TANKLESS WATER
<br />HEATER LOCATION
<br />HEATER LOCATION
<br />ELECTRICAL PLAN 1 /411 = 1' of
<br />100 AMP 24 CIR TYPICAL PANEL
<br />1
<br />WALL PACK LIGHT/ TIMER
<br />1 P20
<br />2
<br />STORAGE LIGHTS
<br />1 P20
<br />3
<br />RESTROOM LIGHTS & FAN
<br />1 P20
<br />4
<br />INSTANT HOT WATER / LAV
<br />1 P20
<br />5
<br />INSTANT HOT WATER / MOP SK
<br />1 P20
<br />6
<br />GFI RECEPTACLE
<br />1 P20
<br />7
<br />EMERGENCY LIGHTS
<br />1P20
<br />8
<br />SPACE
<br />9
<br />SPACE
<br />10
<br />SPACE
<br />11
<br />SPACE
<br />12
<br />SPACE
<br />13
<br />SPACE
<br />14
<br />SPACE
<br />15
<br />SPACE
<br />16
<br />SPACE
<br />17
<br />SPACE
<br />18
<br />SPACE
<br />19
<br />SPACE
<br />20
<br />SPACE
<br />21
<br />SPACE
<br />22
<br />SPACE
<br />23
<br />SPACE
<br />24
<br />SPACE
<br />LOAD CALCULATIONS
<br />LOAD
<br />DEMAND FACTOR
<br />TOTALS
<br />LIGHTING
<br />176 X 3
<br />528
<br />RECPTS
<br />1 X 180
<br />180
<br />TANKLESS
<br />WATER HEATERS
<br />2 @ 360
<br />720
<br />TOTAL
<br />1428
<br />1428 VA
<br />208 VOLTS 6.9 AMPS
<br />ELECTRICAL NOTES
<br />1. All work to be done in accordance with all current national and
<br />local codes and ordinances.
<br />2. Notify Engineer of any discrepancies between these drawings and the
<br />actual field conditions. Obtain clarifications from the Engineer or
<br />Owners prior to commencing work.
<br />3. Contractor will visit site prior to bidding, no allowances for any
<br />extra expenses will be granted as a result of not visiting site.
<br />4. Wire to be THHN/THWN Copper, min. size 14 AWG, unless shown otherwise.
<br />5. RACEWAYS: RIGID STEEL CONDUIT: full weight galvanized threaded pipe,
<br />EMT CONDUIT: compression fittings, PVC: schedule 40, all as allowed
<br />by local codes. Separate raceways shall be used for each voltage system.
<br />6. Any installation conflict with other trades shall be brought to the
<br />attention of the Engineer for clarification before proceeding.
<br />7. Contractor will verify location of equipment and connect as required for
<br />clearances and connections.
<br />8. All ourdoor electrical equipment to be NEMA 3R rated.
<br />LIGHTING & ELECTRICAL LEGEND
<br />A
<br />&
<br />O
<br />LITHONIA LB 1OX48 2 LAMP
<br />110V GROUND
<br />BOSCH GL 5
<br />WRAP FLUORESCENT FIXTURE
<br />FAULT OUTLET
<br />ARISTON 2 1/2
<br />GALLON TANKLESS
<br />WATER HEATER
<br />BI
<br />120V 1500 WATTS
<br />HE
<br />LITHONIA MNSB 132 L T6
<br />2 LAMP FLUORESCENT
<br />100 CFM
<br />FIXTURE
<br />NUTONE 765 HL
<br />EXHAUST FAN
<br />O
<br />PANEL
<br />$MS
<br />MOTION OCCUPANCY
<br />SENSOR SWITCH
<br />STANDARD SWITCH
<br />METER
<br />m
<br />EMERGENCY LIGHT
<br />LITHONIA TWAC
<br />WITH BATTERY B.U.
<br />MINI WALL PACK
<br />3- #3 THNN
<br />1- k3 N
<br />G FOOTER STEEL
<br />CONCRETE ENCASED"UFER"
<br />ELECTRODE REQUIRED PER
<br />CURRENT N.E.C. AND MUST
<br />BE INSPECTED PRIOR TO
<br />CONCRETE PLACEMENT
<br />ELECTRICAL RISER DIAGRAM
<br />NOT TO SCALE
<br />SINGLE PHASE
<br />BREAKER PANEL
<br />MAIN
<br />GROUND ROD
<br />54" MIN TOILET 18" MIN 18" MIN —24" MIN
<br />PAPER
<br />F
<br />1/
<br />HOLDER
<br />42" MIN
<br />:
<br />LAY i
<br />1
<br />z
<br />CLEAR FLOOR
<br />yj
<br />SPACE
<br />HANDICAP TOILET DETAIL -----
<br />---
<br />60" MIN
<br />GRAB BARS
<br />A GRAB BAR SHALL BE PROVIDE, LOCATED 33" INCHES
<br />FROM AND PARALLEL TO THE FINISHED FLOOR. MEASURED
<br />VERTICALLY TO THE TOP OF THE RAIL WITH VARIATION OF
<br />NOT MORE THAN 1/2 INCH AND:
<br />I, SHALL HAVE AN OUTSIDE DIAMETER OF 1 V2 INCHES
<br />2. SHALL PROVIDE 1 112 INCHES OF CLEARANCE BETWEEN
<br />THE RAIL AND THE WALL
<br />3. SHALL BE SO DESIGNED AND SUPPORTED AS TO WITHSTAND
<br />A LOAD OF NOT LESS THAN 250 LBS APPLIED AT ANY POINT,
<br />DOWNWARD OR HORIZONTALLY.
<br />4. SHALL BE CONTINUOUSLY GRASPABLE ALONG THE ENTIRE
<br />LENGTH.
<br />SPECIAL NOTE: GRAB BAR MEETING THE APPLICABLE ANSI STANDARDS
<br />ARE DEEMED TO BE IN COMPLIANCE WITH THE INTENT OF
<br />THE LAW WHETHER CENTER SUPPORTS EXIST OR NOT.
<br />S. SHALL BE AT LEAST 42 INCHES LONG AND SHALL BE CENTERED
<br />AT THE LEADING EDGE OF THE WATER CLOSET.
<br />------------- ----
<br />6" MAX, ----'-- XX
<br />TOE CLEARANCE i z Q
<br />I
<br />I I I
<br />I I
<br />I I
<br />I I
<br />rt" MAX LAV DEPTH B" MIN KNEE CLEARANCE
<br />HANDICAP SINK DETAIL
<br />SINK
<br />1. SINK SHALL BE MOUNTED WITH THE COUNTER OR RIM
<br />NO HIGHER THAN 34" FROM THE FINISH FLOOR. EACH
<br />SINK SHALL BE MINIMUM OF 6 1/2" DEEP,
<br />2, CLEAR FLOOR SPACE RESTROOMS SHALL HAVE AN
<br />UNOBSTRUCTED SPACE OF AT LEAST 60" IN DIAMETER
<br />OR 52" BY Yl" FINISH INSIDE DIMENSIONS ADJACENT TO
<br />THE LAVATORY AREA, SUCH CLEAR FLOOR SPACE SHALL
<br />ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE AND SHALL
<br />EXTEND A MAXIMUM OF 13" UNDERNEATH THE LAVATORY
<br />OR SNK
<br />PLUMBING FIXTURE SCHEDULE
<br />SLOAN OPTIMA FAUCET ETF-80
<br />LAVATORY
<br />KOHLER MODEL K-2030-0 WHITE
<br />CHROME FINISH
<br />SUPPLY AND DRAIN PIPING TO
<br />HAVE TAMPER PROOF SHIELD
<br />UNDER SINK
<br />BOSCH GLS ARISTON 2 1/2
<br />TO BE INSTALLED IN STORAGE
<br />TANKLESS
<br />GALLON
<br />AREA BEHIND LAVATORY
<br />WATER HEATER
<br />WATER CLOSET
<br />KOHLER MODEL K-4368-0
<br />SLOAN MANUAL
<br />FLOOR MOUNT ADA
<br />FLUSHOMETER 110
<br />SLOAN ROYAL EXPOSED
<br />URINAL
<br />KOHLER MODEL K-4904-ET-0
<br />FLUSHOMETER MODEL 180
<br />WALL MOUNT VERITEK
<br />CHROME FAUCET TO FIT
<br />MOP SINK
<br />SOLID MOLDED TUB
<br />TUB WITH WATER HOSE
<br />MANUFACTURE TO BE
<br />ADAPTER
<br />DETERMINED
<br />ELECTRICAL SPECIFICATIONS
<br />1.1 SCOPE
<br />A. WORK INCLUDED: Include the following Work in addition to items normally part of this Section:
<br />01 Wiring for lighting and power.
<br />02 Installation of lighting fixtures with lamps.
<br />03 Lighting panelboards and distribution panelboards.
<br />04 Connection of equipment shown.
<br />05 Control wiring.
<br />06 Disconnection and removal of existing fixtures and wiring not to be reused.
<br />1.2 MINIMUM COMPLIANCE STANDARDS
<br />A. All work shall be done in accordance with the requirements of the following:
<br />01 Latest adopted issue of the National Electrical Code, NFPA 70.
<br />02 Other applicable NFPA Codes.
<br />03 Regulation of local authorities having jurisdiction.
<br />B. Furnish and install all labor, material and equipment and services necessary for complete and
<br />safe installation of the electrical system indicated on the drawings and noted in the
<br />specifications hereinafter. Electrical systems and equipment shall in general include the
<br />following:
<br />01 General provisions for electrical work.
<br />02 Wiring, distribution equipment and devices.
<br />03 Lighting fixtures and lamps.
<br />04 Grounding system.
<br />1.3 GENERAL PROVISIONS FOR ELECTRICAL WORK
<br />A. DRAWINGS: Electrical drawings considered diagrammatic and indicate general arrangement of work
<br />and systems. Refer to other drawings to verify location of equipment, etc. Check drawings of
<br />other trades to verify exact space condition or underground lines. Drawing Scales prohibit the
<br />indication of all offsets, fittings and accessories required, however these items will be
<br />provided by this subcontractor at no extra cost to the owner.
<br />B. QUALITY OF MATERIALS: New, best of their respective kind, free from defects, and listed by
<br />Underwriter's Laboratories, Inc. or bearing their label.
<br />C. SHOP DRAWINGS: Submit four (4) copies of shop drawings for lighting fixtures and panelboards.
<br />Obtain approval before equipment is ordered, built or installed.
<br />D. EXCAVATION AND BACKFILLING: Excavate, backfill and restore surfaces for all electrical work.
<br />E. Visit site and inspect existing facilities before bid in order to ensure proper evaluation of
<br />working conditions and location of existing equipment.
<br />1.4 WIRING, DISTRIBUTION EQUIPMENT AND DEVICES
<br />A. CONDUCTORS: Copper, in accordance with ASTM Standards, size references AWG. Conductors No. 10 and
<br />smaller size solid, No. 8 and larger stranded. Insulation of conductor thermoplastic, type THHN
<br />(min. size: No. 12) any wire installed outside, underground, in slabs, or exposed to moisture
<br />shall have THWN insulation.
<br />B. RACEWAYS: RIGID STEEL CONDUIT, full weight pipe galvanized, threaded, and minimum 112 inch except
<br />as noted or required for wiring. ELECTRICAL METALLIC TUBING (EMT), thin wall pipe, galvanized, threadless,
<br />comression fittings, and minimum 1/2" except as noted or required for wiring. FLEXIBLE STEEL CONDUIT,
<br />continuous singlestrip, galvanized, and minimum 1/2" size except as noted or required for wiring. PVC
<br />CONDUIT, heavy duty type, size as indicated. Type AC or MC cable where permitted. Separate raceways shall
<br />be used for each voltage system.
<br />C. DISCONNECT SWITCHES: General Duty, horsepower rated for motor loads 600 or 250 volt rating, fused
<br />or non -fused as noted; number of poles as indicated, cover Interlocked with switch. Enclosure
<br />NEMA 1 for indoor use and NEMA 3R for weatherproof applications. Switch to be Square "D" or equal.
<br />E
<br />ALL WATER AND SANITARY PIPING TO
<br />BE EXPOSED AND ACCESSIBLE FROM
<br />THIS SIDE OF MASONRY WALL
<br />SANITARY PLAN 1 /411 = 1' 0'
<br />PIPE NOTE:
<br />SANITARY PIPING TO BE SCHL 40 PVC
<br />COLD AND HOT WATER LINES TO BE CPVC
<br />OR EQUAL
<br />D. CIRCUIT BREAKERS: Molded case, thermal -magnetic quick -make, quick -break, bolt -on type with
<br />manually operated insulated trip -free handle. Multi -pole types with internal common trip bar.
<br />Terminals suitable for copper or aluminum conductors. Interrupting capacity minimum 10,000 RMS
<br />symmetrical amperes circuit breakers to be Square "D" or equal, type as required.
<br />E. PANELBOARDS: Voltage, phasing and ampere ratings as indicated, circuit breaker type as indicated,
<br />busbars of hard drawn copper, minimum 98% conductivity, galvanized steel back box, door and trim.
<br />All corners lapped and welded, hardware chrome plated with flush lock and catch. Hinges semi -
<br />concealed, 5 knuckle steel with nonferrous pins, 180 degree openings. Minimum gutter space 5-
<br />3/4" sides, top and bottom. Increase size where required by code. Directory holder complete
<br />with clear plastic transparent cover indicating typewritten list of feeder cables, conduit sizes,
<br />circuit numbers, outlets of equipment supplied, and their location. Circuit breaker type
<br />panelboards to be Square "D" type NQOD or I -Line, or equal. A plastic label shall be located on exterior of
<br />panelboard identifying the system voltage, phase, and current rating.
<br />F. WIRING DEVICES: All devices the product of the same manufacturer. Wall switches singlepole, 20
<br />ampere, 120 volt. Wall switches three-way, 20 ampere, 120 volt. Receptacles duplex, 2-wire; 3
<br />pole grounded, 20 ampere, 120 volt.
<br />G. DEVICE PLATES: Provide for all outlets where devices are installed. Provide engraved marking for
<br />special outlets. Provide blank plates for empty or future outlet boxes. DEVICE AND DEVICE PLATES
<br />COLORS TO BE VERIFIED WITH INTERIOR DESIGNER AND OWNER.
<br />1.5 LIGHTING FIXTURES AND LAMPS
<br />A. Furnish and install complete system of lighting fixtures, lamps, accessories and supports as
<br />specified and indicated. Submittals of equal quality are allowed.
<br />1.6 GROUNDING SYSTEM
<br />A. EQUIPMENT: Ground non -current carrying metal parts of panelboard, raceways and all lighting
<br />fixtures. All conduits shall have equipment grounding conductors.
<br />1.7 INSTALLATION
<br />A. Secure all supports to building structure. Support horizontal runs
<br />of metallic conduit not more than 10 feet apart. Run exposed raceways parallel with or at right
<br />angles to walls.
<br />B. Pass raceways over water, steam or other piping when pull boxes are not required. No raceway
<br />within 3 inches of steam or hot water pipes, or appliances, except crossings where raceway shall
<br />be at least 2 inches from pipe cover.
<br />C. Cut conduit ends square, ream smooth. Paint male threads of field threaded conduit with graphite
<br />base pipe compound. Draw up tight with conduit couplings.
<br />D. Leave wire sufficiently long to permit making final connections. In raceways over 50 feet in
<br />which wiring is not installed, furnish pull wire.
<br />E. Verify locations of outlets and switches.
<br />F. Support panel, junction and pull boxes independently to building structure with no weight bearing
<br />on conduits.
<br />G. Connect conduit to motor conduit terminal boxes with flexible conduit; minimum 18 inches in
<br />length and 50% slack. Do not terminate in or fasten raceways to motor foundation.
<br />H. Contractor to remove and salvage all abandoned electrical equiment.
<br />I. This contractor shall warrant all labor and materials for one year from date of final written
<br />acceptance.
<br />ARKAY ENGINEERING INC.
<br />STRUCTURAL ENGINEERS
<br />RICHARD L. KIDDEY P.E.
<br />FLORIDA LICENSE NUMBER 37296
<br />1 HERBY CERTIFY THAT THESE PLANS AND SPECIFICATIONS
<br />WERE PREPARED BY ME OR UNDER MY DIRECT SUPERVISION
<br />ARE IN COMPLIANCE WITH CHAPTER 16, SECTION 1609 OF THE
<br />FLORIDA BUILDING CODE 2010 AND ASCE 7-10 FOR 137 MPH
<br />WIND ZONE RISK CATEGORY II
<br />Z�
<br />z
<br />0"
<br />z
<br />V1
<br />W
<br />A
<br />C
<br />r-
<br />1
<br />Comm
<br />Cq to*
<br />o�
<br />ma�iii
<br />Z
<br />IL X L J
<br />IL as
<br />z c
<br />_o
<br />0FL
<br />z�>JJJ
<br />LJ
<br />01T
<br />go
<br />w ILL
<br />"_J
<br />1i_ )
<br />W
<br />d
<br />0
<br />z
<br />O
<br />W
<br />W
<br />W
<br />co
<br />CV
<br />N
<br />�
<br />�CC
<br />m
<br />r
<br />G
<br />Z
<br />w
<br />~
<br />O
<br />Z
<br />m
<br />p
<br />p
<br />O
<br />i'
<br />J
<br />U
<br />Q
<br />U.
<br />2
<br />Ct) O
<br />O
<br />cl)
<br />= UJ
<br />N
<br />LL Q
<br />Oa
<br />L)
<br />LU
<br />Z
<br />Z
<br />/D
<br />V
<br />TOTAL AREA
<br />176 SQ. FT.
<br />E1 P1
<br />ARKAY #
<br />
|