C
<br />9412G BATTERY
<br />CALCULATIONS
<br />Description
<br />Device
<br />Quantity
<br />Standby
<br />Current
<br />Tota I
<br />Standby
<br />Current
<br />Alarm
<br />Current
<br />Tota I
<br />Alarm
<br />Current
<br />Control Panel
<br />D9412G
<br />1
<br />0.2250
<br />0.2250
<br />0.3000
<br />0.3000
<br />Battery Lead Supervision Module
<br />D113
<br />1
<br />0.0450
<br />0.0450
<br />0.0450
<br />0.0450
<br />SDI Sp litter
<br />SDI-9114
<br />1
<br />0.0300
<br />0.0300
<br />0.0300
<br />0.0300
<br />Dual Class A/B NAC Module
<br />D192G
<br />1
<br />0.0350
<br />0.0350
<br />0.1000
<br />0.1000
<br />Dual Phone Line DACT Module
<br />D928
<br />1
<br />0.0200
<br />0.0200
<br />0.1000
<br />0.1000
<br />Annunciator / Keypad (CP-SA)
<br />D1256
<br />1
<br />0.1060
<br />0.1060
<br />0.2250
<br />0.2250
<br />POPEX Module
<br />D8125
<br />1
<br />0.0600
<br />0.0600
<br />0.0600
<br />0.0600
<br />POPITS
<br />D9127
<br />84
<br />0.0005
<br />0.0420
<br />0.0008
<br />0.0672
<br />A �
<br />3Q. -
<br />-
<br />-
<br />-
<br />0.
<br />D.
<br />NEW POPITS
<br />D9127
<br />5
<br />0.0005
<br />0.0025
<br />0.0008
<br />0.0040
<br />Dual from C Relay (on Alarm)
<br />D8130
<br />1
<br />0.0070
<br />0.0070
<br />0.0600
<br />0.0600
<br />12v-4w Smoke Detector
<br />D273THE
<br />2
<br />0.0150
<br />0.0300
<br />0.0360
<br />0.0720
<br />-----
<br />TOTALS
<br />--
<br />\\ --Y
<br />--
<br />0.603
<br />L--
<br />ALARM
<br />1.183
<br />jilzrillillillillilm
<br />STANDBY
<br />COMPUTATIONS
<br />0 14.460 AH
<br />TOTAL AMPS USED IN STANDBY 603 X24HOURS
<br />_ _ = !
<br />TOTAL AMPS USED INALARM - 1.183 X 15 MIN 0.296 AH
<br />+20% CONTINGENCY% 2.951 AH
<br />TOTAL STANDBYBATTERYREQUII UgENTS= 17.707 AH
<br />TOTAL BACKUP BATTERYPRoviuw 36 000 AH
<br />TOTAL BACKUP BATTERY REQ L1IItID-. 17.07 7 AH
<br />TOTAL BACKUP BATTERY RESERVED-- 18.293 AH
<br />;EXISTING (2) 18ah batteries to provide 36 amp hours at 12 volts
<br />MONITORED BY 2
<br />DEDICATED SYSTEMS.
<br />1 - NETWORK
<br />1 - TELEPHONE LINE
<br />CENTRAL
<br />STATION
<br />AS PER MNFR'S REC.
<br />POWERED BY A LOCKED AND /
<br />DEDICATED BRANCH CIRCUIT
<br />120V A.C.
<br />THE EXISTING FIRE ALARM EQUIPMENT
<br />SHALL COMPLY WITH NFPA 72 10.6.5
<br />REGARDING CIRCUIT IDENTIFICATION AND
<br />ACCESSIBILITY (10.6.5.2.1), MECHANICAL
<br />PROTECTION (10.6.5.3), AND
<br />OVERCURRENT PROTECTION (10.6.5.5)
<br />MOUNTING HEIGHT
<br />BUSHING, AT
<br />END OF EMT
<br />cNG
<br />CEILING
<br />MOUNT 1 GANG
<br />WALL � i0,
<br />20 MAX. E 0 BACK BOX
<br />A.F.F. 'n AT OR 4S BACK
<br />DISPLREADAY T BOX W/1
<br />Td GANG MUD
<br />600_
<br />AION
<br />RING - TY?
<br />0
<br />48 TO 000NDUIT/EMT
<br />OP RATING
<br />ANNUNCM
<br />FMED
<br />FLOOR
<br />EXISTING I FAA
<br />EXISTING I FACU
<br />EXISTING
<br />FRCP
<br />VOLTAGE DROP CALCULATION
<br />WIRE GAUGE (# 12) R=0.00171 ohm/FT
<br />A
<br />B
<br />C
<br />D
<br />NAC
<br />CIRCUIT
<br />SOURCE
<br />VOLTAGE
<br />TOTAL AMP
<br />WIRE LENGTH
<br />(FAT)
<br />VOLT DROP
<br />(2xWBxC)
<br />% DROP (D/A)
<br />VOLTAGE AT
<br />LAST DEVICE
<br />(A-D)
<br />#4-1
<br />20.4
<br />0.572
<br />285
<br />0.56
<br />2.73
<br />19.84
<br />#4-2
<br />20.4
<br />1.05
<br />340
<br />1.22
<br />5.99
<br />19.18
<br />#4-3
<br />20.4
<br />0.743
<br />270
<br />0.69
<br />3.36
<br />19.71
<br />#4-4
<br />20.4
<br />0.49
<br />260
<br />0.44
<br />2.14
<br />19.96
<br />SCOPE OF WORK
<br />SCOPE OF WORK
<br />TYPICAL SIGNAL LINE CIRCUIT (SLC) CLASS B -18 AWG 3/PR STIR FPL. (IN 4'
<br />EMT CONDUIT IN PLENUM AREAS, IN FREE AIR IN OTHER AREAS).
<br />TYPICAL EXISTING DEVICES
<br />Oz U
<br />0
<br />O
<br />MANUAL
<br />ANSUL
<br />SMOKE PULL
<br />RISER
<br />RISER
<br />HOOD
<br />DUCT
<br />DETECTOR STATION
<br />WATERFLOW
<br />TAMPER
<br />SUPPRESSION
<br />SMOKE
<br />DETECTOR
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />SCOPE OF WORK
<br />Y,.:_ �y,
<br />Total
<br />Total
<br />Standby
<br />Standby Alarm
<br />Alarm
<br />Device
<br />Quantity Current
<br />Current Current
<br />Current
<br />AL1002UL-ADA
<br />1 0.090
<br />0.090 0.175
<br />0.175
<br />x
<br />CEILING STROBE SCWL 15 CD
<br />10 0.000 0.000 0.041 0.410
<br />T E P W 110 D 1 0.000
<br />WALL HORNS ROB 2 L C
<br />0.000
<br />0.162 0.162
<br />3h
<br />4'
<br />0.000
<br />0.143
<br />0.429
<br />CEILING HORN STROBE PC2WL 75 CD
<br />3 0.000
<br />CEILING STROBE SCWL 75 CD
<br />2 0.000
<br />0.000
<br />0.111
<br />0.222
<br />CEILING HORN STROBE PC2WL 15 CD
<br />1 0.000
<br />0.000
<br />0.071
<br />0.071
<br />CEILING STROBE SCWL 15 CD
<br />8 0.000
<br />0.000
<br />0.041
<br />0.328
<br />v. .. � a,' - �
<br />ON
<br />CEILING HORN STROBE PC2WL 75 CD
<br />3 0.000
<br />0.000
<br />0.143
<br />0.429
<br />CEILING STROBE SCWL 75 CD
<br />1 0.000
<br />0.000
<br />0.111
<br />0.111
<br />CEILING STROBE SCWL 15 CD
<br />2 0.000
<br />0.000
<br />0.041
<br />0.082
<br />WALL HORN STROBE P2WL 75 CD
<br />1 0.000
<br />0.000
<br />0.121
<br />0.121
<br />>x
<br />u r
<br />CEILING STROBE SCWL 15 CD
<br />9
<br />0.000
<br />0.000
<br />0.041
<br />0.369
<br />WALL HORN STROBE P2RL 75 CD
<br />1
<br />0.000
<br />0.000
<br />0.121
<br />0.121
<br />TOTAL
<br />TOTAL
<br />TOTALS,
<br />STANDBY
<br />0.090
<br />ALARM
<br />3.030
<br />COMPUTATIONS
<br />TOTAL AM SEb IN STANDBY 0 090 X 24 HOURS 2 160 AH
<br />O PS U
<br />._..e.a. . ,,. ....,. ..a.._. ,...._ ..... ,._.__e ._..,_
<br />TOTAL AMPS USED IN ALARM 3 030 X 5 MINUTES 0.251 AH
<br />.. _ _._ _ .._.. _ . ,__ ..... -._
<br />_.._ ......., .. _- ......... _ _ ., ............ v...... .. _ ...,.r.
<br />+20% CONTINTENCY= 0.482 AH
<br />TOTAL BACKUP BATTERY REQUIREMENTS- 2.894 AH
<br />-----
<br />TOTAL BACKUP BATTERY PROVIDED= 7.000 AH
<br />TOTAL BACKUP BATTERY REQUIRED= 2.894 AH
<br />-;---------- ----
<br />TOTAL BACKUP BATTERY RESERVED= 4.106 AH
<br />Provide (2)12VDC, 7.0 ah batteries for 7.0 amp hours at 24VDC.
<br />SCOPE OF WORK
<br />1 PT PT PT PT PT 1
<br />1 1
<br />POWER SUPPLY #4
<br />::MONNIMRING
<br />#1 #2 ABOVE
<br />NAC #4
<br />EXISTING POWER SUPPLY 1-3
<br />77_�
<br />V Vii V V V V V V HS V V LP7
<br />120V A.C. 15cd 15cd 15cd 15cd 15od 15cd 15cd 15od 110cd 15cd 15od
<br />V v v V V V v �7d VV��LP2
<br />1 NEW 1 d 75cd 7 1 75cd 15cd 15cd 15od 1 15cd 1 1
<br />AL1002-UL
<br />1 POWER V V HS V LP3 1
<br />SUPPLY 1 1 1 75cd 75cd 7 75cd 75W
<br />NAC #4 V V V V V V HS V �155,
<br />LP4 SCOPE OF WORK
<br />15cd 15cd 15cd 1 15od 15cd 75cd 1 15cd d
<br />TYPICAL NOTIFICATION APPLIANCE
<br />CIRCUIT (NAC) CLASS B -12 AWG 2/C
<br />STIR FPL. (IN 4' EMT CONDUIT IN
<br />PLENUM AREAS, AND IN FREE AIR IN
<br />OTHER AREAS)
<br />RISER DIAGRAM
<br />NOTIFICATION CIRCUIT
<br />FROM PREVIOUS
<br />DEVICE OR FACP
<br />NOTIFICATION CIRCUIT
<br />FROM PREVIOUS
<br />DEVICE OR FACP
<br />TO NEXT
<br />DEVICE OR EOL
<br />NOTIFICATION CIRCUIT
<br />TO NEXT
<br />DEVICE OR EOL
<br />NOTIFICATION CIRCUIT
<br />FIRE ALARM HORN/STROBE, STROBE WIRING
<br />SCALE: NONE
<br />1
<br />FP
<br />SECTION A -A
<br />TO EXISTING
<br />INITIATION DEVICES
<br />(84 EXISTING POPITS)
<br />System No. WL1001
<br />(Formerly System No. 147)
<br />F Rating- 1, 2, 3, and 4 Hr (See Items 2 and 3)
<br />T Rating- 0, 1, 2, 3, and 4 Hr (See Item 3)
<br />L Rating At Ambient- Less than 1 CFM/sq ft
<br />L Rating At 400 F- Less than 1 CFM/sq ft
<br />2. Pipe or Conduit- Nom 12 in. diem (or smaller) Schedule 10 (or heavier) steel pipe,
<br />nom 12 in. diam (or smaller) service weight (or heavier) Cast iron soil pie, nom 12
<br />in diem (or smaller) class 50 (or heavier) ductile iron pressure pipe, nom 6 in, diam
<br />(or smaller) steel conduit, nom 4 in. diam (or smaller) steel electrical metallic tubing,
<br />nom 6 in. dlam (or smaller) Type L (or heavier) copper tubing or nom 1 in. diem (or
<br />smaller) flexible steel conduit. When copper pipe is used, max F Rating of firestop
<br />system (Item 3) is 2 hr. Steel pipes or conduits larger than nom 4 in. clam may
<br />only be used in walls constructed using steel charnel studs. A max of one pipe or
<br />conduit is permitted in the firestop system. Pipe or conduit to be installed near
<br />center of stud cavity width and to be rigidly supported on both sides of wall
<br />assembly.
<br />3. Fill, Void or Cavity Material- Caulk- Caulk fill material Installed to completely fig
<br />annular space between pipe or conduit and gypsum wallboard and with a min V4
<br />in. diam bead of caulk applied to perimeter of pipe or conduit at its egress from
<br />the wag. Caulk installed symmetrically on both sides of wall assembly. The hourly F
<br />Rating of the firestop system is dependent upon the hourly fire rating of the wag
<br />assembly in which it is installed, as shown in the following table. The hourly T
<br />Rating of the firestop system is dependent upon the type or size of the pipe or
<br />conduit and the hourly fire rating of the wag assembly in which it is installed as
<br />tabulated below-
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1. Wall Assembly- The 1, 2, 3, or 4 hr fire -rated gypsum wallboard/stud wall assembly
<br />Max Pipe
<br />Annular
<br />F
<br />T
<br />shall be constructed of the materials and in the mamw described in the individual
<br />or Conduit
<br />Space,
<br />Rating,
<br />Rating,
<br />U300 or U400 Series Wag or Partition Designs in the UL Fire Resistance Directory
<br />Diam, In
<br />In
<br />Hr
<br />Hr
<br />and shag include the following construction Features-
<br />1
<br />0 to 3/10
<br />1 or 2
<br />0+, 1 or 2
<br />a. Studs- Wag framing may consist of either wood studs (max 2 hr fire rated
<br />1
<br />V4 to 1/2
<br />3 or 4
<br />3 pr 4
<br />assemblies) or steel channel studs. Wood studs to consist of nom 2 by 4 in.
<br />4
<br />0 to V4
<br />1 or 2
<br />0
<br />lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross
<br />4
<br />1 to 1-1/2•
<br />1 or 2
<br />0
<br />braces. Steel studs to be min 3-5/8 in. wide by 1-3/8 in. deep channels spaced
<br />6
<br />1/4 to 1/2
<br />3 or 4
<br />0
<br />max 24 In. OC.
<br />12
<br />3/10 to 3/8
<br />1 or 2
<br />0
<br />b. Wallboard, Gypsum- Nom V2 or 5/8 in. thick, 4 ft. wide with square or tapered
<br />+ When capper pipe is
<br />used, T Rating is 0 hr
<br />edges. The gypsum wallboard type, thickness, number of layers, fastener type
<br />in 0 to 1-V2 in. annular. space applies only when Type CP-25
<br />WB+ cauk is used
<br />and street orientation shall be specified in the individual U300 or U400 Series
<br />and only when the min
<br />thickness of the gypsum
<br />wallboard is
<br />6/8 in. for 1 hr rated
<br />Design in the UL Fire Resistance Directory Max clam of opening is 13-V2 in.
<br />wags and 1-V4 in. for 2 hr rated wags.
<br />FIRE STOP DETAIL
<br />SCALE: NONE
<br />POINT TO BE
<br />ANNUNCIATED AS
<br />POINT TYPE
<br />FIRE ALARM
<br />SUPERVISORY ALARM
<br />WATER FLOW
<br />X
<br />TAMPER
<br />X
<br />MANUAL PULL STATION
<br />X
<br />SMOKE DETECTORS
<br />X
<br />X
<br />DUCT SMOKE DETECTORS
<br />X
<br />COOKING HOOD SUPPRESSION SYSTEM
<br />X
<br />ALL FIRE ALARM SYSTEM CIRCUIT WIRING MUST ANNUNCIATE A TROUBLE SIGNAL DURING OPEN AND
<br />GROUND FAULT CONDITIONS. ADDITIONALLY ALL OUTPUT CIRCUITS (HORNS/STROBES) ARE REQUIRED TO
<br />ANNUNCIATE A TROUBLE SIGNAL DURING A WIRE TO WIRE SHORT CONDITION. THE FIRE ALARM SYSTEM
<br />WILL BE TESTED BY THE OWNER'S REPRESENTATIVES TO THE CRITERIA OF NFPA 72.
<br />0
<br />71
<br />SEQUENCE OF OPERATIONS
<br />(n
<br />z
<br />O
<br />=
<br />E
<br />a
<br />3
<br />z
<br />�
<br />NOTES:
<br />N
<br />o
<br />o
<br />d
<br />W
<br />o
<br />N
<br />J
<br />o
<br />w
<br />3
<br />fa-
<br />w
<br />Z
<br />M
<br />0
<br />w
<br />M
<br />Q
<br />o-
<br />CENTRAL STATION TO RECEIVE
<br />z
<br />(n
<br />Y
<br />N
<br />a
<br />¢
<br />SEPARATE & DISTINCT SIGNALS.
<br />Z
<br />W
<br />O
<br />0
<br />:3Q
<br />o
<br />3
<br />dU
<br />in
<br />Q
<br />Q
<br />M
<br />O
<br />F
<br />0
<br />0
<br />0
<br />0
<br />0}
<br />0
<br />0
<br />0
<br />0
<br />0
<br />0
<br />00
<br />V)
<br />O
<br />O
<br />U
<br />>
<br />1
<br />�
<br />1
<br />w
<br />m
<br />>
<br />>W
<br />LLJF
<br />F
<br />L=
<br />f- a
<br />f-
<br />F
<br />O
<br />�a
<br />a
<br />a
<br />a((nn
<br />a
<br />a
<br />X
<br />X
<br />X
<br />X
<br />ACTIVATES HORN/STROBE LIGHTS
<br />X
<br />X
<br />X
<br />X
<br />TRANSMIT ALARM SIGNAL TO APPROVED CENTRAL
<br />STATION ALARM MONITORING SERVICE
<br />X
<br />X
<br />TRANSMIT SUPERVISORY SIGNAL TO APPROVED
<br />CENTRAL STATION ALARM MONITORING SERVICE
<br />X
<br />TRANSMIT TROUBLE SIGNAL TO APPROVED
<br />CENTRAL STATION ALARM MONITORING SERVICE
<br />X
<br />ACTIVATES INDIVIDUAL RTU SHUTDOWN
<br />X
<br />ACTIVATES EWP BELL ABOVE FDC
<br />FIRE ALARM SYMBOLS LEGEND
<br />SYMBOL
<br />CITY.
<br />DESCRIPTION
<br />MAKE/MODEL
<br />EDEXISTING
<br />FIRE ALARM CONTROL PANEL
<br />BOSCH D9412G
<br />FACU
<br />EXISTING
<br />FIRE ALARM CONTROL UNIT
<br />BOSCH D1256
<br />ElEXISTING
<br />FIRE ALARM ANNUNCIATOR
<br />BOSCH D1257
<br />NAC
<br />1 NEW
<br />NOTIFICATION POWER SUPPLY
<br />ALTRONIX AL1002ULADA
<br />2
<br />O
<br />1 NEW
<br />SMOKE DETECTOR W/
<br />END OF LINE RELAY
<br />BOSCH D273THE
<br />D2
<br />NEW
<br />MANUAL PULL STATION
<br />BOSCH FMM-100
<br />2DUCT
<br />OEXISTING
<br />SMOKE DETECTOR
<br />SYSTEM SENSOR D4120
<br />O
<br />32 NEW
<br />CEILING MOUNT STROBE
<br />SYSTEM SENSOR SCWL
<br />MULTI CANDELA
<br />®
<br />8 NEW
<br />CEILING MOUNT HORN/STROBE
<br />MULTI CANDELA
<br />SYSTEM SENSOR PC2WL
<br />HS
<br />3 NEW
<br />WALL M MOUNT
<br />HORN STROBE, MULTI CANDELA
<br />SYSTEM SENSOR P2WL
<br />EXISTING
<br />COOKING HOOD SUPPRESSION
<br />SYSTEM
<br />(POINT OF CONNECTION ONLY)
<br />PT
<br />5 NEW
<br />POPT MODULE
<br />BOSCH D9127U
<br />X ,
<br />EXISTING
<br />WATERFLOW INDICATOR SWITCH
<br />(PROVIDED BY OTHERS)
<br />EXISTING
<br />SPRINKLER SYSTEM CONTROL VALVE
<br />(PROVIDED BY OTHERS)
<br />SUPERVISORY TAMPER SWITCH
<br />END OF LINE RESISTOR/DEVICE
<br />PER MANUFACTURER
<br />WIRE LEGEND
<br />A _ _ FIRE ALARM SYSTEM
<br />3pr #18 AWG FPL TWISTED
<br />B _ _ _ _ NOTIFICATION CIRCUIT
<br />-------
<br />1 pr #12 AWG FPL ZIP
<br />C MULTIPLE CABLES
<br />PLENUM RATED CABLE FPLP SHALL BE UTILIZED IN PLENUM RATED CEILING AREAS ONLY
<br />NO PLENUM RATED CEILING IN THIS PROJECT
<br />WP = WEATHERPROOF CABLE SHALL BE PROVIDED AS REQUIRED
<br />(+) POSITIVE CIRCUIT POLARITY (-) NEGATIVE CIRCUIT POLARITY
<br />AHJ / COMPLIANCE NOTES
<br />"PROPRIETARY SYSTEM"
<br />1. THIS SYSTEM DESIGN IS BASED UPON COMPLIANCE
<br />WITH THE NATIONAL, STATE AND LOCAL CODES.
<br />THE OCCUPANCY CLASS IS MERCANTILE.
<br />2. REMOTE ANNUNCIATOR(S) WILL FEATURE POINT I.D.
<br />OF ALL DEVICES/ZONES IN PLAIN ENGLISH DISPLAY.
<br />THE CPU CABINET HAS NO ANNUNCIATOR OR USER
<br />INTERFACE CONTROLS, AND IS A CABINET HOUSING
<br />(NON -ANALOG ADDRESSABLE) CIRCUITRY ONLY.
<br />3. AT LEAST ONE MANUAL STATION WILL BE
<br />INSTALLED AND LOCATED WHERE REQUIRED BY THE
<br />AHJ, PER NFPA 72. UNLESS OTHERWISE SPECIFIED
<br />BY THE AHJ, IT WILL BE LOCATED PER THE
<br />DRAWING.
<br />4. ONE SMOKE DETECTOR WILL BE INSTALLED ABOVE
<br />THE CPU IN ACCORDANCE WITH NFPA 72.
<br />5. AIR HANDLING UNITS IN EXCESS OF 2000 CFM
<br />WHICH INCLUDE DUCT SMOKE DETECTORS SHALL
<br />SHUT DOWN THEIR RESPECTIVE FANS AND CAUSE A
<br />"SUPERVISORY" SIGNAL ON THE CPU PER NFPA
<br />90A. SEE SCOPE OF MECHANICAL CONTRACTORS
<br />SHOP DRAWINGS FOR DETAILS.
<br />6. ALL NON -REQUIRED DEVICES INDICATED IN THE
<br />SUBMITTAL (IF ANY), ARE VOLUNTARILY PROVIDED
<br />AND ARE DESIGNATED AS "SUPPLEMENTARY" IN
<br />NATURE, AS DEFINED IN NFPA 72.
<br />7. AUDIBLE AND VISUAL NOTIFICATION APPLIANCES
<br />ARE PROVIDED AS INDICATED ON THE PLAN.
<br />8. WALMART SECURITY TECHNOLOGY WILL INSTALL THE
<br />FIRE ALARM WHERE LEGALLY ENTITLED BY
<br />LICENSING, PERMITTING, CERTIFICATION OR
<br />EXEMPTION. LOCAL CONTRACTOR TO BE USED
<br />ELSEWHERE.
<br />9. OFF PREMISES, AUTOMATIC EMERGENCY
<br />NOTIFICATION WILL BE VIA 2 APPROVED MEANS OF
<br />COMMUNICATION TO WAL-MART'S UL LISTED
<br />(UUFX) CENTER. SEE UL FILE #S3152-1 FOR
<br />CERTIFICATE INFORMATION.
<br />10. WIRING WILL BE INSTALLED PER (THE NEC) NFPA
<br />70 AND ALL OTHER APPLICABLE SECTIONS. ALL
<br />EQUIPMENT SHALL BE PROPERLY LISTED PER NFPA
<br />72.
<br />11. THIS SYSTEM IS DESIGNATED AS A "PROPRIETARY
<br />SUPERVISING STATION SYSTEM" IN ACCORDANCE
<br />WITH NFPA 72 WITH 24 HOURS OF STAND-BY
<br />POWER THEN 5 MINUTES IN "ALARM" PER NFPA 72.
<br />STORE MANAGEMENT PERSONNEL ARE DESIGNATED
<br />FOR 1 HOUR RUNNER SERVICE.
<br />12. THESE NOTES DO NOT SUPERCEDE REQUIREMENTS
<br />OF OTHER TRADES, SPECIFICALLY INCLUDING
<br />MECHANICAL.
<br />13. APPLICABLE STATE AND LOCAL MODIFICATIONS
<br />ADOPTED THROUGH DUE PROCESS OF LAW AND
<br />WHICH CONFLICT WITH THESE NOTES SHALL
<br />SUPERCEDE AND COPIES SHOULD BE CONVEYED TO
<br />THE CONTACT PERSON INDICATED BELOW.
<br />DIRECT FIRE ALARM RELATED (ONLY) COMPLIANCE
<br />ISSUES TO:
<br />SACRAMENTO ENGINEERING CONSULTANTS
<br />10555 OLD PLACERVILLE RD
<br />SACRAMENTO, CA 95827
<br />PHONE: 916-368-4468
<br />FAX: 916-368-4490
<br />EMAIL: rh@saceng.com
<br />z
<br />a
<br />f-
<br />J
<br />z
<br />0
<br />U
<br />W
<br />- N O f-
<br />0
<br />r`
<br />Q
<br />W
<br />z a
<br />r7 W
<br />0
<br />� rn c f-
<br />U
<br />�a W
<br />C
<br />DO
<br />u�-ia`o3WJ
<br />LOOS- rrQ
<br />z
<br />ova
<br />$
<br />W
<br />A
<br />00
<br />0
<br />00
<br />w
<br />O
<br />U�
<br />M
<br />►--�
<br />j
<br />O
<br />Z
<br />F�LLJ
<br />c)
<br />A
<br />Ri
<br />w
<br />N
<br />fx
<br />w
<br />A
<br />0
<br />►-s
<br />.ISSUE BLOCK
<br />CHECKED BY: RH
<br />DRAWN BY: SM
<br />FILE NAME:
<br />PROTO CYCLE:
<br />DOCUMENT DATE: 12-12-20
<br />1►pt l4At [eX*I#lUI:LI•t>t•]:
<br />Date Signed: April 9, 2021
<br />ELECTRONIC
<br />FIRE
<br />PROTECTION
<br />DETAILS, 8c
<br />CALCS.
<br />�EEEFP2