o dy!!1'� <br />• DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH 2O16 EDITION OF NFPA 13R AND 2016 EDITION <br />OF NFPA 13 WHERE DESIGNATED BY NFPA 13R. <br />• DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH ALL APPLICABLE LOCAL AND STATE CODES. <br />• ALL PIPE AND FITTINGS USED ON THIS PROJECT TO BE IN ACCORDANCE WITH APPLICABLE CODES AND <br />WAFS STANDARDS. SEE PIPE AND FITTINGS GENERAL NOTES (WAFS DETAIL 1N00593N). <br />• ALL HANGERS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH NFPA 13 AND THEIR LISTING. <br />• ALL SEISMIC BRACING, IF REQUIRED, SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH NFPA 13 <br />AND THEIR LISTING. <br />• ALL PENETRATIONS THROUGH RATED BUILDING ASSEMBLIES SHALL BE SEALED WITH FIRE CAULK IN <br />ACCORDANCE WITH DETAILS PROVIDED. WAFS POLICY IS TO USE HILTI FS ONE OR STI LCI. <br />• UNDERGROUND MAINS AND LEAD-INS SHALL BE FLUSHED AND SIGNED TEST CERTIFICATES PROVIDED <br />BEFORE A CONNECTION IS MADE TO THE SPRINKLER SYSTEM. <br />• ALL PIPING SHALL BE INSPECTED AND APPROVED BY PROPER AUTHORITIES PRIOR TO COVERING WITH <br />DRYWALL. COPIES OF SIGNED TEST CERTIFICATES ARE TO BE FORWARDED TO THE PROPER RECIPIENTS. <br />• ALL SYSTEMS SHALL BE TESTED AT 200 PSI FOR 2 HOURS. <br />• ALL SOFFITS REQUIRED TO CONCEAL SPRINKLER PIPING ARE BY OTHERS. <br />• ALL WIRING OF DEVICES (FLOW SWITCHES, TAMPER SWITCHES, COMPRESSORS, ETC) IS BY OTHERS. <br />• CONNECTION OF SPRINKLER DEVICES TO THE BUILDING ALARM OR MONITORING SYSTEM IS BY OTHERS. <br />• ALL PAINTING OF PIPE AS REQUIRED IS BY OTHERS. <br />• ALL INSULATION REQUIRED FOR FREEZE PROTECTION OF SPRINKLER PIPING IS BY OTHERS. <br />• HEATING OF ROOMS TO MAINTAIN TEMPERATURES OF 40 DEGREES OR GREATER IS BY OTHERS. <br />• FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT LESS THAN 18' AND NOT MORE THAN 48' <br />ABOVE THE LEVEL OF THE ADJACENT GRADE. <br />• SPRINKLERS SHALL NOT BE INSTALLED PRIOR TO THE FITTINGS BEING CEMENTED IN PLACE. <br />• ALL SPRINKLERS IN DWELLING UNITS SHALL BE UL LISTED OR FM APPROVED RESIDENTIAL SPRINKLERS. <br />• ALL SPRINKLERS OUTSIDE OF DWELLING UNITS SHALL BE QUICK RESPONSE. RESIDENTIAL SPRINKLERS <br />SHALL BE ALLOWED AS PER NFPA 13R SECTION 6.2.2. <br />• SPARE SPRINKLERS OF EACH TYPE, TEMPERATURE RATING AND ORIFICE SIZE AND APPROPRIATE WRENCH <br />OR WRENCHES SHALL BE LEFT ON THE PREMISES. ON A SINGLE PROPERTY UNDER THE SAME <br />OWNERSHIP, SPRINKLERS WILL BE PROVIDED IN A SINGLE LOCATION. <br />• REFER TO SPACING NOTES ON PLANS FOR MAXIMUM CALCULATED SPACING ALLOWANCES. <br />• SPRINKLERS SHALL BE PROVIDED IN ALL OPEN ENDED CORRIDORS THAT ARE NOT SEPARATED FROM THE <br />EXIT STAIRS PER IBC/NCBC/FBC 903.3.1.2.2. <br />• SPRINKLERS SHALL BE INSTALLED IN ALL AREAS EXCEPT AS FOLLOWS: <br />o BATHROOMS WHERE THE AREA DOES NOT EXCEED 55 SO FT (INCLUDING TUBS AND SHOWERS). <br />o CLOTHES CLOSETS, LINEN CLOSETS AND PANTRIES WITHIN THE DWELLING UNITS THAT DO NOT EXCEED <br />24 SQUARE FEET, THE LEAST DIMENSION DOES NOT EXCEED 3 FEET, AND THE WALLS AND CEILINGS <br />ARE SURFACED WITH NONCOMBUSTIBLE OR LIMITED -COMBUSTIBLE MATERIALS AS DEFINED BY NFPA <br />220, STANDARD ON TYPES OF BUILDING CONSTRUCTION. <br />o ANY PORCHES, BALCONIES (EXCEPT THOSE OF TYPE V CONSTRUCTION). CORRIDORS, AND STAIRS THAT <br />ARE OPEN AND ATTACHED. <br />o ATTICS, PENTHOUSE EQUIPMENT ROOMS, ELEVATOR MACHINE ROOMS, CONCEALED SPACES DEDICATED <br />EXCLUSIVELY TO AND CONTAINING ONLY DWELLING UNIT VENTILATION EQUIPMENT, CRAWL SPACES, <br />FLOOR/CEILING SPACES, NONCOMBUSTIBLE ELEVATOR SHAFTS WHERE THE ELEVATOR CARS COMPLY <br />WITH ANSI A17.1, AND OTHER CONCEALED SPACES THAT ARE NOT USED OR INTENDED FOR LIVING <br />PURPOSES OR STORAGE AND DO NOT CONTAIN FUEL -FIRED EQUIPMENT. <br />o CLOSETS ON EXTERIOR BALCONIES AND EXTERIOR BREEZEWAYS/CORRIDORS, REGARDLESS OF SIZE OR <br />CONTENTS, AS LONG AS THERE ARE NO DOORS OR UNPROTECTED PENETRATIONS FROM THE CLOSET <br />DIRECTLY INTO THE DWELLING UNIT. <br />o CEILING POCKETS THAT MEET THE FOLLOWING REQUIREMENTS: <br />1. THE TOTAL VOLUME OF THE UNPROTECTED CEILING POCKET DOES NOTE EXCEED 100 CU. FT. <br />2. THE DEPTH OF THE UNPROTECTED CEILING POCKET DOES NOT EXCEED 12 IN. <br />3. THE ENTIRE FLOOR OF THE UNPROTECTED CEILING POCKET IS PROTECTED BY THE SPRINKLERS AT <br />THE LOWER CEILING ELEVATIONS. <br />4. THE INTERIOR FINISH OF THE UNPROTECTED CEILING POCKET IS NONCOMBUSTIBLE OR <br />LIMITED -COMBUSTIBLE CONSTRUCTION. <br />• WAFS TO PROVIDE ALL REQUIRED SIGNAGE PER NFPA 13R INCLUDING BUT NOT LIMITED TO VALVES, AND <br />HYDRAULIC PLACARDS. <br />Fire spa dit a bm <br />System No. F—C-2032 <br />F Retina - 1 Hr <br />T Ratings - V4 end 1 Hr (See Item 2) <br />Section A -A <br />1. FLOOR - CEILING ASSEMBLY - THE 1 HR FIRE -RATED SOLID OR TRUSSED LUMBER JOIST FLOOR -CEILING <br />ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN INDIVIDUAL L500 <br />SERIES FLOOR -CEILING DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY, THE GENERAL CONSTRUCTION DETAILS <br />OF THE FLOOR -CEILING ASSEMBLY ARE SUMMARIZED BELOW, <br />A. FLOORING SYSTEM - LUMBER OR PLYWOOD SUBFLOOR WITH FINISH FLOOR OF LUMBER, PLYWOOD OR FLOOR <br />TOPPING MIXTURE• AS SPECIFIED IN THE INDIVIDUAL FLOOR -CEILING DESIGN, MAX DIAM OF FLOOR <br />OPENING IS 4 IN, <br />B. WOOD JOISTS - NOM 2 BY 10 IN, LUMBER JOISTS SPACED 16 IN. OC WITH NOM i BY 3 IN. LUMBER <br />BRIDGING AND WITH ENDS FIRESTOPPED, AS AN ALTERNATE TO LUMBER JOISTS, NOM 10 IN, DEEP (OR <br />DEEPER) LUMBER, STEEL OR COMBINATION LUMBER AND STEEL JOISTS, TRUSSES OR STRUCTURAL WOOD <br />MEMBERS* WITH BRIDGING AS REQUIRED AND WITH ENDS FIRESTOPPED. <br />C. FURRING CHANNELS (NOT SHOWN) - RESILIENT GALV STEEL FURRING INSTALLED PERPENDICULAR TO WOOD <br />JOISTS (ITEM 1B) BETWEEN GYPSUM BOARD (ITEM 1D) AND WOOD JOISTS AS REQUIRED IN THE INDIVIDUAL <br />FLOOR -CEILING DESIGN, <br />D. GYPSUM BOARD* - NOM 4 FT WIDE BY 5/8 IN, THICK AS SPECIFIED IN THE INDIVIDUAL FLOOR -CEILING <br />DESIGN, GYPSUM BOARD SECURED TO WOOD JOISTS OR FURRING CHANNELS AS SPECIFIED IN THE <br />INDIVIDUAL FLOOR -CEILING DESIGN. MAX DIAM OF CEILING OPENING IS 4 IN. <br />2, CHASE WALL (NOT SHOWN) - WHEN REQUIRED (SEE TABLE UNDER ITEM 2), THE THROUGH PENETRANT (ITEM 2) <br />SHALL BE ROUTED THROUGH A 1 HR FIRE -RATED SINGLE, DOUBLE OR STAGGERED WOOD STUD/GYPSUM BOARD <br />CHASE WALL. DEPTH OF CHASE WALL STUD CAVITY TO BE MIN 1/2 IN, GREATER THAN DIAM OF OPENING CUT IN <br />SOLE AND TOP PLATES TO ACCOMMODATE THE THROUGH PENETRANT (ITEM 2). THE CHASE WALL SHALL BE <br />CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 SERIES WALL AND <br />PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING <br />CONSTRUCTION FEATURES, <br />A. STUDS - NOM 2 BY 4 IN, 2 BY 6 IN, OR DOUBLE 2 BY 4 IN, LUMBER STUDS, <br />B. SOLE PLATE - NOM 2 BY 4 IN., 2 BY 6 IN, OR PARALLEL 2 BY 4 IN, LUMBER PLATES, TIGHTLY BUTTED, <br />C. TOP PLATE - THE DOUBLE TOP PLATE SHALL CONSIST OF TWO NOM 2 BY 4 IN, OR 2 BY 6 IN, OR TWO <br />SETS OF PARALLEL 2 BY 4 IN, LUMBER PLATES, TIGHTLY BUTTED, MAX DIAM OF OPENING IS 4 IN, <br />D. GYPSUM BOARD* - THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS SHALL BE AS SPECIFIED IN <br />INDIVIDUAL WALL AND PARTITION DESIGN. <br />Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876 <br />AL Reproduced courtesy of Underwriters Laboratories, Inc. u� <br />STICreated or Revised: XXXXXXXXXXX <br />C800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv@st�restop.com • Website:www.st'fiirestop.com <br />Fire spa MN bm <br />NFPA 13R 201E GENERAL NOTES <br />SCALE: NONE <br />01002N <br />ELK <br />GRAE <br />6' <br />FROM <br />SUPPLY <br />'R " E'B ER D E T A � L <br />THE USE OF THE CHASE WALL IS DEPENDENT UPON THE TYPE OF THROUGH PENETRANT USED AS <br />SPECIFIED IN ITEM 2. <br />3, THROUGH -PENETRANTS - ONE NONMETALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN THE <br />FIRESTOP SYSTEM, DIAM OF OPENINGS HOLE -SAWED THROUGH FLOORING SYSTEM AND THROUGH GYPSUM <br />WALLBOARD CEILING TO BE 1/4 IN, TO 1-5/8 IN, LARGER THAN THE OUTSIDE DIAM OF THROUGH -PENETRANT, <br />PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE FLOOR -CEILING ASSEMBLY. THE <br />FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES, CONDUITS OR TUBING MAY BE USED, <br />A. POLYVINYL CHLORIDE (PVC) PIPE - NOM 2 IN, DIAM (OR SMALLER) SCHEDULE 40 SOLID OR CELLULAR <br />CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) <br />PIPING SYSTEMS, <br />B. RIGID NONMETALLIC CONDUIT(RNC)+ - NOM 2 IN, DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT <br />INSTALLED IN ACCORDANCE WITH ARTICLE 347 OF THE NATIONAL ELECTRICAL CODE (NFPA NO. 70). <br />C. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE - NOM 2 IN, DIAM (OR SMALLER) SDR 17 CPVC PIPE <br />FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS, <br />D. ACRYLONITRILE BUTADIENE STYRENE (ABS) PIPE - NOM 1-1/2 IN, DIAM (OR SMALLER) SCHEDULE 40 <br />CELLULAR OR SOLID CORE ABS PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, <br />WASTE OR VENT) PIPING SYSTEMS. <br />E. POLYBUTYLENE (PB) PIPE - NOM 1 IN, DIAM (OR SMALLER) SDR 11 PB PIPE FOR USE IN CLOSED <br />(PROCESS OR SUPPLY) PIPING SYSTEMS, <br />F. CROSS LINKED POLYETHYLENE ALUMINUM -CROSS LINKED POLYETHYLENE (PEX AL-PEX) TUBING - NOM 1 <br />IN. DIAM (OR SMALLER) SDR 5 PEX-AL-PEX TUBING FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING <br />SYSTEMS, <br />G. CROSS LINKED POLYETHYLENE (PEX) TUBING - NOM I IN, DIAM (OR SMALLER) SDR 9 PEX TUBING FOR <br />USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS <br />H, ELECTRICAL NONMETALLIC TUBING (ENT)+ - NOM 2 IN, DIAM (OR SMALLER) PVC TUBING INSTALLED IN <br />ACCORDANCE WITH ARTICLE 331 OF THE NATIONAL ELECTRICAL CODE (NFPA N0, 70), <br />THE USE OF THE CHASE WALL (ITEM 1.1) IS DEPENDENT UPON THE TYPE AND DIAM OF THROUGH <br />PENETRANT AND TYPE OF PIPING SYSTEM USED AS TABULATED BELOW, <br />TYPE OF TH;rDM <br />MAX DUAIEM OF <br />TYPE OF PIPM 8YSTBEI <br />LIRE OF CHASE WALL <br />PENETRANT <br />THFIOI. 1 PENETRANT N <br />PVC PIPE (A) <br />2 <br />CLOSED OR VENTED <br />OPTIONAL <br />RNC <br />2 <br />NOT APPLICABLE <br />OPTIONAL <br />CPVC PIPE (A) <br />2 <br />CLOSED OR VENTED <br />OPTIONAL <br />ABS PIPE <br />1-1/2 <br />CLOSED OR VENTED <br />OPTIONAL <br />PB PIPE <br />1 <br />CLOSED <br />OPTIONAL <br />PEX-AL-PEX TUBING <br />1 <br />CLOSED <br />REQUIRED <br />PEX TUBING <br />1 <br />CLOSED <br />OPTIONAL <br />ENT <br />2 <br />NOT APPLICABLE <br />OPTIONAL <br />(A)WHEN NOM DIAM OF PIPE EXCEEDS 1 IN. AND CHASE WALL (ITEM Li) IS NOT USED , T RATING IS if <br />HR. <br />WHEN 2A, 211, 2C, 2E, 2F, 215 OR 2H IS USED, THE ANNULAR SPACE SHALL BE MIN 0 IN. (POINT <br />CONTACT) TO MAX 1-5/8 IN, WHEN 2D IS USED, THE ANNULAR SPACE SHALL BE MIN 1/8 IN, TO MAX 1 <br />IN, UNLESS THE PIPE IS ONTAINED WITHIN A CHASE WALL, IN WHICH CASE THE MINIMUM ANNULAR <br />SPACE IS 0 IN, (POINT CONTACT). <br />4, FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 3/4 IN. THICKNESS OF FILL MATERIAL APPLIED <br />WITHIN ANNULUS ON TOP SURFACE OF FLOOR, MIN 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN <br />ANNULUS ON BOTTOM SURFACE OF CEILING OR LOWER TOP PLATE OF CHASE WALL ASSEMBLY, ADDITIONAL <br />FILL MATERIAL TO BE INSTALLED SUCH THAT A MIN 1/8 IN. CROWN IS FORMED AROUND THE THROUGH <br />PENETRANT ON BOTTOM SURFACE OF CEILING OR LOWER PLATE OF CHASE WALL ASSEMBLY, <br />SPECIFIED TECHNOLOGIES INC - SPECSEAL 100, IOL 102, 105, 120 OR 129 SEALANT, SPECSEAL LCI <br />+BEARING THE UL LISTING MARK <br />*BEARING THE UL CLASSIFICATION MARKING <br />FIRE CAULK — STI SYSTEM No. F—C—EM UP TO 2' CPVC PPE fr WOOD FLOOR TRUSS 1—HOUR <br />SCALE: NONE <br />00219N <br />• DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH 2O16 EDITION OF NFPA 14. <br />• DESIGN AND INSTALLATION TO BE IN ACCORDANCE WITH ALL APPLICABLE LOCAL AND STATE CODES. <br />• ALL PIPE AND FITTINGS USED ON THIS PROJECT TO BE IN ACCORDANCE WITH APPLICABLE CODES AND <br />WAFS STANDARDS. SEE PIPE AND FITTINGS GENERAL NOTES (WAFS DETAIL *00593N). <br />• STANDPIPES SHALL BE SUPPORTED ABOVE AND BELOW EVERY LEVEL PER WAFS STANDARDS. <br />• HORIZONTAL PIPING SHALL BE SECURED IN ACCORDANCE WITH NFPA 13. <br />• ALL STANDPIPES SHALL BE PROVIDED WITH A LISTED INDICATING VALVE. <br />• A DRAIN VALVE AND PIPING, LOCATED AT THE LOWEST POINT OF THE STANDPIPE DOWNSTREAM OF <br />THE ISOLATION VALVE, SHALL BE ARRANGED TO DISCHARGE WATER AT AN APPROVED LOCATION. <br />PER SECTION 7.11.2.2. WAFS POLICY IS TO USE THE LOWEST HOSE VALVE AS APPROVED BY THE AHJ. <br />• WHEN THE STANDPIPE IS USED TO SUPPLY SPRINKLERS (COMBINED SYSTEM), A CHECK VALVE SHALL <br />BE PROVIDED IN EACH CONNECTION DOWNSTREAM OF THE SPRINKLER CONTROL VALVE. <br />• A PRESSURE GAUGE WITH VALVE SHALL BE PROVIDED AT THE TOP OF EACH STANDPIPE. <br />• A VALVED OUTLET FOR A PRESSURE GAUGE (PRESSURE GAUGE WILL NOT BE PROVIDED) SHALL BE <br />PROVIDED IMMEDIATELY UPSTREAM OF EVERY PRESSURE REGULATING HOSE VALVE. <br />• PRESSURE GAUGES WITH VALVES SHALL BE PROVIDED IMMEDIATELY UPSTREAM AND DOWNSTREAM OF <br />EVERY PRESSURE REDUCING CONTROL VALVE. <br />• ALL PENETRATIONS THROUGH RATED BUILDING ASSEMBLIES SHALL BE SEALED WITH FIRE CAULK IN <br />ACCORDANCE WITH DETAILS PROVIDED. WAFS POLICY IS TO USE WLTI FS ONE OR STI LCI. <br />• UNDERGROUND MAINS AND LEAD-INS SHALL BE FLUSHED AND SIGNED TEST CERTIFICATES PROVIDED <br />BEFORE A CONNECTION IS MADE TO THE STANDPIPE SYSTEM. <br />• ALL PIPING SHALL BE INSPECTED AND APPROVED BY PROPER AUTHORITIES PRIOR TO COVERING WITH <br />DRYWALL. COPIES OF SIGNED TEST CERTIFICATES ARE TO BE FORWARDED TO THE PROPER <br />RECIPIENTS. <br />• ALL SYSTEMS SHALL BE TESTED FOR 2 HOURS AT 200 PSI OR 50 PSI GREATER THAN MAXIMUM <br />SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER. <br />• ALL CHASES REQUIRED TO CONCEAL STANDPIPE PIPING ARE BY OTHERS. <br />• ALL WIRING OF DEVICES (FLOW SWITCHES, TAMPER SWITCHES, COMPRESSORS, ETC) IS BY OTHERS. <br />• CONNECTION OF ALARM DEVICES TO THE BUILDING ALARM OR MONITORING SYSTEM IS BY OTHERS. <br />• DRY STANDPIPES SHALL BE MONITORED IN ACCORDANCE WITH NFPA 72 WITH SUPERVISORY AIR <br />PRESSURE. <br />• ALL PAINTING OF PIPE AS REQUIRED IS BY OTHERS. <br />• ALL INSULATION REQUIRED FOR FREEZE PROTECTION OF THE STANDPIPE SYSTEM IS BY OTHERS. <br />• HEATING OF ROOMS TO MAINTAIN TEMPERATURES OF 40 DEGREES OR GREATER IS BY OTHERS. <br />• FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT LESS THAN 18' AND NOT MORE THAN 48' <br />ABOVE THE LEVEL OF THE ADJACENT GRADE. <br />• HIGH RISE BUILDINGS SHALL HAVE AT LEAST TWO REMOTELY LOCATED FIRE DEPARTMENT <br />CONNECTIONS. <br />• FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED WITHIN 100'-O' OF A HYDRANT EXCEPT AS <br />APPROVED BY THE AHJ. <br />• WAFS TO PROVIDE ALL NECESSARY SIGNAGE INCLUDING BUT NOT LIMITED TO VALVES, HYDRAULIC <br />PLACARDS AND INSPECTION TAGS. <br />• HOSE VALVES SHALL BE PROVIDED IN THE FOLLOWING LOCATIONS: <br />o AT EACH MAIN LANDING (INTERMEDIATE LANDINGS ONLY WHEN REQUIRED BY THE AHJ) IN EVERY <br />REQUIRED EXIT STAIRWELL <br />o ON EACH SIDE OF THE WALL ADJACENT TO THE EXIT OPENINGS OF HORIZONTAL EXITS EXCEPT AS <br />FROM ALLOWED TO BE REMOVED PER THE BUILDING CODE. <br />FDC o AT THE HIGHEST LANDINGS OF STAIRWAYS WITH ROOF ACCESS AND ON ROOFS WITH A SLOPE OF <br />4:12 OR LESS WHERE STAIRWAYS DO NOT ACCESS THE ROOF. <br />o AS REQUIRED BY THE AHJ WHEN THE TRAVEL DISTANCE EXCEEDS 200 FT EXCEPT FOR THE ROOF. <br />• CALCULATIONS SHALL BE PROVIDED TO PROVE 500 GPM AT 100 PSI FOR THE MOST REMOTE <br />STANDPIPE AND 250 GPM AT 100 PSI FOR EACH ADDITIONAL STANDPIPE UP TO 1250 GPM. <br />BUILDINGS SPRINKLERRED THROUGHOUT WITH NFPA 13 SHALL ONLY BE REQUIRED TO PROVIDE UP TO <br />moo GPM. <br />• ALL PRESSURE REGULATING DEVICES SHALL BE TESTED TO VERIFY THAT THE INSTALLATION IS <br />CORRECT. <br />• WAFS TO PROVIDE ALL REQUIRED SIGNAGE PER NFPA 14 INCLUDING BUT NOT LIMITED TO VALVES, <br />HYDRAULIC PLACARDS, AND INSPECTION TAGS. <br />NFPA 14 201E GENERAL NOTES <br />SCALE: NONE <br />&*onabb Fk* Sp i film Mo. <br />System No. W-L-2241 <br />F Ratings - 1 and 2 Hr (See Item 1) <br />T Ratings - 0, 1/4, 1 and 1-3/4 Hr (See Item 2) <br />Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876 <br />Ak Reproduced courtesy of Underwriters Laboratories, Inc. �` <br />STICreated or Revised: XXXXXXXXXXX <br /><800)992-1180 • (908)526-8000 • FAX (908)231-8415 • E-Mail:techserv(8 stifirestop.com . Website:www.stifirestop.com <br />Fire ep a i" ba <br />01007N <br />1, WALL ASSEMBLY - THE 1 OR 2 HR FIRE -RATED GYPSUM BOARD/STUD WALL ASSEMBLY <br />SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE <br />INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE <br />RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES, <br />A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL <br />STUDS, WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER <br />SPACED MAX 16 IN. (406 MM) OC, STEEL STUDS TO BE MIN 3-1/2 IN, (89 MM) WIDE <br />AND SPACED MAX 24 IN, (610 MM) OC. <br />B. GYPSUM BOARD• - THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS AS <br />SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN.DIAM OF ❑PENING TO BE <br />1 IN. TO 1-1/8 IN, (25 TO 29 MM) LARGER THAN OUTSIDE DIAM OF PIPE, THE <br />HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING <br />OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, <br />2. THROUGH PENETRANT - ONE NONMETALLIC PIPE, CONDUIT OR TUBE TO BE INSTALLED <br />ECCENTRICALLY OR C❑NCENTRICALLY WITHIN THE FIREST❑P SYSTEM, PIPE, C❑NDUIT OR <br />TUBE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY, THE <br />FOLLOWING TYPES AND SIZES OF N❑NMETALLIC PIPES, CONDUITS AND TUBES MAY BE <br />USED, <br />A, POLYVINYL CHLORIDE (PVC) PIPE - NOM 2 IN. (51 MM) DIAM (OR SMALLER) <br />SCHEDULE 40 SOLID OR CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS <br />OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS, ANNULAR SPACE <br />SHALL BE MIN 0 IN, ( 0 MM, POINT CONTACT) TO MAX 1 IN, (25 MM). <br />B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE - NOM 2 IN, (51 MM) DIAM (OR <br />SMALLER) SDR 13,5 CPVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING <br />SYSTEMS, ANNULAR SPACE SHALL BE MIN 0 IN, ( 0 MM, P❑INT CONTACT) TO MAX 1 <br />IN. (25 MM), <br />C. RIGID N❑NMETALLIC CONDUIT+ - NOM 2 IN, (51 MM) DIAM (OR SMALLER) SCHEDULE <br />40 PVC CONDUIT INSTALLED IN ACCORDANCE WITH ARTICLE 347 OF THE NATIONAL <br />ELECTRICAL CODE (NFPA 70), ANNULAR SPACE SHALL BE MIN 0 IN. ( 0 MM, P❑INT <br />CONTACT) TO MAX 1 IN, (25 MM), <br />D. ELECTRICAL NONMETALLIC TUBING+ - NOM 2 IN. (51 MM) DIAM (OR SMALLER) PVC <br />TUBING INSTALLED IN ACCORDANCE WITH ARTICLE 331 OF THE NATIONAL <br />ELECTRICAL CODE (NFPA 70), ANNULAR SPACE SHALL BE MIN 0 IN. ( 0 MM, P❑INT <br />CONTACT) TO MAX 1 IN, (25 MM), <br />E. CROSS LINKED POLYETHYLENE (PEX) TUBING - NOM 1 IN, (25 MM) DIAM (❑R <br />SMALLER) SDR9 PEX TUBING FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING <br />SYSTEMS. ANNULAR SPACE SHALL BE MIN 0 IN, ( 0 MM, P❑INT CONTACT) TO MAX 1 <br />IN, (25 MM). <br />F. ACRYL❑NITRILE BUTADIENE STYRENE (ABS) PIPE - NOM 1-1/2 IN, (38 MM) DIAM (OR <br />SMALLER) SCHEDULE 40 SOLID -CORE OR CELLULAR CORE ABS PIPE FOR USE IN <br />CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING <br />SYSTEMS, ANNULAR SPACE SHALL BE MIN 1/4 IN. (6 MM) TO MAX 3/4 IN. (19 MM), <br />WHEN ITEM 2A OR 2B IS USED, THE T RATING IS 1/4 HR, WHEN ITEM 2C, 2D, OR 2E <br />IS USED, THE T RATING IS 1 HR AND 1-3/4 HR FOR 1 HR AND 2 HR FIRE RATED <br />WALLS, RESPECTIVELY. WHEN ITEM 2F IS USED, T RATING IS 0 HR, <br />3. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 5/8 IN, (16 MM) THICKNESS OF <br />FILL MATERIAL APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL <br />ASSEMBLY, AT P❑INT CONTACT L❑CATION, MIN 1/4 IN, (6 MM) DIAM BEAD OF FILL <br />MATERIAL APPLIED AT NONMETALLIC PIPE/GYPSUM BOARD INTERFACE ON BOTH SURFACES <br />OF WALL, <br />SPECIFIED TECHNOL❑GIES INC - SPECSEAL LCI SEALANT <br />*BEARING THE UL CLASSIFICATION MARK <br />FIRE CAULK - STI SYSTEM No. W-L-M41 <br />LP TO 2' CPVC PPE S DRYWALL 1 TO 2—HOUR <br />SCALE: NONE <br />00217N <br />d <br />Hazard Fire Protection Engineering, Inc. <br />222 CAPITOL COURT OWIM FL 34701 <br />PIA (407) 877-5578 FAX: (407) 656-OM <br />CwbflewW of AudarlraMw Nu w 28038 <br />No. 7137�'- <br />; STATE OF <br />Aebwt '14J0yR ID P . w. PE <br />R. =4Vi n t ��Is 7W4 <br />IMPORTANT OWNER INFORMATION <br />T1GS YMWSE O SAES ON THE OWWM ACCEPTANCE OF M CANVITLY ANTED corm Enmm STATE IA LOCAL) OF OPA 0 AS <br />E ARLICM.E STANDARD ►2t THE IEPECTIR TESTING AM NIMOWCIC OF VATER NO W PROfE = SYSLOIL PER SECTION 44 <br />THE NESPDI33p1TY FOR PIVOLY IMWAROf A WATER SASED TIM PROTECT= SYSTEM SHALL E THAT Or THE OWNOL 3 THE <br />ULTYY WV HAS HOT REO]VEE A COPY OF TMS PA144LET AIY/Ot O NOT FMY.WI WITH THE MUTDN AND NENIOIMCE IF THU <br />SYSTOL PLEASE COrtACT THE WAIST OTTCE OF VATNE AUTOMTC FIE SPI S LOLL NC <br />(PVC COMPATIBILITY NOTICE <br />UNC FIE SPIOSOiR Plllr SYSTEMS HAVE AM USED WCEI rILLY FOR NONE THAN m YEARS N NEW CORTYLTRIL RE -WE ANY <br />HOAR CPVC RmUCrS vim rm THESE Ad""T1717 RE TO THEN OIKTMYSY CDINO®N RESSSTAIM OCCAZLMLLY, <br />NOVENA, 0" CAN SE )MIMm IY CORACT NnN cenALS raw N SOE CMWMWM MATERIALS m SOME NEE; root <br />PE=nN EASED PMWXM ETC) AM MCLJARY PNODLLTS Slut AS TWA SEM.ARrL LEAS DETECTS% FEESn NO.1 N TO S <br />ANY CLEAIERt, ETC. ANY PPMKF TINT CODES N CONTACT WITH (PVC SPROSLSR PIPE NOT E EVALUATES. FOR A LIST OF COPATOLE <br />PR®I1CT; PLEASE REVIEW HRTP/ <br />COPYRIGHT <br />ALL DOCUMENTS, INCLUDING ORIGINAL DRAWINGS, SPECIFICATIONS, FIELD NOTES, ESTIMATES AND DATA, INCLUDING COMPUTER <br />PROGRAMS PURSUANT TO THIS PROJECT ARE AND WILL REMAIN THE PROPERTY OF WAYNE AUTOMATIC FIRE SPRINKLERS, INC. <br />(WAFS) AS INSTRUMENTS OF SERVICE. THEY ARE NOT INTENDED. NOR REPRESENTED TO BE SUITABLE FOR RE -USE BY THE CLIENT, <br />OR OTHERS, ON EXTENSION OF THIS PROJECT, OR FOR ANY OTHER PROJECT. ANY REUSE, OR ADAPTATION OF THE INFORMATION <br />CONTAINED HEREIN, WITHOUT SPECIFIC WRITTEN PERMISSION FROM WAFS WILL BE AT THE CLIENTS SOLE RISK, WITHOUT <br />LIABILITY, OR LEGAL EXPOSURE TO WAFS, AND WILL ENTITLE WAFS TO FURTHER CDMPENSATIDN AT RATES TO BE AGREED ON <br />BETWEEN WAFS AND THE CLIENT, THE CLIENT SHALL ALSO INDEMNIFY AND HOLD WAFS HARMLESS FROM ANY AND ALL CLAIMS, <br />DAMAGES, LOSSES AND EXPENSES, INCLUDING ATTORNEYS FEES RESULTING FROM ANY SUCH PERMISSIONS. <br />GRAPHICS ELEMENTS NOTE <br />I= SPRIPS&M CONISINXT20! DRAWS463 NO SHOP YAVNOS MY NLLLilE RAO(GR "1"WIGS OR GMAPHICS StiOVO <br />n= THE MORTECREAL. CIAL STRUCTLRAL. OR HOP DRAWIGS. THESE LEFOEMLL SApR,mRY ELOOITS ARE rOR <br />GODIAL EIOUMTm7 OR CONTM ONLY AND THE FEE SPIOILEJN ENOEELR MKS OCT ACCEPT ANY IER06'NLLITY roe <br />THESE ELEMENTS. THE FM SPRI NUM ENGINEER IS IDLY RESPOISNLE FO! 110E POn1pIS O' THE FEE SPRI/O.ER <br />DRAWEES DEPMM FIE SPIO ILER SCOPES CE WON. REFON TO APPROVED AROOTECTIRK. STRUMMAL HEP OR CTVLL <br />OBIVEIGS FOR Av11OOTATSVE EXP ESS106 DF 0=6111 Y V#MMMTDN THAT MAY E UTAIM Of FDE SPRIMSLER <br />WATER SUPPLY <br />INFORMATION <br />ACTUAL <br />WOUGIg M DMW RED <br />FIRE PUMP <br />27 <br />9 16 2022 <br />10:30 AM <br />SIZE: GPM 0 PSI <br />STATIC PRESSURE <br />55 <br />HYDRANT ELEV. <br />RESIDUAL PRESSURE <br />50 <br />FLOW IN GPM <br />1000 <br />PITOT READING <br />36 <br />MAWOF PORTS FLOWED <br />1 <br />TEST PROVIDED BY <br />CITY OF ZEPHYR HILLS UTILITIES <br />HYDRANT 11256 <br />DESIGN CRITERIA <br />AREA <br />CLASS <br />ANDPIPES IN DESIGN <br />FLOW <br />OSE VALVES <br />'D 0 BASR <br />rREQQ'D <br />'D 0 BASR <br />'D 0 FDC <br />Q D 0 FDC <br />N 0 HIGHESTVALVE <br />II SPRINKLERS SPACING <br />11 SYMBOL I MAXIMUM I MINIMUM <br />I r— www --, SPRINKLERS <br />11 SYMB. 11 ST 12NO 3RDI 4TH 15TH I SIN I SIZE I K I TEMP I MODEL <br />TOTAL PER FLOOR <br />TOTAL THIS BUILDING <br />SUBMITTALS <br />BY <br />EW <br />VC <br />rIO/28/72022QA <br />NO. <br />DATE <br />REVISIONS <br />BY <br />1 <br />XX/XX/XX <br />-- <br />- <br />WAY N E <br />Automatic Fire Sprinklers, Inc. <br />MAIN OFFICE — ORLANDO. FLORIDA <br />Zee CAPITOL COURT OCOEF_ FLEA 34761 <br />PHONE (407) 30M FAX (407) 668-8026 <br />JACIC>lOtIVLLE R. <br />ISO TATEPA. FL <br />JummaLo eaAcK (9. <br />M28 057TEUnW AVE. WEST <br />328E CHMY PALM ORIVE <br />1500 S. POWEFLEE ROAD <br />JAOCSONVLLE FL 32E56-2745 <br />TAMPA. FL 33e0-OW <br />OEEFRELD EEACLC FL 39442 <br />PH OW (9D4) 266-3030 <br />PIIM (90) 030-0303 <br />P1ERE (954) 9T7-3030 <br />FAX (9134) 266-0724 <br />FAX (00) 030-0312 <br />FAX (954) 917-9424 <br />FT. MYEM FL <br />CONCORD, INC <br />per; INC <br />480 LAfEDO AVE <br />4370 MOTORSP09T OFr4E <br />rA <br />FT. 1AY619, FL 33905-4924 <br />COF(CM NC EOW-6977 <br />TRIAPYLE DRIVE <br />BALE R IB 27 FF <br />C e79746 <br />PHEIPE am) 433-30M <br />PNOPE OOQ 792-3D32 <br />PNR E (919) <br />FAX MW) 433-3283 <br />FAX 904) 795-6638 <br />STATE yamm NC wwaam <br />2974E Nc m ARIA an w -LV sc wFonm = sc ALASEA 536E <br />ZEPHYR COMMONS <br />EMERSON HILL CIRCLE <br />ZEPHYR HILLS, FL. 33541 <br />LANDSOUTH CONSTRUCTION <br />4233 PABLO PROFESSIONAL CT. <br />JACKSONVILLE, FL. 32224 <br />SHEET TITLE, <br />NOTES AND DETAILS <br />DRAWN BY, <br />VINNIE COMO <br />TOTAL A/SI <br />2,854 <br />DATE, <br />9/13/2022 <br />AHJ' <br />PASCO COUNTY <br />CONTRACT # <br />109678 <br />CENTER OF TILE JOB? ❑ YES NO <br />CENTER ON FIXTURES JOB' YES NO <br />SHEET # <br />■ 1 <br />CONSTRUCTION TYPE, <br />V-A <br />OCCUPANCY, <br />R-2 <br />