<br />ELECTRICAL SPECIFICATIONS
<br />A. THE WORK. APPARATUS AND MATERIALS WHICH SHALL BE FURNISHED UNDER THESE SPECIFICATIONS
<br />AND ACCOMPANYING DRAWINGS SHALL INCLUDE ALL ITEMS SPECIFIED HEREINAFTER AND SHOWN ON THE
<br />DRAWINGS. ALL OTHER MATERIALS NECESSARY FOR THE COMPLETE INSTALLATION SHALL BE FURNISHED
<br />AND INSTALLED BY THE CONTRACTOR. CONTRACTOR TO PROVIDE COMPLETE ELECTRICAL SYSTEMS AS
<br />INDICATED ON THE DRAWINGS AND AS SPECIFIED HEREIN.
<br />B. THE CONTRACTOR SHALL EXTEND THE SERVICE FROM THE POINT OF SERVICE ATTACHMENT
<br />FURNISHING ALL PROTECTIVE DEVICES, CONDUCTORS, SUPPORTS, RACEWAYS, ETC. TO PROVIDE
<br />COMPLETE INTERIOR ELECTRICAL SYSTEMS TO SERVE MOTOR LOADS, LIGHTING LOADS AND
<br />MISCELLANEOUS ELECTRICAL LOADS, AS SHOWN ON THE DRAWINGS AND AS SPECIFIED HEREINAFTER.
<br />THE WORK SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING AT THE COMPLETION OF
<br />THE WORK AND MAKING ANY MINOR CONNECTION CHANGES OR ADJUSTMENTS NECESSARY FOR THE
<br />PROPER FUNCTIONING OF THE SYSTEM AND EQUIPMENT. ALL WORKMANSHIP SHALL BE OF THE HIGHEST
<br />QUAU1Y AND NO SUBSTANDARD WORK WILL BE ACCEPTED.
<br />C. VERIFY CONDITIONS AT THE FIELD PRIOR TO PRICING THE JOB. CONTRACTOR SHALL VISIT THE SITE
<br />AND FAMILIARIZE HIMSELF WITH ALL DETAILS OF THE WORK AND EXISTING CONDITIONS.
<br />D. CONTRACTOR SHALL REFER TO INTERIOR ARCHITECTURAL DRAWINGS FOR EXACT MOUNTING HEIGHTS
<br />AND/OR LOCATIONS OF ALL LIGHTING FIXTURE SWITCHES, OUTLETS AND WIRING DEVICES AND SHALL
<br />PERFORM ALL WORK NOTED ON PLANS, IN NOTES OR IN DETAILS RELATED TO ELECTRICAL
<br />1111111K8191��
<br />A. THE WORK UNDER THE REQUIREMENTS OF THESE SPECIFICATIONS SHALL BE IN
<br />CONFORMANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE.
<br />THE INSTALLATION SHALL ALSO COMPLY WITH ALL APPLICABLE RULES AND
<br />REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES.
<br />INTERFERENCES
<br />A. THE PLANS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL COORDINATE THE WORK
<br />WITH THE DIFFERENT TRADES SO THAT INTERFERENCES BETWEEN CONDUITS. PIPING, EQUIPMENT,
<br />ARCHITECTURAL AND STRUCTURAL WORK WILL BE AVOIDED. ALL NECESSARY OFFSETS IN RACEWAYS,
<br />FITTINGS, ETC. REQUIRED TO PROPERLY INSTALL THE WORK SHALL BE FURNISHED SO AS TO TAKE UP A
<br />MINIMUM SPACE, AND ALL MATERIALS REQUIRED TO ACCOMPLISH THIS SHALL BE FURNISHED AND
<br />INSTALLED BY THE CONTRACTOR WITHOUT ADDITIONAL EXPENSE TO THE OWNER. IN CASE INTERFERENCE
<br />DEVELOPS, THE OWNER'S AUTHORIZED REPRESENTATIVE WILL DECIDE WHICH EQUIPMENT. PIPING, ETC.,
<br />MUST BE RELOCATED, REGARDLESS OF WHICH WAS INSTALLED FIRST.
<br />MATERIALS
<br />A. IN GENERAL, MATERIALS AND APPARATUS SHALL COMPLY WITH ALL APPLICABLE TESTS, RATINGS,
<br />SPECIFICATIONS, AND REQUIREMENTS OF THE IEEE AND NEMA AND SHALL BEAR THE APPROVED DEVICE
<br />LABEL OF THE UNDERWRITERS' LABORATORIES, INC.
<br />B. ANY MATERIAL OR PRODUCT SPECIFIED HEREIN OR ON THE DRAWINGS BY MANUFACTURER AND
<br />CATALOG NUMBER AFTER WHICH THE TERM "OR EQUAL" DOES NOT APPEAR SHALL BE INTERPRETED AS
<br />LIMITING SUCH ITEMS BY A PREDETERMINED SELECTION AS STATED. IN SUCH INSTANCES NO
<br />SUBSTITUTIONS WILL BE ALLOWED. ANY MANUFACTURER AND CATALOG NUMBER FOLLOWED BY THE TERM
<br />"OR EQUAL" SHALL BE INTERPRETED TO MEAN EQUAL IN QUALITY, VALUE, AND INTEGRAL PROPERTIES
<br />AND SIMILAR IN APPEARANCE, DESIGN, AND FUNCTIONS. THE CONTRACTOR MAY IN THESE INSTANCES
<br />AFTER OBTAINING WRITTEN APPROVAL OF THE OWNER, SUBSTITUTE MATERIALS OR PRODUCTS OTHER
<br />THAN THE ONE NAMED.
<br />C. THE CONTRACTOR SHALL SUBMIT A LIST OF PRINCIPAL MATERIAL ITEMS, GIVING MANUFACTURER'S
<br />NAMES AND CATALOG NUMBERS. APPROVAL OF THE LIST SHALL BE OBTAINED FROM THE OWNER
<br />BEFORE ORDERS ARE PLACED.
<br />GUARANTEE
<br />A. CONTRACTOR SHALL GUARANTEE ALL WORK FOR A PERIOD OF ONE YEAR FROM DATE OF
<br />SUBSTANTIAL COMPLETION. CONTRACTOR SHALL RECTIFY ANY DEFECTS DUE TO FAULTY MATERIALS OR
<br />WORKMANSHIP AND PAY FOR ANY DAMAGE TO OTHER WORK RESULTING THEREFROM WITHIN SAID
<br />PERIOD. THE OWNER WILL GIVE NOTICE OF DEFECTS WITH REASONABLE PROMPTNESS.
<br />IDENTIFICATION OF EQUIPMENT
<br />A. IDENTIFICATION OF EQUIPMENT SHALL BE PROVIDED FOR ALL ELECTRICAL EQUIPMENT INSTALLED BY
<br />THE CONTRACTOR. ENGRAVED LAMINATED PLASTIC NAMEPLATES SHALL BE PROVIDED AND IDENTIFICATION
<br />SHALL CLEARLY DESCRIBE THE EQUIPMENT AND FUNCTION. COORDINATE NAMES ABBREVIATIONS AND
<br />OTHER DESIGNATIONS USED IN ELECTRICAL IDENTIFICATION WORK WITH CORRESPONDING DESIGNATIONS
<br />SHOWN, SPECIFIED OR SCHEDULED. PROVIDE NUMBERS, LETTERS AND WORDING AS INDICATED OR IF NOT
<br />OTHERWISE INDICATED, AS RECOMMENDED BY MANUFACTURER OR AS REQUIRED FOR PROPER
<br />IDENTIFICATION AND MAINTENANCE OF ELECTRICAL SYSTEMS AND EQUIPMENT.
<br />B. INSTALL LABEL TAGS ON ALL WIRE AND CABLE IN JUNCTION BOXES, WIREWAYS AND WIRING GUTTERS
<br />OF PANELS. TAGS SHALL IDENTIFY WIRE OR CABLE CIRCUIT NUMBER AND/OR EQUIPMENT SERVED AS
<br />SHOWN ON DRAWINGS.
<br />C. ALL JUNCTION BOXES TO BE DESIGNATED WITH PERMANENT MARKER INDICATING PANELBOARD AND
<br />CIRCUIT NUMBERS OF BRANCH CIRCUIT WIRING CONTAINED WITHIN.
<br />D. PANELBOARD DIRECTORIES SHALL BE UPDATED/TYPEWRITTEN WITH ACCURATE AND CURRENT
<br />INFORMATION BY THE CONTRACTOR AT THE END OF CONSTRUCTION. DIRECTORIES SHALL REFLECT
<br />EXISTING UNCHANGED AND NEW RECORD CONDITIONS AND INCLUDE CIRCUIT NUMBER, TENANT NAME,
<br />TYPE AND LOCATION OF LOAD.
<br />RACEWAYS AND FITTINGS
<br />A. CONDUITS RUN EXPOSED ON EXTERIOR OF THE BUILDING OR BELOW GRADE SHALL BE RIGID STEEL
<br />CONDUIT. SCH 40 PVC CONDUIT IS ACCEPTABLE,
<br />B. ALL CONDUIT SHALL BE PROPERLY ALIGNED, GROUPED AND SUPPORTED. EXPOSED CONDUIT SHALL
<br />BE INSTALLED AT RIGHT ANGLES TO OR PARALLEL TO THE PRINCIPAL STRUCTURAL MEMBERS. ALL
<br />CONDUIT SHALL BE SUPPORTED AT INTERVALS NOT EXCEEDING 8 FEET. PROVIDE SUPPORT A MINIMUM
<br />OF 18" FROM BENDS AND OUTLET BOXES AND ON INTERVALS NOT TO EXCEED 8'-0". CONDUIT
<br />IS NOT TO SPAN ANY SPACE UNSUPPORTED. ALL CONDUIT SHALL BE SUPPORTED FROM STRUCTURE
<br />AND NOT FROM CEILING SUPPORT SYSTEM.
<br />C. PROVIDE NYLON PULL CORD AND LEAVE IN PLACE IN EACH EMPTY CONDUIT.
<br />D. THIN WALL CONDUIT:
<br />1. THIN WALL CONDUIT SHALL BE UNDERWRITERS' APPROVED GALVANIZED ELECTRICAL METALLIC TUBING.
<br />COUPLINGS AND CONNECTORS FOR CONDUIT SHALL BE STEEL HEX -NUT, ZINC OR CADMIUM PLATED
<br />SET SCREW TYPE FITTINGS.
<br />E. FLEXIBLE METALLIC CONDUIT:
<br />1. FLEXIBLE METALLIC CONDUIT IN DRY LOCATIONS SHALL BE UNDERWRITERS' APPROVED, ZINC COATED,
<br />SINGLE STRIP TYPE. FITTINGS SHALL BE AS MANUFACTURED BY THOMAS AND BETTS "TITE-BITE",
<br />STRAIGHT OR ANGLE CONNECTORS OR APPROVED EQUAL.
<br />2. FLEXIBLE CONDUIT IN DAMP OR WET LOCATIONS SHALL BE UNDERWRITERS' APPROVED FLEXIBLE,
<br />LIQUID -TIGHT METAL CONDUIT. FITTINGS SHALL BE AS MANUFACTURED BY APPLETON, CROUSE-HINDS
<br />OR THOMAS AND BETTS.
<br />F. RIGID STEEL CONDUIT:
<br />1. RIGID STEEL CONDUIT SHALL BE UNDERWRITERS' APPROVED HOT -DIP GALVANIZED. ZINC METALIZED.
<br />OR SHERADIZED. THE THREADED ENDS OF THE CONDUIT SHALL BE ZINC COATED AND SHALL BE
<br />THREADED TYPE. DOUBLE LOCK NUTS SHALL BE USED ON ALL CONDUIT TERMINATIONS EXCEPT
<br />THREADED HUBS.
<br />2. ALL CONDUIT SHALL BE MADE UP TIGHT AND NO RUNNING THREADS WILL BE PERMITTED, "ERICSON"
<br />COUPLINGS BEING USED WHERE NECESSARY. ALL CONDUIT RUNS BELOW GRADE OR UNDER FLOORS ON
<br />GRADE SHALL BE GIVEN A HEAVY COAT OF ASPHALTIC TYPE PAINT
<br />BOXES
<br />A. ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH SUITABLE SCREW FASTENED
<br />COVERS. OPEN KNOCK -OUTS OR HOLES IN BOXES SHALL BE PLUGGED WITH A SUITABLE BLANKING
<br />ELECTRICAL 6MCIFICATIONS
<br />SCALE. NOT TO SCALE
<br />B. OUTLET BOXES FOR EXPOSED WALL MOUNTING, AND OUTDOOR INSTALLATIONS SHALL BE CAST METAL
<br />TYPE "FS" OR "FD" BOXES WITH SUITABLE GALVANIZED SHEET COVERS, OR CAST METAL WEATHERPROOF
<br />OR VAPOR TIGHT COVERS WHEN NOTED ON THE DRAWINGS. WEATHERPROOF RECEPTACLE COVERS SHALL
<br />HAVE SPRING HINGE LIDS AND IN USE COVERS.
<br />CONDUCTORS
<br />A. UNLESS OTHERWISE INDICATED, ALL BRANCH CIRCUIT CONDUCTORS SHALL BE N0. 12 AWG. BRANCH
<br />CIRCUITS RUN OVER 75 FEET IN LENGTH. MEASURING ONE WAY FROM THE FIRST OUTLET OF THE
<br />CIRCUIT TO THE PANEL, SHALL BE NO. 10 AWG FOR THE ENTIRE CIRCUIT
<br />B. SPLICES, TAPS AND ATTACHMENT FITTINGS AND LUGS SHALL BE ELECTRICALLY AND MECHANICALLY
<br />SECURE AND SOLDERLESS FOR CONDUCTORS SIZES NO. 8 AWG AND LARGER. THERE SHALL BE PLENTY
<br />OF SLACK CABLE IN BOXES. OUTLETS AND CABINETS TO INSURE THAT THERE IS NO BINDING AT THE
<br />BUSHINGS. ALL LUGS SHALL BE OF THE CORRECT SIZES FOR THE CONDUCTORS JOINED AND IN NO
<br />CASE SHALL STRANDS BE CUT FROM A CONDUCTOR IN ORDER TO FIT THE CONDUCTOR INTO A LUG.
<br />TAPING OF JOINTS SHALL BE WITH VINYL PLASTIC ELECTRICAL TAPE TO SECURE INSULATION STRENGTH
<br />EQUAL TO THAT OF THE CONDUCTORS JOINED.
<br />C. ALL CONDUCTORS SHALL BE COPPER. CONDUCTOR INSULATION SHALL BE DUAL TYPE THHN/THWN
<br />75 C. (167 F.) FOR DRY, DAMP & WET LOCATIONS. CONDUCTOR INSULATION WITH SINGLE TYPE
<br />MARKING THHN 90 C. (194 F.) MAY BE USED FOR DRY LOCATIONS ONLY. ALL CONDUCTORS SHALL BE
<br />COLOR CODED AS REQUIRED BY NEC AND FURTHER IDENTIFIED AND CODED AS SPECIFIED HEREINAFTER.
<br />COLOR CODING SHALL BE BY MEANS OF COLORED INSULATING MATERIAL, COLORED BRAID OR JACKET
<br />OVER THE INSULATION OR BY MEANS OF SUITABLE COLORED, PERMANENT, NON -AGING, INSULATING
<br />TAPE APPLIED TO CONDUCTORS AT EACH CABINET OR JUNCTION POINT. THE COLOR CODING SHALL BE
<br />ACCOMPLISHED AS THE CONDUCTORS ARE INSTALLED. THE FOLLOWING SYSTEMS OF COLOR CODING
<br />SHALL BE STRICTLY ADHERED TO:
<br />1) ISOLATED GROUND LEADS: GREEN AND YELLOW
<br />2) GROUND LEADS: GREEN
<br />3) GROUNDED NEUTRAL LEADS: WHITE FOR 120/208V, GRAY FOR 277/480V
<br />4) 120/208 VOLT, UNGROUNDED PHASE WIRES: BLACK, RED, BLUE
<br />THE COLOR CODE ASSIGNED TO EACH PHASE WIRE SHALL BE CONSISTENTLY FOLLOWED THROUGHOUT.
<br />NOTE: WHERE EXISTING BASE BUILDING COLOR CODING DIFFERS FROM COLOR COOING ASSIGNED
<br />HERE --IN. CONTRACTOR SHALL USE EXISTING COLOR COOING AS REQUIRED TO MAINTAIN CONSISTENCY.
<br />ADVISE ENGINEER (IN WRITING) OF COLOR CODING TO BE USED.
<br />D. ALL WIRING IN CEILING SPACE OR IN AIR HANDLING PLENUMS NOT IN CONDUIT SHALL BE UL LISTED
<br />AS SUITABLE FOR PLENUM USE.
<br />E. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR AND MAKE ALL
<br />REQUIRED CONNECTIONS TO SERVE MECHANICAL EQUIPMENT FURNISHED.
<br />F. MODIFY EXISTING ELECTRICAL WORK ABOVE THE CEILING SPACE (CONDUIT, WIRING, EQUIPMENT, BOXES,
<br />ETC.) TO COORDINATE WITH NEW LIGHTS AND HVAC WORK.
<br />G. THE CONTRACTOR SHALL REMOVE ALL EXISTING WIRING AND EQUIPMENT MADE UNNECESSARY BY THE
<br />NEW INSTALLATION. ALL MATERIALS REMOVED AND NOT REUSED IN NEW TENANT RETROFIT. SHALL BE
<br />RETURNED TO BUILDING STOCK.
<br />H. REUSE EXISTING JUNCTION BOXES, CONDUITS AND WIRING TO FEED RECEPTACLES AND LIGHTING
<br />FIXTURES WHERE APPLICABLE. REMOVE AND DISPOSE OF ALL UNUSED CONDUIT AND WIRING BACK TO
<br />LAST ACTIVE DEVICE OR PANEL.
<br />I. ALL CONDUITS AND WIRING PENETRATING RATED FLOORS AND WALLS SHALL BE SEALED TO MAINTAIN
<br />FIRE RATING AND INTEGRITY OF SEPARATION.
<br />GROUNDING
<br />A. THE INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS
<br />REQUIRED BY THE NEC AND AS SPECIFIED HEREINAFTER.
<br />B. ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE AT ALL JOINTS AND
<br />AT ALL BOXES, CABINETS, FITTINGS, AND EQUIPMENT. METALLIC RACEWAYS SHALL BE CONNECTED TO A
<br />DIRECT GROUND AT THE POINT OF ELECTRICAL SERVICE ENTRANCE AND SHALL BE ELECTRICALLY
<br />CONTINUOUS THROUGHOUT THE ENTIRE SYSTEM.
<br />C. ALL GROUND CONDUCTORS SHALL BE INSULATED COPPER UNLESS OTHERWISE NOTED.
<br />D. ALL RACEWAYS WITH NO. 10 OR 12 AWG PHASE CONDUCTORS FOR RECEPTACLES, LIGHTING FIXTURES
<br />AND SIMILAR CIRCUITS (NEW BRANCH CIRCUITS) SHALL BE PROVIDED WITH A PARITY SIZED GREEN
<br />EQUIPMENT GROUND CONDUCTOR. GROUND CONDUCTOR SHALL BE INSTALLED IN ENTIRE RACEWAY
<br />SYSTEM INCLUDING WALL SWITCHES AND FLEXIBLE CONDUIT TO LIGHT FIXTURES. EQUIPMENT GROUND
<br />CONDUCTOR SIZES FOR CIRCUITS WITH PHASE CONDUCTORS LARGER THAN NO. 12 AWG ARE INDICATED
<br />ON DRAWINGS. GROUND CONDUCTORS SHALL BE CONNECTED TO GROUND BUSS IN PANELBOARDS.
<br />E. TERMINATE FEEDER AND BRANCH CIRCUIT INSULATED EQUIPMENT GROUNDING CONDUCTORS WITH
<br />GROUNDING LUG, BUS, OR BUSHING. CONDUCTORS LOOPED UNDER SCREW OR BOLT HEADS WILL NOT BE
<br />PERMITTED.
<br />F. INSTALL CLAMP -ON CONNECTORS ON CLEAN METAL CONTACT SURFACES TO ENSURE ELECTRICAL
<br />CONDUCTIVITY AND CIRCUIT INTEGRITY.
<br />G. PROVIDE GROUNDING BUSHING AND A CONTINUOUS COPPER BONDING JUMPER FROM THE BUSHING TO
<br />THE EQUIPMENT GROUND BUS IN ALL FEEDERS. THE BONDING JUMPER SHALL BE THE SAME SIZE AS
<br />THE EQUIPMENT GROUND CONDUCTOR.
<br />CIRCUIT PROTECTIVE DEVICES
<br />A. GENERAL:
<br />1. UNLESS OTHERWISE INDICATED, PROTECTIVE DEVICES SHALL BE MOUNTED WITH TOP OF CABINET OR
<br />ENCLOSURE 6'- 6" ABOVE FINISHED FLOOR, SHALL BE PROPERLY ALIGNED, AND SHALL BE
<br />ADEQUATELY SUPPORTED INDEPENDENTLY OF THE CONNECTING RACEWAYS. ALL STEEL SHAPES, ETC.,
<br />NECESSARY FOR THE SUPPORT OF THE EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE
<br />CONTRACTOR. UNLESS OTHERWISE INDICATED, ALL BRANCH CIRCUIT PROTECTIVE DEVICES ENCLOSURES
<br />SHALL BE NEMA TYPE I, GENERAL PURPOSE TYPE. CIRCUIT PROTECTIVE DEVICES INSTALLED OUTDOORS
<br />OR EXPOSED TO THE WEATHER SHALL HAVE WEATHERPROOF ENCLOSURES, NEMA TYPE 3R OR TYPE 4
<br />2. INSTALL DISCONNECT SWITCHES FOR USE WITH MOTOR -DRIVEN APPLIANCES, AND MOTORS AND
<br />CONTROLLERS WITHIN SIGHT OF CONTROLLER POSITION UNLESS OTHERWISE INDICATED.
<br />3. SUBMIT MANUFACTURER'S DATA (MINIMUM 5 COPIES) ON CIRCUIT AND MOTOR DISCONNECT SWITCHES
<br />AND/OR MOTOR STARTERS. SUBMIT SHOP DRAWINGS IN BOOKLET FORM WITH SEPARATE SHEET FOR
<br />EACH DEVICE. PROVIDE EQUIPMENT IDENTIFICATION AS DESIGNATED ON PLANS FOR EACH SHOP DRAWING
<br />CUT SHEET SUBMITTED.
<br />B. CIRCUIT BREAKERS:
<br />1. CIRCUIT BREAKERS FOR MOUNTING IN EXISTING PANELBOARD SHALL BE MOLDED PLASTIC CASE, AIR
<br />CIRCUIT BREAKER TYPE. BREAKERS SHALL HAVE THERMAL MAGNETIC TRIP UNITS AND MULTI -POLE
<br />BREAKERS SHALL HAVE A COMMON TRIP BAR SO THAT THE TRIPPING OF ONE POLE WILL
<br />AUTOMATICALLY TRIP ALL POLES OF THE BREAKER. BREAKERS SHALL BE TRIP FREE AND TRIP
<br />INDICATING AND SHALL HAVE QUICK -MAKE, QUICK -BREAK CONTACTS.
<br />C. SAFETY SWITCHES:
<br />1. ALL SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE. SWITCH MECHANISM SHALL BE QUICK -MAKE,
<br />QUICK -BREAK. COVER SHALL BE INTERLOCKED WITH MECHANISM TO PREVENT OPENING UNLESS SWITCH
<br />IS IN THE "OFF" POSITION. ALL ENCLOSURES SHALL BE PRIMED AND FINISHED TO RESIST RUSTING AND
<br />CORROSION. SWITCHES SHALL BE ITE, GENERAL ELECTRIC, SQUARE-D, OR CUTLER -HAMMER. (MATCH
<br />BUILDING STANDARD WHERE APPLICABLE)
<br />D. FUSES:
<br />1. ALL FUSES FOR SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. FUSES SHALL BE BUSSMAN
<br />"FUSETRON" OR CHASE SHAWMUT "TRIONIC". THE CONTRACTOR SHALL FURNISH AND INSTALL PROPER
<br />SIZE FUSES WHERE REQUIRED FOR ALL FUSIBLE EQUIPMENT AND SHALL FURNISH TO THE OWNER A
<br />DUPLICATE CARTRIDGE FOR EACH FUSE INSTALLED.
<br />E. MOTOR STARTERS:
<br />1 COMBINATION MAGNETIC. FULL VOLTAGE STARTERS FOR 3 MOTORS SHALL BE THREE POLE
<br />HORSEPOWER RATED. MAGNETICALLY OPERATED SWITCHES, WITH THREE THERMAL OVERLOAD UNITS AND
<br />FOUR EXTRA AUXILIARY CONTACTS. CONTROL VOLTAGE SHALL BE 1 20V. SUPPLIED FROM A CONTROL
<br />POWER TRANSFORMER. A THREE POLE HORSEPOWER RATED. NON -FUSIBLE DISCONNECT SWITCH SHALL
<br />ALSO BE INCLUDED IN THE ENCLOSURE. AN HOA SWITCH SHALL BE MOUNTED IN FRONT COVER.
<br />STARTERS SHALL BE SQUARE-D CLASS 8538.
<br />2. MANUAL MOTOR STARTERS FOR 115V., 1 MOTORS (1) HORSEPOWER AND SMALLER, SHALL BE
<br />SINGLE POLE, HORSEPOWER RATED SWITCHES WITH THERMAL OVERLOAD UNITS AND HEATERS.
<br />STARTERS SHALL BE SQUARE-D CLASS 2510, WITH STAINLESS STEEL COVER PLATES.
<br />3. MAGNETIC FULL VOLTAGE STARTERS FOR 3 MOTORS SHALL BE THREE POLE, HORSEPOWER RATED,
<br />MAGNETICALLY OPERATED WITH THREE THERMAL OVER LOAD UNITS AND FOUR EXTRA AUXILIARY
<br />CONTACTS. CONTROL VOLTAGE SHALL BE 120V. SUPPLIED FROM A CONTROL POWER TRANSFORMER. A
<br />HAND -OFF -AUTOMATIC, HOA SWITCH SHALL BE MOUNTED IN FRONT COVER. STARTERS SHALL BE
<br />SQUARE-D CLASS 8536.
<br />PANELBOARDS:
<br />A. PANELBOARDS SHALL BE CONNECTED DISTRIBUTED PHASE WITH CIRCUIT NUMBERING AS INDICATED
<br />ON THE DRAWINGS. PANELBOARDS SHALL HAVE CIRCUIT DIRECTORY CARDS SHALL BE COMPLETED WITH
<br />A TYPEWRITER BY THE CONTRACTOR TO INDICATE AREAS AND/OR DEVICES SERVED
<br />BY EACH CIRCUIT.
<br />B. CIRCUIT BREAKERS FOR MOUNTING IN PANELBOARDS OR DISTRIBUTION SECTION
<br />OF SWITCHBOARD SHALL BE MOLDED PLASTIC CASE, AIR CIRCUIT BREAKER TYPE. BREAKERS SHALL
<br />HAVE THERMAL -MAGNETIC TRIP UNITS AND MULTI -POLE BREAKERS. BREAKERS SHALL HAVE A
<br />COMMON TRIP BAR. SO THAT THE TRIPPING OF ONE POLE WILL AUTOMATICALLY TRIP ALL POLES OF
<br />THE BREAKER. BREAKERS SHALL BE TRIP FREE AND TRIP -INDICATING AND SHALL HAVE QUICK -MAKE,
<br />QUICK BREAK CONTACTS.
<br />C. PANELBOARDS SHALL BE INSTALLED COMPLETE WITH CONNECTORS AND ASSOCIATED HARDWARE FOR
<br />ALL CIRCUIT BREAKERS AND SPACES LISTED IN THE PANELBOARD SCHEDULE.
<br />D. PANELBOARDS TO BE DEADFRONT TYPE, WITH COPPER BUS BARS, WITH BOLT -ON TYPE BRANCH
<br />CIRCUIT BREAKERS EQUAL TO SQUARE-D TYPE NQOD, NF, OR I -LINE AS APPLICABLE. ALL CIRCUIT
<br />BREAKERS SHALL BE CONCEALED BEHIND A HINGED, LOCKABLE DOOR INSTALLED ON THE FRONT
<br />PANELBOARD COVER.
<br />E. ALL PANELBOARDS TO BE IDENTIFIED WITH ENGRAVED PLASTIC LAMINATE SIGNS. COORDINATE NAMES
<br />USED FOR IDENTIFICATION WITH CORRESPONDING DESIGNATIONS SHOWN, SPECIFIED OR SCHEDULED.
<br />FASTEN WITH SELF TAPPING STAINLESS STEEL SCREWS, OR CONTACT TYPE PERMANENT ADHESIVE
<br />WHERE SCREWS CAN NOT OR SHOULD NOT PENETRATE SUBSTRATE.
<br />F. SUBMIT MANUFACTURER'S DATA ON PANELBOARDS AND ENCLOSURES. SHOP DRAWINGS SHALL
<br />INDICATE ARRANGEMENT OF BUSSES, BRANCH CIRCUITS, ENCLOSURES, DIMENSIONS, ETC. (MINIMUM 5
<br />COPIES) ACCEPTABLE MANUFACTURER'S: GE. SQUARE-D. SIEMENS AND CUTLER -HAMMER. (MATCH
<br />PROTOTYPE STANDARD WHERE APPLICABLE.)
<br />H. INSTALL PANELBOARDS AND ENCLOSURES AS INDICATED, IN ACCORDANCE WITH MANUFACTURER'S
<br />WRITTEN INSTRUCTIONS, APPLICABLE REQUIREMENTS OF NEC STANDARDS AND NECA'S "STANDARDS OF
<br />INSTALLATION', AND IN COMPLIANCE WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT
<br />PRODUCTS FULFILL REQUIREMENTS.
<br />RECEPTACLES
<br />A. ALL RECEPTACLES SHALL BE THE GROUNDING TYPE WITH GROUND CONNECTION MADE THROUGH AN
<br />EXTRA POLE WHICH SHALL BE PERMANENTLY CONNECTED TO GROUND CONDUCTOR.
<br />B. RECEPTACLES FOR 20 AMPERE, 120V SERVICE SHALL BE THREE -WIRE, TWO POLE RECEPTACLES
<br />RATED 20 AMPERES AT 120 VOLTS. ALL NEW RECEPTACLES SHALL BE THAT OF HUBBELL OR
<br />PRE -APPROVED EQUAL.
<br />C. WALLPLATES: PROVIDE WALLPLATES FOR SINGLE AND COMBINATION WIRING DEVICES, OF TYPES,
<br />SIZES, AND WITH GANGING AND CUTOUTS AS INDICATED. SELECT PLATES WHICH MATE AND MATCH
<br />WIRING DEVICES TO WHICH ATTACHED. CONSTRUCT WITH METAL SCREWS FOR SECURING PLATES TO
<br />DEVICES; SCREW HEADS COLORED TO MATCH FINISH OF PLATES, WALLPLATES COLORED TO MATCH
<br />WIRING DEVICES.
<br />D. ELECTRICAL CONTRACTOR SHALL CONFIRM RECEPTACLE CONFIGURATION, VOLTAGE, PHASE AND
<br />AMPERAGE FOR ALL EQUIPMENT FURNISHED AND INSTALLED FOR THIS WORK. ADVISE ENGINEER IF
<br />REQUIRED.
<br />LIGHTING FIXTURES:
<br />A. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE IN ALL RESPECTS ALL NEW AND
<br />RELOCATED LIGHTING FIXTURES SHOWN ON THE PLANS.
<br />B. LIGHT FIXTURES SHALL BE SELECTED BY THE OWNER
<br />C. BALLASTS FOR FLUORESCENT LAMPS SHALL BE HIGH FREQUENCY ELECTRONIC FOR USE WITH OTIC
<br />TYPE (265MA) LAMPS. THE TOTAL HARMONIC DISTORTION ( %-THD) SHALL BE LESS THAN 20
<br />POWER FACTOR SHALL BE .95 OR HIGHER.
<br />ELECTRONIC BALLASTS FOR FLUORESCENT LAMPS SHALL BE OSRAM SYLVANIA, QUICKTRONIC. ALL
<br />BALLASTS SHALL BE INDIVIDUALLY FUSED ON THE LINE SIDE OF THE BALLAST. ALL BALLASTS SHALL
<br />BE ENERGY SAVING, HIGH POWER FACTOR TYPE AND SHALL BEAR ETL/CBM AND UL LABELS.
<br />D. T-8 AND T-5 FLUORESCENT LAMPS SHALL BE 3500K RAPID START. COMPACT FLUORESCENT
<br />LAMPS SHALL BE 3500K.INCANDESCENT LAMPS SHALL BE 120V. GENERAL PURPOSE TYPE. UNLESS
<br />OTHERWISE NOTED ALL LAMPS SHALL BE TCLP COMPLIANT AND MANUFACTURED BY OSRAM SYLVANIA.
<br />U-SHAPED LAMPS SHALL HAVE 6" SPACING BETWEEN ENDS.
<br />E. ALL FIXTURES SHALL BE PROPERLY AND CAREFULLY SUPPORTED AND ALIGNED, AND THE
<br />CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY STEEL SHAPES, ETC., FOR SUPPORT OF
<br />FIXTURES AS REQUIRED AND DETAILED ON THE DRAWINGS. LIGHTING FIXTURES SHALL BE CLEAN AND
<br />NON -OPERATING LAMPS REPLACED WITH NEW LAMPS AT THE TIME OF FINAL INSPECTION.
<br />F. CONTRACTOR SHALL WEAR PROTECTIVE COTTON GLOVES WHEN HANDLING FIXTURES WITH LOW
<br />IRIDESCENT TRIMS LOUVERS. DO NOT HANDLE FIXTURES IN ANY WAY THAT WILL PUT FINGER
<br />PRINTS ON TRIMS OR LOUVERS.
<br />LEGEND
<br />SYMBOL: DESCRIPTION:
<br />LIGHTING
<br />A 2' x 4' FLUORESCENT FIXTURE. UPPER CASE LETTER DENOTES FIXTURE
<br />q TYPE ING LOWER
<br />SCHEDULER FOR FIXTURE SPECIFICATIONS REFER TO
<br />(TYPICAL FOR ALL FIXTURES ON A CIRCUIT).
<br />13a3 1' x 4' FLUORESCENT FIXTURE.
<br />F-0--1 FLUORESCENT STRIP LIGHTING FIXTURE.
<br />0 CEILING LIGHTING FIXTURE, SEE LIGHTING FIXTURE SCHEDULE FOR
<br />SPECIFICATIONS.
<br />Q WALL MOUNTED LIGHT FIXTURE.
<br />EXIT LIGHT SINGLE FACE UNIVERSAL MOUNT AS SPECIFIED IN THE
<br />FIXTURE SCHEDULE. LETTER INDICATES FIXTURE TYPE. BLACK QUADRANT
<br />INDICATES DIRECTION OF FACE, ARROW(S) INDICATE DIRECTION OF
<br />TRAVEL.
<br />EXIT LIGHT DOUBLE FACE UNIVERSAL MOUNT AS SPECIFIED IN THE
<br />FIXTURE SbHEDULE. LETTER INDICATES F XTURE TYPE. BLACK QUADRANT
<br />INDICATES DIRECTION OF FACE, ARROW()S) INDICATE DIRECTION OF
<br />TRAVEL.
<br />MOUNTING
<br />HEIGHT:
<br />CEILING
<br />CEILING
<br />AS SPECIFIED
<br />CEILING
<br />AS SPECIFIED
<br />CEILING OR WALL
<br />CEILING OR WALL
<br />BATTERY OPERATED EMERGENCY LIGHT
<br />FIXTURE.
<br />8'-0" AFF
<br />COMBINATION EXIT SIGN AND BATTERY
<br />FIXTURE.
<br />OPERATED EMERGENCY LIGHT
<br />8'-0" AFF
<br />DW]
<br />BATTERY OPERATED EMERGENCY LIGHT
<br />FIXTURE, CEILING MOUNTED.
<br />CEILING
<br />S
<br />SINGLE POLE SWITCH.
<br />48" AFF
<br />Sb
<br />M �/
<br />SMALL LLETTER DESIGNCAT10%, IINDICAOTESRLIGHDTINGWZONE CONSULT MFR
<br />48" AFF
<br />LC
<br />LIGHTING CONTACTOR.
<br />AS NOTED
<br />POWER
<br />E)=
<br />DUPLEX RECEPTACLE.
<br />18"
<br />AFF
<br />E~G
<br />DUPLEX RECEPTACLE. IG=ISOLATED GROUND.
<br />18"
<br />AFF
<br />DUPLEX RECEPTACLE, MTD 48" AFF OR 6" ABOVE COUNTER BACKSPLASH.
<br />DUPLEX RECEPTACLE, MOUNTED IN CEILING.
<br />CEILING
<br />>
<br />QUADRAPLEX RECEPTACLE (DOUBLE DUPLEX), MOUNTED IN CEILING..
<br />CEILING
<br />QUADRAPLEX (DOUBLE DUPLEX) RECEPTACLE.
<br />18"
<br />AFF
<br />QUADRAPLEX (DOUBLE DUPLEX) RECEPTACLE, MTD. 48" AFF OR 6" ABOVE COUNTER.
<br />DUPLEX GROUND FAULT CIRCUIT INTERRUPTED RECEPTACLE.
<br />18"
<br />AFF
<br />GFI
<br />P FAULT CIRCUIT INTERRUPTED RECEPTACLE -MOUNTED
<br />DUt LEX GROUN
<br />GFI
<br />48 AFF OR 6 ABOVE COUNTER BACKSPLASH.
<br />®
<br />SPECIAL PURPOSE OUTLET, NEMA CONFIGURATION AS SHOWN.
<br />18"
<br />AFF
<br />=11
<br />PANELBOARD.
<br />6"-6"
<br />TO TOP
<br />RECESSED FLUSH -MOUNTED, PANELBOARD. FRONT OF PANEL INDICATED
<br />6"-6"
<br />TO TOP
<br />BY LONGER EDGES OF SYMBOL.
<br />®
<br />DISTRIBUTION PANELBOARD.
<br />6"-6"
<br />TO TOP,
<br />M
<br />METER SOCKET, PROVIDE PER UTILITY COMPANY REQUIREMENTS. 4'-0"
<br />MIN. TO
<br />5'-0" MAX.
<br />Tc
<br />TIME CLOCK
<br />54"
<br />AFF
<br />El
<br />SHUNT TRIP PUSH BUTTON.
<br />54"
<br />AFF
<br />EQUIPMENT SYMBOLS
<br />MOTOR AND CONNECTION. EQUIPMENT TYPE AS NOTED. REFER TO
<br />MMOTOR CONNECTION SCHED. COORDINATE WITH INSTALLED EQUIPMENT.
<br />=P SAFETY DISCONNECT SWITCH-30A, 3 , 250V, NF, HD, NEMA 1, U.N.O.
<br />CEP MOTOR CONTROLLER
<br />CZP COMBINATION MOTOR STARTER & FUSED DISCONNECT SWITCH, U.N.O.
<br />0 SPECIAL CABINET OR EQUIPMENT AS NOTED, RECESED MOUNTED.
<br />$M MANUAL MOTOR $,TARTER WITH OVERLOAD HEATERS FOR 12OV, 1
<br />FRACTIONAL HP. MOTORS.
<br />Ep ENCLOSED CIRCUIT BREAKER IN NEMA 1 ENCLOSURE, U.N.O.
<br />F7, DRY TYPE TRANSFORMER (NUMBER INDICATES KVA RATING).
<br />CONDUIT, RACEWAY AND WIRING
<br />V
<br />C PHASE. HOWEVER A'SEPARATE
<br />TS SERV G CO PUTEIRS (DATA) CIF
<br />SERVICING DATA IS DEFINED AS ANY RECEPTAC NEX TO A' DATA OUTLET OR
<br />SPECIFICALLY SERVING A DATA PIECE OF EQUIPME T. y�HERE NEUTRALS ARE SHARED
<br />MULTI -POLE BREAKERS SHALL BE USED TO DISCONNECT ALL PHASE CONDUCTORS.
<br />ALL HOME
<br />TO SHALL BEM E OF H SH MARMINIMUM.ATES NUMBER OF CIRCUITS.
<br />GROUNDING CONDUCTOR.
<br />T-T WALL MOUNTED GROUND BAR. (24"W X 3"H X 1/4"T U.N.O.).
<br />CONDUIT IN/UNDER SLAB.
<br />CONDUIT CAP.
<br />- DN CONDUIT STUB -DOWN.
<br />- 0 UP CONDUIT STUB -UP.
<br />A DETAIL NUMBER.
<br />Et ELECTRICAL SHEET NUMBER.
<br />GENERAL NOTES
<br />�APPLI WISHE
<br />TO ALL DIVISION 16000 DRAWINGS)
<br />RE THE REQUIREMENTS OF ANOTHER DIVISION SECTION, OR PART OF THE SPECIFICATIONS
<br />XCEED THE REQgUIRE ENTS OF THIS DIVISION T( OSE REQUIREMENTS SHALL GOVERN. ENGINEER
<br />2. ALL LFLOOR E yy �ANLLL A DECISION OPENETRATIONSIDI SHMMALLT MAINTAINGoER
<br />E - VIRO ME TAIL AND FIRE
<br />RATING OF'THE STRUCTURE. ROF PENETATIONS SHAL BCOORDI ATED �jITH THE ROOFING
<br />CONTRACTOR TO MAINTAIN THE ROOFING WARRANTY. PITCH POCKET ROOF PENETRATIONS ARE
<br />3. ALLL MOUNPE TING HEIGHTS SHOyyN SHALL BE TO CENTER LINE OF DEVICE BACKBOX.
<br />4. ALL COMMUNICATION CONDUIT SHALL HAVE $DE SEEPING BENDS.
<br />5. ALL COMMUNICATION CONDUIT SHALL BE IDE TIFIED Y A DISTINCTIVE NUMBER AND LABELED AT
<br />6. ALLL CONNDUIT IN SLABVBEL( SLAB SHALL BE 3/4" MINIMUM.
<br />7. ALL SYMBOLS PRESENTED M Y NOT NECESSARILY BE USED ON THESE DRAWINGS.
<br />ABBREVIATIONS
<br />A AMPS1AMPERAGE
<br />H
<br />ETAL HALIDE
<br />AFF ABOVE FINISHED FLOOR
<br />T.
<br />OUNTING
<br />AHJ AUTHORITY HAVING JURISDICTION
<br />CB
<br />AIN CIRCUIT BREAKER
<br />HU AIR HANDLER UNIT
<br />C./CDT. CONDUIT
<br />0
<br />�S
<br />AlN LUG ONLY
<br />ANUAL OTOR STARTER
<br />C.B. CIRCUIT BREAKER
<br />NEC
<br />NATIONAL ELECTRICAL CODE
<br />CLG CEILING
<br />NF
<br />NON -FUSED
<br />CU CONDENSING UNIT
<br />DISC DISCONNECT
<br />RTU
<br />ROOF -TOP UNIT
<br />EC ELLECTRICAL
<br />S�y
<br />SHUNT
<br />H TRIP
<br />CONTRACTOR
<br />TCH
<br />EF EXHA05T FAN
<br />TTB
<br />T LEPHONE TERMINAL BACKBOARD
<br />EQQPT EQUIPMENT
<br />TVSS
<br />TRANSIENT VOLTAGE SURGE SUPPRESSOR/
<br />EWC ELECTRIC WATER COOLER
<br />LIGHTNING ARRESTOR
<br />ER ELECTRIC WATER HEATER
<br />UNO
<br />WW
<br />UNLESS NOTED OTHERWISE
<br />GC GENERAL CONTRACTOR
<br />WATTS
<br />GFI GROUND FAULT INTERRUPTOR
<br />Wp
<br />WEATHERPROOF (NEMA 3R)
<br />GND.f G. GROUND
<br />V
<br />VOLTS
<br />H.uD. HEAVY DUTY
<br />PHASE
<br />HIPS HIGH PRESSURE SODIUM
<br />Q
<br />DRAWING NOTE
<br />HIP
<br />HRS HORS�E�PO�WIER RATED SWITCH
<br />IMC INTERMEDIATE METAL CONDUIT
<br />loc
<br />IWH INSTANTANEER
<br />OUS WATER HEATER
<br />KW KILOWATTS
<br />D ELECTRICAL LEGEND
<br />SCALE- NOT TO SCALE
<br />REVISIONS
<br />BY
<br />' 00
<br />co
<br />Y C
<br />I ¢off.
<br />�roti S
<br />U
<br />E ro y
<br />C\J c
<br />/ p U
<br />� ti>
<br />¢00
<br />3
<br />4 N
<br />ti
<br />N
<br />j tt
<br />A
<br />„ .
<br />s. pp
<br />,.ir�
<br />t d,
<br />.2 Of
<br />C3 n
<br />a
<br />u ❑
<br />o Z►
<br />ir ^+
<br />o - !d
<br />4
<br />L3
<br />w
<br />L cy
<br />0
<br />N
<br />C m t
<br />Ln
<br />v M
<br />M
<br />j �
<br />v Q 0 J 7
<br />m m U-U
<br />V) v y
<br />0 >. d
<br />c0
<br />v Z os
<br />0 Z coo m
<br />C O N
<br />m V)
<br />Date: 05. 17. 21
<br />Scale: AS NOTED
<br />Project Mgr: DG
<br />Drawn: WR
<br />Job: 21-018
<br />Sheet
<br />El
<br />
|