ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />PqF <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />6. <br />P4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUSTFAN <br />;O <br />P.®D <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />[BD <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />F a <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />© 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />AM <br />ELECTRIC METER <br />owl <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />C`!'2 <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G r J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />r��'/ j I <br />I I <br />I I <br />I I <br />LAV 1\ <br />� I <br />L TUB/ <br />W/C SHOWER <br />LAV <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I <br />I OPT. <br />LAV <br />I T� <br />SON I <br />I <br />v W/C <br />SHOWER <br />` '\na F <br />STUDOR F� R. <br />VTI DBL SINK <br />EN <br />lj W/ DISP. <br />W/C <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />Unit -B- (1516) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1505 S.F. <br />4515 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10515 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33575 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9430 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31734 <br />LOAD WATTS --- 240 VOLTS <br />I AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />NEMA 1 <br />200 AMP <br />1TER MA N <br />10 200 A P Serial Cable <br />NEMA <br />3R <br />Power Co. Feed 11 I -----T— #4 Solid COPPER Ground <br />II <br />Intersystem Bonding <br />Termination Per <br />NEC 08, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />C.O. <br />DISCONNECT <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE <br />RANGE HOOD PER <br />SPECS <br />OUTDOOR LIVING <br />�%I �> INSTALL LIGHT <br />�Jlfi� ROUGH -IN <br />/ - FOR OPT. <br />GFI i AN/LIGHT <br />AT% <br />GFI <br />I <br />DINING <br />I <br />I <br />I <br />I <br />I <br />I <br />L_SEI� <br />N <br />I UPSTAIRS F <br />( KITCHEN <br />a I GF � \ <br />L— <br />GFI <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />/ <br />/ GREAT ROOM <br />ROUGH -IN<,\ /,ol> <br />FOR OPT. f <br />' FAN/LIGHT J ``'> <br />1 <br />1 I <br />I <br />W.H. / <br />O / ' <br />A. <br />I \ <br />GARAGE1 <br />I <br />GARAGE <br />LIGHT AS / <br />PER SPECS <br />GARAGE <br />DOOR <br />GFI <br />--------------- <br />I <br />I <br />I <br />Ij <br />I <br />I <br />ZIW <br />�IQ <br />I <br />QIIL <br />I <br />_j IU <br />>_ <br />I <br />I <br />I� <br />Uf <br />Uj <br />> Iwl <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />DB <br />-0WP ly <br />ENT <br />@GFI LIGHT <br />PER SPE <br />I <br />I <br />1 <br />2 <br />H <br />DB & GFI TO <br />BE ALIGNED <br />VERTICALLY <br />1ST ELECTRICAL - UNIT-B 1516 <br />SCALE: y4'=V-0" <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />2ND ELECTRICAL - UNIT-B 1516 <br />SCALE: y4'=1'-0" <br />N <br />0 <br />N <br />00 <br />v <br />o <br />� W <br />✓ O <br />tea cUN <br />m X <br />N L <br />G <br />d <br />y C <br />m d d a <br />U d <br />7 O C <br />f T <br />'ate <br />�E <br />ca O <br />a <br />CV <br />N <br />0 <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within <br />these <br />drawings comply with the 2020 <br />Florida Building Code <br />- <br />Residential 7th Edition. Engineer's signature and seal <br />is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />r. <br />Q <br />E <br />o C', � o <br />C N_ <br />0 <br />N <br />13 <br />&mom 3 # u <br />J LL LL a <br />w <br />Z <br />-V <br />a co <br />1_2 <br />W <br />W <br />_ <br />LL <br />YYo o <br />0 <br />(n m <br />N <br />W <br />< <br />O U ¢ L) <br />❑U a <br />Z N cQD <br />o <br />Z O Q <br />Q� <br />Wv) <br />v <br />z <br />o <br />i:, <br />a <br />4_j cn <br />0 <br />V) <br />/�''�' <br />o <br />c N <br />y <br />J <br />� V <br />r- <br />U <br />W A <br />E <br />gl.._... <br />U i; °0 <br />c CD Y <br />Q <br />• <br />�O <br />N <br />I� <br />O <br />M <br />CO <br />< <br />o ¢ <br />w <br />Z <br />G L <br />Erucc <br />g p <br />¢U <br />N�zw <br />°o <br />ZF—Q <br />O E <br />10. <br />¢M¢o� <br />ao <br />0 <br />�oZa <br />i <br /><� <br />mo <br />Z <br />CU <br />J <br />Nm <br />Zr <br />I <br />N <br />a <br />�Z <br />W <br />a`ni 3 <br />a <br />U <br />op <br />3° <br />a <br />mZ <br />a° <br />3 <br />Mj <br />o <br />O <br />�J <br />a <br />0la <br />ou 3 <br />c <br />•° T <br />N <br />>� <br />T <br />ci <br />� <br />c� <br />C <br />T <br /><6 <br />T <br />V J <br />T <br />I� <br />T <br />_ <br />CD <br />CDCN <br />+�� <br />I.L <br />Cfl <br />o <br />C m <br />OO <br />00 <br />T <br />E <br />OCD <br />� <br />CD <br />CN <br />Gi <br />L <br />Q C6 <br />o <br />LO <br />09 <br />CD <br />Eo <br />3 Q <br />z <br />z <br />E <br />U J <br />Q <br />J <br />JOB <br />NO: 22-09500-09493 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />14 <br />