-- -- -------- <br />AS <br />REQUIRED PER ZONE <br />FOR CONTROL OF 0-10V LOADS <br />r---------------------------------------� <br />I <br />ZONE X <br />SWITCHED POWER <br />(8A MAX) <br />I I <br />I I ® I <br />0-10V DIM <br />(60 mA MAX) <br />RMJS-8T-DV-B <br />POWPAK DIMMING MODULE <br />120/277V-, 50/60 Hz <br />W/ 0-10 V CONTROL <br />DIMENSIONS: <br />3.42"(H) X 2.82"(W) X 1.25"(D) <br />I (87mm X 72mm X 32mm) I <br />LOCATE ABOVE ACCESSIBLE CEILING <br />I I <br />IL---------------------------------------J <br />TYPICAL QS <br />TIMECLOCK <br />AS REQUIRED <br />---------------- <br />I I <br />I I <br />I OQ I <br />I <br />QSGR-TC-3S-WH-CPN5825 I <br />QS TIMECLOCK <br />w/ 3 SHADE COLUMNS <br />(4 GANG US BACKBOX BY OTHERS) <br />LOCATE IN MAIN ELECTRICAL CLOSET <br />I I <br />L------------------------------t <br />TYPICAL OF RESTROOMS <br />AS <br />REQUIRED <br />r--------------------------------- <br />I I <br />I I <br />i <br />I I <br />I I <br />I I <br />(1) PJ2-2BRL-GWH-XXX <br />434 MHZ PICO WIRELESS <br />2 BUTTON CONTROL WITH RAISE/LOWER <br />SHOWN WITH CW-2-WH <br />CLARO WALLPLATE <br />*SEE SPECIFICATION SHEET FOR <br />DIMENSIONS, ENGRAVING OPTIONS, <br />& MOUNTING INSTRUCTIONS <br />I I <br />REFER TO FLOOR PLAN FOR <br />QUANTITY AND LOCATIONS <br />-------------------------------- <br />I I <br />AS REQUIRED <br />FOR CONTROL OF NORMAL 0-10V & NON -DIM LOADS <br />ZONES <br />r------------------------------------- <br />I I <br />I I <br />ZONE X <br />120V/277V E1`0 <br />120V/277V <br />120V/277V <br />120V/277V E3-- <br />120/277V <br />I <br />TO QUANTUM HkJB&Q <br />0-10V <br />I <br />I <br />ZONE X <br />0-10V <br />I <br />® <br />I <br />ZONE X <br />0-10V <br />I <br />ZONE X <br />0-10V I <br />ESN# <br />To QS Devices <br />(Up to 14 PDUs) <br />QSN-4T16-S <br />ENERGI SAVR NODE QS (ESN) <br />WITH (4) SWITCHED OUTPUTS, <br />(4) 0-10V CHANNELS, AND <br />I I <br />(1) QS COMMUNICATIONS LINK <br />DIMENSIONS: <br />13.25"[336,7mm] (H) X 9.25"[235mm] (W) <br />X 3.16"[80,3mm] (D) <br />LOCATE ABOVE ACCESSIBLE CEILING <br />I I <br />L------------------------------------J <br />LUTRON PROVIDED JACK OR (FOR US INSTALLATIONS ONLY) <br />OQ ETHERNET PORT BY OTHERS C-ESN-SETUP <br />a <<< <br />(WIRELESS ROUTER <br />QSE-CI-AP-D NT-05E/B-NFB-WH-E-CPW1338 <br />ENERGI SAVR NODE LUTRON LIGHTING SYSTEM APPLE®IPOD TOUCH <br />PROGRAMMING INTERFACE DEDICATED PROGRAMMING PORT OR IPHONE"MOBILE <br />DIMENSIONS: (1 GANG US BACKBOX BY OTHERS) DIGITAL DEVICE <br />3.5"[89mm] (H) X 2.1"[53mm] (Vv) — — — — — — — — <br />X 2.4"[61 mm] (D) <br />LOCATION TBD <br />TYPICAL OF OPEN AREA AND KITCHEN <br />AS <br />I <br />REQUIRED <br />r-----------------------------� <br />I I <br />I I I <br />I I <br />LRF2-VCR2B-P-WH <br />434MHZ WIRELESS I I <br />OCCUPANCY SENSOR i I <br />3.57"[90,7mm] (DIA) X 1.13"[28,7mm] (D) <br />MAX 10 PER QSM <br />*DEVICE IS SURFACE -MOUNTED AND <br />BATTERY POWERED, DOES NOT i I <br />REQUIRE POWER FEED <br />I I <br />I I <br />(OPTION:WITH L-CRMK-WH i I <br />RECESS MOUNT KIT FOR I <br />NON-METALLIC CEILINGS) <br />REFER TO FLOOR PLAN FOR <br />QUANTITY AND LOCATIONS <br />L----------------------------- J <br />TYPICAL OF SALE AREA AND BACK OF HOUSE <br />AS REQUIRED <br />MAX OF 10 PER QSM <br />r---------------------------- <br />I I <br />I I I <br />I I <br />I I <br />I I <br />LRF2-OCR2B-P-WH <br />I i 434MHZ WIRELESS <br />OCCUPANCY/VACANCY SENSOR <br />I 3.57"[90,7mm] (DIA) X 1.13"[28,7mm] (D) I <br />MAX 10 PER QSM <br />I i -DEVICE IS SURFACE -MOUNTED AND <br />BATTERY POWERED, DOES NOT <br />REQUIRE POWER FEED <br />I I <br />I i (OPTION:WITH L-CRMK-WH <br />RECESS MOUNT KIT FOR <br />NON-METALLIC CEILINGS) <br />REFER TO FLOOR PLAN FOR <br />QUANTITY AND LOCATIONS <br />LL---------------------------J <br />AS REQUIRED <br />-------------------- <br />I I <br />I I <br />I I <br />I I <br />QSM# <br />I QQ I <br />I I <br />QSM2-4W C <br />QUANTUM SENSOR MODULE (QSM) <br />WITH (4) UNIVERSAL WIRED INPUTS <br />AND 434MHZ WIRELESS RECEIVER I <br />60'[18.29m] RADIUS RF COVERAGE <br />(30'[9.14m] THROUGH WALLS) <br />4.04"[102.6mm] (DIA) X 1.17"[29.7mm] (D) I <br />LOCATION TBD <br />I I <br />I I <br />I I <br />L------------------------------ J <br />AS REQUIRED <br />MAX OF 10 PER QSM <br />----------------------------i <br />I i-I <br />I I <br />I I I <br />I � I <br />LRF2-DCRB-WH <br />434MHZ WIRELESS i I <br />DAYLIGHT SENSOR <br />1.6"[40,6mm] (DIA) X 0.7"[17,8mm] (D) <br />MAX 10 PER QSM <br />*DEVICE IS SURFACE -MOUNTED AND i I <br />BATTERY POWERED, DOES NOT <br />REQUIRE POWER FEED <br />REFER TO FLOOR PLAN FOR i I <br />QUANTITY AND LOCATIONS <br />I I <br />TYPICAL OVERRIDE KEYPAD <br />AS REQUIRED <br />r--------------------------- <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I LQ m I <br />I I <br />QSWS2-5BRLI-WH <br />5-BUTTON SCENE <br />SELECT WITH RAISE/LOWER <br />(1 GANG US BACKBOX BY OTHERS) <br />REFER TO FLOOR PLAN FOR <br />QUANTITY AND LOCATIONS <br />L--------------------------J <br />*ALTERNATE DATA -ONLY CABLE: USE APPROVED DATA LINK CABLE (22 AWG [0.5 mm2] <br />TWISTED/SHIELDED) FROM BELDEN (MODEL # 9461). <br />**TOTAL LENGTH OF THE QS LINK MUST NOT EXCEED 2,000 ft (600 m). <br />0 INPUT POWER (NORMAL -EMERGENCY) <br />❑ INPUT POWER (NORMAL) <br />2 #12AWG (4 mm2) <br />O 3 #12AWG (4 1 <br />® 0-1OV SIGNAL: 2 #18AWG (1.0 mm2) <br />E❑ CAT5E OR BETTER CABLE FOR LUTRON <br />NETWORK TERMINATED WITH RJ45 <br />CONNECTORS (TO BE PROVIDED BY <br />OTHERS). 328 ft (100 m) MAXIMUM RUN. <br />1-WAY RF COMMUNICATION <br />2-WAY RF COMMUNICATION <br />2 #18AWG (1.0 mm2) <br />CONCEPT DRAWING NOTES: <br />CONTROL SYSTEM DRAWING IS PROVIDED FOR CONCEPTUAL PURPOSES ONLY AND IS NOT <br />INTENDED FOR CONSTRUCTION. EXACT EQUIPMENT REQUIREMENTS, INCLUDING LOCATIONS AND <br />QUANTITIES, SHOULD BE VERIFIED IN ACCORDANCE WITH THE MOST UP-TO-DATE <br />LIGHTING/ELECTRICAL REFLECTED CEILING PLANS, LIGHTING FIXTURE SCHEDULES, PANEL <br />SCHEDULES, CONTROL INTENT AND SPECIFICATIONS. SHADE EQUIPMENT SHOULD BE VERIFIED IN <br />ACCORDANCE WITH ARCHITECTURAL PLANS, SPECIFICATIONS AND WINDOW <br />SCHEDULES/DETAILS. <br />WIRING LEGEND: <br />QQ QS CONTROL LINK (SEE WIRE DESCRIPTION BELOW) <br />.Q QS CONTROL LINK (SEE WIRE DESCRIPTION BELOW) <br />(CONNECT WIRES 1, 3 AND 4. DO NOT CONNECT WIRE # 2) <br />QS WIRING AS REQUIRED BY CONTROL LINK LENGTH <br />(REFER TO QS SMART PANEL POWER SUPPLY WIRING GUIDE FOR SHADE WIRING NOTES): <br />TOTAL CONTROL <br />WIRE GAUGE <br />AVAILABLE FROM LUTRON IN ONE <br />LINK LENGTH <br />CABLE: <br />POWER (TERMINALS 1&2): <br />LESS THAN 500ft <br />1 PAIR 18 AWG (1.0 mm0 <br />GRX-CBL-346S (NON -PLENUM) <br />(152.4 m) <br />OR <br />GRX-PCBL-346S (PLENUM) <br />DATA (TERMINALS 3&4): <br />1 PAIR 22 AWG (0.5 mm�, TWISTED AND SHIELDED* <br />POWER (TERMINALS 1&2): <br />500ft (152.4 m) TO <br />1 PAIR 12 AWG (4.0 mm� <br />GRX-CBL-46L (NON -PLENUM) <br />2,000ft (610 m)** <br />OR <br />GRX-PCBL-46L (PLENUM) <br />DATA (TERMINALS 3&4): <br />1 PAIR 22 AWG (0.5 ni TWISTED AND SHIELDED* <br />WIRING NOTES: <br />QS LINK RULES <br />THE FOLLOWING LINK RULES MUST BE OBSERVED FOR PROPER OPERATION: <br />• THIS IS A TOPOLOGY -FREE LINK (T-TAP, HOME -RUN, ETC. IS OK); REFER TO TABLE BELOW FOR <br />WIRE RUN LIMITS. <br />• IF WIRED DIFFERENTLY THAN WHAT IS SHOWN, POWER DRAW UNIT REQUIREMENTS NEED TO <br />BE CONFIRMED; SEE POWER DRAW UNITS (PDUs) SPECIFICATION SHEET INCLUDED IN THIS <br />SUBMITTAL. <br />• MAXIMUM OF 512 OUTPUTS (BALLASTS, SHADES, CONTACT CLOSURES, ETC). <br />• MAXIMUM OF 100 OCCUPANCY SENSORS, 100 DAYLIGHT SENSORS/RADIO SHADOW SENSORS <br />AND 100 KEYPADS. <br />• MAXIMUM OF 100 QS DEVICES (SUCH AS A GRAFIK EYEO QS, SEETOUCHO QS KEYPAD, SMART <br />PANEL POWER SUPPLY [ASPS-Px-10-60], ESN, OR SIVOIAO QS SHADE / DRAPERY DRIVE UNIT). <br />QUANTUM PROCESSOR COUNTS AS 1 DEVICE PER LINK. <br />• MAXIMUM OF 100 ZONES - SUCH AS A SIVOIA QS SHADE / DRAPERY DRIVE UNIT, OR A LIGHTING <br />ZONE ON A GRAFIK EYE QS (DOES NOT APPLY TO QUANTUM SYSTEMS). <br />• THE 10 OUTPUTS ON A QSPS-Px-10-60 CANNOT EXCEED A COMBINED LENGTH OF 2,000 ft (600 m). <br />QUANTUM NETWORK <br />WHEN A LIGHTING MANAGEMENT NETWORK (LMN) IS REQUIRED <br />TO ENABLE COMMUNICATIONS BETWEEN INDIVIDUAL LIGHT <br />MANAGEMENT HUBS (LMH) AND BETWEEN LMH AND THE <br />SYSTEM SERVER/DESKTOP/LAPTOP (Q-MANAGER). THE LMN <br />REQUIRES A DEDICATED LAN OR VLAN. IT IS THE <br />RESPONSIBILITY OF THE NETWORK PROVIDER TO ENSURE THE <br />RELIABILITY AND SECURITY OF THE LMN. <br />CAT5E OR BETTER ETHERNET CABLE TO BE RUN FOR <br />DEDICATED LMN TERMINATED WITH RJ45 CONNECTORS <br />(PROVIDED BY OTHERS). THE NUMBER OF ETHERNET <br />HOPS/SEGMENTS BETWEEN THE SERVER/DESKTOP/LAPTOP <br />(Q-MANAGER) AND ANY LMN NODE SHALL NOT EXCEED 6. <br />TOTAL LENGTH OF ETHERNET CABLE SHALL NOT EXCEED 328 <br />FT (100M) POINT-TO-POINT. <br />IF LONGER RUNS ARE REQUIRED, MULTI -MODE FIBER OPTIC <br />CABLE CAN BE USED INSTEAD WITH APPROPRIATE FIBER OPTIC <br />CONNECTORS (PROVIDED BY OTHERS). CONSULT WITH <br />NETWORK PROVIDER FOR STANDARD ETHERNET AND FIBER <br />OPTIC WIRING RULES FOR DISTANCE AND SEPARATION AS <br />WELL AS FOR PLACEMENT OF SWITCHES, ROUTERS, HUBS, ETC. <br />FOR MORE INFORMATION REGARDING NETWORK EQUIPMENT <br />REQUIREMENTS AND NETWORK CONFIGURATION, PLEASE <br />REFER TO THE QUANTUM LIGHTING MANAGEMENT NETWORK <br />SPECIFICATION SHEET OR CONTACT LUTRON. <br />PANEL LINK RULES <br />THE FOLLOWING LINK RULES MUST BE OBSERVED FOR PROPER OPERATION: <br />• PANELS ARE DAISY -CHAINED ON ONE OF THE CONFIGURABLE LINKS PER <br />LUTRON'S DRAWING, HOWEVER THEY DO NOT HAVE TO BE IN THE ORDER <br />SHOWN. <br />• DO NOT HOME -RUN OR T-TAP THIS WIRING LINK. ALL CIRCUITS NEED TO BE <br />LANDED IN THESE PANELS PER LUTRON'S PANEL SCHEDULES. <br />• THE MAXIMUM WIRE LENGTH OF A PANEL LINK IS 2,000 ft (600 m). A MX-RPTR IS <br />USED TO EXTEND THE LENGTH OF A LINK ANOTHER 2,000 ft (600 m). A MAXIMUM <br />OF (3) MX-RPTR'S MAY BE USED PER LINK FOR MAXIMUM LENGTH OF 8,000 ft <br />(2,430 m) PER LINK. <br />• IF A PANEL IS MOVED TO ANOTHER LINK, OR THE LOADS ARE NOT WIRED AS <br />SHOWN IN LUTRON PANEL SCHEDULES, LUTRON MUST BE NOTIFIED. THIS <br />INFORMATION IS IMPORTANT FOR PROGRAMMING THE SYSTEM. <br />• UP TO 32 CIRCUIT SELECTORS PER LINK <br />• UP TO 512 SWITCH LEGS OR ZONES PER LINK <br />• LT-1 LINK TERMINATORS NEEDED ON EACH END OF THE LINK <br />LED DIMMING REQUIRES AN EXACT MATCH BETWEEN THE LED ARRAY, DRIVER AND CONTROL. <br />LUTRON CANNOT GUARANTEE COMPATIBILITY OR PERFORMANCE WITHOUT TESTING THIS <br />COMBINATION. <br />TO CONFIRM WHAT PRODUCTS LUTRON HAS AVAILABLE OR WHAT INTERFACES MAY BE <br />REQUIRED, CALL 1-877-DIM-LED8 OR CHECK LUTRON'S PRODUCT COMPATIBILITY MATRIX ON-LINE <br />AT WWW.LUTRON.COM/LED. <br />TO REQUEST THE TESTING OF AN LED PRODUCT BY LUTRON MANUFACTURERS CAN FILL OUT AN <br />LED EVALUATION REQUEST FORM ON-LINE AT WWW.LUTRON.COM/LED OR CONTACT <br />LEDS@LUTRON.COM. <br />LUTRON CAN GUARANTEE COMPATIBILITY AND PERFORMANCE OF LUTRON HI-LUME A -SERIES LED <br />DRIVERS USED WITH APPROPRIATE LUTRON CONTROLS. THE HI-LUME A -SERIES LED DRIVER CAN <br />BE USED ON PRODUCTS UNDER 40 WATTS WITH SUITABLE MOUNTING LOCATIONS. PLEASE <br />REFER TO THE SPECIFICATION SUBMITTAL SHEET FOR FURTHER INFORMATION. <br />IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING 0-10V CONTROL, PERFORMANCE AND <br />COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. PRODUCTS FOLLOWING THE IEC <br />STANDARD 60929 ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS. <br />DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER'S DISCRETION. <br />IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING PHASE CONTROL, PERFORMANCE <br />AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. A -SERIES OR ELV PRODUCTS <br />PROVIDING HIGH END AND LOW END TRIM ADJUSTMENTS ARE MORE LIKELY TO PROVIDE <br />ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO <br />THE USER'S DISCRETION. <br />ELECTRICAL DETAILS <br />SCALE: NOT TO SCALE <br />E <br />II � <br />C&K ARCHITECTS I INTERIORS <br />architecture • interior design • client services <br />AAC001629 <br />4221 WEST BOY SCOUT BLVD., SUITE 150 <br />TAMPA, FL 33607-5743 <br />813.884.2000 <br />280 WEST CENTRAL AVE. <br />WINTER HAVEN, FL33880-2957 <br />863.577.2054 <br />Q J• F f �- <br />� �\CENSF.•.F� <br />��. <br />Q 65083. <br />5/1 2021 ° W <br />O STATE OF <br />F •••••:�C•0R \ 0 P� 'G� <br />SS/ONAL•�� <br />0 <br />N <br />s <br />r <br />mQ <br />0 <br />O <br />z <br />I.L. <br />J <br />J <br />a <br />w <br />N <br />W <br />0 <br />W � <br />Q �O <br />V_ a <br />N <br />0`' <br />i <br />V m <br />LU <br />m <br />i <br />LU <br />1100 <br />m <br />Q <br />C9 <br />M <br />to <br />0, <br />ISSUED FOR; <br />PERMIT <br />PROJECT NUMBER <br />21020 <br />DATE <br />5.5.21 <br />DRAWING NUMBER <br />E9III <br />i <br />- rr —7-r-FIF r i l � — _ -1 11 1- 1 1 11iu: f i, 1 i 11 11 1 11110 li iri,a. aril, Aflil.E i -,i i i I A i,usi i I I i I I T i <br />