r6130 <br />.3 Exterlor windows, sliding and patio glass doors. <br />3.1 <br />Testing and labeling. Exterior windows and glass doors shall be tested by an approved independent testing laboratory, and shall be labeled to <br />indicate compliance with the requirements of one of the following specifications: <br />ANSI/AAMA/NWWDA101/I.S.2 or ANSI/AAMA/WDMA 101/I.S.2/NAFS or AAMA/WDMA/CSA 101/I.S.2/A440 or TAS 202 (HVHZ shall comply with TAS 202 utilizing ASTM E 1300-98 <br />or ASTM E 1300-04 02). <br />Exterior windows and sliding glass doors shall be labeled with a permanent label, marking, or etching providing traceability to the manufacturer and product. <br />The following shall also be required either on a permanent label or on a temporary supplemental label applied by the manufacturer: information identifying <br />the manufacturer, the product model/series number, positive and negative design pressure rating, product maximum size, glazing thickness, impact -resistance <br />rating if applicable, Florida Product Approval number or Miami -Dade Product Approval number, applicable test standard(s), and approved product certification <br />agency, testing laboratory, evaluation entity or Miami -Dade Product Approval. <br />The labels are limited to one design pressure rating per reference standard. The temporary supplemental label shall remain on the window or door until final <br />approval by the building official. <br />Exceptions: <br />1. Door assemblies installed in nonhobitoble areas where the door assembly and area are designed to accept water infiltration need not be tested for water <br />infiltration. <br />2. Door assemblies installed where the overhang (OH) ratio is equal to or more than 1 need not be tested for water infiltration. The overhang ratio shall be <br />calculated by the following equation: <br />OH ratio = OH length/OH height <br />Where: <br />OH length The horizontal measure of how for an overhang over a door projects out from door's surface. <br />OH height = The vertical measure of the distance from the door's sill to the bottom of the overhang over a door. <br />3. Pass -through windows for serving from a single-family kitchen, where protected by a roof overhang of 5 feet (1.5 m) or more shall be exempted from the <br />requirements of the water Infiltration test. <br />4. Decorative glazed openings. <br />Gloss Strength: Products tested and labeled as conforming to ANSI/AAMA/NWWDA 101/I.S.2 or ANSI/AAMA/WDMA 101/I.S.2/NAFS or AAMA/WDMA/CSA 101/I.S.2/A440 or <br />TAS 202 shall not be subject to the requirements of the Florida Building Code, Building. Determination of load resistance of glass for specific loads of <br />products not tested and certified In accordance with Section R613.3.1 sholl be designed and labeled to comply with ASTM E 1300. The temporary supplemental <br />label shall designate the type and thickness of glass or glazing material. <br />Glass Strength: Products tested and labeled as conforming to ANSI/AAMA/NWWDA 101/I.S.2 or 101/I.S.2/NAFS or AAMA/WDMA/CSA 101/I.S.2/A440 or TAS 202 shall not <br />be subject to the requirements of the Florida Building Code, Building. Determination of load resistance of glass for specific loads of products not tested <br />and certified in accordance with Section R613.3.I shall be designed and labeled to comply with ASTM E 1300. The supplemental label shall designate the type <br />and thickness of glass or glazing material. <br />R308.6.9 Testing and labeling of skylights. Exterior skylights shall be tested by an approved independent testing laboratory, and shall be labeled to <br />indicate compliance with the requirements of one of the following specification: <br />ANSI/AAMA/WDMA 101/I.S_2/NAFS or AAMA/WDMA/CSA 101/1.S.2/A440, or TAS 202 (HVHZ shall comply with TAS 202). <br />Exterior skylights shall be labeled with a permanent label, marking, or etching providing traceability to the manufacturer and product. The following shall <br />also be required either on a permanent label or on a temporary supplemental label applied by the manufacturer: information Identifying the manufacturer, the <br />product model/series number, positive and negative design pressure rating, product maximum size, type and thickness of glass or glazing material, <br />impact -resistance rating if applicable, Florida Product Approval number or Miami -Dade Product Approval number, applicable test standard(s), and approved <br />product certification agency, testing laboratory, evaluation entity or Miami -Dade Product Approval. <br />Labels are limited to one design pressure rating per reference standard. The temporary supplemental label shall remain on the skylight until final approval <br />by the building official. <br />R613.3.2 Comparative Analysis Label. A temporary supplemental label conforming to AAMA 203. Procedural Guide for the Window Inspection and Notification <br />System, shall be acceptable for establishing and communicating the calculated allowable design pressures higher than indicated on the label required by <br />Section R613.3.1 for window or door sizes smaller than that required by the ANSI/AAMA/NWWDA 101/I.S.2 or ANSI/AAMA/WDMA 101/I.S.2/NAFS or AAMA/WDMA/CSA <br />101/I.S.2/A440 test requirements. This temporary supplemental label shall be applied by the manufacturer and remain on the window or door until final <br />approval by the building official. <br />Exception 1: <br />Comparative analysis of operative windows and glazed doors may be made, provided the proposed unit complies with the following: <br />1. Shall always be compared with a tested and currently approved unit. <br />2. Varies only in width, height and/or load requirements. <br />3. Shall not exceed 100 percent of the proportional deflection for fiber stress of the intermediate members of the approved unit. <br />4. Shall conform as to extruded members, reinforcement and in all other ways with the tested approved unit. <br />5. Shall not exceed 100 percent of the concentrated load at the juncture of the Intermediate members and the frame of the approved unit. <br />6. Shall not permit more air and water Infiltration than the approved unit based on the height above grade. <br />7. Compared unit shall not exceed the maximum cyclic pressure when tested per TAS 203 or ASTM E 1886 and ASTM E 1996. <br />Exception 2: <br />Comparative analysis of fixed glass windows may be made, provided the proposed unit complies with the following: <br />1. Shall always be compared with a tested and currently approved unit. <br />2. Varies only in width, height and/or load requirements. <br />3. The design is identical in all respects, e.g., extrusions, glazing system, joinery, fasteners, etc. <br />4. Shall not permit more air and water infiltration than the approved unit based on height above grade. <br />5. The maximum uniform load distribution (ULD) of any side is equal to the uniform load carried by the side divided by the length of the side. <br />6. The ULD of any member must not exceed the ULD of the corresponding member of the tested window. <br />7. The uniform load distribution on each member shall be calculated in accordance to Section 2, Engineering Design Rules, of the AAMA 103.3 Procedural <br />Guide. <br />8. Compared unit shall not exceed the maximum cyclic pressure when tested per TAS 203 or ASTM E 1886 and ASTM E 1996. <br />R613.4 Exterior door assemblies. Exterior door assemblies not covered by Sections R613.3 or R613.4.3 shall comply with Sections R613.4.1 or R613.4.2. <br />R613.4.1 Exterior door assemblies shall be tested for structural integrity In accordance with ASTM E 330 Procedure A at a load of 1.5 times the required <br />design pressure load. The load shall be sustained for 10 seconds with no permanent deformation of any main frame or panel member in excess of 0.4 percent of <br />its span after the load is removed. HVHZ shall comply with TAS 202. After each specified loading, there shall be no glass breakage, permanent damage to <br />fasteners, hardware parts, or any other damage which causes the door to be inoperable. <br />The minimum test sizes and minimum design pressures shall be as indicated in Table R613.4 <br />The unit size tested shall qualify all units smaller in width and/or height of the some operation type and be limited to cases where frame, panels and <br />structural members maintain the same profile as tested. <br />R613.4.2 Sectional garage doors shall be tested for determination of structural performance under uniform static air pressure difference in accordance with <br />ANSI/DASMA 108 or TAS 202 (HVHZ sholl comply with TAS 202). <br />R613.4.3 Custom doors. Custom (one of a kind) exterior door assemblies shall be tested by an approved testing laboratory or be engineered In accordance with <br />accepted engineering practices. <br />R613.4.4 Door components evaluated by an approved product evaluation entity, certification agency, testing laboratory or engineer may be interchangeable in <br />exterior door assemblies provided that the door component( s) provide equal or greater structural performance as demonstrated by accepted engineering <br />practices. <br />R613.4.4.1 Optional exterior door component testing. With the exception of HVHZ, exterior side -hinged door assemblies not covered by Section R613.3 shall <br />have the option to have the components of the assembly tested and rated for structural integrity in accordance with the following specification: <br />SDI A250. 13 <br />Following the structural testing of exterior door components, there shall be no permanent deformation of any perimeter frame or panel member in excess of <br />0.4 percent of its span after the load is removed. After each specified loading, there shall be no glass breakage, permanent damage to fasteners, hardware <br />parts, or any other damage that causes the door to be inoperable, as applicable. <br />R613.4.5 Garage door labeling. Garage doors shall be labeled with a permanent label provided by the manufacturer. The label shall Identify the manufacturer, <br />the garage door model/series number, the positive and negative design pressure rating, indicate Impact rated if applicable, the installation Instruction <br />drawing reference number, the Florida Product Approval or Miami -Dade Product Approval number If applicable, and the applicable test standards. <br />The required garage door components for an approved garage door assembly may be indicated using a checklist format on the label. If a checklist format is <br />used on the label, the installer or manufacturer shall mark the selected components on the checklist that are required to assemble an approved garage door <br />system. <br />The installation instructions shall be provided and available on the job site. <br />R613.5 Wind-borne debris protection. Protection of exterior windows, glass doors and other glazed areas shall be in accordance with Section R301.2.1.2. <br />R613.5.1 Fenestration testing and labeling. Reserved. <br />R613.6 Anchorage methods. <br />R613.6.1 Anchoring requirements. Window and door assembly anchoring systems shall be tested to achieve the design pressure specified. Substitute anchoring <br />systems shall provide equal or greater anchoring performance as demonstrated by accepted engineering practice. When provided, the manufacturer's published <br />installation instructions for as tested or substitute anchoring systems can be used. In no case shall the anchorage exceed the spacing for the tested rated <br />per f or monce. <br />R613.6.1.1 Masonry, concrete or other structural substrate. Where the wood shim or buck thickness is less than 11/2 inches (38 mm), window and door <br />assemblies shall be anchored through the main frame or by jamb clip or subfrome system, in accordance with the manufacturers published installation <br />instructions. Anchors shall be securely fastened directly into the masonry, concrete or other structural substrate material. Unless otherwise tested, bucks <br />shall extend beyond the interior face of the window or door frame such that full support of the frame is provided. Shims shall be made from materials capable <br />of sustaining applicable loads, located and applied in a thickness capable of sustaining applicable loads. Anchors shall be provided to transfer load from <br />the window or door frame to the rough opening substrate. <br />Where the wood buck thickness is 11/2 inches (38 mm) or greater, the buck shall be securely fastened to transfer load to the masonry, concrete or other <br />structural substrate and the buck shall extend beyond the interior face of the window or door frame. Window and door assemblies shall be anchored through the <br />main frame or by jamb clip or sub frame system or through the flange to the secured wood buck In accordance with the manufacturers published installation <br />instructions. Unless otherwise tested, bucks shall extend beyond the interior face of the window or door frame such that full support of the frame is <br />provided. Shims sholl be made from materials capable of sustaining applicable loads, located and applied in a thickness capable of sustaining applicable <br />loads. Anchors shall be provided to transfer load from the window or door frame assembly to the secured wood buck. <br />R613.6.1.2 Wood or other approved framing material. Where the framing material is wood or other approved framing material, window and glass door assemblies <br />shall be anchored through the main frame or by jamb clip or subfrome system or through the flonge in accordance with the manufacturer's published <br />installation instructions. Shims shall be made from materials capable of sustaining applicable loads, located and applied in a thickness capable of <br />sustaining applicable loads. Anchors shall be provided to transfer load from the window or door frame to the rough opening substrate. <br />R613.7 Mullions occurring between Individual window and glass door assemblies. <br />R613.7.1 Mullions. Mullions, other than mullions which are an integral port of a window or glass door assembly tested and labeled in accordance with Section <br />R613.3.1, shall be tested by an approved testing laboratory in accordance with AAMA 450 or be engineered in accordance with accepted engineering practice. <br />R613.7.1.1 Engineered mullions. Mullions qualified by accepted engineering practice shall comply with the performance criteria in Sections R613.7.2, <br />R613.7.3, and R613.7.4. <br />R613.7.1.2 Mullions tested as stand alone units. Mullions tested as stand alone units in accordance with AAMA 450 shall comply with the performance criteria <br />In Sections R613.7.2, R613.7.3, and R613.7.4. <br />R613.7.1.3 Mullions tested In an assembly. Mullions qualified by a test of an entire assembly in accordance with AAMA 450 shall comply with Sections <br />R613.7.2 and R613.7.4. <br />R613.7.2 Load transfer. Mullions shall be designed to transfer the design pressure loads applied by the window and door assemblies to the rough opening <br />substrate. <br />TABLE R613.4 <br />MINIMUM TEST SIZES, INCLUDING FRAMING <br />Performance Class* Width x Height (mm) <br />Width x Height (in.) <br />Minimum Performance Grade <br />(Design Pressure) <br />Residential (R) <br />900 x 2000 <br />(36 x 79) <br />720 Pa <br />(15 psf) <br />Light Commercial (LC) <br />900 x 2100 <br />(36 x 83) <br />1200 Pa <br />(25 psf) <br />Commercial (C) <br />1000 x 2100 <br />(40 <br />x 83) <br />1440 Pa (30 <br />psf) <br />Heavy Commercial (HC) <br />1200 x 2400 <br />(48 <br />x 95) <br />1920 Po (40 <br />psf) <br />Architectural (AW) <br />1200 x 2400 <br />(48 <br />x 95) <br />1920 Pa (40 <br />psf) <br />*Performance Class and Performance Grade per ANSI/AAMA/NWWDA 101/I.S.2-97 <br />R613.7.3 Deflection. Mullions shall be capable of resisting the design pressure loads applied by the window and door assemblies to be supported without <br />deflecting more than L/175, where L is the span of the mullion In inches. <br />R613.7.4 Structural safety factor. Mullions shall be capable of resisting a load of 1.5 times the design pressure loads applied by the window and door <br />assemblies to be supported without exceeding the appropriate material stress levels. If tested by an approved laboratory, the 1.5 times the design pressure <br />load shall be sustained for 10 seconds, and the permanent deformation shall not exceed 0.4 percent of the mullion span after the 1.5 times design pressure <br />load is removed. <br />R613.7.5 Installation Instruction for exterior windows and doors. Windows and doors shall be installed in accordance with ASTM E 2112 or in accordance with <br />the manufacturer's installation Instruction. <br />R613.8 Flashing, sealants and weatherstripping. Flashing and sealants for exterior windows and doors shall comply with Section R703.8. <br />R613.8.1 All exterior fenestration products shall be sealed at the juncture with the building wall with a sealant complying with AAMA 800 and ASTM C 920 <br />Class 25 Grade NS or greater for proper joint expansion and contraction, ASTM C 1281, AAMA 612, or other approved standard as appropriate for the type of <br />eolant. <br />R 8.2 Masonry rough openings. Masonry rough opening dimensions shall be within the tolerances specified at Section R606.12 and in addition shall provide <br />for dow perimeter sealant joint a maximum of 1A inches In width. <br />rL <br />0 <br />F <br />Z <br />2"A2" BEAM <br />r- - - - r7 - - - - - - - - - - - - - - - - - <br />I II II II <br />EXISTING TRUSSES I <br />I II II <br />I II II II <br />I II II II <br />I II II II <br />I II II II <br />SIMPSON ST18 STAPQ 24" O.G. T� I I I I IN f <br />f SPEGCI �'CA TIONS <br />2X4 TOP PLATE <br />INSULATION <br />UNLESS OTHERWISE NOTED - ALL THERMAL INSULATION <br />SHALL BE AS FOLLOWS: <br />GONG BLOCK WALLS <br />R-3 BLOWN CELLULOSE OR R-45 <br />ALUMINUM MULTI SHEETS FOIL <br />FRAMED WALLS <br />R-I1 FIBERGLASS BATT <br />INTERIOR CEILINGS <br />R-M FIBERGLASS BATT OR BLOWN <br />CEILINGS UNDER ATTIC <br />R-30 FIBERSLASS BATT OR BLOW( <br />TOP PLATE <br />U PINE TEXTURED STUCCO OVER <br />EXP. MTL. LATH OVER <br />015 BLDG. FELT ON <br />ASPHALT IMPREGNATED <br />COMP. BOARD (OR <br />INSULATIVE FIBER BOARD <br />SHEATHING, <br />e-, I I BEAM POC<ET DETAI <br />m <br />EXTERIOR SIDING OVER <br />015 BLDG. FELT WITH <br />OR WITHOUT INSULATIVE <br />FIBER BOARD 4 SHEATHING <br />FOR NAILING SEE SHEET 525 <br />1/2" CD OR 5/8" <br />DRYWALL ON CEILING <br />6IMP50N SPI a EA_ STUD <br />1/2 "DRYWALL OVER <br />2X4 STUDS a 16" O.G. <br />or 2X6 6 24"O.C. <br />2X4 or 2X6 BLOCKING <br />NOTE: <br />INSTALL 2X4 CORNER <br />BRACING AT ALL EXT <br />CORNERS OR PLYWOOD <br />SHEATHING AT EACH <br />SIDE OF CORNER <br />TABLE 2304.9.1 FASTENING SCHEDULE I U I <br />SIMPSON 5/8" WEDGE -ALL g 32" O.G. <br />I I <br />EXISTING CONCRETE KNEE WALL <br />I I WOOD BASE <br />�J=---d--- a --�- �- <br />- - - - - - - - - - <br />1.0 <br />5.1 <br />- ^O/ 1 <br />2X4 <br />TOP PLATE <br />2X4 or 2X6 <br />JACKS <br />(2)2X6 02 YELLOW <br />PINE HEADER CUP <br />TO 5'-0" SPAN) OR <br />(2) 2XI2 Y.P. HDR <br />W/NO JACKS) <br />.UM. WINDOW <br />�RBLE SILL <br />:4 SILL PL. or 2X6 SILL OL. <br />0 1 TYPICAL WALL SECTION, <br />THROAD00 ROD OPIMION <br />PLYWD SHEATHING AND SIDING <br />2x6 GYP. SD. BACKER <br />2x6 END STUD <br />2x6 END STUD rN <br />(CONVENTION CORNER <br />(PRE -INSULATE VOIDS VFLYWD SHEATHING AND SIDING <br />BACKING FOR EXT. SIDING 4 TRIM <br />0 1' 3 STUD <br />CORNUR DETA IL. <br />EXISTING TRUSSES <br />�- I - - - - - - - <br />i <br />Frame Wa I I <br />_$" AL <br />_UNIT DIMENSION <br />- WIDTH <br />JAMB <br />WINDOW 4 DOOR FASTENNVCs <br />2011 Flaride ®ulldirb Code NOTES <br />L ALL EXTERIOR UNNPOUI6 AND GLASS DOORS SHALL <br />BE TESTED M ACCORDANCE WITH ANSI7AMMA&J=A <br />OV162 STANDARD AND BEAR AN AMMA OR UNDMA <br />LABEL INDICATING, MANFACTIIRERB PERF0RI'W4CE AND <br />APPROVED PRODUCT TESTING ENTITY, IN ACCORDANCE <br />WITH 20n Florida Bulldkig Cods, SECTION r1014]1 <br />2. ALL EXTERIOR DOORS AND tINNDOWS, SHALL BE <br />AI44C4101111ED M ACCORDANCE UNTH K FACTURERS <br />SPECIFIC:ATkX*, IN ACCORDANCE UNTH 20n FLORroA <br />BUILOMG CODE r10141 <br />9. IIIINOOWS AND DOORS FASTENED TO BUCK STRIPS <br />LESS THAN I I*" SHALL BE ANCHORED TWROUGH <br />THE JAME TO THE STRUCTURAL SUBSTRATE, M <br />ACCORDANCE WITH 20n Florida BuildMg Coda 1`101442 <br />4. UNNDOW AND DOOR MULLION ASSEMBLIES SHALL BE <br />DESIGNED AND TESTED TO TRANSFER IS TIMES THE <br />INDICATED DESIGN LOADS, TO THE STRUCTURAL SUBSTRATE <br />IN ACCORDANCE WITH, 20n Florida Buildkg Cods <br />rW 1.45J AND n01.4S4. <br />WOOD UJIN170UJ <br />4NCHOR,4ar: (NTS) <br />ATTACHMENT OF <br />WINDOW TO FRAME <br />WALL TO RE PER <br />MANUFACTURERS <br />RECOMMENDATION. <br />ALL WIDT <br />-J <br />2-II/16" <br />4LUM. (OR FIN TYPE <br />UJINDOUJ ,4NGH0R,4Gr= (NITS) <br />-�--A-, I I WIPIDOW /DOOR ANCHOR <br />(FRAME) <br />2x4 TOP PLATE ATTACHED <br />WITH SIMPSON SDSJ X 31 I1 <br />6" O.G. STAGGERED <br />TEXTURED STUCCO OVER <br />EXP. MTL. LATH OVER <br />015 BLDG. FELT ON <br />ASPHALT IMPREGNATED <br />COMP. BOARD (OR <br />INSULATIVE FIBER BOARD <br />SHEATHING. <br />�4 <br />EXTERIOR SIDING OVER <br />015 BLDG. FELT WITH <br />OR WITHOUT INSULATIVE <br />FIBER BOARD 4 SHEATHING <br />FOR NAILING SEE SHEET 625 <br />TABLE 2304.9.1 FASTENING SCHEDULE <br />SIMPSON I" WEDGE -ALL 6 32" O.G. <br />FIN. GRADE <br />EXISTING BEAM <br />SIMPSON SPI 61 EA, STUD <br />1/2 "DRYWALL OVER <br />2X4 STUDS 6 16" O.G. <br />or 2X(o t1 24"O.C. <br />U <br />c <br />a <br />7 <br />O <br />2X4 or 2X6 BLOCKING C� <br />C <br />NOTE: rn <br />INSTALL 2X4 CORNER <br />BRACING AT ALL EXT <br />p <br />CORNERS OR PLYWOOD <br />SHEATHING AT EACH <br />c <br />SIDE OF CORNER <br />0 <br />U) <br />L <br />N <br />C <br />L <br />O <br />i <br />Ki SIMPSON SPI m EA. STUD � <br />0 <br />2x4 PT CONT. N <br />O <br />EX. GONG. FLOOR 0 <br />------------� <br />0 <br />