TYPMAL <br />DESIGN AREA #DA1 <br />4TH FLOOR UNIT Cl COMMON AREA <br />COMPARTMENT DESIGN PER NFPA 13R, <br />SECTION 7.1.1 <br />18' X 18' SPACING 18' X 18' SPACING <br />S1 17GPM @ 12 PSI S17GPM @ 12 PSI <br />18' X 18' SPACING <br />S <br />17GPM @ 12 PSI <br />DENSITY.05 <br />DOMESTIC DEMAND - 177 GPM R00947N <br />DESIGN AREA #DA2 <br />4TH FLOOR UNIT Cl BEDROOM <br />COMPARTMENT DESIGN PER NFPA 13R, <br />SECTION 7.1 <br />S4 20' X 20' SPACING <br />20 GPM @ 16.7 PSI <br />SINGLE SPRINKLER PROOF CALCULATION <br />DOMESTIC DEMAND - 177 GPM R00943N <br />DESIGN AREA #DA3 <br />4TH FLOOR OUTSIDE DWELLING UNIT <br />we RrMh l r. DESIGN PER NFPA 13R, <br />SECTION 7.2 <br />18' X 18' SPACING 18' X 18' SPACING <br />S5 17 GPM @ 12 PSI S6 17 GPM @ 12 PSI <br />18' X 18' SPACING 18' X 18' SPACING <br />S7 17GPM @ 12 PSI SS 17GPM @ 12 PSI <br />DENSITY.05 <br />DOMESTIC DEMAND - 177 GPM R00946N <br />UNT A <br />UNIT B <br />UNIT C <br />TABLES AAA (a)/(b) DOMESTIC OEMAM <br />SCALE: NONE <br />aleo..t+b R'• 1p I dd..� k 00334N <br />TOTAL <br />FUCNRE LOAD PER ITEM <br />NLIMBER OF ITEMS <br />ITEM <br />BATH GRouPs W FLUSH TAW 1 6 6 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SA�BCS 1 2 2 <br />LAVATORY <br />W <br />WATER CLOSET FLUSH TANG - 3 0 <br />DISFIWASHERS 1 1 1 <br />WAS MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 11 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF ITEMS <br />ITEM <br />BATH GROUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SNKS 1 2 2 <br />LAVATORY 1 1 1 <br />WATER CLOSET W FLUSH TANK - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHING MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 18 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF RENTS <br />REM <br />BATH c�IOUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KRC�'IEN SINKS 1 2 2 <br />LAVATORY 2 1 2 <br />WATER CLOSET W RUSH TANG - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHNC�i MACFNES 1 2 2 <br />TOTAL FIXTURE LOAD PER LINT 19 <br />in <br />LINT A LINT B LINT C <br />TOTAL AXTVRE LOAD PER LINT 11 18 19 <br />TOTAL UNITS PER BULDN4 25 23 4 <br />TOTAL LOAD LINTS PERLINT 275 414 76 <br />TOTAL UM' DEMAND PER BUt.DIVC 765 <br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED <br />LI <br />SPRINKLERS <br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE <br />15,132 SQ. Fi. EACH <br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE <br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5 <br />CEI <br />NG HEIGFTT 9'-0' A.F.F. <br />I <br />-- 1 •1 IYI_ - - <br />1 I :1 <br />DESIGN AREA #DA2 <br />4TH FLOOR UNIT Cl BEDROOM <br />COMPARTMENT DESIGN PER NFPA 13R, <br />SECTION 7.1 <br />S4 20' X 20' SPACING <br />20 GPM @ 16.7 PSI <br />SINGLE SPRINKLER PROOF CALCULATION <br />DOMESTIC DEMAND - 177 GPM R00943N <br />DESIGN AREA #DA3 <br />4TH FLOOR OUTSIDE DWELLING UNIT <br />we RrMh l r. DESIGN PER NFPA 13R, <br />SECTION 7.2 <br />18' X 18' SPACING 18' X 18' SPACING <br />S5 17 GPM @ 12 PSI S6 17 GPM @ 12 PSI <br />18' X 18' SPACING 18' X 18' SPACING <br />S7 17GPM @ 12 PSI SS 17GPM @ 12 PSI <br />DENSITY.05 <br />DOMESTIC DEMAND - 177 GPM R00946N <br />UNT A <br />UNIT B <br />UNIT C <br />TABLES AAA (a)/(b) DOMESTIC OEMAM <br />SCALE: NONE <br />aleo..t+b R'• 1p I dd..� k 00334N <br />TOTAL <br />FUCNRE LOAD PER ITEM <br />NLIMBER OF ITEMS <br />ITEM <br />BATH GRouPs W FLUSH TAW 1 6 6 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SA�BCS 1 2 2 <br />LAVATORY <br />W <br />WATER CLOSET FLUSH TANG - 3 0 <br />DISFIWASHERS 1 1 1 <br />WAS MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 11 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF ITEMS <br />ITEM <br />BATH GROUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SNKS 1 2 2 <br />LAVATORY 1 1 1 <br />WATER CLOSET W FLUSH TANK - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHING MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 18 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF RENTS <br />REM <br />BATH c�IOUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KRC�'IEN SINKS 1 2 2 <br />LAVATORY 2 1 2 <br />WATER CLOSET W RUSH TANG - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHNC�i MACFNES 1 2 2 <br />TOTAL FIXTURE LOAD PER LINT 19 <br />in <br />LINT A LINT B LINT C <br />TOTAL AXTVRE LOAD PER LINT 11 18 19 <br />TOTAL UNITS PER BULDN4 25 23 4 <br />TOTAL LOAD LINTS PERLINT 275 414 76 <br />TOTAL UM' DEMAND PER BUt.DIVC 765 <br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED <br />LI <br />SPRINKLERS <br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE <br />15,132 SQ. Fi. EACH <br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE <br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5 <br />CEI <br />NG HEIGFTT 9'-0' A.F.F. <br />I <br />-- 1 •1 IYI_ - - <br />1 I :1 <br />DESIGN AREA #DA3 <br />4TH FLOOR OUTSIDE DWELLING UNIT <br />we RrMh l r. DESIGN PER NFPA 13R, <br />SECTION 7.2 <br />18' X 18' SPACING 18' X 18' SPACING <br />S5 17 GPM @ 12 PSI S6 17 GPM @ 12 PSI <br />18' X 18' SPACING 18' X 18' SPACING <br />S7 17GPM @ 12 PSI SS 17GPM @ 12 PSI <br />DENSITY.05 <br />DOMESTIC DEMAND - 177 GPM R00946N <br />UNT A <br />UNIT B <br />UNIT C <br />TABLES AAA (a)/(b) DOMESTIC OEMAM <br />SCALE: NONE <br />aleo..t+b R'• 1p I dd..� k 00334N <br />TOTAL <br />FUCNRE LOAD PER ITEM <br />NLIMBER OF ITEMS <br />ITEM <br />BATH GRouPs W FLUSH TAW 1 6 6 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SA�BCS 1 2 2 <br />LAVATORY <br />W <br />WATER CLOSET FLUSH TANG - 3 0 <br />DISFIWASHERS 1 1 1 <br />WAS MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 11 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF ITEMS <br />ITEM <br />BATH GROUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SNKS 1 2 2 <br />LAVATORY 1 1 1 <br />WATER CLOSET W FLUSH TANK - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHING MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 18 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF RENTS <br />REM <br />BATH c�IOUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KRC�'IEN SINKS 1 2 2 <br />LAVATORY 2 1 2 <br />WATER CLOSET W RUSH TANG - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHNC�i MACFNES 1 2 2 <br />TOTAL FIXTURE LOAD PER LINT 19 <br />in <br />LINT A LINT B LINT C <br />TOTAL AXTVRE LOAD PER LINT 11 18 19 <br />TOTAL UNITS PER BULDN4 25 23 4 <br />TOTAL LOAD LINTS PERLINT 275 414 76 <br />TOTAL UM' DEMAND PER BUt.DIVC 765 <br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED <br />LI <br />SPRINKLERS <br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE <br />15,132 SQ. Fi. EACH <br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE <br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5 <br />CEI <br />NG HEIGFTT 9'-0' A.F.F. <br />I <br />-- 1 •1 IYI_ - - <br />1 I :1 <br />UNT A <br />UNIT B <br />UNIT C <br />TABLES AAA (a)/(b) DOMESTIC OEMAM <br />SCALE: NONE <br />aleo..t+b R'• 1p I dd..� k 00334N <br />TOTAL <br />FUCNRE LOAD PER ITEM <br />NLIMBER OF ITEMS <br />ITEM <br />BATH GRouPs W FLUSH TAW 1 6 6 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SA�BCS 1 2 2 <br />LAVATORY <br />W <br />WATER CLOSET FLUSH TANG - 3 0 <br />DISFIWASHERS 1 1 1 <br />WAS MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 11 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF ITEMS <br />ITEM <br />BATH GROUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SNKS 1 2 2 <br />LAVATORY 1 1 1 <br />WATER CLOSET W FLUSH TANK - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHING MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 18 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF RENTS <br />REM <br />BATH c�IOUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KRC�'IEN SINKS 1 2 2 <br />LAVATORY 2 1 2 <br />WATER CLOSET W RUSH TANG - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHNC�i MACFNES 1 2 2 <br />TOTAL FIXTURE LOAD PER LINT 19 <br />in <br />LINT A LINT B LINT C <br />TOTAL AXTVRE LOAD PER LINT 11 18 19 <br />TOTAL UNITS PER BULDN4 25 23 4 <br />TOTAL LOAD LINTS PERLINT 275 414 76 <br />TOTAL UM' DEMAND PER BUt.DIVC 765 <br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED <br />LI <br />SPRINKLERS <br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE <br />15,132 SQ. Fi. EACH <br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE <br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5 <br />CEI <br />NG HEIGFTT 9'-0' A.F.F. <br />I <br />-- 1 •1 IYI_ - - <br />1 I :1 <br />TOTAL <br />FUCNRE LOAD PER ITEM <br />NLIMBER OF ITEMS <br />ITEM <br />BATH GRouPs W FLUSH TAW 1 6 6 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SA�BCS 1 2 2 <br />LAVATORY <br />W <br />WATER CLOSET FLUSH TANG - 3 0 <br />DISFIWASHERS 1 1 1 <br />WAS MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 11 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF ITEMS <br />ITEM <br />BATH GROUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SNKS 1 2 2 <br />LAVATORY 1 1 1 <br />WATER CLOSET W FLUSH TANK - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHING MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 18 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF RENTS <br />REM <br />BATH c�IOUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KRC�'IEN SINKS 1 2 2 <br />LAVATORY 2 1 2 <br />WATER CLOSET W RUSH TANG - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHNC�i MACFNES 1 2 2 <br />TOTAL FIXTURE LOAD PER LINT 19 <br />in <br />LINT A LINT B LINT C <br />TOTAL AXTVRE LOAD PER LINT 11 18 19 <br />TOTAL UNITS PER BULDN4 25 23 4 <br />TOTAL LOAD LINTS PERLINT 275 414 76 <br />TOTAL UM' DEMAND PER BUt.DIVC 765 <br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED <br />LI <br />SPRINKLERS <br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE <br />15,132 SQ. Fi. EACH <br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE <br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5 <br />CEI <br />NG HEIGFTT 9'-0' A.F.F. <br />I <br />-- 1 •1 IYI_ - - <br />1 I :1 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF ITEMS <br />ITEM <br />BATH GROUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KITCHEN SNKS 1 2 2 <br />LAVATORY 1 1 1 <br />WATER CLOSET W FLUSH TANK - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHING MACHINES 1 2 2 <br />TOTAL FIXTURE LOAD PER UNIT 18 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF RENTS <br />REM <br />BATH c�IOUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KRC�'IEN SINKS 1 2 2 <br />LAVATORY 2 1 2 <br />WATER CLOSET W RUSH TANG - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHNC�i MACFNES 1 2 2 <br />TOTAL FIXTURE LOAD PER LINT 19 <br />in <br />LINT A LINT B LINT C <br />TOTAL AXTVRE LOAD PER LINT 11 18 19 <br />TOTAL UNITS PER BULDN4 25 23 4 <br />TOTAL LOAD LINTS PERLINT 275 414 76 <br />TOTAL UM' DEMAND PER BUt.DIVC 765 <br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED <br />LI <br />SPRINKLERS <br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE <br />15,132 SQ. Fi. EACH <br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE <br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5 <br />CEI <br />NG HEIGFTT 9'-0' A.F.F. <br />I <br />-- 1 •1 IYI_ - - <br />1 I :1 <br />TOTAL <br />RXTURE LOAD PER ITEM <br />NUMBER OF RENTS <br />REM <br />BATH c�IOUPS W FLUSH TANG 2 6 12 <br />BATHTUB OR SHOWER STALL - 2 0 <br />KRC�'IEN SINKS 1 2 2 <br />LAVATORY 2 1 2 <br />WATER CLOSET W RUSH TANG - 3 0 <br />DISI-NVASHERS 1 1 1 <br />WASHNC�i MACFNES 1 2 2 <br />TOTAL FIXTURE LOAD PER LINT 19 <br />in <br />LINT A LINT B LINT C <br />TOTAL AXTVRE LOAD PER LINT 11 18 19 <br />TOTAL UNITS PER BULDN4 25 23 4 <br />TOTAL LOAD LINTS PERLINT 275 414 76 <br />TOTAL UM' DEMAND PER BUt.DIVC 765 <br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED <br />LI <br />SPRINKLERS <br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE <br />15,132 SQ. Fi. EACH <br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE <br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5 <br />CEI <br />NG HEIGFTT 9'-0' A.F.F. <br />I <br />-- 1 •1 IYI_ - - <br />1 I :1 <br />LINT A LINT B LINT C <br />TOTAL AXTVRE LOAD PER LINT 11 18 19 <br />TOTAL UNITS PER BULDN4 25 23 4 <br />TOTAL LOAD LINTS PERLINT 275 414 76 <br />TOTAL UM' DEMAND PER BUt.DIVC 765 <br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED <br />LI <br />SPRINKLERS <br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE <br />15,132 SQ. Fi. EACH <br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE <br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5 <br />CEI <br />NG HEIGFTT 9'-0' A.F.F. <br />I <br />-- 1 •1 IYI_ - - <br />1 I :1 <br />SPRINKLERS <br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE <br />15,132 SQ. Fi. EACH <br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE <br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5 <br />CEI <br />NG HEIGFTT 9'-0' A.F.F. <br />I <br />-- 1 •1 IYI_ - - <br />1 I :1 <br />No.7,1374 <br />i) <br />1l:.cv; <br />TATE OF 1(/ <br />\ <br />� 4 P ORIVP-�w�^� P8 <br />PL <br />89 w. • • •FL LILEditf Nk�7W4 <br />TNR mm a ORL OI m CIAM ACa"ma w TIE C M LY Mmm mm cm LUTE Ot Lmu W WR m M <br />E M%MUU ffMEAO FOR VIE HE/FCTDL IMM M NANIIOW= W VATLE WO FM PNM== ZVSMM M RCTOI K <br />WE fl�ftY FM PI MMY NAMM A WHIM M R PNOI OM Mrf= 9KL TE TIMT O• M 9WNM S TIE <br />ALM ULAEA NM NLY =nM A CWY OF TIO PM"UT AMOR a NU ►MLdM VONVIE WWTOI M IM NnN= W THIS <br />113IEIL RIME CMRACF THE NPIM WM W VAYIE MM MY! FM OFMAM ■C <br />CPVC COMPATIBILITY NOTICE <br />CPC FM aIIMBLO FlIE tril[IE NINE B IItEO >IWi71MULY Fitt TOE TWA R WAU 9 NEW W6MCn0l4 K-M Ai <br />NOWR QVC PEA ME OGLLr BIETD FM TIES 4""TOE BE ID TILR OIfEM � flawm 6 0WRIOWLY. <br />N AEV% CPVC CM t NWAD N CIWACT V)M 04)MMs FLOE IN = ORIMOM R%M MU M EBE VWL nJ^ <br />R MMA IYAO POMWM 00 AIM M=LW PMWM MBl1 M TNLTiM WAAfM LEAK ffiItOM FEC111 L NU Noah <br />M azmmL ETC NM Fumm TMT mO EI CORMT VHR CPA ilpRO F@E NUT ME LVMJATO, FOR A LW W CMMTMZ <br />PIE RM FLEAS RViV NI1N <br />COPYRIGHT <br />ALL DOCUMENTS, INCLUDING ORIGINAL DRAWINGS, SPECIFICATIONS, FIELD NOTES, ESTIMATES AND DATA, INCLUDING COMPUTER <br />PROGRAMS PURSUANT TO THIS PROJECT ARE AND WILL REMAIN THE PROPERTY OF VAYNE AUTOMATIC FIRE SPRINKLERS, INC. <br />(VAFS) AS INSTRUMENTS OF SERVICE. THEY ARE NOT INTENDED. NOR REPRESENTED TO BE SUITABLE FDR RE -USE BY THE CL1E� <br />OR OTHERS, ON EXTENSION OF THIS PROJECT, OR F12R ANY OTHER PROJECT. ANY REUSE OR ADAPTATION OF THE INFORMATION <br />CONTAINED HEREIN WITHOUT SPECIFIC WRITTEN PERMISSION FROM VAFS WILL BE AT THE CLIENTS SGLE RISK, WITHOUT <br />LIABILITY, OR LEGAL EXPOSURE TD VAFS, AND WILL ENTITLE VAFS TO FURTHER COMPENSATION AT RATES TO RE AGREED IN <br />BETWEEN WAFS AND THE CLIENT. THE CLIENT SHALL ALSO INDEMNIFY AND HOLD VAFS HARMLESS FROM ANY AND ALL CLAIMS, <br />DAMAGES, LOSSES AND EXPENSES, INCLUDING ATTORNEYS FEES RESULTING FROM ANY SUCH PERMISSIONS. <br />GRAPHICS ELEMENTS NOTE <br />FM OPME t COOM M 1I V= M TAW N A MM MY MMM TUa = M OMWOMB M OUR= )IaLN1YO <br />"M M AMMMTUMI, CIVIL, 9n9 CIUA6 M MP MMWNM. TTELE LEFITIEFEEE MMM M MMOrR ME FM <br />ODIOML WOIMUN Ot COIfW ONLY M M FM V=K= ENONULR aER NU ACM" ANY I WOMMM rM <br />TNDE LLOLMi M FM iFIDLLJD OAfO®t N OLY rM MM POI RM W YNE FM WO" <br />aLAwm SPMMLI FM EFmm" uQEL W WM II = 10 MM M AR09= WL iTLNA:TI OM. NL} M CLVL <br />EMVDM! rM AUfMWATM t Q >1R MOM WOWYM DAY MY ! URTSD IM FTAE BFMMM <br />WATER SUPPLY INFORMATION <br />XMK WOW �o�AIKIM FRE PUMP <br />sU. GPM 0 PSI <br />STATIC PRESSURE 55 2 - <br />FrAM PARE 50 OF TEST 9 16 <br />FLOW IN GPM 1000 TI& OF TEST 10:30 <br />PITOT REAM 36 PAR OF PORTS RMM 1 <br />TEST PROVIDED BY CRY OF ZEPHYR HIUS UTILITIES <br />HYDRANT 11256 <br />ff SPNN4FR5 N DESIGN AND <br />4 <br />1 <br />4 <br />MNIIWM DENSITY <br />.05 <br />.05 <br />.05 <br />DESIGN AREA S.F. <br />4 SPRINKLERS <br />1 SPRINKLER <br />4 SPRINKLERS <br />PSI 0 BO <br />46.9 PSI <br />42.3 PSI <br />34.9 PSI <br />GPM RE b 0 BASR <br />55.6 GPM <br />20.0 GPM <br />59.2 GPM <br />PSI 'D 0 TEST <br />51.3 PSI <br />46.0 PSI <br />39.5 PSI <br />GPY REO'D O TEST <br />1 232.6 GPM <br />1 197.0 GPM <br />1 246.2 GPM <br />IKO� ®"■��i,77i�yt�.:il111::�iillli�l:� 5;�i;d;')♦ <br />N <br />� r� I�htt;;ii�l�:�riiF)if��I:►;;'„i�;t�:'� <br />'I� �■ `" � �`.A°i�I�MtF;;i(Il:'�litti•1il:F;;1;��;�F;_� <br />1 <br />DATE sTJSMrrt'AI,s BY <br />10/28/2022 CA REVIEW V C <br />INE / l \ 1 Ai/Al/Ai 1 -- 1-1 <br />WAYI� <br />AtJbNY1atIC Rre sarlfiderSF Ir1c. <br />MAIN OFFICE — ORLANDO. FLORIDA <br />� cAPrrai. <br />COURT K]K:COE, R.oRDA 34781 <br />FHONE (407) <br />3030 FAX (SOT e6Q�6 <br />IACK/OrVLLE, R. <br />TAdPA, FL <br />�a iIAQI, FL <br />Us OMTflBITIOV AVE WM3EEs <br />Ci6NY PALM ONE <br />ow PtTPIH<!E FELLD <br />CSUNVLLE R.�ti <br />TAAPA, FL 87BA-s837 <br />Ot$Ft3D BEAM R.38M2PNDE <br />OWiM8-8090 <br />Rt1FE am880-U®03 <br />PLgF6 ON)sD-3080FAX <br />WM E[8-078A <br />PJACFFr. <br />FAK OMs30-fl8E <br />FAXOb{) BD-LM24 <br />PT.wr■MPL.co�coRo�INC�LATMO <br />AVE <br />AAYL3f8, FL 88906-4U2A <br />487U ADTON9POR O1VETHAFMLE <br />CWCOQ NC 2R7PJ-sYT7 <br />WM <br />pN,gK NC OW <br />P)AFE (E9iu 488-:1080 <br />FAX O'9M 493-9Es3 <br />PI06 004) 782-3082 <br />FAX 004) 796-ELiBU <br />PFM (M 7E8-284U <br />ZEPHYR COMMON <br />EMERSON HILL CIRCLE <br />ZEPHYR HILLS, FL. 33541 <br />LANDSOUTH CONSTRUCTION <br />4233 PABLO PROFESSIONAL CT. <br />JACKSONVILLE, FL. 32224 <br />SHEET TITLE] <br />BLDG TYPE I FOURTH FLOOR PLAN <br />DRAWN BY, <br />VINNIE COMO <br />TOTAL A/S1 <br />2,854 <br />DATE, <br />9/13/2022 <br />AHJI <br />PASCO COUNTY <br />CONTRACT • <br />109678 <br />CENTER OF TILE JOB? E] YES NO <br />CENTER ON FIXTURES JOB? [:] YES NO <br />SHEET FP1 2 # <br />■ <br />CONSTRUCTIUN TYPE, <br />V-A <br />OCCUPANCYI <br />R-2 <br />