TRUSS SHOP DRAVANG NOTES: <br />THE GENERAL CONTRACTOR SHALL REVI EW AND APPROVE ROOF TRUSS SHOP DRAWINGS FOR <br />SIZE, SHAPE, DIMENSIONING, AND LAYOUT PRIOR TO SUBMITTAL TO THE ENGINEERS OF <br />RECORD FOR REVIEW! <br />PREFABRICATED WOOD TRUSSES SHALL BE DESIGNED IN ACCORDANCE WITH THE LATEST <br />EDITION OF"THE NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION" BY THE <br />NATIONAL FOREST PRODUCTS ASSOCIATION. WOOD TRUSS SHOP DRAWINGS SHALL INDICATE <br />THE FOLLOWING MINIMUM INFORMATION <br />1 . SHOP DRAWINGS SHALL BEAR THE SEAL AND SIGNATURE OF THE REGISTERED <br />PROFESSIONAL (STRUCTURAL) ENGINEER RESPONSIBLE FOR THE STRUCTURAL ANALYSIS <br />AND DESIGN OF THE INDIVIDUAL ROOF TRUSSES AND THE ROOF TRUSS SYSTEM. THIS <br />ENGINEER SHALL HOLD CURRENT VALID REGISTRATION AS A PROFESSIONAL ENGINEER IN <br />THE STATE OF FLORIDA. INDIVIDUAL TRUSS DESIGN SHEETS SHALL BE FULLY <br />COORDINATED WITH AND KEYED TO THE ROOF TRUSS FRAMING PLAN, WHICH SHALL <br />LIKEWISE BE SIGNED AND SEALED. IF THIS REQUIREMENT IS NOT FULFILLED IN DETAIL, THE <br />SUBMITTAL WILL BE REJECTED AND RETURNED AS INADEQUATEL <br />2. REQUIRED GENERAL INFORMATION: <br />A. ERECTION PLAN: SHOWING DIMENSIONED LOCATION AND TRUSS IDENTIFICATION- <br />B. BEARING DETAILS: SHOWING BEARING LENGTH, WIDTH AND DEPTH ONDICATING <br />CONFORMANCE TO DESIGN CALCULATIONS). <br />C. DESIGN LOADS: ALL DEAD, LIVE & WIND LOADS SHALL BE SHOWN ON THE ERECTION <br />PLAN OR TRUSS ELEVA11ON INDICATING CONFORMANCE TO TRUSS CALCULATIONS AND <br />ORIGINAL DESIGN CRITERIA. TRUSS SYSTEM DESIGNER SHALL GIVE FULL <br />CONSIDERATION TO THE FOLLOWING: <br />1. TRUSS DESIGN ENGINEER SHALL BE PROVIDED WITH A COMPLETE SET OF BOTH <br />ARCHITECTURAL AND STRUCTURAL CONTRACT DOCUMENTS PRIOR TO BEGINNING <br />DESIGN OF THE ROOF TRUSS SYSTEM. <br />2. TRUSS SYSTEM SHALL BE DESIGNED AS "COMPONENTS AND CLADDING"AS <br />DEFINED BY THE APPLICABLE BUILDING CODE WITH DUE CONSIDERATION OF, <br />ENCLOSED", -PARTALLY ENCLOSEU' AND -COMPLETELY OPEN" PORTIONS OF THE <br />STRUCTURE AND USE OF APPROPRIATE GUST RESPONSE & SHAPE FACTORS. <br />D. ALL PERMANENT BRACING AND BRIDGING: SHOW TOP CHORD, BOTTOM CHORD, AND <br />WEB MEMBER BRACING ON ERECTION LAYOUT PLAN AND TRUSS ELEVATIONS. <br />SUPPLIER AND INSTALLER OF THIS BRACING SHALL ALSO BE INDICATED. <br />E. TRUSS DIMENSION: SHOW DEPTH, SPAN, BEARING, HEIGHT AND SLOPES AT ALL <br />CRITICAL POINTS. <br />3. INFORMATION THAT SHALL BE THE RESPONSIBILITY OF THE FABRICATOR AND TRUSS <br />DESIGNER AND SHALL BE COMPLETELY DETAILED WITHIN THE SHOP DRAWING SUBMITTAL. <br />A. MEMBER DESIGN: INCLUDING WEB CONFIGURATION, MEMBER SIZE, GRADE AND <br />SPECIES OF LUMBER, FABRICATED SPLICES <br />AND MEMBER BRACING REQUIRED BY TRUSS DESIGN. <br />B. INTERIOR CONNECTION: DESIGN AND SHOW DETAIL OF WEB AND CHORD CONNECTIONS, <br />CONNECTION PLATES AND PLATE CAPACITIES. <br />C. ERECTION PLAN: <br />SHOW SPACING AND LAYOUT OF ANY TEMPORARY BRACING REQUIRED FOR ERECTION. <br />D. STRUCTURAL DESIGN OF TRUSSES: <br />SUBMIT COMPLETE TRUSS CALCULATIONS AND OBTAIN ALL APPROVALS NECESSARY FOR <br />CONFORMANCE TO BUILDING CODE. VERIFY SUBMITTAL AND APPROVAL BY SENDING A <br />COPY TO THE ENGINEER OF RECORD. <br />E. ERECTION: <br />FURNISH TRUSS ERECTOR WITH ALL DATA NECESSARY FOR PROPER INSTALLATION. <br />F. INDICATE GRAVITY LOAD REACTIONS AND UPLIFT REACTIONS AT ALL SUPPORT POINTS <br />FOR EACH SPECIFIC TRUSS TYPE. <br />G. CONNECTION HARDWARE: <br />SUBMIT REQUIRED CAPACITY AND SUGGESTED MANUFACTURER AND MODEL OF ANY <br />REQUIRED PRE-ENGINEERED PREFABRICATED HARDWARE. QNCLUDE NUMBER OF MAILS, <br />SPLICES OR BOLTS REQUIRED TO MAKE <br />PROPER CONNECTION). <br />NOTE: ALL CONNECTIONS BETWEEN PRE-ENGINEERED PREFABRICATED TRUSSES SHALL BE <br />THE RESPONSIBILITY OF THE TRUSS DESIGNER/FABRICATOR (BECAUSE OF THE <br />EFFECT OF THE CONNECTION FASTENINGS ON THE TRUSS DESIGN). <br />H. ALL PERMANENT BRIDGING REQUIRED TO BRACE THE BOTTOM CHORDS AGAINST <br />BUCKLING DUE TO POTENTIAL STRESS REVERSAL AND BOTTOM CHORD COMPRESSION <br />RESULTING FROM UPLIFT FORCES ON THE ROOF IMPOSED BY THE SPECIFIED WIND <br />LOADING CRITERIA. <br />4. MINIMUM ROOF TRUSS DESIGN LOADS: <br />A. ROOF LIVE: <br />20 PSF. <br />B. TOP CHORD DEAD LOAD: <br />15 PSF. <br />C. BOTTOM CHORD DEAD LOAD: <br />5 PSF. <br />D. WIND FORCES: DESIGN FOR THE MAXIMUM FORCES, (INCLUDING UPLIFT), REQUIRED BY <br />THE FLORIDA BUILDING CODE <br />67 ED. (2017) AND ASCE 7-10- SEE DESIGN LOADS FOR WIND <br />LOAD DESIGN CRITERIA. <br />"SPECIALTY" DELEGATED STRUCTURAL ENGINEER NOTE: <br />SPECIALTY ENGINEERING WORK SHALL BE PERFORMED BY KNOWLEDGEABLE PROFESSIONAL <br />ENGINEERS WHO'S DISCIPLINE SHALL BE STRUCTURAL. THEY SHALL HOLD CURRENT VALID <br />REGISTRATION IN THE STATE OF FLORIDA AS PROFESSIONAL ENGINEERS. THE GENERAL <br />CONTRACTOR AND STRUCTURAL SUBCONTRACTORS ARE ADVISED THAT THE ARCHITECT AND <br />STRUCTURAL ENG NEER OF RECORD SHALL HAVE THE RIGHT TO APPROVE OR DISAPPROVE <br />ANY INDIVIDUAL SPECIALTY ENGINEER, WITHOUT INCURRING ANY ADDITIONAL COSTS OR <br />LIABILITY TO THE OWNER, THE ARCHITECT OF RECORD OR THE ENGINEER OF RECORD. IT <br />WOULD BE PRUDENT FOR THE G.C_ TO SUBMIT THE QUALIFICATIONS OF THE PROPOSED <br />"SPECIALTY' STRUCTURAL ENGINEER(S) TO THE STRUCTURAL ENGINEER OF RECORD, PRIOR <br />TO FORMALLY CONTRACTING FOR SUCH SERVICES. THE "SPECIALTY" STRUCTURAL ENGINEER <br />IS CAUTIONED THAT ALL SUBMITTALS MUST BE PREPARED AND SUBMITTED IN ACCORDANCE <br />WITH THE GUIDELINES PUBLISHED BY THE FLORIDA DEPARTMENT OF PROFESSIONAL <br />REGULATION, BOARD OF PROFESSIONAL ENGINEERS IN RULE NUMBER 21 H-19-001, -RULE AND <br />STATEMENTS ON RESPONSIBILITY OF PROFESSIONAL ENGINEERS". <br />1 . IT IS THE DELEGATED SPECIALTY ENGINEERS RESPONSIBILITY TO REVIEW THE ENGINEER <br />OF RECORD'S WRITTEN ENGINEERING CRITERIA REGARDING THE SPECIALTY ENGINEERING <br />REQUIREMENTS IN ORDER TO DETERMINE THE SCOPE OF WORK OF THE SPECIALTY <br />ENGINEERING. <br />2. THE DELEGATED ENGINEERING DOCUMENT SUBMITTALS SHALL CCMPLYWITH THE <br />WRITTEN ENGINEERING REQUIREMENTS RECEIVED FROM THE ENGINEER OF RECORD. THE <br />DELEGATED ENGINEERING SUBMITTAL SHALL INCLUDE THE PROJECT NAME AND THE <br />DESIGN CRITERIA USED IN PREPARING THE SUBMITTAL. <br />3. IF THE DELEGATED ENGINEER DETERMINES THERE ARE DETAJLS, FEATURES OR <br />UNANTICIPATED PROJECT LIMITS WHICH CONFLICT WITH THE WRITTEN ENGINEERING <br />REQUIREMENTS PROVIDED BY THE ENGINEER OF RECORD, THE DELEGATED ENGINEER <br />SHALL IMMEDIATELY CONTACT THE ENGINEER OF RECORD TO RESOLVE THE CONFLICT. <br />4. THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS <br />TO THE ENGINEER OF RECORD FOR REVIEW. ALL DELEGATED ENGINEERING DOCUMENTS <br />SHALL BE SIGNED AND SEALED BY THE DELEGATED ENGINEER AND SHALL INCLUDE THE <br />FOLLOWING: <br />A. FRAMING PLANS, DETAILS, CONNECTIONS, ETC. AS REQUIRED TO DEFINING THE <br />CONFIGURATION AND STRUCTURAL CAPACITY OF STRUCTURAL COMPONENTS AND/OR <br />THEIR ASSEMBLY INTO STRUCTURAL SYSTEM. <br />B. COMPUTATIONS HAVING ADEQUATE DETAIL FOR THE ENGINEER OF RECORD TO <br />DETERMINE THAT THE SUBMITTAL WAS FULLY ENGINEERED AND DOCUMENTED. NO <br />DETAILED REV�IEW OF THE DELEGATED SPECIALTY ENGINEERING CALCULATIONS WILL <br />BE PROVI DIED BY THE E.O.R. <br />INSTRUCTIONS FOR INSTALLATION OF DRILLED IN RODS. SCREWS. AND DOWEL <br />ANCHORS: <br />I . SEE DRAWINGS FOR SIZE, LENGTH TYPE AND SPACING OF ANCHORS REQUIRED. <br />NOTE: DRILLED IN ANCHORS WILL NOT BE AN ACCEPTABLE ALTERNATIVE TO <br />SPECIFIED EMBEDDED ANCHORS (ANCHOR BOLTS, HEADED STUDS, ETC-) <br />2. CLOSELY FOLLOW ANCHOR INSTALLATION INSTRUCTIONS PROVIDED WITH THE PRODUCT, <br />BY THE MANUFACTURER. THIS INFORMATION INCLUDES DRILL TYPE AND DIAMETER FOR A <br />GIVEN ANCHOR OR DOWEL SIZE, CLEANING INSTRUCTIONS FOR THE HOLE (REMOVAL OF <br />DRILL DUST OR SLURRY BY COMPRESSED AIR AND WATER), AND MATERIAL INSTALLATION <br />AND QUANTITY FOR A GIVEN APPLICATION. <br />3. REGARDING "EPDXYANCHORS, PROVIDE ADHESIVES WHICH ARE MANUFACTURED AND <br />DISTRIBUTED AS TWO PART (BASE/HARDENER) CARTRIDGE INSTALLED WITH DOUBLE <br />PLUNGER CAULKING GUN WITH AUTOMATIC MIXING NOZZLE SUPPLIED BY THE <br />MANUFACTURER. EPDXY SHALL MEET THE MINIMUM REQUIREMENTS OF ASTM C a8l <br />SPECIFICATION FOR TYPE 1, 11, IV, V, GRADE 3, CLASS B, C AND D AND MUST DEVELOP A <br />MINIMUM 12,650 PSI COMPRESSIVE YIELD STRENGTH AFTER 7 DAY CURE. <br />PREFERABLE MANUFACTURERS ARE AS FOLLOW: <br />A- SIMPSON STRONG TIE "SET-XP" EPDXY <br />B. HILTI'HY-150" <br />OTHER MANUFACTURER'S PRODUCTS WILL NOT BE CONSIDERED UNLESS ALLOWABLE <br />LOAD DATA, BASED UPON TESTING LABORATORY RESULTS, ARE SUBMI[TTED FOR REVIEW <br />AND CONSIDERATION. OUR PREFERENCE FOR THESE PRODUCTS IS BASED UPON THE <br />AUTOMATIC MIXING OF THE TWO PARTS PRIOR TO DISCHARGE FROM THE GUN AND THEIR <br />LITERATURE WHICH REPRESENTS A CONSIDERABLE AMOUNT OF BACK UP TESTING. <br />4. GENERALLY, ANCHOR DRILLED IN DEPTHS SHOULD NOT BE LESS THAN 8 INCHES <br />WHENEVER POSSIBLE. WHEN ANCHORS ARE INSTALLED THROUGH BRICK AND/OR VENEER, <br />THE ANCHOR SHALL PENETRATE INTO THE BACK UP STRUCTURAL MASONRY OR CONCRETE <br />AT LEAST 6 INCHES. <br />5. WHERE DRILLED IN EXPANSION ANCHORS ARE REQUESTED IN LIEU OF CAST IN PLACE <br />ANCHORS, THEY MUST BE REQUESTED IN WRITING BEFORE INSTALLATION AND ADEQUATE <br />MANUFACTURER'S LITERATURE MUST BE SUBMITTED AS DOCUMENTATION. THE <br />SUBSTITUTION OF EXPANSION ANCHORS MAY OR MAY NOT BE ACCEPTED DEPENDING <br />UPON THE LOADING AND SPECIFIC APPLICATION. DO NOT SUBMIT SLEEVE ANCHORS. ALL <br />EXPANSION ANCHORS MUST BE WEDGE ANCHORS. GENERALLY, IF EXPANSION ANCHORS <br />ARE PERMITTED THEY WILL BE REQUIRED TO BE AT LEAST ONE SIZE LARGER AND MORE <br />CLOSELY SPACED THAN THE SPECIFIED EMBEDDED ANCHORS. <br />6. CONCRETE AND MASONRY SCREWS SHALL BE 114" DIAMETER 1 1/2" MINIMUM EMBEDMENT <br />INSTALLED IN DRILLED HOLES USING AN APPROPRIATE BIT DIAMETER. SCREWS SHALL BE <br />MADE FROM TEN HUNDRED SERIES COLD ROLLED STEEL AND SHALL BE FLUOROCARBON <br />COATED. PROVIDE "TITAN"SCREWS BY SIMPSON STRONG TIE OR EQUAL. <br />7. SCREWS SHALL BE MADE FROM TEN HUNDRED SERIES COLD ROLLED STEEL AND SHALL BE <br />FLUOROCARBON COATED. PROVIDE "TITAN" SCREWS BY SIMPSON STRONG TIE OR EQUAL. <br />8. DRILL IN REBAR DOWELS SHALL BE SET USING A TWO PART EPDXY AS DESCRIBED ABOVE <br />IN NOTE NO. 2. <br />9. ALL BOLTS AND SCREWS TO BE HOT -DIPPED, GALVANIZED OR STAINLESS STEEL. <br />STRUCTURAL SYSTEM, MATERIAL OR PROCEDURES SUBSTITUTION REQUESTS: <br />I . UNDER NO CIRCUMSTANCES WILL STRUCTURAL SYSTEM, STRUCTURAL MATERIAL OR <br />STRUCTURAL PROCEDURE SUBSTITUTIONS BE CONSIDERED BEFORE THE BIDS ARE <br />ANALYZED AND A SUCCESSFUL BIDDER IS SELECTED. BIDS ARE TO BE BASED UPON AS <br />SPECIFIED STRUCTURAL SYSTEMS, MATERIALS AND PROCEDURES. STRUCTURAL BIDS <br />RECEIVED WITH FOOTNOTES OR CAVIIATES WILL BE MARKED AS NON -COMPLIANT AND WILL <br />BE REJECTED. <br />2. SHOULD THE SUCCESSFUL BIDDER WISH TO SUBMIT AN ALTERNATE STRUCTURAL <br />MATERIAL, SYSTEM OR PROCEDURE, THE FOLLOWING WILL BE REQUIRED AND SHALL BE <br />CLEARLY UNDERSTOOD BY THE CONTRACTOR PRIOR TO THE SUBMITTAL OF ANY SUCH <br />SUBSTITUTION: <br />A. CONTACT THE ARCHITECT AND STRUCTURAL ENGINEER TO DISCUSS THE PROPOSED <br />SUBSTITUTION BEFORE MAKING ANY FORMAL SUBMITTAL. THERE MAY BE REASONS <br />WHY THE SUBSTITUTION WILL BE REJECTED AND BETTER TO FIND THAT OUT BEFORE <br />WASTING TIME IN THE PREPARATION OF A FORMAL SUBMITTAL. <br />B. IF THE ARCHITECT AND THE STRUCTURAL ENGINEER HAVE NO OBJECTION TO THE <br />INTENT OF THE SUBSTITUTION, THE FORMAL SUBMITTAL SHALL INCLUDE THE <br />PROPOSED CREDIT (ALONG WITH BACK-UP COST DATA) TO THE OWNER TO BE <br />SUBTRACTED FROM THE CONTRACT PRICE, SHOULD THE SUBSTITUTION BE ACCEPTED. <br />C. IF THE SUBSTITUTION ONLY REQUIRES A BRIEF REVIEW, SUCH WILL BE PROVIDED <br />WITHOUT CHARGE. IF THE DETERMINATION OF THE ACCEPTABILITY OF THE PROPOSED <br />SUBSTITUTION WILL REQUIRE STRUCTURAL ANALYSIS AND OR RESEARCH, THE <br />CONTRACTOR SHALL BE PREPARED TO REIMBURSE (ON THE BASIS OF HOURLY <br />INVOICING) THE STRUCTURAL ENGINEER FOR THE TIME REQUIRED TO ANALYZE THE <br />STRUCTURAL RAMIFICATIONS OF MAKING THE SUBSTITUTION. IF THE SUBSTITUTION IS <br />ACCEPTABLE AND THE CONTRACTOR AND OWNER AGREE TO PROCEED WITH THE <br />CHANGE, THE ARCHITECT AND STRUCTURAL ENGINEER WILL BE REIMBURSED FOR <br />MAKING THE CHANGES TO THE DESIGN AND THE STRUCTURAL DRAWING DETAILS ON <br />THE BASIS OF HOURLY INVOICING AND SUCH WILL BE SUBTRACTED FROM THE CREDIT <br />RESULTING FROM MAKIING THE PROPOSED CHANGE TO THE STRUCTURAL SYSTEM, <br />MATERIAL(S) OR PROCEDURES - <br />DIMENSIONING FOR BUILDING LAYOUT: <br />NOTE: THE MAJORITY OF THE PLAN DIMENSIONING IS PROVIDED ON THE ARCHITECTURAL <br />DRAWINGS. USE BOTH STRUCTURAL AND ARCHITECTURAL DRAWINGS TOGETHER FOR <br />BASIC LAYOUT AND CONSTRUCTION OF THIS PROJECT. ANY OBSERVED <br />DESCREPAINCIES BETWEEN ARCHITECTURAL DRAWING DIMENSIONING AND <br />STRUCTURAL DRAWING SCALE LAYOUT SHOULD BE BROUGHT TO THE ATTENTION OF <br />THE ARCHITECT IMMEDIATELY UPON DISCOVERY. <br />DESIGN WIND PRESSURE CRITERIA: <br />BUILDING CODE: THE FLORIDA BUILDING CODE 6TH ED. (2017) <br />SPECIAL INSPECTION REQUIREMENTS: NO <br />(ENHANCED HURRICANE PROTECTION AREAS (EHPA)): NONE <br />DESIGN WIND LOADING CRITERIA: <br />CODE: ASCE 7-10 <br />RISK CATEGORY OF BUILDINGS: CATEGORY 11 <br />ULTIMATE DESIGN WIND SPEED VuLT 138 MPH (3 SEC GUSTS) <br />NOMINAL DESIGN WIND SPEED VASD 107 MPH (3 SEC GUSTS) <br />EXPOSURE CATEGORY = B <br />WINDBORNE DEBRIS REGION - NO <br />(+/-) APPLIED PRESSURES AGAINST BUILDING SURFACES: <br />ALL TABULATED VALUES BELOW ARE ULTIMATE LOADS <br />ZONE 1: IS LOCATED MORE THAN DISTANCE (a) FROM THE EDGE OF THE ROOF <br />ZONE 2: IS LOCATED WITHIN DISTANCE (a) FROM THE EDGE OF THE ROOF <br />ZONE 3: IS LOCATED WITHIN DISTANCE (a) FROM EACH ROOF EDGE AT EXTERIOR <br />CORNERS <br />ZONE 4: IS LOCATED MORE THAN DISTANCE (a) FROM THE EDGE OF THE BUILDING <br />ZONE 5: IS LOCATED WITHIN DISTANCE (a) FROM THE EDGE OF THE BUILDING <br />EFFECTIVE AREA (SQ. FT.) <br />ALL AREAS <br />ZONE 3 <br />59 PSF <br />89 PSF <br />ZONE4 <br />ZONE 5 <br />10 <br />20 <br />34 <br />37 <br />33 . <br />i16 <br />34 <br />46 <br />33 <br />43 <br />'a"= T- 9' <br />�V' <br />�yccilc: 1/4" = 1'-0" <br />kNALL ELEVATION_ <br />�%GMAN <br />ARCHITECTS, P.A. <br />AA0003150 <br />625 EAST ORANGE ST. <br />LAKELAND, FL 33BOl <br />E-MAIL: FWARCH@ <br />FURRANDWEGMAN.COM <br />TEL 863 688 121 1 <br />FAX 863 6E3E3 1473 <br />@ COPYRIGHT 2019 FURR & AEGMAN ARCHITECTS, P-A. <br />THE DESIGN AND CONCEPTS DEPICTED HEREIMTH ARE THE <br />SOLE PROPERTY OF FURR & IAEGMAN ARCHITECTS, P.A. <br />NO REPRODUCTION, REVISION, OR REUSE OF THIS <br />DRAWING IS AUTHORIZED WITHOUT SPECIFIC WRITTEN <br />PERMISSION. ALL RIGHTS RESERVED. <br />in <br />In M3 <br />NJ ED <br />z to <br />.4 0*% <br />m <br />z <br />0 129 <br />101� w <br />Z f] <br />w <br />F- <br />z <br />0 <br />Lu <br />Lli <br />m: <br />U) <br />F7 <br />z <br />0 <br />F- <br />2: <br />cr_ <br />C) <br />U) <br />LLI <br />0 <br />z <br />0 <br />U) <br />5; <br />LLI <br />w <br />Lu <br />F- <br /><1 <br />C14 <br />cl) <br />It <br />to <br />co <br />r­ <br />04 <br />c:) <br />Q <br />CID <br />cy) <br />0 <br />cl <br />z <br />0 <br />z <br />w <br />F_ <br />w <br />c/) <br />0 <br />w <br />_j 0 <br />0 <br />_j < <br />z <br />U) <br />W <br />0 <br />u) <br />U) <br />F__ <br />0 <br />z <br />m <br />0 <br />0 <br />w <br />n _r 04 <br />T <br />z <br />< <br />w cl) <br />Lo <br />w <br />0 <br />N w co <br />(D :3 <br />LL <br />_j <br />Z LL <br />LL < w cd <br />c:) <br />0— > <br />C) <br />w <br />Y <br />Lo Q� <br />W <br />>- <br />I- T <br />< cl) a- <br />co <br />< <br />Lo <br />Do w <br />0 MN <br />:f <br />CL <br />PROJ MGR: <br />BY: <br />D H7CKn <br />SF <br />JOB <br />NUMBER: <br />2020-13 <br />SHEET <br />NUMBER: <br />SN-2_ <br />