Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />�IQW,P. WEATHERPROOF DUPLEX OUTLET <br />G.F.I. GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ WALL SWITCH <br />$3 THREE-WAY SWITCH <br />?4 FOUR-WAY SWITCH <br />$R RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED LIGHT FIXTURE <br />P.C. LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O EXHAUST FAN <br />;Q EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH CHIMES (OPTIONAL) <br />PB PUSH BUTTON SWITCH (OPTIONAL) <br />�D PUSH BUTTON SWITCH - DOOR BELL <br />SD SMOKE DETECTOR <br />CM SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB TELEPHONE/USB (OPTIONAL) <br />© TELEVISION (OPTIONAL) <br />2 (2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />0 THERMOSTAT <br />ELECTRIC METER <br />ELECTRIC PANEL <br />_i DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />L J <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />Ci r J OPT. CEILING FAN <br />W (1) PHONE LINE, (1) DATA PORT <br />3" VTR ELECTRICAL SPECIFICATION NOTES: <br />3" VTR AIL <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />I OF FIXTURE TO BE USED. LIGHT FIXTURES <br />I I <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I <br />I OPT. <br />I I <br />LAV LAV <br />HANSON I <br />BOX I <br />3„ <br />;\ I W/C <br />LAV <br />T SHOWER <br />TUB/ DISCONNECT <br />W/C SHOWER <br />O — <br />------------------------- <br />2� OUTDOOR LIVING <br />3" end F <br />LVE <br />R C.O. '\ �` <br />W/ p SINK INSTALL LIGHT ��yi> <br />ROUGH -IN / Jr <br />2„ FOR OPT. <br />LAV 3" FAN/LIGHT �' WP <br />��2,. j H I GFI <br />,70 <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />Unit -A- (1532) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1533 S.F. <br />4599 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10599 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />SUBTOTAL: 23060 <br />TOTAL: 33659 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9464 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31768 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service 200A <br />Same As Underground Indoor Panel <br />150 Or 200 Amp Service Center <br />NEMA 1 <br />200 AMP <br />TER MA N <br />1-0 <br />A P Serial Cable <br />NEMA <br />3R <br />Power Co. Feed #4 Solid COPPER Ground <br />Intersystem Bonding <br />Termination Per <br />NEC 08, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />typical 150-200 Amp Electrical Riser Diagram <br />OTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />HE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />\db GFI <br />I DEDICATED <br />IGFI RECEPTACLE FOR <br />I MICROWAVE b OWNER'S <br />D PER <br />DINING ` RANGE HOOPECS BEDROOM <br />/,>ROUGH -IN <br />KITCHEN) � - � FAN/LOIGHT <br />F --- I I \ I <br />JF I O r1 J <br />- GFI-6 --- GFI ------ <br />SWITCH FOR-----------t <br />DISPOSAL IN CAB C.M - O. BATH I <br />UNDER SINK <br />\ W/PC I <br />\71 L LLJWIC <br />GREAT ROOM �� 1 <br />/,^ROUGH -IN\ _ �' \ I 1- <br />FOR OPT. �H \ OWNSTAI <br /><� fi'-->FAN/LIGHT 1 = W P. <br />I / C.M. <br />UPSTAIRS I I T <br />II no <br />FOYER <,- <br />' O <br />I I <br />I <br />I DB <br />ENtRY I WPo- <br />LIGHT AS b GFI <br />DB & GFI TO <br />PER SPECS <br />----------- <br />BE ALIGNED <br />/ <br />VERTICALLY <br />GFI <br />@ 44" <br />` \ <br />��WH. <br />A.F.F. <br />' <br />\ O <br />1 <br />I <br />I <br />I GARAG E <br />I <br />GARAGE <br />LIGHT AS <br />NPER SPECS <br />GARAGE <br />DOOR <br />GFI <br />--------------- <br />I <br />I J <br />I <br />I <br />Ip Z <br />I <br />100Q <br />I <br />I� U <br />I <br />ILL <br />IX W <br />I <br />I> W <br />I <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />1ST ELECTRICAL - UNIT -A 1532 <br />SCALE:1'4'=V-0" <br />BATH 2 <br />­"��17 <br />€ 1 `i <br />V,RTUAi- REV,EW ASSIST <br />AE7F.°at, Inc. <br />Plaw� , ); ,feted and approved <br />for corr.pkr ,ice tr,`I`;1 1C A(.�,� r I 0� yth <br />Edition by Debh_l- <br />I�I <br />LOFT <br />C.M \ <br />S.D. <br />/ I <br />^ROUGH -IN <br />FOR OPT. <br />FAN/LIGHT <br />\\BEDROOM 2 <br />LE <br />O O <br />2ND ELECTRICAL -UNIT-A 1532 <br />SCALE: Y"=1'-0" <br />CV <br />CV <br />0 <br />CV <br />r_ <br />0 <br />0 <br />To the best of the Engineers knowledge, information and belief, <br />the structural <br />plans and specifications contained <br />within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential <br />7th Edition. Engineer's signature and seal is only for <br />the structural <br />engineering portions of the drawing pages bearing <br />Engineers <br />signature and seal. <br />H <br />ti <br />W <br />g <br />0 E <br />M <br />N <br />LL <br />(� <br />N <br />N o cr <br />(0w � <br />0 <br />N <br />? n 00 <br />a <br />o # <br />H <br />Q <br />13 <br />U)1-- <br />vMv 3 <br />JI.L' <br />_ <br />< u- <br />fl <br />w <br />Z <br />Uc °' <br />'IT <br />o O co <br />� <br />Lao <br />� 0 <br />0 <br />0 2 1— <br />00 <br />W <br />�. <br />ILW <br />IL <br />- <br />cN N Z <br />m J <br />Q <br />Z <br />N O U <br />v S 0 <br />W <br />❑❑❑ <br />EMISSION <br />z N M <br />0 0 <br />z N <br />z o � <br />J <br />QWAIMEE& <br />M <br />z1CM <br />C- <br />CU <br />�N <br />U <br />OLjj <br />V) <br />v <br />g <br />Ly N <br />ws <br />f6 <br />'— u) <br />all <br />U g <br />W J <br />NNN <br />U O <br />c u' w <br />o <br />® Q <br />N m <br />� <br />o <br />co <br />w <br />CJ <br />M <br />Z <br />ca <br />cL <br />E <br />=o <br />z <br />u <br />co <br />X0 <br />o< <br />uo <br />O E <br />O 03 <br />a o <br />< <br />a z <br />i <br />o <br />az <br />J <br />m� <br />rp <br />Y <br />o <br />o l <br />v <br />cL 3 <br />oa <br />w <br />Zz <br />go <br />a <br />�w <br />W <br />U <br />oz <br />J <br />=3 <br />o� <br />o <br />w <br />�o <br />zlaF <br />< <br />° 3 <br />0 <br />o� <br />.L <br />>� <br />m <br />Z*- <br />C7 <br />CD <br />o <br />N <br />"'> <br />O <br />r <br />c <br />GV <br />r <br />C m <br />o <br />00 <br />E N <br />N <br />Cfl <br />� <br />CN <br />o <br />a--+EE <br />N <br />Q <br />CO <br />r <br />00LO <br />O <br />o <br />z <br />cu <br />Z <br />E O <br />N <br />co <br />C <br />a <br />E <br />U _j <br />m <br />Q p <br />JOB <br />NO: 22-03339-03346 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />13 <br />