TYPMAL
<br />DESIGN AREA #DA1
<br />4TH FLOOR UNIT Cl COMMON AREA
<br />COMPARTMENT DESIGN PER NFPA 13R,
<br />SECTION 7.1.1
<br />18' X 18' SPACING 18' X 18' SPACING
<br />S1 17GPM @ 12 PSI S17GPM @ 12 PSI
<br />18' X 18' SPACING
<br />S
<br />17GPM @ 12 PSI
<br />DENSITY.05
<br />DOMESTIC DEMAND - 177 GPM R00947N
<br />DESIGN AREA #DA2
<br />4TH FLOOR UNIT Cl BEDROOM
<br />COMPARTMENT DESIGN PER NFPA 13R,
<br />SECTION 7.1
<br />S4 20' X 20' SPACING
<br />20 GPM @ 16.7 PSI
<br />SINGLE SPRINKLER PROOF CALCULATION
<br />DOMESTIC DEMAND - 177 GPM R00943N
<br />DESIGN AREA #DA3
<br />4TH FLOOR OUTSIDE DWELLING UNIT
<br />we RrMh l r. DESIGN PER NFPA 13R,
<br />SECTION 7.2
<br />18' X 18' SPACING 18' X 18' SPACING
<br />S5 17 GPM @ 12 PSI S6 17 GPM @ 12 PSI
<br />18' X 18' SPACING 18' X 18' SPACING
<br />S7 17GPM @ 12 PSI SS 17GPM @ 12 PSI
<br />DENSITY.05
<br />DOMESTIC DEMAND - 177 GPM R00946N
<br />UNT A
<br />UNIT B
<br />UNIT C
<br />TABLES AAA (a)/(b) DOMESTIC OEMAM
<br />SCALE: NONE
<br />aleo..t+b R'• 1p I dd..� k 00334N
<br />TOTAL
<br />FUCNRE LOAD PER ITEM
<br />NLIMBER OF ITEMS
<br />ITEM
<br />BATH GRouPs W FLUSH TAW 1 6 6
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SA�BCS 1 2 2
<br />LAVATORY
<br />W
<br />WATER CLOSET FLUSH TANG - 3 0
<br />DISFIWASHERS 1 1 1
<br />WAS MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 11
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF ITEMS
<br />ITEM
<br />BATH GROUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SNKS 1 2 2
<br />LAVATORY 1 1 1
<br />WATER CLOSET W FLUSH TANK - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHING MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 18
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF RENTS
<br />REM
<br />BATH c�IOUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KRC�'IEN SINKS 1 2 2
<br />LAVATORY 2 1 2
<br />WATER CLOSET W RUSH TANG - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHNC�i MACFNES 1 2 2
<br />TOTAL FIXTURE LOAD PER LINT 19
<br />in
<br />LINT A LINT B LINT C
<br />TOTAL AXTVRE LOAD PER LINT 11 18 19
<br />TOTAL UNITS PER BULDN4 25 23 4
<br />TOTAL LOAD LINTS PERLINT 275 414 76
<br />TOTAL UM' DEMAND PER BUt.DIVC 765
<br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED
<br />LI
<br />SPRINKLERS
<br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE
<br />15,132 SQ. Fi. EACH
<br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE
<br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5
<br />CEI
<br />NG HEIGFTT 9'-0' A.F.F.
<br />I
<br />-- 1 •1 IYI_ - -
<br />1 I :1
<br />DESIGN AREA #DA2
<br />4TH FLOOR UNIT Cl BEDROOM
<br />COMPARTMENT DESIGN PER NFPA 13R,
<br />SECTION 7.1
<br />S4 20' X 20' SPACING
<br />20 GPM @ 16.7 PSI
<br />SINGLE SPRINKLER PROOF CALCULATION
<br />DOMESTIC DEMAND - 177 GPM R00943N
<br />DESIGN AREA #DA3
<br />4TH FLOOR OUTSIDE DWELLING UNIT
<br />we RrMh l r. DESIGN PER NFPA 13R,
<br />SECTION 7.2
<br />18' X 18' SPACING 18' X 18' SPACING
<br />S5 17 GPM @ 12 PSI S6 17 GPM @ 12 PSI
<br />18' X 18' SPACING 18' X 18' SPACING
<br />S7 17GPM @ 12 PSI SS 17GPM @ 12 PSI
<br />DENSITY.05
<br />DOMESTIC DEMAND - 177 GPM R00946N
<br />UNT A
<br />UNIT B
<br />UNIT C
<br />TABLES AAA (a)/(b) DOMESTIC OEMAM
<br />SCALE: NONE
<br />aleo..t+b R'• 1p I dd..� k 00334N
<br />TOTAL
<br />FUCNRE LOAD PER ITEM
<br />NLIMBER OF ITEMS
<br />ITEM
<br />BATH GRouPs W FLUSH TAW 1 6 6
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SA�BCS 1 2 2
<br />LAVATORY
<br />W
<br />WATER CLOSET FLUSH TANG - 3 0
<br />DISFIWASHERS 1 1 1
<br />WAS MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 11
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF ITEMS
<br />ITEM
<br />BATH GROUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SNKS 1 2 2
<br />LAVATORY 1 1 1
<br />WATER CLOSET W FLUSH TANK - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHING MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 18
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF RENTS
<br />REM
<br />BATH c�IOUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KRC�'IEN SINKS 1 2 2
<br />LAVATORY 2 1 2
<br />WATER CLOSET W RUSH TANG - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHNC�i MACFNES 1 2 2
<br />TOTAL FIXTURE LOAD PER LINT 19
<br />in
<br />LINT A LINT B LINT C
<br />TOTAL AXTVRE LOAD PER LINT 11 18 19
<br />TOTAL UNITS PER BULDN4 25 23 4
<br />TOTAL LOAD LINTS PERLINT 275 414 76
<br />TOTAL UM' DEMAND PER BUt.DIVC 765
<br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED
<br />LI
<br />SPRINKLERS
<br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE
<br />15,132 SQ. Fi. EACH
<br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE
<br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5
<br />CEI
<br />NG HEIGFTT 9'-0' A.F.F.
<br />I
<br />-- 1 •1 IYI_ - -
<br />1 I :1
<br />DESIGN AREA #DA3
<br />4TH FLOOR OUTSIDE DWELLING UNIT
<br />we RrMh l r. DESIGN PER NFPA 13R,
<br />SECTION 7.2
<br />18' X 18' SPACING 18' X 18' SPACING
<br />S5 17 GPM @ 12 PSI S6 17 GPM @ 12 PSI
<br />18' X 18' SPACING 18' X 18' SPACING
<br />S7 17GPM @ 12 PSI SS 17GPM @ 12 PSI
<br />DENSITY.05
<br />DOMESTIC DEMAND - 177 GPM R00946N
<br />UNT A
<br />UNIT B
<br />UNIT C
<br />TABLES AAA (a)/(b) DOMESTIC OEMAM
<br />SCALE: NONE
<br />aleo..t+b R'• 1p I dd..� k 00334N
<br />TOTAL
<br />FUCNRE LOAD PER ITEM
<br />NLIMBER OF ITEMS
<br />ITEM
<br />BATH GRouPs W FLUSH TAW 1 6 6
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SA�BCS 1 2 2
<br />LAVATORY
<br />W
<br />WATER CLOSET FLUSH TANG - 3 0
<br />DISFIWASHERS 1 1 1
<br />WAS MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 11
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF ITEMS
<br />ITEM
<br />BATH GROUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SNKS 1 2 2
<br />LAVATORY 1 1 1
<br />WATER CLOSET W FLUSH TANK - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHING MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 18
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF RENTS
<br />REM
<br />BATH c�IOUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KRC�'IEN SINKS 1 2 2
<br />LAVATORY 2 1 2
<br />WATER CLOSET W RUSH TANG - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHNC�i MACFNES 1 2 2
<br />TOTAL FIXTURE LOAD PER LINT 19
<br />in
<br />LINT A LINT B LINT C
<br />TOTAL AXTVRE LOAD PER LINT 11 18 19
<br />TOTAL UNITS PER BULDN4 25 23 4
<br />TOTAL LOAD LINTS PERLINT 275 414 76
<br />TOTAL UM' DEMAND PER BUt.DIVC 765
<br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED
<br />LI
<br />SPRINKLERS
<br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE
<br />15,132 SQ. Fi. EACH
<br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE
<br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5
<br />CEI
<br />NG HEIGFTT 9'-0' A.F.F.
<br />I
<br />-- 1 •1 IYI_ - -
<br />1 I :1
<br />UNT A
<br />UNIT B
<br />UNIT C
<br />TABLES AAA (a)/(b) DOMESTIC OEMAM
<br />SCALE: NONE
<br />aleo..t+b R'• 1p I dd..� k 00334N
<br />TOTAL
<br />FUCNRE LOAD PER ITEM
<br />NLIMBER OF ITEMS
<br />ITEM
<br />BATH GRouPs W FLUSH TAW 1 6 6
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SA�BCS 1 2 2
<br />LAVATORY
<br />W
<br />WATER CLOSET FLUSH TANG - 3 0
<br />DISFIWASHERS 1 1 1
<br />WAS MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 11
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF ITEMS
<br />ITEM
<br />BATH GROUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SNKS 1 2 2
<br />LAVATORY 1 1 1
<br />WATER CLOSET W FLUSH TANK - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHING MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 18
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF RENTS
<br />REM
<br />BATH c�IOUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KRC�'IEN SINKS 1 2 2
<br />LAVATORY 2 1 2
<br />WATER CLOSET W RUSH TANG - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHNC�i MACFNES 1 2 2
<br />TOTAL FIXTURE LOAD PER LINT 19
<br />in
<br />LINT A LINT B LINT C
<br />TOTAL AXTVRE LOAD PER LINT 11 18 19
<br />TOTAL UNITS PER BULDN4 25 23 4
<br />TOTAL LOAD LINTS PERLINT 275 414 76
<br />TOTAL UM' DEMAND PER BUt.DIVC 765
<br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED
<br />LI
<br />SPRINKLERS
<br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE
<br />15,132 SQ. Fi. EACH
<br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE
<br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5
<br />CEI
<br />NG HEIGFTT 9'-0' A.F.F.
<br />I
<br />-- 1 •1 IYI_ - -
<br />1 I :1
<br />TOTAL
<br />FUCNRE LOAD PER ITEM
<br />NLIMBER OF ITEMS
<br />ITEM
<br />BATH GRouPs W FLUSH TAW 1 6 6
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SA�BCS 1 2 2
<br />LAVATORY
<br />W
<br />WATER CLOSET FLUSH TANG - 3 0
<br />DISFIWASHERS 1 1 1
<br />WAS MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 11
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF ITEMS
<br />ITEM
<br />BATH GROUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SNKS 1 2 2
<br />LAVATORY 1 1 1
<br />WATER CLOSET W FLUSH TANK - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHING MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 18
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF RENTS
<br />REM
<br />BATH c�IOUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KRC�'IEN SINKS 1 2 2
<br />LAVATORY 2 1 2
<br />WATER CLOSET W RUSH TANG - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHNC�i MACFNES 1 2 2
<br />TOTAL FIXTURE LOAD PER LINT 19
<br />in
<br />LINT A LINT B LINT C
<br />TOTAL AXTVRE LOAD PER LINT 11 18 19
<br />TOTAL UNITS PER BULDN4 25 23 4
<br />TOTAL LOAD LINTS PERLINT 275 414 76
<br />TOTAL UM' DEMAND PER BUt.DIVC 765
<br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED
<br />LI
<br />SPRINKLERS
<br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE
<br />15,132 SQ. Fi. EACH
<br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE
<br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5
<br />CEI
<br />NG HEIGFTT 9'-0' A.F.F.
<br />I
<br />-- 1 •1 IYI_ - -
<br />1 I :1
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF ITEMS
<br />ITEM
<br />BATH GROUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KITCHEN SNKS 1 2 2
<br />LAVATORY 1 1 1
<br />WATER CLOSET W FLUSH TANK - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHING MACHINES 1 2 2
<br />TOTAL FIXTURE LOAD PER UNIT 18
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF RENTS
<br />REM
<br />BATH c�IOUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KRC�'IEN SINKS 1 2 2
<br />LAVATORY 2 1 2
<br />WATER CLOSET W RUSH TANG - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHNC�i MACFNES 1 2 2
<br />TOTAL FIXTURE LOAD PER LINT 19
<br />in
<br />LINT A LINT B LINT C
<br />TOTAL AXTVRE LOAD PER LINT 11 18 19
<br />TOTAL UNITS PER BULDN4 25 23 4
<br />TOTAL LOAD LINTS PERLINT 275 414 76
<br />TOTAL UM' DEMAND PER BUt.DIVC 765
<br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED
<br />LI
<br />SPRINKLERS
<br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE
<br />15,132 SQ. Fi. EACH
<br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE
<br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5
<br />CEI
<br />NG HEIGFTT 9'-0' A.F.F.
<br />I
<br />-- 1 •1 IYI_ - -
<br />1 I :1
<br />TOTAL
<br />RXTURE LOAD PER ITEM
<br />NUMBER OF RENTS
<br />REM
<br />BATH c�IOUPS W FLUSH TANG 2 6 12
<br />BATHTUB OR SHOWER STALL - 2 0
<br />KRC�'IEN SINKS 1 2 2
<br />LAVATORY 2 1 2
<br />WATER CLOSET W RUSH TANG - 3 0
<br />DISI-NVASHERS 1 1 1
<br />WASHNC�i MACFNES 1 2 2
<br />TOTAL FIXTURE LOAD PER LINT 19
<br />in
<br />LINT A LINT B LINT C
<br />TOTAL AXTVRE LOAD PER LINT 11 18 19
<br />TOTAL UNITS PER BULDN4 25 23 4
<br />TOTAL LOAD LINTS PERLINT 275 414 76
<br />TOTAL UM' DEMAND PER BUt.DIVC 765
<br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED
<br />LI
<br />SPRINKLERS
<br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE
<br />15,132 SQ. Fi. EACH
<br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE
<br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5
<br />CEI
<br />NG HEIGFTT 9'-0' A.F.F.
<br />I
<br />-- 1 •1 IYI_ - -
<br />1 I :1
<br />LINT A LINT B LINT C
<br />TOTAL AXTVRE LOAD PER LINT 11 18 19
<br />TOTAL UNITS PER BULDN4 25 23 4
<br />TOTAL LOAD LINTS PERLINT 275 414 76
<br />TOTAL UM' DEMAND PER BUt.DIVC 765
<br />TOTAL DOMIN GM ESTIC DEMAND 177PER BLDC3 TION USED
<br />LI
<br />SPRINKLERS
<br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE
<br />15,132 SQ. Fi. EACH
<br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE
<br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5
<br />CEI
<br />NG HEIGFTT 9'-0' A.F.F.
<br />I
<br />-- 1 •1 IYI_ - -
<br />1 I :1
<br />SPRINKLERS
<br />FOURTH FLOOR FIRE PROTECTION PLAN L��L _STEEL PIPE
<br />15,132 SQ. Fi. EACH
<br />2HR SEPARATION BETNiEEN UNfiS � —CPVC PIPE
<br />THIS LAYOUT TYPICAL FOR UNITS 3,4,dc5
<br />CEI
<br />NG HEIGFTT 9'-0' A.F.F.
<br />I
<br />-- 1 •1 IYI_ - -
<br />1 I :1
<br />No.7,1374
<br />i)
<br />1l:.cv;
<br />TATE OF 1(/
<br />\
<br />� 4 P ORIVP-�w�^� P8
<br />PL
<br />89 w. • • •FL LILEditf Nk�7W4
<br />TNR mm a ORL OI m CIAM ACa"ma w TIE C M LY Mmm mm cm LUTE Ot Lmu W WR m M
<br />E M%MUU ffMEAO FOR VIE HE/FCTDL IMM M NANIIOW= W VATLE WO FM PNM== ZVSMM M RCTOI K
<br />WE fl�ftY FM PI MMY NAMM A WHIM M R PNOI OM Mrf= 9KL TE TIMT O• M 9WNM S TIE
<br />ALM ULAEA NM NLY =nM A CWY OF TIO PM"UT AMOR a NU ►MLdM VONVIE WWTOI M IM NnN= W THIS
<br />113IEIL RIME CMRACF THE NPIM WM W VAYIE MM MY! FM OFMAM ■C
<br />CPVC COMPATIBILITY NOTICE
<br />CPC FM aIIMBLO FlIE tril[IE NINE B IItEO >IWi71MULY Fitt TOE TWA R WAU 9 NEW W6MCn0l4 K-M Ai
<br />NOWR QVC PEA ME OGLLr BIETD FM TIES 4""TOE BE ID TILR OIfEM � flawm 6 0WRIOWLY.
<br />N AEV% CPVC CM t NWAD N CIWACT V)M 04)MMs FLOE IN = ORIMOM R%M MU M EBE VWL nJ^
<br />R MMA IYAO POMWM 00 AIM M=LW PMWM MBl1 M TNLTiM WAAfM LEAK ffiItOM FEC111 L NU Noah
<br />M azmmL ETC NM Fumm TMT mO EI CORMT VHR CPA ilpRO F@E NUT ME LVMJATO, FOR A LW W CMMTMZ
<br />PIE RM FLEAS RViV NI1N
<br />COPYRIGHT
<br />ALL DOCUMENTS, INCLUDING ORIGINAL DRAWINGS, SPECIFICATIONS, FIELD NOTES, ESTIMATES AND DATA, INCLUDING COMPUTER
<br />PROGRAMS PURSUANT TO THIS PROJECT ARE AND WILL REMAIN THE PROPERTY OF VAYNE AUTOMATIC FIRE SPRINKLERS, INC.
<br />(VAFS) AS INSTRUMENTS OF SERVICE. THEY ARE NOT INTENDED. NOR REPRESENTED TO BE SUITABLE FDR RE -USE BY THE CL1E�
<br />OR OTHERS, ON EXTENSION OF THIS PROJECT, OR F12R ANY OTHER PROJECT. ANY REUSE OR ADAPTATION OF THE INFORMATION
<br />CONTAINED HEREIN WITHOUT SPECIFIC WRITTEN PERMISSION FROM VAFS WILL BE AT THE CLIENTS SGLE RISK, WITHOUT
<br />LIABILITY, OR LEGAL EXPOSURE TD VAFS, AND WILL ENTITLE VAFS TO FURTHER COMPENSATION AT RATES TO RE AGREED IN
<br />BETWEEN WAFS AND THE CLIENT. THE CLIENT SHALL ALSO INDEMNIFY AND HOLD VAFS HARMLESS FROM ANY AND ALL CLAIMS,
<br />DAMAGES, LOSSES AND EXPENSES, INCLUDING ATTORNEYS FEES RESULTING FROM ANY SUCH PERMISSIONS.
<br />GRAPHICS ELEMENTS NOTE
<br />FM OPME t COOM M 1I V= M TAW N A MM MY MMM TUa = M OMWOMB M OUR= )IaLN1YO
<br />"M M AMMMTUMI, CIVIL, 9n9 CIUA6 M MP MMWNM. TTELE LEFITIEFEEE MMM M MMOrR ME FM
<br />ODIOML WOIMUN Ot COIfW ONLY M M FM V=K= ENONULR aER NU ACM" ANY I WOMMM rM
<br />TNDE LLOLMi M FM iFIDLLJD OAfO®t N OLY rM MM POI RM W YNE FM WO"
<br />aLAwm SPMMLI FM EFmm" uQEL W WM II = 10 MM M AR09= WL iTLNA:TI OM. NL} M CLVL
<br />EMVDM! rM AUfMWATM t Q >1R MOM WOWYM DAY MY ! URTSD IM FTAE BFMMM
<br />WATER SUPPLY INFORMATION
<br />XMK WOW �o�AIKIM FRE PUMP
<br />sU. GPM 0 PSI
<br />STATIC PRESSURE 55 2 -
<br />FrAM PARE 50 OF TEST 9 16
<br />FLOW IN GPM 1000 TI& OF TEST 10:30
<br />PITOT REAM 36 PAR OF PORTS RMM 1
<br />TEST PROVIDED BY CRY OF ZEPHYR HIUS UTILITIES
<br />HYDRANT 11256
<br />ff SPNN4FR5 N DESIGN AND
<br />4
<br />1
<br />4
<br />MNIIWM DENSITY
<br />.05
<br />.05
<br />.05
<br />DESIGN AREA S.F.
<br />4 SPRINKLERS
<br />1 SPRINKLER
<br />4 SPRINKLERS
<br />PSI 0 BO
<br />46.9 PSI
<br />42.3 PSI
<br />34.9 PSI
<br />GPM RE b 0 BASR
<br />55.6 GPM
<br />20.0 GPM
<br />59.2 GPM
<br />PSI 'D 0 TEST
<br />51.3 PSI
<br />46.0 PSI
<br />39.5 PSI
<br />GPY REO'D O TEST
<br />1 232.6 GPM
<br />1 197.0 GPM
<br />1 246.2 GPM
<br />IKO� ®"■��i,77i�yt�.:il111::�iillli�l:� 5;�i;d;')♦
<br />N
<br />� r� I�htt;;ii�l�:�riiF)if��I:►;;'„i�;t�:'�
<br />'I� �■ `" � �`.A°i�I�MtF;;i(Il:'�litti•1il:F;;1;��;�F;_�
<br />1
<br />DATE sTJSMrrt'AI,s BY
<br />10/28/2022 CA REVIEW V C
<br />INE / l \ 1 Ai/Al/Ai 1 -- 1-1
<br />WAYI�
<br />AtJbNY1atIC Rre sarlfiderSF Ir1c.
<br />MAIN OFFICE — ORLANDO. FLORIDA
<br />� cAPrrai.
<br />COURT K]K:COE, R.oRDA 34781
<br />FHONE (407)
<br />3030 FAX (SOT e6Q�6
<br />IACK/OrVLLE, R.
<br />TAdPA, FL
<br />�a iIAQI, FL
<br />Us OMTflBITIOV AVE WM3EEs
<br />Ci6NY PALM ONE
<br />ow PtTPIH<!E FELLD
<br />CSUNVLLE R.�ti
<br />TAAPA, FL 87BA-s837
<br />Ot$Ft3D BEAM R.38M2PNDE
<br />OWiM8-8090
<br />Rt1FE am880-U®03
<br />PLgF6 ON)sD-3080FAX
<br />WM E[8-078A
<br />PJACFFr.
<br />FAK OMs30-fl8E
<br />FAXOb{) BD-LM24
<br />PT.wr■MPL.co�coRo�INC�LATMO
<br />AVE
<br />AAYL3f8, FL 88906-4U2A
<br />487U ADTON9POR O1VETHAFMLE
<br />CWCOQ NC 2R7PJ-sYT7
<br />WM
<br />pN,gK NC OW
<br />P)AFE (E9iu 488-:1080
<br />FAX O'9M 493-9Es3
<br />PI06 004) 782-3082
<br />FAX 004) 796-ELiBU
<br />PFM (M 7E8-284U
<br />ZEPHYR COMMON
<br />EMERSON HILL CIRCLE
<br />ZEPHYR HILLS, FL. 33541
<br />LANDSOUTH CONSTRUCTION
<br />4233 PABLO PROFESSIONAL CT.
<br />JACKSONVILLE, FL. 32224
<br />SHEET TITLE]
<br />BLDG TYPE I FOURTH FLOOR PLAN
<br />DRAWN BY,
<br />VINNIE COMO
<br />TOTAL A/S1
<br />2,854
<br />DATE,
<br />9/13/2022
<br />AHJI
<br />PASCO COUNTY
<br />CONTRACT •
<br />109678
<br />CENTER OF TILE JOB? E] YES NO
<br />CENTER ON FIXTURES JOB? [:] YES NO
<br />SHEET FP1 2 #
<br />■
<br />CONSTRUCTIUN TYPE,
<br />V-A
<br />OCCUPANCYI
<br />R-2