ELECTRICAL NOTES: <br />1. GFCI'S ARE TO BE INSTALLED IN THE FOLLOWING <br />LOCATIONS AS SPECIFIED PER NFPA 70 (NEC) 2017 <br />A) BATHROOMS <br />B) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT <br />HAVE A FLOOR LOCATED AT OR BELOW GRADE LEVEL <br />NOT INTENDED AS HABITABLE ROOMS AND LIMITED TO <br />STORAGE AREAS, WORK AREAS, AND AREAS OF <br />SIMILAR USE. <br />C) CRAWL SPACES AT CAR BELOW GRADE. <br />D) KITCHENS - WHERE THE RECEPTACLES ARE <br />INSTALLED TO SERVE THE COUNTERTOP SURFACES. <br />E) LAUNDRY, UTILITY, AND WET BAR SINKS - WHERE <br />THE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OF <br />THE OUTSIDE EDGE OF THE SINK. <br />2. ARCH FAULT OUTLETS ARE REQUIRED PER NFPA 70 <br />(NEC) 2017, INCLUDING ARTICLES 210 AND 400. <br />3. ANY CONFLICTS BETWEEN LOCATION OF <br />MECHANICAL FIXTURES ON PLANS AND THE ABILITY TO <br />LOCATE THEM IN THE FIELD MUST BE REPORTED TO THE <br />ARCHITECT PRIOR TO INSTALLATION. <br />4, RECEPTACLE OUTLET S IN GARAGE MUST BE <br />SERVED BY SEPARATE BRANCH CIRCUIT THAT DOES NOT <br />SUPPLY OTHER OUTLETS. <br />5. CM MUST BE AT LEAST 3' FROM BATH DOOR AND AT <br />LEAST 6' FROM KITCHEN RANGE/OVEN. <br />NOTES: <br />UNLESS OTHERWISE NOTED <br />1. ELECTRICAL OUTLET HEIGHTS AS MEASURED FROM FINISHED <br />FLOOR TO CENTERED LINE OF THE BOX TO BE: 12" AFF <br />(GENERAL) <br />KITCHEN <br />44" AFF <br />BATHROOM <br />39" AFF <br />LAUNDRY ROOM <br />36" AFF <br />EXTERIOR WATERPROOF <br />12" AFF <br />GARAGE GENERAL PURPOSE <br />42"AFF <br />RANGE <br />2" AFF <br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE <br />POSSIBLE. <br />3. ELECTRICAL SWITCHES TO BE AT 42" CENTERLINE ABOVE <br />FINISHED FLOOR <br />4. ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY. <br />ALL WORK SHALL. BE DONE IN STRICT ACCORDANCE WITH THE <br />NATIONAL ELECTRIC CODE, LATEST EDITION, BY A LICENSED <br />ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE FOR <br />THE INSTALLATION & SIZING OF ALL ELECTRICAL, WIRING & <br />ACCESSORIES. <br />5. SMOKE DETECTORS SHALL BE INSTALLED AS DIRECTED BY <br />THE 2016 NFPA 72 NATIONAL FIRE ALARM CODE. <br />6. ALL ELECTRICAL IN THE LIVING ROOMS, DINING ROOMS, <br />SUNROOMS, FAMILY ROOMS, DENS, LIBRARIES, SLEEPING ROOMS, <br />PARLORS AND SIMILAR ROOMS OR AREAS SHALL BE ON AN A,F.C.I. <br />PROTECT CIRCUIT PER NFPA 70 (NEC) 2017. <br />7. IN ALL AREA SPECIFIED IN NFPA 70 (NEC) 2017 210.52, ALL 125 <br />VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED <br />TAMPER -RESISTANT RECEPTACLES. <br />U �az3 <br />Virtual Review Assist, Inc. <br />Plans Review completed and approved <br />toy compliance with the 2020 FRC 7th Edition <br />by Debra Anne Kiahr PX2300 <br />SECOND FLOOR ELECTRICAL PLAN (A, B, K, L & M <br />11411 = 1'-011 <br />ELECTRICAL DETAIL: <br />INTERCOM <br />SPEAKER <br />ALIGNED W/ <br />EDGE OF <br />SWITCH <br />SWITCH ° <br />DOORJAMB DUPLEX <br />OUTLET cn <br />TRIM o <br />0 <br />BASE <br />NOTE: <br />ALL DIMENSIONS ARE FROM ROUGH FRAMING <br />SMOKE DETECTOR LOCATION: <br />WALL <br />oz <br />k r� <br />SMOKE DETECTOR <br />MIN. <br />ELECTRICAL LEGEND: <br />NOTE: ALL HEIGHTS ABOVE FINISH FLOOR <br />E 110V DUPLEX OUTLET AT 12" <br />110V DUPLEX OUTLET AT 39" <br />NOTE: ALL <br />RECEPTACLES <br />110V DUPLEX OUTLET AT 43" <br />ABOVE <br />COUNTERS <br />110V DUPLEX OUTLET AT 45" <br />SHALL BE <br />SPLIT 110V DUPLEX OUTLET <br />MOUNTED <br />HORIZONTAL <br />AT 12" - TOP PLUG IS HOT <br />110V QUAD OUTLET AT 12" <br />WEATHERPROOF GFCI OUTLET AT 12" <br />220V OUTLET AT 30" <br />110V DUPLEX FLOOR OUTLET <br />OUTLET -VERIFY W/MANUF. SPECS <br />FOR LOCATION & TYPE <br />TELEPHONE OUTLET AT 12" OR AS NOTED <br />TELEVISION OUTLET AT 12" - WIRE FOR <br />CABLE & SATELLITE <br /><> STRUCTURED WIRE OUTLET <br />SWITCH AT 36" <br />6 3 WAY SWITCH AT 36" <br />-cam 4 WAY SWITCH AT 36" <br />-0 PUSH BUTTON FOR GARAGE DOOR OPENER <br />-o DIMMER SWITCH AT 36" <br />PUSH-BUTTON DOORBELL <br />-OfA3- CLG MNT LT FIXTURE <br />{B} CLG MNT PREWIRE - FIXTURE BY OWNER <br />-}- SURFACE MNT FIXTURE <br />- WALL MNT FIXTURE <br />NOTE: <br />C ND OPALEX - ALTERNATE <br />TUB/SHOWERCANS MAY BE <br />C 50W PAR30 NFL 6" WHITE BAFFLE USEDIF <br />APPROVED BY <br />C 50W MR16 4" LOW VOLTAGE OWNER <br />T 50W PAR20 NFL 4" MINI ROUND RECESS <br />, 0 50W PAR20 NFL 6" RD REGRESSED BAFFLE EYEBALL <br />-�- CLG FAN PREWIRE AND SWITCH <br />COMBINATION CARBON MONOIXED DETECTOR/ <br />cs SMOKE DETECTOR <br />C SMOKE DETECTOR <br />=U-18= UNDER CABINET 18" <br />=S-18= SINGLE 18" FLUOR STRIP <br />=U-24= UNDER CABINET 24" <br />=S-24= <br />SINGLE 24" FLUOR STRIP <br />=D-24= <br />DOUBLE 24" FLUOR STRIP <br />c U-36 = <br />UNDER CABINET 36" <br />= S-36 = <br />SINGLE 36" FLUOR STRIP <br />= D-36 = <br />DOUBLE 36" FLUOR STRIP <br />— S-48 — <br />SINGLE 48" FLUOR STRIP <br />— D-48 <br />DOUBLE 48" FLUOR STRIP <br />24 24"CLG MNT WRAPPED FLUOR LIGHT <br />48 48"CLG MNT WRAPPED FLUOR LIGHT <br />9F24:R 24" VANITY LIGHTING <br />F;;F 36 :;;R 36" VANITY LIGHTING <br />48 48" VANITY LIGHTING <br />�j EXHAUST FAN/LIGHT <br />0 EXHAUST FAN <br />DOUBLE FLOOD LIGHT W/ COVERS AND <br />150W PAR 38 FL <br />® INTERCOM SPEAKER AT 5'-0" ABV FINISH FLOOR <br />O CEILING MNT SPEAKER <br />ED CHIMES (DELETE W/ INTERCOM) <br />MASTER STATION <br />i►�I. ELEC PANEL <br />VACUM OUTLET AT 12" <br />WAI CEILING RETURN AIR <br />F71 A/C REGISTER <br />OT THERMOSTAT <br />ED SECURITY PAD <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR LOCATION PURPOSES. <br />m <br />O <br />fF F, <br />m <br />N <br />�, Y� , <br />Cl)e' <br />4 S <br />a <br />q G <br />o <br />00 <br />r5 <br />.tl <br />® <br />' d <br />yry <br />-10 ra s0 <br />t° x <br />Q <br />W <br />t X <br />_ <br />O <br />w <br />0 <br />z <br />Q <br />nN N LO <br />L � U <br />W <br />co ai <br />M <br />2 <br />cN V -6- 2 M <br />C E 'E :Eo <br />U0 <br />O <br />�- a LL_o o Q <br />•- <br />0 V w QN <br />W 0o E� <br />L, <br />r\ i7 a Q) <br />W <br />Q <br />w <br />W W J w200 <br />H R J CrCC Z W' <br />Uj ¢ <br />< Op - J 0 O� W 0 w U O Ow O <br />OF¢- <br />Z d <br />Q <br />O¢ ZIWL LLo Z2 <br />OWWOtRooJ❑Za <br />cWZwziW <br />¢0WwoWOpa�QpQ <br />Q <br /><< <br />OZawFWw <br />LLJ <br />ZQp <br />aILL <br />owea <br />Op 0hY <br />LL ¢ O I— LL <br />O <br />z W <br />OI­_ <br />U—)5ti <br />0 1.—:M <br />Q (1)M <br />O <br />Lo <br />� CA LL ti <br />W <br />U?0-c� <br />00 <br />Q Q <br />z U �- <br />3: <br />Wz <br />W <br />J O <br />O <br />CD <br />4 <br />O <br />a <br />N <br />O <br />N <br />N <br />O <br />oN <br />O <br />O <br />O <br />CD\r <br />� <br />O <br />O <br />r <br />O <br />r <br />N <br />O <br />CD\ <br />O <br />O <br />; <br />z <br />' <br />O <br />NLo <br />W <br />0 <br />0 <br />0 <br />0 <br />0 <br />0 <br />1 <br />> <br />CO v1 <br />Qz <br />a--+ <br />O <br />W <br />W <br />O <br />O <br />V <br />W O <br />UVV5 <br />F_ <br />0 <br />Z)z5; <br />or< <br />Q <br />z <br />a IZ <br />Q0 <br />F- <br />W Q <br />N(D <br />W F— <br />F-�W <br />== <br />N <br />� <br />ZO <br />■ ■ <br />W <br />0 <br />Qo? <br />:q�2 <br />ZWO <br />r, <br />`! <br />aZLL <br />W <br />Z <br />z <br />�z <br />�2 <br />U <br />00 <br />� <br />A6. 1 <br />z <br />z <br />w <br />WT_ <br />J <br />ti <br />r <br />LAST PLOT DATE <br />o <br />N <br />z O <br />March 23, 2023 <br />2ND FLOOR <br />J <br />ELECTRICAL PLAN A, <br />B;K,L&M) <br />-_. <br />r—_. __F --- I P_-"I-TT-11 <br />