PLUMBING NOTE
<br />GENERAL:
<br />1. THE INTENT IS TO INSTALL NEW PLUMBING FIXTURES. PRIOR TO PURCHASING,
<br />FIELD VERIFY THAT ALL SPECIFIED FIXTURES CAN BE INSTALLED TO SPECIFIED
<br />LOCATIDNS.
<br />2. REFER TO FIXTURE SCHEDULE FOR L-1 LAVATORY: PROVIDE SINGLE MULTI -UNIT
<br />POWER ADAPTER TO SERVE ALL AUTOMATIC FAUCETS AND FLUSH VALVES FOR EACH
<br />SEPARATE TOILET ROOM. INSTALL BELOW LAVATORY COUNTERTOP. LOW VOLTAGE
<br />WIRING TO URINALS AND WATER CLOSETS SHALL BE IN CONDUIT (CONDUIT
<br />INSTALLED BY ELECTRICAL TRADE).
<br />3. RECONNECT ALL TRAP PRIMERS TO WATER SOURCE. EXTEND PIPING WHERE
<br />REQUIRED.
<br />4. ALL WORK SHALL COMPLY WITH APPLICABLE NATIONAL, STATE, AND LOCAL
<br />CODES. THIS SHALL INCLUDE, 13UT NOT BE LIMITED TO, THE 2016 FLORIDA PLUM13ING
<br />CODE, 6TH EDITION.
<br />5. REVIEW PLANS OF ALL TRADES PRIOR TO BIDDING AND INSTALLATION TO
<br />INCLUDE ALL PLUMBING FOR COMPLETE SYSTEMS SHOWN ON THE PLANS AND AS
<br />REQUIRED.
<br />6. COORDINATE WITH OTHER TRADES TO PREVENT INTERFERENCE WITH HVAC
<br />DUCTS, STRUCTURE, ELECTRICAL LIGHTING AND OTHER PIPING IN THE CEILING
<br />SPACE. VENT PIPING AND WATER PIPING SHALL BE HELD EITHER ABOVE OR BELOW
<br />HVAC OUCTWORK AS COORDINATED WITH THE HVAC CONTRACTOR.
<br />7. ALL CHANGES SHALL BE REVIEWED BY THE ARCHITECT.
<br />B. COORDINATE WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING -IN PLUMBING
<br />FIXTURES AND EQUIPMENT SUPPLIES.
<br />9. THE PLUMBING SUBCONTRACTOR SHALL FURNISH AND INSTALL ALL PLUMBING
<br />FIXTURES, UNLESS NOTED OTHERWISE.
<br />10. VERIFY MOUNTING HEIGHT AND WATER CONNECTION SIZES TO ALL PLUMBING
<br />FIXTURES PRIOR TO ROUGH -IN. FURNISH CUTOUT TEMPLATES FOR PLUMBING
<br />FIXTURES TO BE INSTALLED IN MILLWORK, TO THE GENERAL EQUIPMENT.
<br />11. MAKE PROPER COLO WATER, WASTE AND VENT PIPING CONNECTIONS TO ALL
<br />FIXTURES AND EQUIPMENT EVEN THOUGH ALL FITTINGS AND CONNECTIONS ARE NOT
<br />SHOWN.
<br />12. VERIFY LOCATION OF EXISTING WATER SERVICE AND THE LOCATION/INVERTS
<br />OF SANITARY PIPING PRIOR TO INSTALLATION.
<br />13. IT IS THE INTENT OF THESE DRAWINGS TO COVER ALL WORK AND MATERIAL.
<br />ANY EQUIPMENT, PLUMBING FIXTURES, TRIM HARDWARE, AND/OR DEVICES USUALLY
<br />UTILIZED IN THE CLASS OF WORK, THOUGH NOT SPECIFICALLY MENTIONED OR SHOWN
<br />ON THESE DRAWINGS, BUT WHICH MAY BE NECESSARY FOR THE SATISFACTORY
<br />COMPLETION OF THE WORK (AS DETERMINED BY THE ARCHITECT) SHALL BE
<br />FURNISHED AND INSTALLED BY THE CONTRACTOR AS PART OF HIS TOTAL WORK.
<br />14. THE EQUIPMENT ROUGH -IN ITEMS AND THEIR DIMENSIONED LOCATIONS FOR ALL
<br />CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE. IN SOME
<br />INSTANCES THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS OR THE EQUIPMENT
<br />ITEMS MAY VARY FROM WHAT IS SHOWN. THEREFORE, THESE ITEMS AND DIMENSIONS
<br />SHALL BE VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER ANO/OR EQUIPMENT
<br />ROUGH -IN DRAWING. FAILURE OF THE APPROPRIATE CONTRACTOR TO VERIFY
<br />ROUGH -INS OR THEIR LOCATIONS SHALL PLACE THE RESPONSIBILITY FOR ANY
<br />SUBSEQUENT RELOCATION AND/OR ADDITIONAL ROUGH -INS DIRECTLY UPON THE
<br />CONTRACTOR.
<br />15. CONTRACTOR SHALL SUPPLY TO THE ARCHITECr THE REQUIRED COPIES OF SHOP
<br />DRAWINGS FOR APPROVAL SO THE QUALITY OF INTENDED MAT71RIALS OR EQUIPMENT
<br />CAN BE REVIEWED BEFORE INSTALLATION. THERE WILL BE �d DRAW UNTIL SHOP
<br />DRAWINGS HAVE BEEN SUBMITTED AND REVIEWED BY THE ARCHITECT/ENGINEER.
<br />16. DO NOT SCALE THIS DRAWING. REFER TO ARCHITECTURAL FLOOR PLAN FOR
<br />BUILDING DIMENSIONS.
<br />17. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY
<br />SHOW ALL ELBOWS, OFFSETS, UNIONS, VALVES, AND FITTINGS REQUIRED TO
<br />COMPLETE THE INSTALLATION OF THE WORK. THE SUBMISSION OF A PROPOSAL SHALL
<br />BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED HIMSELF
<br />WITH THE PLANS AND BUILDING SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL
<br />FOR MATERIALS AND LABOR BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE
<br />RECOGNIZED.
<br />18. THE CONTRACTOR SHALL COOPERATE FULLY AMONG THE TRADES.
<br />19. THE WATER PIPING SYSTEM SHALL BE FLUSHED AND STERILIZED IN ACCORDANCE
<br />WITH LOCAL REGULATIONS.
<br />20. DOMESTIC WATER SUPPLY BRANCHES FOR ALL EQUIPMENT HAVING QUICK
<br />CLOSING VALVES OF ANY TYPE SHALL HAVE WATER HAMMER ARRESTOR INSTALLED
<br />AT THE HIGH POINT ON THE END OF EACH BRANCH.
<br />21. FURNISH AND INSTALL SHUTOFF OR BALL VALVE AND DIELECTRIC UNIONS ON
<br />ALL EQUIPMENT DOMESTIC WATER LINES. PLUMBING CONTRACTOR SHALL MAKE ALL
<br />FINAL CONNECTIONS TO EQUIPMENT. COORDINATE WITH EQUIPMENT SUPPLIER FOR
<br />EXACT REQUIREMENTS.
<br />22. PROVIDE CHROME PLATED ESCUTCHEONS AT ALL WALL PENETRATIONS.
<br />23. MATERIALS, EQUIPMENT, ASSEMBLIES AND SYSTEMS SHALL MEET ALL PERTINENT
<br />REQUIREMENTS OF NATIONALLY RECOGNIZED TESTING ORGANIZATIONS SUCH AS UL,
<br />ASTM, ASSE, AWWE, AGA, AND NFPA AS WELL AS THE MOST CURRENT VERSION OF
<br />THE STATE AND LOCAL CODES.
<br />24. ALL INSTALLED SYSTEMS, DEVICES, AND RELATED ITEMS SHALL BE TESTED IN
<br />PLACE. REPLACE ANY AND ALL CONTRACTOR SUPPLIED DEFECTIVE DEVICES, ITEMS
<br />OR SYSTEMS AT CONTRACTOR'S OWN EXPENSE BEFORE COMPLETION OF PROJECT.
<br />25. WHERE JOB CONDITIONS REQUIRE CHANGES FROM THE CONTRACT DOCUMENTS
<br />THAT DO NOT CHANGE THE SCOPE OR NATURE OF WORK REQUIRED, THE CONTRACTOR
<br />SHALL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE OWNER. NO OTHER
<br />CHANGES MAY BE MADE WITHOUT WRITTEN PERMISSION OF THE ENGINEER.
<br />26. ALL EQUIPMENT, FIXTURES, AND MATERIALS SHALL BE NEW AND UNUSED, AND
<br />INSTALLED IN STRICT CONFORMANCE TO MANUFACTURER'S RECOMMENDATIONS (U.O.N.).
<br />PROVIDE COMPLETE WITH ALL TRIM, STOPS, HANGERS, CARRIERS, SUPPORTS, ETC.
<br />INCLUDING PROVISIONS FOR BARRIER FREE USE, IF REQUIRED. WHERE FIXTURES ARE
<br />ACCESSIBLE THEY MUST COMPLY WITH ALL FEDERAL A.D.A. REGULATIONS AND STATE
<br />OF FLORIDA ACCESSIBILITY CODE.
<br />27. CONTRACTOR SHALL GUARANTEE ALL WORK FOR WHICH MATERIALS ARE
<br />FURNISHED, FABRICATED OR FIELD ERECTED, ALL FACTORY ASSEMBLED EQUIPMENT
<br />FOR WHICH NO SPECIFIC MANUFACTURER'S GUARANTEE IS FURNISHED, AND ALL WORK
<br />IN CONNECTION WITH THE INSTALLATION OF MANUFACTURER'S GUARANTEED
<br />EQUIPMENT. THE CONTRACTOR'S GUARANTEE SHALL LAST ONE YEAR FROM THE FINAL
<br />OWNER ACCEPTANCE OF THE WORK AND SHALL APPLY TO ALL DEFECTS IN
<br />MATERIALS AND WORKMANSHIP OF ANY KIND.
<br />28. PLUG OR CAP PIPE AND FITTINGS TO KEEP OUT DEBRIS DURING CONSTRUCTION.
<br />29. TURNS SHALL BE MADE WITH 2-6 BENDS WHERE SPACE PERMITS, ELSEWHERE
<br />WITH Y FITTINGS AND 6 BENDS.
<br />30. GENERAL CONTRACTOR SHALL INSURE/VERIFY THAT LOCATIONS INDICATED FOR
<br />PLUMBING CORRESPOND WITH STANDARD FIXTURES AS INDICATED ON ELEVATION,
<br />PLAN & DETAIL SHEET(S). ANY DISCREPANCIES SHALL BE REPORTED TO THE OWNER
<br />PRIOR TO INSTALLATION OF FIXTURES, UTILITIES AND PLUMBING EQUIPMENT.
<br />DISCREPANCIES REPORTED FOLLOWING INSTALLATION ARE THE SOLE RESPONSABILITY
<br />OF THE GENERAL CONTRACTOR.
<br />PLUMBING FIXTURES:
<br />1. INSTALL ALL PIPING AND FITTINGS FOR PLUMBING FIXTURES AS SHOWN ON THE
<br />DRAWINGS AND AS HEREINAFTER SPECIFIED, MAKING ALL CONNECTIONS THERETO.
<br />THE PLUMBING TRADE SHALL REVIEW THE ARCHITECTURAL DRAWINGS AND INCLUDE
<br />IN HIS BID AN AMOUNT TO FURNISH ANY FIXTURES SHOWN IN ADDITION TO THE
<br />FIXTURES SHOWN ON THE PLUMBING DRAWINGS.
<br />2. ALL ROUGHING -IN SHALL BE ACCURATELY LAID OUT, AND NO OFFSETS WILL BE
<br />ACCEPTED.
<br />3. PROVIDE CHROME PLATED RIGID OR FLEXIBLE SUPPLIES WITH STOPS, REDUCERS
<br />AND ESCUTCHEONS TO FIXTURES.
<br />4. WHERE FUTURE FIXTURES ARE SHOWN ON DRAWINGS TO BE ROUGHEO-IN, PLUG
<br />OR CAP OUTLET BRANCHES FOR SAME, GAS TIGHT AND WATER TIGHT. CAP OPENINGS
<br />IN WALLS WITH STAINLESS STEEL COVER PLATES, SECURED WITH KNOCK -OFF HEAD
<br />SCREWS
<br />5. ACCESSIABLE TOILETS TO HAVE FLUSH LEVER ON OPEN SIDE OF TOILET
<br />STALL.
<br />WATER PIPING AND FITTINGS:
<br />1. PROVIDE ALL WASHROOM GROUPS AND BRANCH TAKE -OFFS FROM MAINS WITH
<br />ISOLATING GATE VALVES. INSTALL STOP VALVE IN EACH FIXTURE SUPPLY.
<br />2. ABOVE GROUND WATER SERVICE SHALL BE PEX ASTM F B77, SOR 9 TUBING
<br />3. FITTINGS FOR PEX TUBE; ASTM F 1807, METAL -INSERT TYPE WITH COPPER OR
<br />STAINLESS STEEL CRIMP RINGS WITH MATCHING PEX TUBE DIMENSIONS
<br />4. MANIFOLD: MULTIPLE -OUTLET, PLASTIC OR CORROSIVE RESISTANT METAL
<br />ASSEMBLY COMPLYING WITH ASTM F 877j WITH PLASTIC OR CORROSION -RESISTANT
<br />METAL VALVE FOR EACH OUTLET.
<br />5. ALL HOT WATER PIPING SHALL BE INSULATED WITH 1' THICK JOHNS MANVILLE
<br />MICRO-LOK PIPE INSULATION, COMPLETE WITH VAPOR RETARDING JACKET AND LAP
<br />SEALING SYSTEM.
<br />SANITARY DRAINS AND FITTINGS:
<br />1. ALL SANITARY DRAINS SHALL BE TYPE OWV-PVC AS PERMITTED BY CODE.
<br />SUPPORTS:
<br />1. 2' NOMINAL AND UNDER, USE GRINNELL NO. 65 CLEVIS TYPE. 2-j' NOMINAL
<br />AND OVER, USE GRINNELL NO. 260 CLEVIS TYPE. PROVIDE SUITABLE HANGER ROOS
<br />AND BEAM CLAMPS OR INSERTS. PROVIDE PLASTIC INSERTS OVER HANGERS OR USE
<br />COPPER HANGERS FOR COPPER PIPING. IF COPPER PLATED STEEL HANGERS ARE
<br />USED, THE STEEL ROO SUPPORTS MUST BE ISOLATED FROM THE HANGER.
<br />2. SUPPORT VERTICAL LINES WITH GRINNELL 261 RISER CLAMP.
<br />3. HANG PIPING FROM BEAMS, GIRDERS, PURLINS, LONG SPAN JOISTS OR FROM
<br />ANGLES SUPPLIED AND INSTALLED BY THIS TRADE, SPANNING BETWEEN BEAMS,
<br />JOISTS OR OTHER SUPPORTS.
<br />4. HANGERS SHALL BE HUNG FROM STRUCTURAL STEEL MEMBERS WITH
<br />APPROPRIATE HANGER CLAMPS. NO WELDING TO OR BURNING, DRILLING OR PUNCHING
<br />OF STRUCTURAL STEEL MEMBER BY THIS TRADE, WILL BE PERMITTED UNDER ANY
<br />CIRCUMSTANCES.
<br />VENT PIPING:
<br />1. VENT PIPING UP TO AND INCLUDING 4' SHALL BE DWV-PVC. PROVIDE ALL
<br />FIXTURES WITH TRAPS AND VENTS.
<br />2. ALL VENT CONNECTIONS SHALL BE WITHIN 5'-0' OF THE TRAP AND NOT
<br />CLOSER THAN ONE DIAMETER OF THE TRAP PIPE SIZE.
<br />3. A VENT MAY BE CONNECTED TO A VENT STACK. ALL VENTS SHALL CONTINUE
<br />TO RISE AFTER LEAVING THE TRAP AND TERMINATE IN A VENT THRU ROOF WHERE
<br />SHOWN ON THE DRAWINGS.
<br />VALVES:
<br />1. ALL EXPOSED FIXTURE STOPS SHALL BE CHROME PLATED.
<br />2. VALVES SHALL BE THE SAME SIZE AS THE PIPE IN WHICH THEY ARE
<br />INSTALLED.
<br />EXPANSION JOINTS:
<br />1. AT HOT WATER LINES, USE FLEXONIC EXPANSION COMPENSATORS MODEL HB,
<br />PRESSURE EXTERNAL TO THE BELLOWS, DESIGNED FOR MAXIMUM WORKING PRESSURE
<br />OF 150 PSI.
<br />2. ALLOW FOR EXPANSION IN VERTICAL RUNS TO COMPENSATE FOR TEMPERATURE
<br />AND BUILDING STRUCTURAL MOVEMENTS.
<br />FLOOR DRAINS:
<br />1. INSTALL ALL FLOOR DRAINS WITH TRAP PRIMERS CONNECTED TO NEAREST COLO
<br />WATER FLUSH VALVE. ALL FLOOR DRAIN TRAPS SHALL BE VENTED.
<br />2. COOPERATE WITH GENERAL CONTRACTOR TO ESTABLISH FLOOR DRAIN LEVELS.
<br />PIPING INSULATION:
<br />1. INSTALL WATER OVERHEAD, STRAIGHT, PARALLEL OR PERPENDICULAR TO
<br />STRUCTURE AND WALLS. USE STANDARD FITTINGS FOR DIRECTION CHANGES.
<br />2. INSTALL GROUPS OF PIPING PARALLEL TO EACH OTHER WITH SPACE TO PERMIT
<br />APPLICATION OF INSULATION, IDENTIFICATIONS, AND SERVICE ACCESS, ON TRAPEZE
<br />HANGERS.
<br />3. INSTALL ECCENTRIC REDUCERS IN HORIZONTAL PIPING TO PERMIT DRAINAGE AND
<br />ELIMINATE AIR POCKETS.
<br />4. SHALL BE FREE FROM SURFACE DAMAGE. REPLACE ANY DAMAGED PIPE OR
<br />TUBING.
<br />5.
<br />6. INSTALL FLANGES OR UNIONS TO PERMIT REMOVAL OF EQUIPMENT WITHOUT
<br />DISTURBING PIPING SYSTEMS.
<br />7. ASSEMBLE JOINTS WITHOUT BENDING.
<br />B. ALL HANGERS AND ROOS SHALL BE OF A SIZE AND WEIGHT TO SAFELY
<br />SUPPORT THE PIPE SYSTEMS.
<br />9. ALL HANGERS MUST BE SUITABLE FOR TYPE OF MATERIALS BEING SUPPORTED
<br />TO PREVENT ELECTROLYSIS AND ABRASION.
<br />10. PIPING UP TO AND INCLUDING 2' SHALL BE SUPPORTED EVERY 8'-0'. PIPING
<br />2-j' AND OVER SHALL BE SUPPORTED EVERY 10'-0'.
<br />PLUMBING FIXTURE SCHEDULE:
<br />L-1 LAVATORY - AMERICAN STANDARD 'AQUALYN' NO. 0475.047, SELF RIMMING,
<br />VITREOUS CHINA, COUNTER MOUNTED, CENTER HOLE ONLY, WHITE. INSTALL 2-j'
<br />FROM FRONT EDGE OF COUNTERTOP. FAUCET HYDROTEK NON -MIXING AUTOMATIC
<br />FAUCET MODEL H-2603C(AC), SOLID BRASS, CHROME PLATED, SINGLE HOLE MOUNT.
<br />PROVIDE STANDARD PACKAGE WITH OPTIONAL HBL-02 THERMOSTATIC MIXING VALVE
<br />WITH CHECKS. PROVIDE HC-010 MULTI -UNIT POWER ADAPTER (ONE PER GROUP
<br />TOILET ROOM) MCGUIRE MFG. CO. NO. 155A CAST BRASS CHROME PLATED OPEN GRID
<br />P.O. PLUG, SEAMLESS BRASS TAILPIECE; NO. C8872 CHROME PLATED CAST BRASS
<br />BODY P-TRAP WITH CLEANOUTj NO 2165CC LAVATORY SUPPLY KIT, CHROME PLATED
<br />BRASS STOPS WITH FULL TURN BRASS STEM.
<br />V-1 VALVE - AMERICAN STANDARD 'WASHBROOK' NO. 6501.010 TOP SPUD,
<br />VITREOUS CHINA, WHITE. FLUSHVALVE HYDROTEK AUTOFLUSH VALVE NO. H-800C
<br />(AC), SOLID BRASS CHROME PLATED. CONNECT AUTOFLUSH VALVE TO POWER
<br />PROVIDED UNDER FIXTURE L-1.
<br />V-2 VALVE - SAME AS V-1 EXCEPT INSTALL IN CONFORMANCE WITH THE
<br />FLORIDA ACCESSIBILITY CODE WITH RIM AT 17' AFF. WC-1 WATER CLOSET AMERICAN
<br />STANDARD AFWALL ELONGATED FLUSH VALVE TOILET NO. 2257.103 TOP SPUD,
<br />VITREOUS CHINA, WHITE. FLUSHVALVE HYOROTEK AUTOFLUSH VALVE NO. H-8000C
<br />(AC), SOLID BRASS CHROME PLATED. CONNECT AUTOFLUSH VALVE TO POWER
<br />PROVIDED UNDER FIXTURE L-1. SEAT BEMIS NO. 1655C, OPEN FRONT LESS COVER,
<br />STAINLESS STEEL CHECK HINGE.
<br />WC-1 WATER CLOSET - AMERICAN STANDARD 'YORKVILLE' 1.6 GPF RIGHT HEIGHT
<br />ELONGATED PRESSURE ASSISTED TOILET, NO. 2878.016.020, WHITE (020), 30.75- x
<br />20.5' x 29.75'
<br />FO FLOOR DRAIN - STRAINERS TO BE POLISHED NICKEL BRONZE TOP, VANDAL
<br />PROOF SECURED.
<br />21412al
<br />0
<br />kalmm�
<br />LOCATION
<br />DOMESTIC PLAN
<br />1/4 to = 1 $-C 4/ 0 21 4/
<br />2- 2'
<br />SAN ITARY PLA,N
<br />1/4 of = 1 1-099 4/ 0 21 4/
<br />12- V N,
<br />LAV
<br />1 2" 11� 41�4' VTR
<br />I . ix 'N� � 1 -1
<br />12 V
<br />CO WC 12" V
<br />3' 1
<br />2/ MS
<br />3-
<br />LAV 3- WC
<br />WC FD
<br />W wc
<br />C
<br />FID
<br />PLUMBING SANITARY RISER
<br />IN
<br />N,
<br />UR 2" V
<br />UR
<br />WC
<br />�_41_AV LAV
<br />N, N 2 " 1
<br />2" V " f (LA K, z1qf
<br />CO
<br />FIELD VERIFY LOCATION OF 4
<br />SANITARY LINE TIE-IN
<br />DOMESTIC LEGEND
<br />SINK
<br />TOILET
<br />"W
<br />hLA
<br />URINAL
<br />DOMESTIC LINES
<br />PIPE SIZE
<br />C: COLD H: HOT
<br />DOMESTIC TIE-IN
<br />SANITARY LEGEND
<br />LAV LAVATORY
<br />WC TOILET
<br />UR URINAL
<br />-0 MS MOP SINK
<br />SANITARY LINES
<br />VENT LINES
<br />11 FD FLOOR DRAIN
<br />SANITARY TIE-IN
<br />VERTICAL STACK
<br />L
<br />tit
<br />111C
<br />kr,,
<br />It
<br />�_q
<br />r- 170
<br />L_
<br />0
<br />0
<br />F�"
<br />MA
<br />"__j
<br />0
<br />an
<br />W_j
<br />C)e
<br />rl�
<br />ine
<br />0
<br />U
<br />0
<br />cn
<br />0
<br />C_.)
<br />M
<br />(3)
<br />r4,)
<br />C.0
<br />L0
<br />C)
<br />00
<br />E
<br />0
<br />0
<br />Lo
<br />> to
<br />04 00
<br />LO
<br />04 cm
<br />W
<br />c) a)
<br />r--: PC)
<br />V) LO CO
<br />LO U-)
<br />Lj C14
<br />co
<br />En CR C:)
<br />M C)
<br />R
<br />V) ro
<br />V) C)
<br />C)
<br />LO
<br />C:)
<br />C/)
<br />C:)
<br />r'.) to
<br />- 00 U-
<br />19CO29
<br />cf)
<br />Q)
<br />C14
<br />LO
<br />c-
<br />U
<br />LL_
<br />:E
<br />0-
<br />V)
<br />U)
<br />Q) M
<br />c- NO
<br />C)
<br />Lr)
<br />review 06-24-2019
<br />approval 07-29-2019
<br />permit
<br />revision
<br />revision
<br />P- 101,
<br />
|