ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />PEF <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />P4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PP <br />PUSH BUTTON SWITCH (OPTIONAL) <br />�B <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />®2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />]M <br />ELECTRIC METER <br />owl <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />C� J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />HANSON <br />I I <br />BOX <br />I I <br />--� — I I u W/C <br />LAV i\ <br />-1 1 3" SHOWER <br />ti TUB/ <br />W/C SHOWER <br />WA& <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I <br />I OPT. <br />LAV <br />LAV <br />I <br />I <br />„ end F FAR <br />STUDOR <br />VENTT LTJ DBL SINK <br />W/ DISP. <br />W/C ,A" <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />Unit -C- (1624) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1625 S.F. <br />4875 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10875 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33935 <br />list 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9574 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31878 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />P \- <br />NEMA 1 <br />200 AMP <br />TER MA N <br />1�0-200 AIV(P I IT, -Serial Cable <br />NEM <br />3R <br />Power Co. Feed --, I J I_ ir— #4 Solid COPPER Ground <br />3" <br />Intersystem Bonding <br />Termination Per <br />NEC 08, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />C.O. <br />DB & GFI TO <br />BE ALIGNED <br />VERTICALLY <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. / l�/T <br />FAN/LIGHT i `� �' WP <br />GFI <br />I� <br />1 <br />DINING <br />KITCHEN ) <br />FI O <br />GFI <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM <br />/,,>ROUGH -IN\ <br />FOR OPT. <br />FAN/LIGHT' <br />I <br />1 / <br />0w <br />0 <br />\�1�1UJ <br />?gym <br />W <br />DISCONNECT <br />WK DEDICATED <br />0*4 <br />"M • • <br />►� 14 <br />..• - • <br />.WA <br />y RAHOOD PSPECS <br />ER <br />I <br />I <br />I <br />I <br />I <br />I <br />rCzE1_� <br />C.M <br />1 UPSTAIRS � <br />FI <br />44" <br />LW-H <br />A.F.F. <br />' <br />` 0 <br />I <br />\ <br />1 <br />I <br />I <br />I GARAGE <br />I <br />\ <br />GARAGE <br />LIGHT AS <br />PER SPECS <br />GARAGE <br />DOOR <br />GFI <br />r- — — <br />I <br />— — <br />— — — — — — — — —-- <br />I <br />I <br />I <br />J <br />I <br />I <br />10 Z <br />I <br />I�z Q <br />IQ <br />I <br />I <br />I0 Q <br />I <br />IJ U <br />I <br />L U <br />I <br />IW LU <br />I <br />- <br />5 w <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />1ST ELECTRICAL - UNIT-C 1624 <br />SCALE: Ya"=V-0" <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />2ND ELECTRICAL - UNIT-C 1624 <br />SCALE: Y4'=V-0" <br />N <br />U <br />o L <br />Q <br />C1� <br />= n v N <br />v_o cv c� <br />Q N Y <br />[r, V • � fd <br />a� �o <br />N <br />co 0 <br />Ij <br />d o <br />N <br />N <br />0 <br />co <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />f- v <br />v <br />T <br />' A(� <br />,- 0 <br />O N 0) 0 <br />o c m r <br />�LO�CC) N <br />y <br />�r-- r� 2 <br />N O 2 LL <br />` I11 <br />rp W L.L d <br />J <br />a <br />Z <br />m e U) <br />Y°O 3 <br />W <br />7 �_Y <br />�`\' O Y <br />- <br />W <br />Z <br />LL� <br />m w <br />" <br />� MZ a <br />N J <br />Z <br />O U J O <br />.a., <br />v: W <br />❑ ❑ <br />V M � <br />Z N 0 <br />o g <br />z N <br />z o � <br />J <br />N <br />Q13 <br />N <br />z <br />o <br />4 <br />LL <br />° <br />U <br />0 <br />- N <br />C <br />wra <br />t!1 <br />U) <br />w <br />® � <br />Y <br />U o H <br />Cn <br />Y <br />Q 2 <br />• <br />—Q <br />t� <br />� <br />w <br />M <br />co <br />z ¢ <br />z <br />E <br />ao <br />aR <br />d O <br />z® <br />z <br /><- <br />O1 <br />oa <br />0 OU <br />Za¢ <br />o <br />0� <br />wZ <br />N � <br />< <br />p <br />0 <br />aw <br />ro <br />Cn <br /><z <br />< <br />mo <br />f <br />C <br />� <br />�m <br />o <br />Z <br />Z <br />Q) <br />J <br />¢ ° <br /><<w <br />z <br />to <br />N <br />o§ <br />g° <br />C' <br />wLL <br />a <br />w <br />W <br />v <br /><o <br />= <br />CDaQ <br />Jw <br />;o <br />a <br />zla <br />o � <br />>� <br />iv <br />rn <br />N <br />� <br />Ccc <br />cC> <br />c-6 <br />T <br />t\ <br />_ <br />CD <br />T <br />\V <br />O <br />Itn <br />o <br />00 <br />m <br />CD <br />00 <br />E <br />O <br />. - <br />N <br />04 <br />LO <br />CDN <br />CD <br />QLO <br />(� <br />00 <br />Op <br />00 <br />OO <br />T <br />E <br />'E <br />o <br />z <br />E O <br />Li <br />Ch <br />c <br />a <br />U <br />Q p <br />c <br />JOB <br />NO: 22-09500-09493 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />15 <br />