Laserfiche WebLink
ESTIMATED VOLTAGE DROP (208V) <br />COPPER SERVICE FEEDER <br />CONDUCTORS <br />CONDUCTOR SIZE <br />600 kCMIL, CU <br />RESISTANCE (0/1000') <br />0.028 <br />NUMBER OF PARALLEL RUNS <br />1 <br />CONDUCTOR LENGTH <br />50' <br />APPROXIMATE LOAD <br />400 A <br />PHASE <br />3PH <br />ESTIMATED VOLTAGE DROP <br />0.97 V <br />VOLTAGE <br />1 208 V <br />VOLTAGE DROP <br />0.47 % <br />VOLTAGE DROP BELOW 3% PER NEC 215.2 AND FBC-E, 7TH ED. C405.5.3 <br />PANELBOARDe 'MAIN' (COPPER) <br />ESTIMATED FAULT CURRENT <br />CONDUCTOR SIZE <br />600 kCMIL, CU <br />CONDUCTOR LENGTH <br />50' <br />CONDUCTOR "C" <br />28,033 <br />NUMBER OF PARALLEL RUNS <br />1 <br />TOTAL CONDUCTOR "C" <br />28,033 <br />ESTIMATED TRANSFORMER SCA <br />65,000 A <br />VOLTAGE <br />208 V <br />FAULT CURRENT <br />33,07 2A <br />FAULT CURRENT <br />SCA/(1+[(1.73*L*SCA)/(C*V)]) <br />33,072A SHORT CIRCUIT AMPS <br />i ESTIMATED AT PANEL <br />NOTE: FAULT CURRENT CALCULATION IS BASED ON ESTIMATED UTILITY <br />TRANSFORMER AVAILABLE FAULT CURRENT AND LOCATIONS OF <br />EQUIPMENT SHOWN ON THE PLANS. ELECTRICAL CONTRACTOR SHALL <br />CONFIRM ABOVE INFORMATION IS CORRECT PRIOR TO ORDERING <br />EQUIPMENT. ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT <br />WITH SUITABLE INTERRUPT RATINGS. ANY DISCREPANCIES SHALL BE <br />REPORTED TO THE ENGINEER. <br />ESTIMATED VOLTAGE DROP (208V) <br />COPPER SERVICE FEEDER <br />CONDUCTORS <br />CONDUCTOR SIZE <br />600 kCMIL, CU <br />RESISTANCE (0/1000') <br />0.028 <br />NUMBER OF PARALLEL RUNS <br />1 <br />CONDUCTOR LENGTH <br />10, <br />APPROXIMATE LOAD <br />400 A <br />PHASE <br />3PH <br />ESTIMATED VOLTAGE DROP <br />0.19 V <br />VOLTAGE <br />208 V <br />VOLTAGE DROP <br />0.09 % <br />VOLTAGE DROP BELOW 3% PER NEC 215.2 AND FBC-E, 7TH ED, C405.5.3 <br />PANELBOARDe 'BK' (COPPER) <br />ESTIMATED FAULT CURRENT <br />CONDUCTOR SIZE <br />600 kCMIL, CU <br />CONDUCTOR LENGTH <br />10, <br />CONDUCTOR "C" <br />28,033 <br />NUMBER OF PARALLEL RUNS <br />1 <br />TOTAL CONDUCTOR "C" <br />28,033 <br />ESTIMATED TRANSFORMER SCA <br />33,072 A <br />VOLTAGE <br />208 V <br />FAULT CURRENT <br />30,114 A <br />FAULT CURRENT <br />SCA/(1+[(1.73*L*SCA)/(C*V)]) <br />30,114A SHORT CIRCUIT AMPS <br />ESTIMATED AT PANEL <br />NOTE: FAULT CURRENT CALCULATION IS BASED ON ESTIMATED UTILITY <br />TRANSFORMER AVAILABLE FAULT CURRENT AND LOCATIONS OF <br />EQUIPMENT SHOWN ON THE PLANS, ELECTRICAL CONTRACTOR SHALL <br />CONFIRM ABOVE INFORMATION IS CORRECT PRIOR TO ORDERING <br />EQUIPMENT. ELECTRICAL CONTRACTOR SHALL PROVIDE EQUIPMENT <br />WITH SUITABLE INTERRUPT RATINGS. ANY DISCREPANCIES SHALL BE <br />REPORTED TO THE ENGINEER. <br />400A <br />NEW PANEL <br />"BK" <br />208/120V/3PH <br />NEMA 1 <br />400A <br />DISCONNECT <br />208/12OV/3PH <br />NEMA 3R <br />D-6 <br />PANELBOARDm 'BK' <br />ELECTRICAL SERVICE CALCULATION <br />LOAD <br />CONNECTED <br />DEMAND <br />LIGHTING <br />1,488 <br />1,860 <br />RECEPTACLES <br />2,880 <br />2,880 <br />GAS WATER HEATER <br />180 <br />180 <br />CEILING FANS <br />700 <br />700 <br />SIGN <br />1,200 <br />1,500 <br />POS (2) <br />1,000 <br />1,000 <br />RTU-1 <br />16,212 <br />16,212 <br />RTU-2 <br />24,858 <br />24,858 <br />KSF-1 <br />2,088 <br />2,088 <br />KEF-1 <br />900 <br />900 <br />KEF-2 <br />900 <br />900 <br />#2 - ICE CUBE MAKER <br />1,086 <br />1,086 <br />#22 - RICE COOKER (4) <br />7,200 <br />4,680 <br />#30 - SALAD REF. <br />276 <br />179 <br />#34 - FOOD WARMER (3) <br />3,600 <br />2,340 <br />#46 - REACH IN FREEZER <br />1,020 <br />663 <br />#40 - PEPSI COOLER <br />1,000 <br />650 <br />#41 - DRINK DISP. <br />1,000 <br />1,000 <br />#3 - MENU BOARD (2) <br />360 <br />360 <br />#4 - WALK IN COOLER <br />120 <br />78 <br />#8 - SANDWICH REF. <br />648 <br />421 <br />#9 - HOT FOOD TABLE <br />2,100 <br />1,365 <br />#10 - FRENCH FRY WARMER <br />1,120 <br />728 <br />#11 - FOOD TOPPING WARMER <br />504 <br />328 <br />#12 - PANINI GRILL <br />1,800 <br />1,170 <br />#13 - REACH IN FREEZER <br />780 <br />507 <br />#15 - REF. EQUIP. STAND <br />276 <br />179 <br />COOLER CAPSULE PACK <br />2,000 <br />2,000 <br />- <br />0 <br />0 <br />TOTAL <br />77,296 <br />70,813 <br />197 AMP DEMAND <br />400A SERVICE @ 208V, 3-PHASE PROVIDED <br />+ .65 DEMAND FACTOR PER NEC 220.56 <br />RISER KEYED (VOTES <br />ONEW 400 AMP SERVICE FEEDER: (1) 3-1/2" CONDUIT WITH (4) 600KCM <br />CU. <br />ONEW 400 AMP SERVICE FEEDER: (1) 3-1/2" CONDUIT WITH (4) 600KCM <br />CU AND (1) #3 AWG CU E.G. <br />ONEW #1/0 CU GROUNDING ELECTRODE CONDUCTOR IN 1" CONDUIT. <br />BOND TO METAL UNDERGROUND WATER PIPE, BUILDING STEEL, ETC. <br />PER NEC 250.50. <br />O#6 AWG COPPER TO (3) NEW 5/8"X1 O' COPPER GROUND RODS <br />SPACED 10' APART. <br />ONEW SURGE PROTECTIVE DEVICE. MINIMUM RATING OF 100KA PER <br />PHASE SURGE CURRENT RATING. PQ PROTECTION PQC100, OR <br />EQUIVALENT. <br />RISER LEGEND <br />EXISTING TO REMAIN <br />NEW <br />O <br />NEW 400A <br />METER <br />ENCLOSURE <br />ELECTRICAL RISER DIAGRAMS <br />SCALE: NOT TO SCALE <br />EXISTING UTILITY <br />TRANSFORMER WITH <br />CT CABINET <br />1 <br />PANELBOARD <br />DESIGNATION <br />'BK' <br />VOLTAGE: 208/120V <br />30 4W <br />MAINS RATING: 400 AMPS <br />MAIN CB TRIP RATING: 400 AMPS <br />SURFACE MCB <br />FLUSH 0 MLO <br />COPPER BUS <br />INTERRUPTING RATING: 65000 AIC <br />ENCLOSURE:NEMA1 <br />SERVES <br />CB SIZE <br />LOAD VA <br />CKT <br />A <br />B <br />C <br />CKT <br />LOAD VA <br />CB SIZE <br />SERVES <br />#2 - ICE CUBE MAKER <br />20 <br />1086 <br />1 <br />2 <br />180 <br />20 <br />#3 - MENU BOARD RECEPT, <br />#22 - RICE COOKER <br />20 <br />1800 <br />3 <br />4p <br />4 <br />180 <br />20 <br />#3 - MENU BOARD RECEPT. <br />#22 - RICE COOKER <br />20 <br />1800 <br />5 <br />6 <br />120 <br />20 <br />#4 - WALK IN COOLER <br />#22 - RICE COOKER <br />20 <br />1800 <br />7 <br />40 <br />8 <br />500 <br />20 <br />#7 - POS <br />#22 - RICE COOKER <br />20 <br />1800 <br />9 <br />411 <br />1 10 <br />648 <br />20 <br />#8 - SANDWICH REF. <br />#30 - SALAD REF. <br />20 <br />276 <br />11 <br />140 <br />12 <br />2100 <br />25 <br />#9 - HOT FOOD TABLE <br />#34 - FOOD WARMER <br />20 <br />1200 <br />13 <br />4 1 <br />14 <br />1120 <br />20 <br />#10 -FRENCH FRY WARMER <br />#34 - FOOD WARMER <br />20 <br />1200 <br />15 <br />16 <br />504 <br />20 <br />#11 - FOOD TOPPING WARMER <br />#34 - FOOD WARMER <br />20 <br />1200 <br />17 <br />1 0 <br />18 <br />1800 <br />20 <br />#12 - PANINI GRILL <br />#46 - REACH IN FREEZER <br />20 <br />1020 <br />19 <br />4 0 <br />20 <br />780 <br />20 <br />#13 -REACH IN FREEZER <br />DINING AREA RECEPT. <br />20 <br />1080 <br />21 <br />41 <br />22 <br />276 <br />20 <br />#15 - REF. EQUIP. STAND <br />B.O.H. RECEPTACLES <br />20 <br />1080 <br />23 <br />1 <br />24 <br />1 SHUNT TRIP <br />KITCHEN RECEPT, <br />20 <br />540 <br />25 <br />ql <br />1 <br />11 <br />26 <br />500 <br />20 <br />POS <br />#40 - PEPSI COOLER <br />20 <br />1000 <br />27 <br />28 <br />1200 <br />20 <br />SIGN <br />#41 -DRINK DISPENSER <br />20 <br />1000 <br />29 <br />1 30 <br />5404 <br />45 <br />RTU-1 <br />LIGHTING <br />20 <br />1194 <br />31 <br />4 1 <br />32 <br />5404 <br />LIGHTING C3 <br />20 <br />294 <br />33 <br />41 <br />34 <br />5404 <br />CEILING FANS <br />20 <br />700 <br />35 <br />40 <br />36 <br />8286 <br />70 <br />RTU-2 <br />KEF-1 <br />20 <br />300 <br />37 <br />11 <br />38 <br />8286 <br />300 <br />39 <br />4PI <br />11 <br />40 <br />8286 <br />300 <br />41 <br />42 <br />696 <br />20 <br />KSF-1 <br />KEF-2 <br />20 <br />300 <br />43 <br />40 <br />44 <br />696 <br />300 <br />45 <br />41 <br />46 <br />696 <br />300 <br />47 <br />48 <br />SHUNT TRIP <br />GAS WATER HEATER <br />20 <br />180 <br />49 <br />4 0 <br />1 <br />50 <br />180 <br />20 <br />ROOF GFI <br />COOLER CAPSULE <br />PACK <br />20 <br />1000 <br />51 <br />41 <br />1 <br />52 <br />0 <br />20 <br />SPARE <br />1000 <br />53 <br />0 <br />20 <br />SPARE <br />SPACE <br />20 <br />0 <br />54 <br />r60 <br />0 <br />30 <br />SPD <br />SPACE <br />20 <br />0 <br />57 <br />0 <br />SPACE <br />20 <br />0 <br />59;1 <br />0 <br />* COORDINATE REQUIREMENTS WITH EQUIPMENT PROVIDER. <br />L PROVIDE LOCKABLE OFF PROVISION PER NEC 422.31. <br />ELECTRICAL SCHEDULES <br />SCALE: NOT TO SCALE <br />C&K ARCHITECTS I INTERIORS <br />architecture • interior design • client services <br />AAC001629 <br />4221 WEST BOY SCOUT BLVD., SUITE 150 <br />TAMPA, FL 33607-5743 <br />813.884.2000 <br />280 WEST CENTRAL AVE. <br />WINTER HAVEN, FL 33880-2957 <br />863.577.2054 <br />° OCE <br />�N, <br />a 5083`�7 <br />4/2021 W <br />'., STATE OF ;'44 <br />Fss� <br />G <br />o N A <br />Z <br />0 <br />N <br />lC <br />K <br />mQ <br />0 <br />0 <br />z <br />LL <br />N <br />J_ <br />s <br />ix <br />x <br />a <br />W <br />N <br />W <br />J O <br />W Q/ <br />Z <br />U) V <br />J =0 <br />Q W <br />N <br />V <br />r_ 0�e <br />m <br />V 00 <br />W � <br />J m <br />W <br />J <br />CD <br />J <br />J <br />rQ <br />V <br />M <br />01 <br />ISSUED FOR: <br />PERMIT <br />PROJECT NUMBER <br />21020 <br />DATE <br />5.5.21 <br />DRAWING NUMBER <br />E 7 <br />11 <br />