATION <br />cum <br />ELECTRICAL CHARACTERISTICS <br />v/o/HZ <br />115/1/60 <br />NOTES <br />(D PROVIDE FLEXIBLE CONNECTORS AT ALL DUCT CONNECTIONS TO FAN. <br />PROVIDE FAN WITH GRAVITY BACKDRAFT DAMPER. REFER TO STANDARD <br />MECHANICAL DETAILS FOR FURTHER DETAILS. <br />(D PROVIDE WITH FACTORY MOUNTED DISCONNECT SWITCH. <br />@PROVIDE FAN WITH SPED CONTROLLER. MOUNT SPEED CONTROLLER IN 2X4 <br />METALLIC BOX ADJACENT TO FAN IN CEILING. TEST AND BALANCE <br />CONTRACTORS SHALL ADJUST FAN PERFORMANCE THROUGH USE OF SPEED <br />CONTROLLER. <br />SPLIT SYSTEM A/C SCHEDULE <br />AIR HANDUNG UNIT DATA <br />MARK <br />AH-3 <br />AH-4 <br />MANUFACTURER <br />TRANE <br />MITSUBISHI <br />MODEL <br />TAM4AOC60 <br />SEZ—KD12NA4 <br />TOTAL COOLING CAPACITY <br />MBH <br />56.2 <br />8.7 <br />SENSIBLE CAPACITY <br />MBH <br />42.6 <br />5.9 <br />SUPPLY AIR QUANTITY <br />CFM <br />1840 <br />275 <br />OUTSIDE AIR QUANTITY <br />CFM <br />190 <br />0 <br />MOTOR SIZE <br />HP <br />I HP (ECM MOTOR) <br />96 WATTS <br />ELECTRICAL <br />V/O/HZ <br />230/1/60 <br />230/1/60 <br />ELECTRICAL HEAT <br />KW <br />9.6 <br />— <br />S.E.E.R. <br />16.0 <br />16.0 <br />ENTERING AIR TEMP. DB/WI3 <br />'F /'F <br />75.4/63.4 <br />74/64 <br />LEAVING AIR TEMP. DB/WB <br />'F /'F <br />55.0/53.0 <br />55.0/53.0 <br />EXT. STATIC PRESSURE <br />IN. W.C. <br />0.2 <br />0.04 <br />FILTER <br />10 THROWAWAY <br />POLYPROPYLENE <br />HONEYCOMB <br />REFRIGERANT TYPE <br />R410A <br />R410A <br />WEIGHT <br />159 <br />50 <br />CONDENSING UNIT DATA <br />MARK <br />CU-3 <br />CU-4 <br />MANUFACTURER <br />TRANE <br />MITSUBISHI <br />MODEL <br />4TWR606OA1000A <br />SUZ—KAl2NA <br />OUTDOOR TEMPERATURE DB/WB <br />T <br />95.0 <br />95.0 <br />ELECTRICAL CHARACTERISTICS <br />V/O/HZ <br />230/1/60 <br />230/1/60 <br />MIN. CKT. AMPS <br />41 <br />12 <br />FNOTES. <br />0 @ 0 <br />PROVIDE WITH 7—DAY PROGRAMMABLE THERMOSTAT NTH AUTO CHANGEOVER BETWEEN HEATING <br />AND COOLING MODE. PROVIDE WITH AUXILIARY DRAIN PAN MICH EXTENDS 10" BEYOND <br />PERIMETER OF UNIT ALL AROUND TO PROVIDE SPACE FOR EXTERNAL CONDENSATE PUMP TO <br />RESIDE IN PAN. INCLUDE FLOAT SWITCH AS PART OF PAN TO SHUT UNIT DOWN UPON PRESENCE <br />OF WATER. <br />(2) PROVIDE REFRIGERANT PIPING SIZED IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS <br />TO INCLUDE PRESSURE DROP, RISE AND LENGTH CONSIDERATIONS. REFRIGERANT TYPE IS R-410A. <br />PROVIDE NTH WALL MOUNTED PROGRAMMABLE THERMOSTAT, MODEL PAR-21MAA. <br />PROVIDE NTH FILTER BOX NTH MERV 8 FILTERS (MODEL FBL1-2). PROVIDE NTH <br />BOTTOM RETURN PLATE (MODEL BRP-2) IN ORDER TO FIELD CONVERT RETURN TO <br />UNIT FROM REAR RETURN TO BOTTOM RETURN. CONSULT MANUFACTURER'S <br />INSTALLATION GUIDELINES FOR MORE INFORMATION. PROVIDE NTH AUXILIARY DRAIN <br />PAN WHICH EXTENDS 6" BEYOND PERIMETER OF UNIT ALL AROUND, INCLUDE FLOAT <br />SWITCH TO SHUT UNIT DOWN UPON PRESENCE OF WATER. <br />PROVIDE UNIT NTH CONDENSATE PUMP MANUFACTURED BY HARTELL PUMP SHALL BE MODEL <br />A3X-115, OR EQUAL, WITH ELECTRICAL CHARACTERISTICS AS FOLLOWS: 115V/10/60HZ. PUMP <br />SHALL BE COMPLETE WITH WATER COLLECTING RESERVOIR PLACED IN INTERNAL S.S. DRAIN PAN <br />FOR UNIT. REFER TO DETAILS FOR INSTALLATION INFORMATION. <br />E <br />ot <br />z <br />'y <br />V:� <br />W4 <br />Q, <br />op <br />­ 3� <br />og <br />pg.� smug <br />a <br />C; <br />Z <br />Zu <br />Z -S <br />z <br />pr, <br />0 W <br />04 <br />0 <br />C14 <br />o@ <br />LEANDRO A. ARROYO <br />FL. REG. NO. 12326 <br />CITY OF ZEPHYRHILLS <br />RENOVATION <br />OF <br />FIRE RESCUE <br />STATION NO. 2 <br />::1 <br />MECHAN I CAL 9CHE-l;)ULmr:9 <br />1/8" = r-o" 0 <br />CONSTRUCTION <br />DOCUMENTS <br />12-07-2012 <br />CB+A #1202 <br />CANERDAY <br />BELFSKY <br />ARROYO <br />ARCHITECTS <br />800 SECOND AVENUE SOUTH <br />ST. PETERSBURG, FL 33701 <br />(727) 823-0675 <br />AA26000587 <br />M4.1 <br />