<br />• DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH 2O16 EDITION OF NFPA 13R AND 2016 EDITION
<br />OF NFPA 13 WHERE DESIGNATED BY NFPA 13R.
<br />• DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH ALL APPLICABLE LOCAL AND STATE CODES.
<br />• ALL PIPE AND FITTINGS USED ON THIS PROJECT TO BE IN ACCORDANCE WITH APPLICABLE CODES AND
<br />WAFS STANDARDS. SEE PIPE AND FITTINGS GENERAL NOTES (WAFS DETAIL 1N00593N).
<br />• ALL HANGERS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH NFPA 13 AND THEIR LISTING.
<br />• ALL SEISMIC BRACING, IF REQUIRED, SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH NFPA 13
<br />AND THEIR LISTING.
<br />• ALL PENETRATIONS THROUGH RATED BUILDING ASSEMBLIES SHALL BE SEALED WITH FIRE CAULK IN
<br />ACCORDANCE WITH DETAILS PROVIDED. WAFS POLICY IS TO USE HILTI FS ONE OR STI LCI.
<br />• UNDERGROUND MAINS AND LEAD-INS SHALL BE FLUSHED AND SIGNED TEST CERTIFICATES PROVIDED
<br />BEFORE A CONNECTION IS MADE TO THE SPRINKLER SYSTEM.
<br />• ALL PIPING SHALL BE INSPECTED AND APPROVED BY PROPER AUTHORITIES PRIOR TO COVERING WITH
<br />DRYWALL. COPIES OF SIGNED TEST CERTIFICATES ARE TO BE FORWARDED TO THE PROPER RECIPIENTS.
<br />• ALL SYSTEMS SHALL BE TESTED AT 200 PSI FOR 2 HOURS.
<br />• ALL SOFFITS REQUIRED TO CONCEAL SPRINKLER PIPING ARE BY OTHERS.
<br />• ALL WIRING OF DEVICES (FLOW SWITCHES, TAMPER SWITCHES, COMPRESSORS, ETC) IS BY OTHERS.
<br />• CONNECTION OF SPRINKLER DEVICES TO THE BUILDING ALARM OR MONITORING SYSTEM IS BY OTHERS.
<br />• ALL PAINTING OF PIPE AS REQUIRED IS BY OTHERS.
<br />• ALL INSULATION REQUIRED FOR FREEZE PROTECTION OF SPRINKLER PIPING IS BY OTHERS.
<br />• HEATING OF ROOMS TO MAINTAIN TEMPERATURES OF 40 DEGREES OR GREATER IS BY OTHERS.
<br />• FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT LESS THAN 18' AND NOT MORE THAN 48'
<br />ABOVE THE LEVEL OF THE ADJACENT GRADE.
<br />• SPRINKLERS SHALL NOT BE INSTALLED PRIOR TO THE FITTINGS BEING CEMENTED IN PLACE.
<br />• ALL SPRINKLERS IN DWELLING UNITS SHALL BE UL LISTED OR FM APPROVED RESIDENTIAL SPRINKLERS.
<br />• ALL SPRINKLERS OUTSIDE OF DWELLING UNITS SHALL BE QUICK RESPONSE. RESIDENTIAL SPRINKLERS
<br />SHALL BE ALLOWED AS PER NFPA 13R SECTION 6.2.2.
<br />• SPARE SPRINKLERS OF EACH TYPE, TEMPERATURE RATING AND ORIFICE SIZE AND APPROPRIATE WRENCH
<br />OR WRENCHES SHALL BE LEFT ON THE PREMISES. ON A SINGLE PROPERTY UNDER THE SAME
<br />OWNERSHIP, SPRINKLERS WILL BE PROVIDED IN A SINGLE LOCATION.
<br />• REFER TO SPACING NOTES ON PLANS FOR MAXIMUM CALCULATED SPACING ALLOWANCES.
<br />• SPRINKLERS SHALL BE PROVIDED IN ALL OPEN ENDED CORRIDORS THAT ARE NOT SEPARATED FROM THE
<br />EXIT STAIRS PER IBC/NCBC/FBC 903.3.1.2.2.
<br />• SPRINKLERS SHALL BE INSTALLED IN ALL AREAS EXCEPT AS FOLLOWS:
<br />o BATHROOMS WHERE THE AREA DOES NOT EXCEED 55 SO FT (INCLUDING TUBS AND SHOWERS).
<br />o CLOTHES CLOSETS, LINEN CLOSETS AND PANTRIES WITHIN THE DWELLING UNITS THAT DO NOT EXCEED
<br />24 SQUARE FEET, THE LEAST DIMENSION DOES NOT EXCEED 3 FEET, AND THE WALLS AND CEILINGS
<br />ARE SURFACED WITH NONCOMBUSTIBLE OR LIMITED -COMBUSTIBLE MATERIALS AS DEFINED BY NFPA
<br />220, STANDARD ON TYPES OF BUILDING CONSTRUCTION.
<br />o ANY PORCHES, BALCONIES (EXCEPT THOSE OF TYPE V CONSTRUCTION). CORRIDORS, AND STAIRS THAT
<br />ARE OPEN AND ATTACHED.
<br />o ATTICS, PENTHOUSE EQUIPMENT ROOMS, ELEVATOR MACHINE ROOMS, CONCEALED SPACES DEDICATED
<br />EXCLUSIVELY TO AND CONTAINING ONLY DWELLING UNIT VENTILATION EQUIPMENT, CRAWL SPACES,
<br />FLOOR/CEILING SPACES, NONCOMBUSTIBLE ELEVATOR SHAFTS WHERE THE ELEVATOR CARS COMPLY
<br />WITH ANSI A17.1, AND OTHER CONCEALED SPACES THAT ARE NOT USED OR INTENDED FOR LIVING
<br />PURPOSES OR STORAGE AND DO NOT CONTAIN FUEL -FIRED EQUIPMENT.
<br />o CLOSETS ON EXTERIOR BALCONIES AND EXTERIOR BREEZEWAYS/CORRIDORS, REGARDLESS OF SIZE OR
<br />CONTENTS, AS LONG AS THERE ARE NO DOORS OR UNPROTECTED PENETRATIONS FROM THE CLOSET
<br />DIRECTLY INTO THE DWELLING UNIT.
<br />o CEILING POCKETS THAT MEET THE FOLLOWING REQUIREMENTS:
<br />1. THE TOTAL VOLUME OF THE UNPROTECTED CEILING POCKET DOES NOTE EXCEED 100 CU. FT.
<br />2. THE DEPTH OF THE UNPROTECTED CEILING POCKET DOES NOT EXCEED 12 IN.
<br />3. THE ENTIRE FLOOR OF THE UNPROTECTED CEILING POCKET IS PROTECTED BY THE SPRINKLERS AT
<br />THE LOWER CEILING ELEVATIONS.
<br />4. THE INTERIOR FINISH OF THE UNPROTECTED CEILING POCKET IS NONCOMBUSTIBLE OR
<br />LIMITED -COMBUSTIBLE CONSTRUCTION.
<br />• WAFS TO PROVIDE ALL REQUIRED SIGNAGE PER NFPA 13R INCLUDING BUT NOT LIMITED TO VALVES, AND
<br />HYDRAULIC PLACARDS.
<br />Fire spa dit a bm
<br />System No. F—C-2032
<br />F Retina - 1 Hr
<br />T Ratings - V4 end 1 Hr (See Item 2)
<br />Section A -A
<br />1. FLOOR - CEILING ASSEMBLY - THE 1 HR FIRE -RATED SOLID OR TRUSSED LUMBER JOIST FLOOR -CEILING
<br />ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN INDIVIDUAL L500
<br />SERIES FLOOR -CEILING DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY, THE GENERAL CONSTRUCTION DETAILS
<br />OF THE FLOOR -CEILING ASSEMBLY ARE SUMMARIZED BELOW,
<br />A. FLOORING SYSTEM - LUMBER OR PLYWOOD SUBFLOOR WITH FINISH FLOOR OF LUMBER, PLYWOOD OR FLOOR
<br />TOPPING MIXTURE• AS SPECIFIED IN THE INDIVIDUAL FLOOR -CEILING DESIGN, MAX DIAM OF FLOOR
<br />OPENING IS 4 IN,
<br />B. WOOD JOISTS - NOM 2 BY 10 IN, LUMBER JOISTS SPACED 16 IN. OC WITH NOM i BY 3 IN. LUMBER
<br />BRIDGING AND WITH ENDS FIRESTOPPED, AS AN ALTERNATE TO LUMBER JOISTS, NOM 10 IN, DEEP (OR
<br />DEEPER) LUMBER, STEEL OR COMBINATION LUMBER AND STEEL JOISTS, TRUSSES OR STRUCTURAL WOOD
<br />MEMBERS* WITH BRIDGING AS REQUIRED AND WITH ENDS FIRESTOPPED.
<br />C. FURRING CHANNELS (NOT SHOWN) - RESILIENT GALV STEEL FURRING INSTALLED PERPENDICULAR TO WOOD
<br />JOISTS (ITEM 1B) BETWEEN GYPSUM BOARD (ITEM 1D) AND WOOD JOISTS AS REQUIRED IN THE INDIVIDUAL
<br />FLOOR -CEILING DESIGN,
<br />D. GYPSUM BOARD* - NOM 4 FT WIDE BY 5/8 IN, THICK AS SPECIFIED IN THE INDIVIDUAL FLOOR -CEILING
<br />DESIGN, GYPSUM BOARD SECURED TO WOOD JOISTS OR FURRING CHANNELS AS SPECIFIED IN THE
<br />INDIVIDUAL FLOOR -CEILING DESIGN. MAX DIAM OF CEILING OPENING IS 4 IN.
<br />2, CHASE WALL (NOT SHOWN) - WHEN REQUIRED (SEE TABLE UNDER ITEM 2), THE THROUGH PENETRANT (ITEM 2)
<br />SHALL BE ROUTED THROUGH A 1 HR FIRE -RATED SINGLE, DOUBLE OR STAGGERED WOOD STUD/GYPSUM BOARD
<br />CHASE WALL. DEPTH OF CHASE WALL STUD CAVITY TO BE MIN 1/2 IN, GREATER THAN DIAM OF OPENING CUT IN
<br />SOLE AND TOP PLATES TO ACCOMMODATE THE THROUGH PENETRANT (ITEM 2). THE CHASE WALL SHALL BE
<br />CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 SERIES WALL AND
<br />PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING
<br />CONSTRUCTION FEATURES,
<br />A. STUDS - NOM 2 BY 4 IN, 2 BY 6 IN, OR DOUBLE 2 BY 4 IN, LUMBER STUDS,
<br />B. SOLE PLATE - NOM 2 BY 4 IN., 2 BY 6 IN, OR PARALLEL 2 BY 4 IN, LUMBER PLATES, TIGHTLY BUTTED,
<br />C. TOP PLATE - THE DOUBLE TOP PLATE SHALL CONSIST OF TWO NOM 2 BY 4 IN, OR 2 BY 6 IN, OR TWO
<br />SETS OF PARALLEL 2 BY 4 IN, LUMBER PLATES, TIGHTLY BUTTED, MAX DIAM OF OPENING IS 4 IN,
<br />D. GYPSUM BOARD* - THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS SHALL BE AS SPECIFIED IN
<br />INDIVIDUAL WALL AND PARTITION DESIGN.
<br />Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876
<br />AL Reproduced courtesy of Underwriters Laboratories, Inc. u�
<br />STICreated or Revised: XXXXXXXXXXX
<br />C800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@st�restop.com • Website:www.st'fiirestop.com
<br />Fire spa MN bm
<br />NFPA 13R 201E GENERAL NOTES
<br />SCALE: NONE
<br />01002N
<br />ELK
<br />GRAE
<br />6'
<br />FROM
<br />SUPPLY
<br />'R " E'B ER D E T A � L
<br />THE USE OF THE CHASE WALL IS DEPENDENT UPON THE TYPE OF THROUGH PENETRANT USED AS
<br />SPECIFIED IN ITEM 2.
<br />3, THROUGH -PENETRANTS - ONE NONMETALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN THE
<br />FIRESTOP SYSTEM, DIAM OF OPENINGS HOLE -SAWED THROUGH FLOORING SYSTEM AND THROUGH GYPSUM
<br />WALLBOARD CEILING TO BE 1/4 IN, TO 1-5/8 IN, LARGER THAN THE OUTSIDE DIAM OF THROUGH -PENETRANT,
<br />PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE FLOOR -CEILING ASSEMBLY. THE
<br />FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES, CONDUITS OR TUBING MAY BE USED,
<br />A. POLYVINYL CHLORIDE (PVC) PIPE - NOM 2 IN, DIAM (OR SMALLER) SCHEDULE 40 SOLID OR CELLULAR
<br />CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT)
<br />PIPING SYSTEMS,
<br />B. RIGID NONMETALLIC CONDUIT(RNC)+ - NOM 2 IN, DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT
<br />INSTALLED IN ACCORDANCE WITH ARTICLE 347 OF THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).
<br />C. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE - NOM 2 IN, DIAM (OR SMALLER) SDR 17 CPVC PIPE
<br />FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS,
<br />D. ACRYLONITRILE BUTADIENE STYRENE (ABS) PIPE - NOM 1-1/2 IN, DIAM (OR SMALLER) SCHEDULE 40
<br />CELLULAR OR SOLID CORE ABS PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN,
<br />WASTE OR VENT) PIPING SYSTEMS.
<br />E. POLYBUTYLENE (PB) PIPE - NOM 1 IN, DIAM (OR SMALLER) SDR 11 PB PIPE FOR USE IN CLOSED
<br />(PROCESS OR SUPPLY) PIPING SYSTEMS,
<br />F. CROSS LINKED POLYETHYLENE ALUMINUM -CROSS LINKED POLYETHYLENE (PEX AL-PEX) TUBING - NOM 1
<br />IN. DIAM (OR SMALLER) SDR 5 PEX-AL-PEX TUBING FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING
<br />SYSTEMS,
<br />G. CROSS LINKED POLYETHYLENE (PEX) TUBING - NOM I IN, DIAM (OR SMALLER) SDR 9 PEX TUBING FOR
<br />USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS
<br />H, ELECTRICAL NONMETALLIC TUBING (ENT)+ - NOM 2 IN, DIAM (OR SMALLER) PVC TUBING INSTALLED IN
<br />ACCORDANCE WITH ARTICLE 331 OF THE NATIONAL ELECTRICAL CODE (NFPA N0, 70),
<br />THE USE OF THE CHASE WALL (ITEM 1.1) IS DEPENDENT UPON THE TYPE AND DIAM OF THROUGH
<br />PENETRANT AND TYPE OF PIPING SYSTEM USED AS TABULATED BELOW,
<br />TYPE OF TH;rDM
<br />MAX DUAIEM OF
<br />TYPE OF PIPM 8YSTBEI
<br />LIRE OF CHASE WALL
<br />PENETRANT
<br />THFIOI. 1 PENETRANT N
<br />PVC PIPE (A)
<br />2
<br />CLOSED OR VENTED
<br />OPTIONAL
<br />RNC
<br />2
<br />NOT APPLICABLE
<br />OPTIONAL
<br />CPVC PIPE (A)
<br />2
<br />CLOSED OR VENTED
<br />OPTIONAL
<br />ABS PIPE
<br />1-1/2
<br />CLOSED OR VENTED
<br />OPTIONAL
<br />PB PIPE
<br />1
<br />CLOSED
<br />OPTIONAL
<br />PEX-AL-PEX TUBING
<br />1
<br />CLOSED
<br />REQUIRED
<br />PEX TUBING
<br />1
<br />CLOSED
<br />OPTIONAL
<br />ENT
<br />2
<br />NOT APPLICABLE
<br />OPTIONAL
<br />(A)WHEN NOM DIAM OF PIPE EXCEEDS 1 IN. AND CHASE WALL (ITEM Li) IS NOT USED , T RATING IS if
<br />HR.
<br />WHEN 2A, 211, 2C, 2E, 2F, 215 OR 2H IS USED, THE ANNULAR SPACE SHALL BE MIN 0 IN. (POINT
<br />CONTACT) TO MAX 1-5/8 IN, WHEN 2D IS USED, THE ANNULAR SPACE SHALL BE MIN 1/8 IN, TO MAX 1
<br />IN, UNLESS THE PIPE IS ONTAINED WITHIN A CHASE WALL, IN WHICH CASE THE MINIMUM ANNULAR
<br />SPACE IS 0 IN, (POINT CONTACT).
<br />4, FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 3/4 IN. THICKNESS OF FILL MATERIAL APPLIED
<br />WITHIN ANNULUS ON TOP SURFACE OF FLOOR, MIN 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN
<br />ANNULUS ON BOTTOM SURFACE OF CEILING OR LOWER TOP PLATE OF CHASE WALL ASSEMBLY, ADDITIONAL
<br />FILL MATERIAL TO BE INSTALLED SUCH THAT A MIN 1/8 IN. CROWN IS FORMED AROUND THE THROUGH
<br />PENETRANT ON BOTTOM SURFACE OF CEILING OR LOWER PLATE OF CHASE WALL ASSEMBLY,
<br />SPECIFIED TECHNOLOGIES INC - SPECSEAL 100, IOL 102, 105, 120 OR 129 SEALANT, SPECSEAL LCI
<br />+BEARING THE UL LISTING MARK
<br />*BEARING THE UL CLASSIFICATION MARKING
<br />FIRE CAULK — STI SYSTEM No. F—C—EM UP TO 2' CPVC PPE fr WOOD FLOOR TRUSS 1—HOUR
<br />SCALE: NONE
<br />00219N
<br />• DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH 2O16 EDITION OF NFPA 14.
<br />• DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH ALL APPLICABLE LOCAL AND STATE CODES.
<br />• ALL PIPE AND FITTINGS USED ON THIS PROJECT TO BE IN ACCORDANCE WITH APPLICABLE CODES AND
<br />WAFS STANDARDS. SEE PIPE AND FITTINGS GENERAL NOTES (WAFS DETAIL *00593N).
<br />• STANDPIPES SHALL BE SUPPORTED ABOVE AND BELOW EVERY LEVEL PER WAFS STANDARDS.
<br />• HORIZONTAL PIPING SHALL BE SECURED IN ACCORDANCE WITH NFPA 13.
<br />• ALL STANDPIPES SHALL BE PROVIDED WITH A LISTED INDICATING VALVE.
<br />• A DRAIN VALVE AND PIPING, LOCATED AT THE LOWEST POINT OF THE STANDPIPE DOWNSTREAM OF
<br />THE ISOLATION VALVE, SHALL BE ARRANGED TO DISCHARGE WATER AT AN APPROVED LOCATION.
<br />PER SECTION 7.11.2.2. WAFS POLICY IS TO USE THE LOWEST HOSE VALVE AS APPROVED BY THE AHJ.
<br />• WHEN THE STANDPIPE IS USED TO SUPPLY SPRINKLERS (COMBINED SYSTEM), A CHECK VALVE SHALL
<br />BE PROVIDED IN EACH CONNECTION DOWNSTREAM OF THE SPRINKLER CONTROL VALVE.
<br />• A PRESSURE GAUGE WITH VALVE SHALL BE PROVIDED AT THE TOP OF EACH STANDPIPE.
<br />• A VALVED OUTLET FOR A PRESSURE GAUGE (PRESSURE GAUGE WILL NOT BE PROVIDED) SHALL BE
<br />PROVIDED IMMEDIATELY UPSTREAM OF EVERY PRESSURE REGULATING HOSE VALVE.
<br />• PRESSURE GAUGES WITH VALVES SHALL BE PROVIDED IMMEDIATELY UPSTREAM AND DOWNSTREAM OF
<br />EVERY PRESSURE REDUCING CONTROL VALVE.
<br />• ALL PENETRATIONS THROUGH RATED BUILDING ASSEMBLIES SHALL BE SEALED WITH FIRE CAULK IN
<br />ACCORDANCE WITH DETAILS PROVIDED. WAFS POLICY IS TO USE WLTI FS ONE OR STI LCI.
<br />• UNDERGROUND MAINS AND LEAD-INS SHALL BE FLUSHED AND SIGNED TEST CERTIFICATES PROVIDED
<br />BEFORE A CONNECTION IS MADE TO THE STANDPIPE SYSTEM.
<br />• ALL PIPING SHALL BE INSPECTED AND APPROVED BY PROPER AUTHORITIES PRIOR TO COVERING WITH
<br />DRYWALL. COPIES OF SIGNED TEST CERTIFICATES ARE TO BE FORWARDED TO THE PROPER
<br />RECIPIENTS.
<br />• ALL SYSTEMS SHALL BE TESTED FOR 2 HOURS AT 200 PSI OR 50 PSI GREATER THAN MAXIMUM
<br />SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER.
<br />• ALL CHASES REQUIRED TO CONCEAL STANDPIPE PIPING ARE BY OTHERS.
<br />• ALL WIRING OF DEVICES (FLOW SWITCHES, TAMPER SWITCHES, COMPRESSORS, ETC) IS BY OTHERS.
<br />• CONNECTION OF ALARM DEVICES TO THE BUILDING ALARM OR MONITORING SYSTEM IS BY OTHERS.
<br />• DRY STANDPIPES SHALL BE MONITORED IN ACCORDANCE WITH NFPA 72 WITH SUPERVISORY AIR
<br />PRESSURE.
<br />• ALL PAINTING OF PIPE AS REQUIRED IS BY OTHERS.
<br />• ALL INSULATION REQUIRED FOR FREEZE PROTECTION OF THE STANDPIPE SYSTEM IS BY OTHERS.
<br />• HEATING OF ROOMS TO MAINTAIN TEMPERATURES OF 40 DEGREES OR GREATER IS BY OTHERS.
<br />• FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT LESS THAN 18' AND NOT MORE THAN 48'
<br />ABOVE THE LEVEL OF THE ADJACENT GRADE.
<br />• HIGH RISE BUILDINGS SHALL HAVE AT LEAST TWO REMOTELY LOCATED FIRE DEPARTMENT
<br />CONNECTIONS.
<br />• FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED WITHIN 100'-O' OF A HYDRANT EXCEPT AS
<br />APPROVED BY THE AHJ.
<br />• WAFS TO PROVIDE ALL NECESSARY SIGNAGE INCLUDING BUT NOT LIMITED TO VALVES, HYDRAULIC
<br />PLACARDS AND INSPECTION TAGS.
<br />• HOSE VALVES SHALL BE PROVIDED IN THE FOLLOWING LOCATIONS:
<br />o AT EACH MAIN LANDING (INTERMEDIATE LANDINGS ONLY WHEN REQUIRED BY THE AHJ) IN EVERY
<br />REQUIRED EXIT STAIRWELL
<br />o ON EACH SIDE OF THE WALL ADJACENT TO THE EXIT OPENINGS OF HORIZONTAL EXITS EXCEPT AS
<br />FROM ALLOWED TO BE REMOVED PER THE BUILDING CODE.
<br />FDC o AT THE HIGHEST LANDINGS OF STAIRWAYS WITH ROOF ACCESS AND ON ROOFS WITH A SLOPE OF
<br />4:12 OR LESS WHERE STAIRWAYS DO NOT ACCESS THE ROOF.
<br />o AS REQUIRED BY THE AHJ WHEN THE TRAVEL DISTANCE EXCEEDS 200 FT EXCEPT FOR THE ROOF.
<br />• CALCULATIONS SHALL BE PROVIDED TO PROVE 500 GPM AT 100 PSI FOR THE MOST REMOTE
<br />STANDPIPE AND 250 GPM AT 100 PSI FOR EACH ADDITIONAL STANDPIPE UP TO 1250 GPM.
<br />BUILDINGS SPRINKLERRED THROUGHOUT WITH NFPA 13 SHALL ONLY BE REQUIRED TO PROVIDE UP TO
<br />moo GPM.
<br />• ALL PRESSURE REGULATING DEVICES SHALL BE TESTED TO VERIFY THAT THE INSTALLATION IS
<br />CORRECT.
<br />• WAFS TO PROVIDE ALL REQUIRED SIGNAGE PER NFPA 14 INCLUDING BUT NOT LIMITED TO VALVES,
<br />HYDRAULIC PLACARDS, AND INSPECTION TAGS.
<br />NFPA 14 201E GENERAL NOTES
<br />SCALE: NONE
<br />&*onabb Fk* Sp i film Mo.
<br />System No. W-L-2241
<br />F Ratings - 1 and 2 Hr (See Item 1)
<br />T Ratings - 0, 1/4, 1 and 1-3/4 Hr (See Item 2)
<br />Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876
<br />Ak Reproduced courtesy of Underwriters Laboratories, Inc. �`
<br />STICreated or Revised: XXXXXXXXXXX
<br /><800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv(8 stifirestop.com . Website:www.stifirestop.com
<br />Fire ep a i" ba
<br />01007N
<br />1, WALL ASSEMBLY - THE 1 OR 2 HR FIRE -RATED GYPSUM BOARD/STUD WALL ASSEMBLY
<br />SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE
<br />INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE
<br />RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES,
<br />A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL
<br />STUDS, WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER
<br />SPACED MAX 16 IN. (406 MM) OC, STEEL STUDS TO BE MIN 3-1/2 IN, (89 MM) WIDE
<br />AND SPACED MAX 24 IN, (610 MM) OC.
<br />B. GYPSUM BOARD• - THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS AS
<br />SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN.DIAM OF ❑PENING TO BE
<br />1 IN. TO 1-1/8 IN, (25 TO 29 MM) LARGER THAN OUTSIDE DIAM OF PIPE, THE
<br />HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING
<br />OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED,
<br />2. THROUGH PENETRANT - ONE NONMETALLIC PIPE, CONDUIT OR TUBE TO BE INSTALLED
<br />ECCENTRICALLY OR C❑NCENTRICALLY WITHIN THE FIREST❑P SYSTEM, PIPE, C❑NDUIT OR
<br />TUBE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY, THE
<br />FOLLOWING TYPES AND SIZES OF N❑NMETALLIC PIPES, CONDUITS AND TUBES MAY BE
<br />USED,
<br />A, POLYVINYL CHLORIDE (PVC) PIPE - NOM 2 IN. (51 MM) DIAM (OR SMALLER)
<br />SCHEDULE 40 SOLID OR CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS
<br />OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS, ANNULAR SPACE
<br />SHALL BE MIN 0 IN, ( 0 MM, POINT CONTACT) TO MAX 1 IN, (25 MM).
<br />B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE - NOM 2 IN, (51 MM) DIAM (OR
<br />SMALLER) SDR 13,5 CPVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING
<br />SYSTEMS, ANNULAR SPACE SHALL BE MIN 0 IN, ( 0 MM, P❑INT CONTACT) TO MAX 1
<br />IN. (25 MM),
<br />C. RIGID N❑NMETALLIC CONDUIT+ - NOM 2 IN, (51 MM) DIAM (OR SMALLER) SCHEDULE
<br />40 PVC CONDUIT INSTALLED IN ACCORDANCE WITH ARTICLE 347 OF THE NATIONAL
<br />ELECTRICAL CODE (NFPA 70), ANNULAR SPACE SHALL BE MIN 0 IN. ( 0 MM, P❑INT
<br />CONTACT) TO MAX 1 IN, (25 MM),
<br />D. ELECTRICAL NONMETALLIC TUBING+ - NOM 2 IN. (51 MM) DIAM (OR SMALLER) PVC
<br />TUBING INSTALLED IN ACCORDANCE WITH ARTICLE 331 OF THE NATIONAL
<br />ELECTRICAL CODE (NFPA 70), ANNULAR SPACE SHALL BE MIN 0 IN. ( 0 MM, P❑INT
<br />CONTACT) TO MAX 1 IN, (25 MM),
<br />E. CROSS LINKED POLYETHYLENE (PEX) TUBING - NOM 1 IN, (25 MM) DIAM (❑R
<br />SMALLER) SDR9 PEX TUBING FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING
<br />SYSTEMS. ANNULAR SPACE SHALL BE MIN 0 IN, ( 0 MM, P❑INT CONTACT) TO MAX 1
<br />IN, (25 MM).
<br />F. ACRYL❑NITRILE BUTADIENE STYRENE (ABS) PIPE - NOM 1-1/2 IN, (38 MM) DIAM (OR
<br />SMALLER) SCHEDULE 40 SOLID -CORE OR CELLULAR CORE ABS PIPE FOR USE IN
<br />CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING
<br />SYSTEMS, ANNULAR SPACE SHALL BE MIN 1/4 IN. (6 MM) TO MAX 3/4 IN. (19 MM),
<br />WHEN ITEM 2A OR 2B IS USED, THE T RATING IS 1/4 HR, WHEN ITEM 2C, 2D, OR 2E
<br />IS USED, THE T RATING IS 1 HR AND 1-3/4 HR FOR 1 HR AND 2 HR FIRE RATED
<br />WALLS, RESPECTIVELY. WHEN ITEM 2F IS USED, T RATING IS 0 HR,
<br />3. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 5/8 IN, (16 MM) THICKNESS OF
<br />FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL
<br />ASSEMBLY, AT P❑INT CONTACT L❑CATION, MIN 1/4 IN, (6 MM) DIAM BEAD OF FILL
<br />MATERIAL APPLIED AT NONMETALLIC PIPE/GYPSUM BOARD INTERFACE ON BOTH SURFACES
<br />OF WALL,
<br />SPECIFIED TECHNOL❑GIES INC - SPECSEAL LCI SEALANT
<br />*BEARING THE UL CLASSIFICATION MARK
<br />FIRE CAULK - STI SYSTEM No. W-L-M41
<br />LP TO 2' CPVC PPE S DRYWALL 1 TO 2—HOUR
<br />SCALE: NONE
<br />00217N
<br />d
<br />Hazard Fire Protection Engineering, Inc.
<br />222 CAPITOL COURT OWIM FL 34701
<br />PIA (407) 877-5578 FAX: (407) 656-OM
<br />CwbflewW of AudarlraMw Nu w 28038
<br />No. 7137�'-
<br />; STATE OF
<br />Aebwt '14J0yR ID P . w. PE
<br />R. =4Vi n t ��Is 7W4
<br />IMPORTANT OWNER INFORMATION
<br />T1GS YMWSE O SAES ON THE OWWM ACCEPTANCE OF M CANVITLY ANTED corm Enmm STATE IA LOCAL) OF OPA 0 AS
<br />E ARLICM.E STANDARD ►2t THE IEPECTIR TESTING AM NIMOWCIC OF VATER NO W PROfE = SYSLOIL PER SECTION 44
<br />THE NESPDI33p1TY FOR PIVOLY IMWAROf A WATER SASED TIM PROTECT= SYSTEM SHALL E THAT Or THE OWNOL 3 THE
<br />ULTYY WV HAS HOT REO]VEE A COPY OF TMS PA144LET AIY/Ot O NOT FMY.WI WITH THE MUTDN AND NENIOIMCE IF THU
<br />SYSTOL PLEASE COrtACT THE WAIST OTTCE OF VATNE AUTOMTC FIE SPI S LOLL NC
<br />(PVC COMPATIBILITY NOTICE
<br />UNC FIE SPIOSOiR Plllr SYSTEMS HAVE AM USED WCEI rILLY FOR NONE THAN m YEARS N NEW CORTYLTRIL RE -WE ANY
<br />HOAR CPVC RmUCrS vim rm THESE Ad""T1717 RE TO THEN OIKTMYSY CDINO®N RESSSTAIM OCCAZLMLLY,
<br />NOVENA, 0" CAN SE )MIMm IY CORACT NnN cenALS raw N SOE CMWMWM MATERIALS m SOME NEE; root
<br />PE=nN EASED PMWXM ETC) AM MCLJARY PNODLLTS Slut AS TWA SEM.ARrL LEAS DETECTS% FEESn NO.1 N TO S
<br />ANY CLEAIERt, ETC. ANY PPMKF TINT CODES N CONTACT WITH (PVC SPROSLSR PIPE NOT E EVALUATES. FOR A LIST OF COPATOLE
<br />PR®I1CT; PLEASE REVIEW HRTP/
<br />COPYRIGHT
<br />ALL DOCUMENTS, INCLUDING ORIGINAL DRAWINGS, SPECIFICATIONS, FIELD NOTES, ESTIMATES AND DATA, INCLUDING COMPUTER
<br />PROGRAMS PURSUANT TO THIS PROJECT ARE AND WILL REMAIN THE PROPERTY OF WAYNE AUTOMATIC FIRE SPRINKLERS, INC.
<br />(WAFS) AS INSTRUMENTS OF SERVICE. THEY ARE NOT INTENDED. NOR REPRESENTED TO BE SUITABLE FOR RE -USE BY THE CLIENT,
<br />OR OTHERS, ON EXTENSION OF THIS PROJECT, OR FOR ANY OTHER PROJECT. ANY REUSE, OR ADAPTATION OF THE INFORMATION
<br />CONTAINED HEREIN, WITHOUT SPECIFIC WRITTEN PERMISSION FROM WAFS WILL BE AT THE CLIENTS SOLE RISK, WITHOUT
<br />LIABILITY, OR LEGAL EXPOSURE TO WAFS, AND WILL ENTITLE WAFS TO FURTHER CDMPENSATIDN AT RATES TO BE AGREED ON
<br />BETWEEN WAFS AND THE CLIENT, THE CLIENT SHALL ALSO INDEMNIFY AND HOLD WAFS HARMLESS FROM ANY AND ALL CLAIMS,
<br />DAMAGES, LOSSES AND EXPENSES, INCLUDING ATTORNEYS FEES RESULTING FROM ANY SUCH PERMISSIONS.
<br />GRAPHICS ELEMENTS NOTE
<br />I= SPRIPS&M CONISINXT20! DRAWS463 NO SHOP YAVNOS MY NLLLilE RAO(GR "1"WIGS OR GMAPHICS StiOVO
<br />n= THE MORTECREAL. CIAL STRUCTLRAL. OR HOP DRAWIGS. THESE LEFOEMLL SApR,mRY ELOOITS ARE rOR
<br />GODIAL EIOUMTm7 OR CONTM ONLY AND THE FEE SPIOILEJN ENOEELR MKS OCT ACCEPT ANY IER06'NLLITY roe
<br />THESE ELEMENTS. THE FM SPRI NUM ENGINEER IS IDLY RESPOISNLE FO! 110E POn1pIS O' THE FEE SPRI/O.ER
<br />DRAWEES DEPMM FIE SPIO ILER SCOPES CE WON. REFON TO APPROVED AROOTECTIRK. STRUMMAL HEP OR CTVLL
<br />OBIVEIGS FOR Av11OOTATSVE EXP ESS106 DF 0=6111 Y V#MMMTDN THAT MAY E UTAIM Of FDE SPRIMSLER
<br />WATER SUPPLY
<br />INFORMATION
<br />ACTUAL
<br />WOUGIg M DMW RED
<br />FIRE PUMP
<br />27
<br />9 16 2022
<br />10:30 AM
<br />SIZE: GPM 0 PSI
<br />STATIC PRESSURE
<br />55
<br />HYDRANT ELEV.
<br />RESIDUAL PRESSURE
<br />50
<br />FLOW IN GPM
<br />1000
<br />PITOT READING
<br />36
<br />MAWOF PORTS FLOWED
<br />1
<br />TEST PROVIDED BY
<br />CITY OF ZEPHYR HILLS UTILITIES
<br />HYDRANT 11256
<br />DESIGN CRITERIA
<br />AREA
<br />CLASS
<br />ANDPIPES IN DESIGN
<br />FLOW
<br />OSE VALVES
<br />'D 0 BASR
<br />rREQQ'D
<br />'D 0 BASR
<br />'D 0 FDC
<br />Q D 0 FDC
<br />N 0 HIGHESTVALVE
<br />II SPRINKLERS SPACING
<br />11 SYMBOL I MAXIMUM I MINIMUM
<br />I r— www --, SPRINKLERS
<br />11 SYMB. 11 ST 12NO 3RDI 4TH 15TH I SIN I SIZE I K I TEMP I MODEL
<br />TOTAL PER FLOOR
<br />TOTAL THIS BUILDING
<br />SUBMITTALS
<br />BY
<br />EW
<br />VC
<br />rIO/28/72022QA
<br />NO.
<br />DATE
<br />REVISIONS
<br />BY
<br />1
<br />XX/XX/XX
<br />--
<br />-
<br />WAY N E
<br />Automatic Fire Sprinklers, Inc.
<br />MAIN OFFICE — ORLANDO. FLORIDA
<br />Zee CAPITOL COURT OCOEF_ FLEA 34761
<br />PHONE (407) 30M FAX (407) 668-8026
<br />JACIC>lOtIVLLE R.
<br />ISO TATEPA. FL
<br />JummaLo eaAcK (9.
<br />M28 057TEUnW AVE. WEST
<br />328E CHMY PALM ORIVE
<br />1500 S. POWEFLEE ROAD
<br />JAOCSONVLLE FL 32E56-2745
<br />TAMPA. FL 33e0-OW
<br />OEEFRELD EEACLC FL 39442
<br />PH OW (9D4) 266-3030
<br />PIIM (90) 030-0303
<br />P1ERE (954) 9T7-3030
<br />FAX (9134) 266-0724
<br />FAX (00) 030-0312
<br />FAX (954) 917-9424
<br />FT. MYEM FL
<br />CONCORD, INC
<br />per; INC
<br />480 LAfEDO AVE
<br />4370 MOTORSP09T OFr4E
<br />rA
<br />FT. 1AY619, FL 33905-4924
<br />COF(CM NC EOW-6977
<br />TRIAPYLE DRIVE
<br />BALE R IB 27 FF
<br />C e79746
<br />PHEIPE am) 433-30M
<br />PNOPE OOQ 792-3D32
<br />PNR E (919)
<br />FAX MW) 433-3283
<br />FAX 904) 795-6638
<br />STATE yamm NC wwaam
<br />2974E Nc m ARIA an w -LV sc wFonm = sc ALASEA 536E
<br />ZEPHYR COMMONS
<br />EMERSON HILL CIRCLE
<br />ZEPHYR HILLS, FL. 33541
<br />LANDSOUTH CONSTRUCTION
<br />4233 PABLO PROFESSIONAL CT.
<br />JACKSONVILLE, FL. 32224
<br />SHEET TITLE,
<br />NOTES AND DETAILS
<br />DRAWN BY,
<br />VINNIE COMO
<br />TOTAL A/SI
<br />2,854
<br />DATE,
<br />9/13/2022
<br />AHJ'
<br />PASCO COUNTY
<br />CONTRACT #
<br />109678
<br />CENTER OF TILE JOB? ❑ YES NO
<br />CENTER ON FIXTURES JOB' YES NO
<br />SHEET #
<br />■ 1
<br />CONSTRUCTION TYPE,
<br />V-A
<br />OCCUPANCY,
<br />R-2