LIGHT FIXTURE SCHEDULE
<br />LAMPS
<br />TYPE
<br />MANUFACTURER CATALOG NUMBER
<br />VOLTS
<br />MOUNTING
<br />COMMENTS
<br />I
<br />QTY
<br />WATTS/TYPE
<br />CREE LIGHTING CR22-32L; 35WLED; 50K
<br />2X2 LED LIGHT FIXTURE, COORDINATE
<br />FINAL LIGHTING SELECTION WITH
<br />APPROVED EQUAL FROM TAMPA BAY LIGHTING
<br />35W
<br />GRID
<br />OWNER.
<br />Al
<br />_
<br />LED
<br />120V
<br />CEILING
<br />APPROVED EQUAL FROM SESCO LIGHTING
<br />APPROVED EQUAL FROM WESTERN FLORIDA LIGHTING
<br />CREE LIGHTING
<br />2X2 LED LIGHT FIXTURE, COORDINATE
<br />BACK UP
<br />FINAL LIGHTING SELECTION WITH
<br />APPROVED EQUAL FROM TAMPA BAY LIGHTING
<br />35W
<br />GRID
<br />OWNER. WITH EMERGENCY BATTERY
<br />Al/EM
<br />_
<br />LED
<br />120V
<br />CEILING
<br />BACK UP.
<br />APPROVED EQUAL FROM SESCO LIGHTING
<br />APPROVED EQUAL FROM WESTERN FLORIDA LIGHTING
<br />LITHONIA
<br />72TL4 2'X4' LED
<br />2X4 LED LIGHT FIXTURE, COORDINATE
<br />FINAL LIGHTING SELECTION WITH
<br />APPROVED EQUAL FROM TAMPA BAY LIGHTING
<br />44W
<br />GRID
<br />OWNER.
<br />B
<br />-
<br />LED
<br />120V
<br />CEILING
<br />APPROVED EQUAL FROM SESCO LIGHTING
<br />APPROVED EQUAL FROM WESTERN FLORIDA LIGHTING
<br />LITHONIA
<br />7BACKUP
<br />2X4 LED LIGHT FIXTURE, COORDINATE
<br />FINAL LIGHTING SELECTION WITH
<br />APPROVED EQUAL FROM TAMPA BAY LIGHTING
<br />44W
<br />GRID
<br />OWNER. WITH EMERGENCY BATTERY
<br />B/EM
<br />_
<br />LED
<br />120V
<br />CEILING
<br />BACK UP.
<br />APPROVED EQUAL FROM SESCO LIGHTING
<br />APPROVED EQUAL FROM WESTERN FLORIDA LIGHTING
<br />LITHONIA
<br />LITHONIA
<br />WF6-LED-50K-90CRI-MW
<br />7W
<br />6" LED RECESSED CAN LIGHT,
<br />COORDINATE FINAL LIGHTING
<br />APPROVED EQUAL FROM TAMPA BAY LIGHTING
<br />14W
<br />SELECTION WITH OWNER.
<br />C
<br />LED
<br />120V
<br />RECESSED
<br />APPROVED EQUAL FROM SESCO LIGHTING
<br />APPROVED EQUAL FROM WESTERN FLORIDA LIGHTING
<br />MACRO AIR
<br />CEILING FAN, COORDINATE FINAL
<br />COLOR BLACK
<br />SELECTION WITH OWNER.
<br />APPROVED EQUAL FROM TAMPA BAY LIGHTING
<br />350W
<br />CEILING
<br />F
<br />-
<br />LED
<br />120V
<br />FAN
<br />APPROVED EQUAL FROM SESCO LIGHTING
<br />APPROVED EQUAL FROM WESTERN FLORIDA LIGHTING
<br />LITHONIA
<br />ELM2L
<br />120V OR 277V AC. EMERGENCY UNIT
<br />PROVIDED WITH TEST SWITCH, STATUS
<br />APPROVED EQUAL FROM TAMPA BAY LIGHTING
<br />120/
<br />WALL
<br />INDICATOR AND RECHARGEABLE
<br />EL
<br />2
<br />1.8W/LED
<br />277V
<br />OR
<br />BATTERY. MAINTENANCE -FREE
<br />APPROVED EQUAL FROM SESCO LIGHTING
<br />CEILING
<br />NICKEL -CADMIUM BATTERY PROVIDES
<br />APPROVED EQUAL FROM WESTERN FLORIDA LIGHTING
<br />90 MINUTES OF EMERGENCY POWER.
<br />LITHONIA
<br />EXR LED EL M6
<br />EXIT SIGN WITH RED LETTERS. WHITE
<br />CEILING
<br />THERMOPLASTIC HOUSING.
<br />APPROVED EQUAL FROM TAMPA BAY LIGHTING
<br />120/
<br />OR
<br />MAINTENANCE -FREE NI -CAD BATTERY
<br />EX
<br />-
<br />2W/LED
<br />277V
<br />WALL
<br />PROVIDES 90 MINUTES OF
<br />APPROVED EQUAL FROM SESCO LIGHTING
<br />MOUNT
<br />EMERGENCY POWER.
<br />APPROVED EQUAL FROM WESTERN FLORIDA LIGHTING
<br />LITHONIA
<br />ECR LED HO M6
<br />RED LETTERS, DUAL -VOLTAGE INPUT
<br />120V OR 277V AC; 9.6V OUTPUT.
<br />APPROVED EQUAL FROM TAMPA BAY LIGHTING
<br />120/
<br />NICKEL -CADMIUM BATTERY PROVIDES
<br />EXL
<br />2
<br />3.8WlLED
<br />277V
<br />CEILING
<br />90 MINUTES OF EMERGENCY POWER.
<br />APPROVED EQUAL FROM SESCO LIGHTING
<br />HIGH OUTPUT (HO) OPTION POWERS UP
<br />APPROVED EQUAL FROM WESTERN FLORIDA LIGHTING
<br />TO 2 LED REMOTE LAMPS.
<br />NOTES:
<br />1. SUBSTITUTIONS WILL NOT BE PERMITTED WITHOUT APPROVAL FROM THE ENGINEER, FOURTEEN DAYS PRIOR TO BID DATE.
<br />2. VERIFY LIGHTING FIXTURE COLOR/FINISH WITH ARCHITECT PRIOR TO ORDERING.
<br />3. ADJUST MOUNTING HEIGHTS/LOCATIONS TO SUIT FIELD CONDITIONS.
<br />4. (2) LAMPS TO BE WIRED IN PARALLEL FOR EMERGENCY BALLAST.
<br />DISCONNECT SCHEDULE
<br />D/C #
<br />SIZE
<br />POLES
<br />PHASE
<br />NEMA
<br />FUSE
<br />VOLT.
<br />SERVES
<br />COMMENTS
<br />D-1
<br />60A
<br />3
<br />3
<br />3R
<br />NON-F
<br />208
<br />RTU-1
<br />MOUNT ON UNIT
<br />D-2
<br />60A
<br />3
<br />3
<br />3R
<br />NON-F
<br />208
<br />RTU-2
<br />MOUNT ON UNIT
<br />D-3
<br />30A
<br />3
<br />3
<br />3R
<br />NON-F
<br />208
<br />KSF-1
<br />MOUNT ON UNIT
<br />D-4
<br />30A
<br />3
<br />3
<br />3R
<br />NON-F
<br />208
<br />KEF-1
<br />MOUNT ON UNIT
<br />D-5
<br />30A
<br />3
<br />3
<br />3R
<br />NON-F
<br />208
<br />KEF-2
<br />MOUNT ON UNIT
<br />D-6
<br />400A
<br />3
<br />3
<br />3R
<br />400A
<br />208
<br />MAIN
<br />MOUNT ON WALL
<br />NOTES
<br />1.
<br />VERIFY FUSE SIZES FOR ACTUAL EQUIPMENT SUBMITTED.
<br />2.
<br />FUSES SHALL BE DUAL ELEMENT, TIME DELAY, 100,000 AIC MININUM.
<br />3.
<br />FINAL CONNECTIONS TO MECHANICAL EQUIPMENT FROM DISCONNECT SHALL BE FLEX. FLEX
<br />SHALL BE WATERTIGHT AT EXTERIOR OR WET LOCATIONS.
<br />ADDITIONAL POLE TO DISCONNECT NEUTRAL SHALL BE PROVIDED WHERE REQUIRED.
<br />L4.
<br />5.
<br />ALL DISCONNECTS SHALL HAVE LOCKED OFF PROVISION.
<br />SPECIAL INFORMATIONAL NOTE:
<br />THIS DRAWING PREPARED FOR TENANT IMPROVEMENTS TO AN
<br />EXISTING BUILDING OR BUILDING CONSTRUCTED BY OTHERS
<br />IT IS UNDERSTOOD THAT ANY WARRANTY INFORMATION
<br />CONCERNING EQUIPMENT INSTALLED MUST BE FORWARDED TO
<br />THE OWNER AND THAT ANY AND ALL CONTRACTORS SHALL
<br />GUARANTEE THEIR WORK FOR A PERIOD OF ONE YEAR FROM THE
<br />DATE OF OWNERS ACCEPTANCE.
<br />ENGINEER IS NOT RESPONSIBLE FOR MATERIALS, METHODS,
<br />INSTALLATION, AND CONSTRUCTION WHICH DEVIATE FROM
<br />CONSTRUCTION DOCUMENTS AND SPECIFICATIONS.
<br />ELECTRICAL SHEET INDEX
<br />EO.1 -
<br />ELECTRICAL GENERAL
<br />EO.2 —
<br />ELECTRICAL SPECIFICATIONS
<br />E4.1 —
<br />ELECTRICAL PROPOSED LIGHTING PLAN
<br />E5.1 —
<br />ELECTRICAL PROPOSED POWER PLAN
<br />E5.2 —
<br />ELECTRICAL ROOF POWER PLAN
<br />E7.1 —
<br />ELECTRICAL SCHEDULES & RISER DIAGRAM
<br />E8.1 -
<br />NOT USED
<br />EO.1 -
<br />ELECTRICAL DETAILS
<br />SWITCHES
<br />0
<br />$M
<br />0S
<br />$a
<br />REFER TO SHEET E9.1 FOR SWITCH DETAILS.
<br />ELECTRICAL SYMBOL LEGEND
<br />WIRING DEVICES
<br />NOTE: THE FOLLOWING ABBREVIATIONS APPLY TO WIRING DEVICES WHERE INDICATED:
<br />'WP' INDICATES WEATHERPROOF WHILE -IN -USE ENCLOSURE. ENCLOSURE SHALL HAVE
<br />LOCKABLE COVER. DEVICES SHALL BE LISTED AS WEATHER RESISTANT. (WR)
<br />'EWC' INDICATES DEVICE MOUNTED BEHIND ELECTRIC WATER COOLER ENCLOSURE.
<br />COORDINATE DEVICE LOCATION WITH PLUMBING CONTRACTOR AND APPROVED
<br />"2P" INDICATES A 2-POLE SWITCH
<br />SHOP DRAWINGS PRIOR TO ROUGH -IN. CIRCUIT BREAKER SHALL BE GFCI TYPE.
<br />'H'
<br />INDICATES HORIZONTALLY MOUNTED WIRING DEVICE.
<br />"3" INDICATES THREE-WAY SWITCH
<br />'R'
<br />INDICATES DEVICE SHALL BE A RED COLOR. DEVICE IS CONNECTED TO A CIRCUIT
<br />FED FROM THE GENERATOR (IF APPLICABLE).
<br />"4" INDICATES FOUR-WAY SWITCH
<br />'FD'
<br />INDICATES RECEPTACLE MOUNTED IN FLOOR DUCT. INSTALL ACCESSORIES FOR
<br />MOUNTING OF RECEPTACLE IN FLOOR DUCT SYSTEM.
<br />"30A" INDICATES THE AMPERAGE OF THE SWITCH FOR NON-STANDARD
<br />'IG'
<br />ISOLATED GROUND
<br />SWITCHES
<br />'USB'
<br />INDICATES RECEPTACLE WITH USB OUTLETS.
<br />(I)
<br />20 AMP SIMPLEX RECEPTACLE, RECESS MOUNT 18" AFF TO CENTER OF BACKBOX OR
<br />REFER TO SHEET E9.1 FOR SWITCH DETAILS.
<br />'I'
<br />AT HEIGHT INDICATED.
<br />"K" INDICATES KEY SWITCH. PROVIDE OWNER WITH (2) KEYS PER SWITCH.
<br />20 AMP DUPLEX RECEPTACLE, RECESS MOUNT 18" AFF TO CENTER OF BACKBOX.
<br />MATCH ANY EXISTING KEYED SWITCHES IF RENOVATION. VERIFY KEY TYPE
<br />20 AMP DUPLEX RECEPTACLE, RECESS MOUNT AT HEIGHT INDICATED OR ABOVE
<br />(MANUFACTURER) WITH OWNER
<br />COUNTER, CASEWORK, ETC. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL
<br />"M" INDICATES THE SWITCH SHALL BE MOTOR DUTY RATED
<br />ELEVATIONS AND EXISTING CONDITIONS PRIOR TO ROUGH -IN.
<br />AFCI
<br />20 AMP DUPLEX RECEPTACLE WITH ARC FAULT CIRCUIT INTERRUPTER (AFCI)
<br />"OS" INDICATES OCCUPANCY SENSOR SWITCH (SENSOR SWITCH WSX PDT)
<br />If
<br />PROTECTION, RECESS MOUNT AT HEIGHT INDICATED OR ABOVE COUNTER,
<br />CASEWORK, ETC. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL
<br />"TS" INDICATES INTERVAL TIMER SWITCH PROGRAMMED FOR 30 MINUTES
<br />ELEVATIONS AND EXISTING CONDITIONS PRIOR TO ROUGH -IN.
<br />MAXIMUM ALLOWED TIME (SENSOR SWITCH PTS60)
<br />AFCI
<br />20 AMP DUPLEX RECEPTACLE WITH ARC FAULT CIRCUIT INTERRUPTER (AFCI)
<br />"P" INDICATES SWITCH WITH PILOT LIGHT.
<br />(ttj
<br />PROTECTION, RECESS MOUNT 18" AFF TO CENTER OF BACKBOX. 1 OF 2
<br />RECEPTACLES IS SWITCHED, REMOVE JUMPER BETWEEN OUTLETS.
<br />"R" INDICATES DEVICE SHALL BE A RED COLOR. DEVICE IS CONNECTED TO A
<br />AFCI
<br />1p
<br />20 AMP DUPLEX RECEPTACLE WITH ARC FAULT CIRCUIT INTERRUPTER (AFCI)
<br />CIRCUIT FED FROM A GENERATOR (IF APPLICABLE).
<br />PROTECTION, RECESS MOUNT 18" AFF TO CENTER OF BACKBOX.
<br />LOWER CASE LETTER (i.e. "a") INDICATES THE FIXTURE(S) CONTROLLED BY
<br />!1fh:
<br />20 AMP DOUBLE DUPLEX (QUAD) RECEPTACLE WITH COMMON COVER PLATE, RECESS
<br />THE SWITCH.
<br />MOUNT 18" AFF TO CENTER OF BACKBOX.
<br />20 AMP DOUBLE DUPLEX (QUAD) RECEPTACLE WITH COMMON COVER PLATE, RECESS
<br />MOUNT ABOVE COUNTER, CASEWORK, ETC OR AT HEIGHT INDICATED. COORDINATE
<br />LIGHTING FIXTURES (REFER TO THE "LIGHTING FIXTURE SCHEDULE")
<br />MOUNTING HEIGHT WITH ARCHITECTURAL ELEVATIONS AND CONDITIONS PRIOR TO
<br />ROUGH -IN.
<br />2' x 4' FLUORESCENT LIGHT FIXTURE (SEE LIGHT FIXTURE SCHEDULE)
<br />b
<br />NOTE: THE FOLLOWING ABBREVIATIONS APPLY TO LIGHTING FIXTURES WHERE
<br />20 AMP DUPLEX RECEPTACLE, RECESS MOUNT 18" AFF TO CENTER OF BACKBOX. 1 OF
<br />INDICATED:
<br />2 RECEPTACLES IS SWITCHED, REMOVE JUMPER BETWEEN OUTLETS.
<br />i 'A2' INDICATES FIXTURE TYPE
<br />UPPER CASE LETTER/NUMBER .e. I IC I
<br />( )
<br />F
<br />®
<br />ERE E FLUSH WITH FLOOR IN SINGLE GANG FLOOR
<br />20 AMP DUPLEX RECEPTACLE. RECESS
<br />LOWER CASE LETTER (i.e. 'U) INDICATES CONNECTION TO INDICATED SWITCH.
<br />BOX. COVER SHALL BE BRASS WITH HINGED LID FOR EACH OUTLET OF RECEPTACLE.
<br />NOTE: THE FOLLOWING ABBREVIATIONS APPLY TO LIGHTING FIXTURES WHERE
<br />F(E)
<br />20 AMP DOUBLE DUPLEX (QUAD) RECEPTACLE. RECESS FLUSH WITH FLOOR IN
<br />EM
<br />INDICATED:
<br />DOUBLE GANG FLOOR BOX. COVER SHALL BE BRASS WITH HINGED LID FOR EACH
<br />"EM" INDICATES LIGHT FIXTURE WITH EMERGENCY BATTERY PACK.
<br />OUTLET OF RECEPTACLES.
<br />0
<br />FLUORESCENT LIGHT FIXTURE (SEE LIGHT FIXTURE SCHEDULE)
<br />GFI
<br />20A SIMPLEX RECEPTACLE WITH GFCI PROTECTION MOUNTED AT HEIGHT OR AS
<br />O
<br />DOWNLIGHT
<br />`P
<br />INDICATED. VERIFY RATING AND NEMA CONFIGURATION FOR EQUIPMENT TO BE
<br />CONNECTED.
<br />WALL SCONCE
<br />GFI
<br />20 AMP DUPLEX RECEPTACLE WITH GFCI PROTECTION, RECESS MOUNT 18" AFF TO
<br />PENDANT
<br />[P
<br />CENTER OF BACKBOX.
<br />EXIT SIGN WITH BATTERY PACK, MOUNTED WITHIN 6'-8" OF TOP OF
<br />OPENING PER NFPA 101:7.10.1.9. FACES AND ARROWS SHALL BE AS
<br />GFI
<br />20 AMP DUPLEX RECEPTACLE WITH GFCI PROTECTION, RECESS MOUNT ABOVE SINK,
<br />COUNTER, CASEWORK, ETC. OR AT HEIGHT INDICATED. COORDINATE MOUNTING
<br />[P
<br />IITT
<br />INDICATED ON PLANS. CONNECT FIXTURE TO LIGHTING CIRCUIT SERVING
<br />HEIGHT WITH ARCHITECTURAL ELEVATIONS AND CONDITIONS PRIOR TO ROUGH -IN.
<br />THE AREA, AHEAD OF ANY SWITCHING OR CONTROLS.
<br />GFI
<br />20 AMP DOUBLE DUPLEX (QUAD) RECEPTACLE WITH GFCI PROTECTION AND COMMON
<br />A f
<br />EMERGENCY EGRESS LIGHTING UNIT WITH BATTERY PACK MOUNTED
<br />COVER PLATE, RECESS MOUNT 18" AFF TO CENTER OF BACKBOX.
<br />T-6" AFF OR AS INDICATED. CONNECT FIXTURE TO LIGHTING CIRCUIT
<br />SERVING THE AREA, AHEAD OF ANY SWITCHING OR CONTROLS.
<br />®
<br />MULTI -POLE RECEPTACLE FOR APPLIANCE MOUNTED AS INDICATE. COORDINATE
<br />EXIT SIGN AND EMERGENCY EGRESS LIGHTING COMBO UNIT WITH
<br />ID
<br />AMPERAGE RATING, POLES, NEMA CONFIGURATION, ETC. WITH EQUIPMENT TO BE
<br />A&
<br />BATTERY PACK MOUNTED T-6" AFF. CONNECT FIXTURE TO LIGHTING
<br />CONNECTED.
<br />CIRCUIT SERVING THE AREA, AHEAD OF ANY SWITCHING OR
<br />20 AMP DUPLEX RECEPTACLE, RECESS MOUNT HORIZONTALLY AT HEIGHT INDICATED.
<br />CONTROLS.
<br />PASSIVE INFRARED (PIR) OCCUPANCY SENSOR. 360°. 450 SQ. FT.
<br />20 AMP DUPLEX RECEPTACLE MOUNTED 18" AFF, ABOVE COUNTER, OR AT HEIGHT
<br />INDICATED RECEPTACLE COORDINATED WITH DATA OUTLET FOR
<br />COVERAGE. SENSOR SWITCH CM 10. CONNECT TO LOCAL POWER PACK.
<br />(INDICATES
<br />COMPUTER USE).
<br />MULTI-TECHNLOGY (PIR & ULTRASONIC) OCCUPANCY SENSOR. 360°. 1000
<br />SQ. FT. COVERAGE. SENSOR SWITCH CM-PDT-10. CONNECT TO LOCAL
<br />20 AMP DOUBLE DUPLEX (QUAD) RECEPTACLE MOUNTED 18" AFF, ABOVE COUNTER,
<br />POWER PACK.
<br />OR AT HEIGHT INDICATED (INDICATES RECEPTACLE COORDINATED WITH DATA
<br />EXT.
<br />EXTERIOR PASSIVE INFRARED (PIR) OCCUPANCY SENSOR SBO-10-OEX.
<br />OUTLET FOR COMPUTER USE).
<br />CONNECT TO LOCAL POWER PACK. PROVIDE BOX FOR CEILING MOUNTING.
<br />0
<br />POWER POLE. 2-SECTION (POWER AND COMMUNICATIONS), 2" SQUARE METALLIC,
<br />PP
<br />OCCUPANCY SENSOR POWER PACK. 20A @120/277VAC. PROVIDE
<br />BRUSHED ALUMINUM FINISH. DEVICES MOUNTED AT POLE AS SHOWN. POLE SHALL
<br />QUANTITY AS NEEDED. SENSOR SWITCH PP-20-2P. CONNECT TO LOCAL
<br />EXTEND FROM FLOOR TO CEILING, SECURE TO CEILING.
<br />Ps
<br />OCCUPANCY SENSORS.
<br />20 AMP DUPLEX RECEPTACLE, FLUSH MOUNT AT CEILING. SUPPORT BACKBOX FROM
<br />LED POWER SUPPLY (TECLED MODEL: VBS-12060DO24)
<br />®
<br />STRUCTURE, NOT GRID.
<br />COMMUNICATIONS
<br />F
<br />2-SECTION FLOOR BOX WITH DUPLEX RECEPTACLE AND DATA SECTION. FLOOR BOX
<br />1-GANG DEEP BOX FOR TELEPHONE OUTLET, RECESS MOUNT 18" TO CENTER
<br />SHALL BE FLUSH WITH FLOOR WITH CARPET/TILE PLATE AND TRAP DOOR FOR WIRING
<br />OF BACKBOX AFF, ABOVE COUNTER OR AS NOTED. INSTALL 3/4" CONDUIT
<br />OUT OF BOX.
<br />WITH BUSHINGS AND PULL STRING STUBBED INTO ACCESSIBLE CEILING
<br />0
<br />JUNCTION BOX. FAN RATED IN DWELLING UNITS.
<br />SPACE ABOVE BACKBOX. INSTALL BLANK COVERPLATE. NUMBER OF PHONE
<br />JACKS AS INDICATED OR INSTALL BLANK COVERPLATE. 'W INDICATES PHONE
<br />DC
<br />DROP CORD. RECEPTACLE AND BOX SUSPENDED FROM JUNCTION BOX AT CEILING
<br />WILL BE WALL MOUNTED, MOUNT AT 48" AFF TO CENTER OF BACKBOX AND
<br />°
<br />WITH S/O CORD. PROVIDE STRAIN RELIEF AT EACH END OF CORD. RECEPTACLE
<br />INSTALL WALL PHONE PLATE.
<br />SHALL BE TYPE OF DEVICE SHOWN.
<br />®
<br />(2) GANG DEEP BOX FOR DECORA STYLE DUPLEX RECEPTACLE AND
<br />PLUGMOLD WITH RECEPTACLES 12" ON -CENTER. PLUGMOLD SHALL BE
<br />TELEVISION OUTLET. COORDINATE MOUNTING HEIGHT AND LOCATION.
<br />cmwmw*a
<br />NON-METALLIC, 2-PIECE. MOUNT AS INDICATED. VERIFY COLOR OF FINISH,
<br />INSTALL 3/4" CONDUIT FOR LOW VOLTAGE WIRING WITH BUSHINGS AND PULL
<br />STRING STUBBED INTO ACCESSIBLE CEILING SPACE ABOVE BACKBOX.
<br />POWER DISTRIBUTION (REFER TO THE "ELECTRICAL RISER DIAGRAM")
<br />INSTALL DECORA COVERPLATE.
<br />v 1-GANG DEEP BOX FOR TELEPHONE / DATA OUTLET, RECESS MOUNT 18" TO
<br />CENTER OF BACKBOX AFF, ABOVE COUNTER OR AS NOTED. INSTALL 3/4"
<br />CONDUIT WITH BUSHINGS AND PULL STRING STUBBED INTO ACCESSIBLE
<br />CEILING SPACE ABOVE BACKBOX. INSTALL BLANK COVERPLATE.
<br />CABINET. SEE PLANS AND SPECIFICATIONS FOR USAGE AND
<br />REQUIREMENTS.
<br />MISCELLANEOUS
<br />O KEYED NOTE INDICATOR. REFER TO THE "KEYED NOTES" WHERE
<br />INDICATED.
<br />Q®Q EXHAUST FAN.
<br />'R' SYMBOL INDICATES TO PROVIDE AND INSTALL 10 MINUTE TIME DELAY OFF
<br />RELAY. EXHAUST FAN SHALL OPERATE FOR 10 MINUTES AFTER
<br />LIGHTING SWITCH IS TURNED OFF. CONNECT HOT LEAD FROM
<br />AHEAD OF SWITCH TO RELAY FOR DELAYED OPERATION AND
<br />SWITCH LEG TO RELAY FOR NORMAL OPERATION.
<br />'T' SYMBOL INDICATES TO PROVIDE AND INSTALL 277V-120V
<br />TRANSFORMER. WATTAGE OF TRANSFORMER VA SHALL BE A
<br />MINIMUM 20% GREATER THAN EXHAUST FAN POWER
<br />REQUIREMENTS, COORDINATE WITH MECHANICAL CONTRACTOR.
<br />r7I MOTORIZED DAMPER. PROVIDE POWER AND MAKE CONNECTIONS AS
<br />INDICATED. COORDINATE WITH MECHANICAL CONTRACTOR.
<br />sP CEILING MOUNTED SPEAKER LOCATIONS ON A/V SYSTEM
<br />ABBREVIATIONS
<br />AFF
<br />HEIGHT ABOVE FINISHED FLOOR
<br />AFG
<br />HEIGHT ABOVE FINISHED GRADE
<br />ETR
<br />EXISTING TO REMAIN
<br />EXT
<br />EXTERIOR
<br />TYPE WIRING DEVICE OR CIRCUIT
<br />BREAKER
<br />LTG
<br />LIGHTING
<br />MTR
<br />MOTOR
<br />N.I.C.
<br />NOT IN CONTRACT
<br />NF
<br />NON -FUSED
<br />PH
<br />PHASE
<br />REL
<br />RELOCATED
<br />REM
<br />TO BE REMOVED
<br />REP
<br />REPLACE WITH NEW
<br />TBR
<br />TO BE RELOCATED
<br />U.N.O.
<br />UNLESS NOTED OTHERWISE
<br />VA
<br />VOLT AMPERE (POWER)
<br />WP
<br />WEATHERPROOF ENCLOSURE
<br />XFMR
<br />TRANSFORMER
<br />+48"
<br />DEVICE MOUNTED AT HEIGHT
<br />INDICATED
<br />. . r-/ANCLDU1-%r, J, r[C1,C00 IVIVL/IV 1 Iry FIIVIJ"L_L1 JrnV CO, 3urxFnVC IVIV VIv 1 11V Un�.r\ V1
<br />HOUSE. REFER TO THE "PANELBOARD SCHEDULE".
<br />FEEDER OR BRANCH CIRCUIT RACEWAY CONCEALED IN WALL, CEILING.
<br />"— FEEDER OR BRANCH CIRCUIT RACEWAY CONCEALED UNDER FLOOR, IN SLAB OR
<br />BELOW GRADE.
<br />C=l' DISCONNECT SWITCH. PROVIDE DISCONNECT SWITCH AS INDICATED ON THE
<br />SCHEDULES. REFER TO PLANS AND SCHEDULES FOR ADDITIONAL REQUIREMENTS.
<br />FUSES SHALL BE DUAL ELEMENT TIME DELAY. VERIFY NAMEPLATE RATINGS OF
<br />FRAME SIZE AND FUSING OF THE ACTUAL EQUIPMENT TO BE INSTALLED.
<br />DRY -TYPE VENTILATED TRANSFORMER. SEE SPECIFICATIONS, PLANS AND RISER
<br />FOR REQUIREMENTS. TRANSFORMERS SHALL BE NEMA 1 UNLESS AT THE EXTERIOR
<br />OR IN AREAS WHERE WATER MAY BE PRESENT. MOUNT ON 4" HOUSE KEEPING PAD
<br />BOLTED TO PAD. MAINTAIN REQUIRED CLEARANCE FROM WALLS OR
<br />OBSTRUCTIONS FOR VENTILATION.
<br />�f— GROUND TO METAL FRAME OF BUILDING, SLAB STEEL, OTHER MADE ELECTRODES,
<br />AND METAL UNDERGROUND WATER PIPE. PROVIDE A MINIMUM OF (3) 3/4" DIA, 10
<br />FOOT LONG COPPER CLAD GROUND RODS LOCATED AT LEAST 6 FEET APART. ALL
<br />CONCEALED CONNECTIONS SHALL BE EXOTHERMICALLY WELDED. INTERIOR
<br />GROUND RODS SHALL STUB ABOVE FLOOR AT LOCATIONS NOT INTERFERING WITH
<br />FOOT TRAFFIC. LOCATE EXTERIOR GROUND ROD ASSEMBLY IN LANDSCAPE AREA
<br />OR PROVIDE WELL FOR ACCESS TO EACH GROUND ROD IF ASSEMBLY IS LOCATED
<br />IN HARD SURFACE AREAS, SUCH AS CONCRETE, ASPHALT, ETC. PROVIDE BOLTED
<br />PRESSURE CLAMP WITH AT LEAST TWO BOLTS ON RODS IN TEST WELLS. ALL
<br />GROUND ROD LOCATIONS SHALL BE ACCESSIBLE.
<br />VARIABLE FREQUENCY DRIVE. REFER TO SPECIFICATIONS, AND FLOOR PLANS FOR
<br />ADDITIONAL ELECTRICAL REQUIREMENTS. VFD SUPPLIED BY MECHANICAL
<br />CONTRACTOR (U.N.O.) AND INSTALLED BY ELECTRICAL CONTRACTOR. ALL
<br />CONNECTIONS TO VFD, DISCONNECT AND EQUIPMENT SERVED SHALL BE BY THE
<br />ELECTRICAL CONTRACTOR. CIRCUIT SHALL UTILIZE METAL CONDUIT TO MINIMIZE
<br />RFI NOISE.
<br />COMBINATION MOTOR STARTER WITH FUSED DISCONNECT OR CIRCUIT BREAKER
<br />DISCONNECT. REFER TO PLANS AND SCHEDULES FOR ADDITIONAL REQUIREMENTS.
<br />FUSES SHALL BE DUAL ELEMENT TIME DELAY. VERIFY NAMEPLATE RATINGS OF
<br />FRAME SIZE AND FUSING OF THE ACTUAL EQUIPMENT TO BE INSTALLED.
<br />LP-1 PANEL HOMERUN/CIRCUIT
<br />PANEL DESIGNATION/CIRCUIT NUMBER
<br />NOTE: NOT ALL SYMBOLS SHOWN ON LEGEND ARE USED ON FLOOR PLANS.
<br />GENERAL NOTES
<br />**GENERAL NOTES APPLY TO ALL ELECTRICAL SHEETS**
<br />1. DO NOT SCALE FROM THESE DRAWINGS.
<br />2. ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH THE 2017 EDITION OF
<br />THE NATIONAL ELECTRICAL CODE (NEC) NFPA 70.
<br />3. ELECTRICAL CONTRACTOR (E.C.) SHALL COORDINATE WORK WITH ALL OTHER TRADES
<br />TO ASSURE PROPER CLEARANCES FOR EQUIPMENT AND TO KEEP THE JOB
<br />PROGRESSING.
<br />4. DRAWINGS ARE BASED ON FIELD OBSERVATION AND EXISTING DOCUMENTS. REPORT
<br />ANY DISCREPANCIES TO THE ENGINEER BEFORE DISTURBING EXISTING INSTALLATION.
<br />5. EXISTING TO REMAIN ELECTRICAL CIRCUITRY DOWNSTREAM AND UPSTREAM OF
<br />DEMOLISHED DEVICES SHALL BE MAINTAINED, E.C. SHALL PROVIDE ALL ELECTRICAL
<br />COMPONENTS (BOXES, CONDUIT, WIRING, ETC.) AS REQUIRED.
<br />6. ELECTRICAL CONTRACTOR SHALL BE REQUIRED TO CUT, CAPTURE AND EXTEND OR
<br />RE-ROUTE EXISTING CONDUITS AND CONDUCTORS AS REQUIRED TO ACCOMMODATE
<br />NEW DUCTWORK. COORDINATE WITH MECHANICAL CONTRACTOR AS REQUIRED.
<br />7. REFER TO MECHANICAL DRAWINGS FOR EQUIPMENT NEEDING ELECTRICAL
<br />CONNECTIONS (MOTORS, FANS, PUMPS, ETC.). MAKE ALL CONNECTIONS AND PROVIDE
<br />APPROPRIATE WIRE, CONDUIT, AND OVERCURRENT PROTECTION FOR ALL EQUIPMENT.
<br />INSTALL ANY ELECTRICAL EQUIPMENT (STARTERS, RELAYS, VFD'S, ETC.) FURNISHED
<br />BY MECHANICAL CONTRACTOR (DIV 15). COORDINATE EXACT REQUIREMENTS WITH
<br />MECHANICAL CONTRACTOR.
<br />8. VOLTAGE DROP: THE CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS COMBINED
<br />SHALL BE SIZED FOR A MAXIMUM OF 5% VOLTAGE DROP TOTAL PER FBC-ENERGY
<br />C405.6.3. USE 10 AWG CU. CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS
<br />LONGER THAN 75 FEET. USE 10 AWG CU. WHERE WIRE SIZE IS INCREASED IN SIZE FOR
<br />VOLTAGE DROP, E.G SHALL BE INCREASED PROPORTIONATELY. PER NEC 250.122 (B).
<br />9. ALL CEILING MOUNTED ITEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE
<br />ARCHITECTURAL REFLECTED CEILING PLANS. IF LOCATION FOR AN ITEM IS NOT SHOWN
<br />ON THE ARCHITECTURAL REFLECTED CEILING PLANS, VERIFY THE EXACT LOCATION OF
<br />THE ITEM WITH THE ARCHITECT PRIOR TO INSTALLATION.
<br />10. WHERE DISCONNECTING MEANS IS NOT PROVIDED "WITHIN SIGHT" FROM EQUIPMENT
<br />SERVED, THE OVERCURRENT DEVICE SERVING SUCH EQUIPMENT SHALL HAVE
<br />PERMANENT PROVISION TO LOCK IN THE OPEN POSITION PER NEC 422.31 AND 110.25.
<br />11. CONDUIT RUNS SHOWN ARE DIAGRAMMATIC IN NATURE. ELECTRICAL CONTRACTOR
<br />SHALL BE RESPONSIBLE FOR SIZING AND LOCATING PULL BOXES PER NEC.
<br />12. PROVIDE ALL H.I.D. AND FLUORESCENT LIGHT FIXTURES WITH INTEGRAL FUSING.
<br />13. CONNECT EXIT SIGNS AND EGRESS LIGHTS TO LOCAL LIGHTING CIRCUIT AHEAD OF
<br />ANY SWITCHING PER NEC 700.12(F).
<br />14. RECEPTACLES IN MECHANICAL ROOMS, ELECTRICAL ROOMS, STORAGE ROOMS, AND
<br />JANITOR CLOSETS SHALL BE G.F.C.I. TYPE MOUNTED AT 48" A.F.F.
<br />15, PROVIDE REVISED PHOTOMETRICS FOR ANY SUBSTITUTE FIXTURES.
<br />CONDUIT AND CONDUCTOR SCHEDULE
<br />C.B.
<br />POLES
<br />WIRE SIZE P THW)
<br />CONDUIT
<br />PHASE
<br />20A
<br />1
<br />2412, 1412 E.G.
<br />3/4
<br />10 2W
<br />2
<br />2-#12, 1-#12 E.G.
<br />10 2W
<br />3
<br />3-#12, 1-#12 E.G.
<br />30 3W
<br />3
<br />3412, 1412 N., 1412 E.G.
<br />30 4W
<br />25A
<br />1
<br />2410, 1410 E.G.
<br />3/4
<br />10 2W
<br />2
<br />2-#10, 1-#10 E.G.
<br />10 2W
<br />3
<br />3-#10, 1-#10 E.G.
<br />30 3W
<br />3
<br />3410, 1-#10 N., 1410 E.G.
<br />30 4W
<br />30A
<br />1
<br />2410, 1410 E.G.
<br />3/4
<br />10 2W
<br />2
<br />2-#10, 1-#10 E.G.
<br />10 2W
<br />3
<br />3-#10, 1-#10 E.G.
<br />30 3W
<br />3
<br />3410, 1410 N., 1410 E.G.
<br />30 4W
<br />35A
<br />3
<br />3-#8, 1-#10 E.G.
<br />1
<br />30 3W
<br />3
<br />3-#8, 148 N., 1-#10 E.G.
<br />30 4W
<br />40A
<br />2
<br />248, 1-#10 E.G.
<br />1"
<br />10 2W
<br />3
<br />348, 1410 E.G.
<br />30 3W
<br />3
<br />348, 148 N., 1410 E.G.
<br />30 4W
<br />45A
<br />2
<br />248, 1410 E.G.
<br />1"
<br />10 2W
<br />3
<br />348, 1410 E.G.
<br />30 3W
<br />3
<br />348, 148 N., 1410 E.G.
<br />30 4W
<br />50A
<br />2
<br />248, 1410 E.G.
<br />1"
<br />10 2W
<br />3
<br />348, 1410 E.G.
<br />30 3W
<br />3
<br />348, 148 N., 1410 E.G.
<br />30 4W
<br />60A
<br />2
<br />246, 1410 E.G.
<br />1
<br />10 2W
<br />3
<br />346, 1410 E.G.
<br />30 3W
<br />3
<br />346, 146 N., 1410 E.G.
<br />1 1/4"
<br />30 4W
<br />2
<br />244, 148 E.G.
<br />1"
<br />10 2W
<br />70A
<br />3
<br />344, 148 E.G.
<br />1 1/4"
<br />30 3W
<br />3
<br />3-#4, 1-#4 N., 148 E.G.
<br />30 4W
<br />2
<br />244, 148 E.G.
<br />1"
<br />10 2W
<br />80A
<br />3
<br />344, 148 E.G.
<br />1 1/4"
<br />30 3W
<br />3
<br />344, 144 N., 148 E.G.
<br />30 4W
<br />90A
<br />2
<br />243, 148 E.G.
<br />1 1/4"
<br />10 2W
<br />3
<br />343, 148 E.G.
<br />30 3W
<br />3
<br />343, 143 N., 148 E.G.
<br />30 4W
<br />100A
<br />2
<br />243, 148 E.G.
<br />1 1/4"
<br />10 2W
<br />3
<br />343, 148 E.G.
<br />30 3W
<br />3
<br />343, 143 N., 148 E.G.
<br />30 4W
<br />NOTES:
<br />1. ALL CONDUCTORS SHALL BE COPPER
<br />2. ALL CONDUIT SHALL HAVE EQUIPMENT GROUNDING CONDUCTOR INSTALLED.
<br />3. CONDUIT BELOW GRADE OUTSIDE OF BUILDING SHALL BE 1" MINIMUM.
<br />4. SIZING OF CONDUCTORS SHALL BE ALTERED FOR DERATING PER N.E.C. OR VOLTAGE
<br />DROP CONSIDERATIONS.
<br />5. SEE RISER DIAGRAM FOR SIZING OF CIRCUITS GREATER THAN 100A.
<br />6. USE #10 AWG, COPPER CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS
<br />LONGER THAN 75 FEET. USE #10 AWG, COPPER CONDUCTORS FOR 20 AMPERE, 277 VOLT
<br />BRANCH CIRCUITS LONGER THAN 200 FEET. WHERE WIRE SIZE IS INCREASED IN SIZE FOR
<br />VOLTAGE DROP, EQUIPMENT GROUND SHALL BE INCREASED PROPORTIONATELY PER
<br />NEC 250.122 (B).
<br />7. WHERE MC CABLE IS ALLOWED BY THE AUTHORITY HAVING JURISDICTION, THE
<br />CONDUCTORS FOR MC CABLE SHALL BE THHN. JACKET SHALL BE THE MANUFACTURER'S
<br />STANDARD SIZE FOR CONDUCTORS UTILIZED.
<br />GS JOB iP: SS31 .21 .00
<br />GLOBAL
<br />34%NCrLjirC__Z1NC
<br />MEPP ENGINEERING
<br />INFO@GLOBAL-SANCHEZ. COM
<br />CA#: 6237
<br />B 1 6 MANATEE AVE. E, SUITE 1 B
<br />BRADENTON, FL 3420B
<br />PHONE: 941-75B-2551
<br />3B25 HENDERSON BLVD.,
<br />SUITE 1 ❑3
<br />TAMPA, FL 33629
<br />PHONE: 81 3-2B 1 -❑❑❑ 1
<br />C&K ARCHITECTS I INTERIORS
<br />architecture. interior design• client services
<br />AAC001629
<br />4221 WEST BOY SCOUT BLVD., SUITE 150
<br />TAMPA, FL 33607-5743
<br />813.884.2000
<br />280 WEST CENTRAL AVE.
<br />WINTER HAVEN, FL 33880-2957
<br />863.577.2054
<br />�P 3. FE/
<br />•°ENS°'•!rF
<br />Q 5083 °•
<br />5 /2021;` W
<br />O STATE OF <v
<br />� ••'' :r�•OR10P•° Gam?
<br />°
<br />sS/
<br />�\41
<br />0 N A L
<br />0
<br />0
<br />s
<br />ma
<br />0
<br />0
<br />Z
<br />J
<br />LL
<br />J
<br />x
<br />a
<br />1,,
<br />N
<br />J U)
<br />q 0
<br />LZ H
<br />�.�..� Q/
<br />Z
<br />Lu
<br />to
<br />Q =0
<br />w
<br />V °' 0
<br />N
<br />�
<br />C
<br />V m
<br />W m
<br />J
<br />Lu m
<br />0
<br />J
<br />m
<br />J
<br />Q
<br />C9
<br />M
<br />L0
<br />0,
<br />LO
<br />ISSUED FOR:
<br />PERMIT
<br />PROJECT NUMBER
<br />21020
<br />DATE
<br />5.5.21
<br />DRAWING NUMBER
<br />
|