PORCH <br />1 � <br />ELECTRICAL PLAN (ELEVATIONS A & B <br />1 /411 _ 1 1_011 <br />DICONNECT <br />ELECTRICAL NOTES: <br />1. GFCI'S ARE TO BE INSTALLED IN THE FOLLOWING <br />LOCATIONS AS SPECIFIED PER NFPA 70 (NEC) 2017 <br />A) BATHROOMS <br />B) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT <br />HAVE A FLOOR LOCATED AT OR BELOW GRADE LEVEL <br />NOT INTENDED AS HABITABLE ROOMS AND LIMITED TO <br />STORAGE AREAS, WORK AREAS, AND AREAS OF <br />SIMILAR USE. <br />C) CRAWL SPACES AT OR BELOW GRADE. <br />D) KITCHENS - WHERE THE RECEPTACLES ARE <br />INSTALLED TO SERVE THE COUNTERTOP SURFACES. <br />E) LAUNDRY, UTILITY, AND WET BAR SINKS - WHERE <br />THE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OF <br />THE OUTSIDE EDGE OF THE SINK. <br />2. ARCH FAULT OUTLETS ARE REQUIRED PER NFPA 70 <br />(NEC) 2017, INCLUDING ARTICLES 210 AND 400. <br />3. ANY CONFLICTS BETWEEN LOCATION OF <br />MECHANICAL FIXTURES ON PLANS AND THE ABILITY TO <br />LOCATE THEM IN THE FIELD MUST BE REPORTED TO THE <br />ARCHITECT PRIOR TO INSTALLATION. <br />4. RECEPTACLE OUTLETS IN GARAGE MUST BE <br />SERVED BY SEPARATE BRANCH CIRCUIT THAT DOES NOT <br />SUPPLY OTHER OUTLETS. <br />5. CM MUST BE AT LEAST T FROM BATH DOOR AND AT <br />LEAST 6' FROM KITCHEN RANGE/OVEN. <br />NOTES: <br />UNLESS OTHERWISE NOTED <br />1. ELECTRICAL OUTLET HEIGHTS AS MEASURED FROM FINISHED <br />FLOOR TO CENTERED LINE OF THE BOX TO BE: 12" AFF <br />(GENERAL) <br />KITCHEN <br />44" AFF <br />BATHROOM <br />39" AFF <br />LAUNDRY ROOM <br />36" AFF <br />EXTERIOR WATERPROOF <br />12" AFF <br />GARAGE GENERAL PURPOSE <br />42" AFF <br />RANGE <br />2" AFF <br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE <br />POSSIBLE. <br />3. ELECTRICAL SWITCHES TO BE AT 42" CENTERLINE ABOVE <br />FINISHED FLOOR <br />4. ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY. <br />ALL WORK SHALL. BE DONE IN STRICT ACCORDANCE WITH THE <br />NATIONAL ELECTRIC CODE, LATEST EDITION, BY A LICENSED <br />ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE FOR <br />THE INSTALLATION & SIZING OF ALL ELECTRICAL, WIRING & <br />ACCESSORIES. <br />5. SMOKE DETECTORS SHALL BE INSTALLED AS DIRECTED BY <br />THE 2016 NFPA 72 NATIONAL FIRE ALARM CODE. <br />6. ALL ELECTRICAL IN THE LIVING ROOMS, DINING ROOMS, <br />SUNROOMS, FAMILY ROOMS, DENS, LIBRARIES, SLEEPING ROOMS, <br />PARLORS AND SIMILAR ROOMS OR AREAS SHALL BE ON AN A.F.C.I. <br />PROTECT CIRCUIT PER NFPA 70 (NEC) 2017. <br />7. IN ALL AREA SPECIFIED IN NFPA 70 (NEC) 2017 210.52, ALL 125 <br />VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED <br />TAMPER -RESISTANT RECEPTACLES. <br />200A INDOOR PANEL <br />CENTER <br />01 #15 copper to lights & outlets <br />NEMA 1 <br />00 #12 copper to 20 amp ckts <br />200 AMP <br />00 #10-2 copper to WH <br />00 #10-3 copper to Dryer <br />METER <br />2/0 or 4/0 SER Alu <br />MAIN <br />0 <br />200 amp <br />150 amp <br />Disconnect <br />POWER CO. FEED <br />4 Bare Cu Ground <br />Footer STEEL <br />Groundrod tied to footer steel <br />OR <br />4 Bare attached to footer steel <br />TYPICAL 150-200 AMP ELECTRICAL <br />RISER DIAGRAM <br />NTS <br />ELECTRICAL DETAIL: <br />INTERCOM <br />SPEAKER <br />ALIGNED W/ <br />EDGE OF <br />SWITCy <br />SWITCH ° <br />4 1/2" <br />DOORJAMB DUPLEX <br />OUTLET c� <br />TRIM o <br />0 <br />BASE <br />NOTE: <br />ALL DIMENSIONS ARE FROM ROUGH FRAMING <br />SMOKE DETECTOR LOCATION: <br />WALL <br />oz <br />Ql�'___ <br />SMOKE DETECTOR <br />1'-0" <br />MIN. <br />ELECTRICAL LEGEND: <br />NOTE: ALL HEIGHTS ABOVE FINISH FLOOR <br />Er 110V DUPLEX OUTLET AT 12" <br />110V DUPLEX OUTLET AT 39" NOTE: ALL <br />RECEPTACLES <br />110V DUPLEX OUTLET AT 43" ABOVE <br />COUNTERS <br />110V DUPLEX OUTLET AT 45" SHALL BE <br />SPLIT 110V DUPLEX OUTLET MOUNTED <br />AT 12" - TOP PLUG IS HOT HORIZONTAL <br />110V QUAD OUTLET AT 12" <br />WEATHERPROOF GFCI OUTLET AT 12" <br />220V OUTLET AT 30" <br />110V DUPLEX FLOOR OUTLET <br />OUTLET - VERIFY W/MANUF. SPECS <br />4FOR LOCATION & TYPE <br />TELEPHONE OUTLET AT 12" OR AS NOTED <br />TELEVISION OUTLET AT 12" - WIRE FOR <br />CABLE & SATELLITE <br /><� STRUCTURED WIRE OUTLET <br />�- SWITCH AT 36" <br />3 WAY SWITCH AT 36" <br />4 WAY SWITCH AT 36" <br />-0 PUSH BUTTON FOR GARAGE DOOR OPENER <br />---o DIMMER SWITCH AT 36" <br />--0 PUSH-BUTTON DOORBELL <br /><} CLG MNT LT FIXTURE <br />} CLG MNT PREWIRE - FIXTURE BY OWNER <br />-�- SURFACE MNT FIXTURE <br />-C- WALL MNT FIXTURE <br />NOTE: <br />C TUB/SHOWERND OPALEX - ALTERNATE <br />CANS MAY BE <br />4� " USED IF 50W PAR30 NFL 6WHITE BAFFLE <br />C APPROVED BY <br />0 50W MR16 4" LOW VOLTAGE OWNER <br />C 50W PAR20 NFL 4" MINI ROUND RECESS <br />�� 50W PAR20 NFL 6" RD REGRESSED BAFFLE EYEBALL <br />{} CLG FAN PREWIRE AND SWITCH <br />Cos COMBINATION CARBON MONOIXED DETECTOR/ <br />SMOKE DETECTOR <br />O SMOKE DETECTOR <br />=U-18= UNDER CABINET 18" <br />=S-18= SINGLE 18" FLUOR STRIP <br />=U-24= UNDER CABINET 24" <br />=S-24= SINGLE 24" FLUOR STRIP <br />=D-24= DOUBLE 24" FLUOR STRIP <br />U-36 = UNDER CABINET 36" <br />S-36 = SINGLE 36" FLUOR STRIP <br />D-36 = DOUBLE 36" FLUOR STRIP <br />S-48 SINGLE 48" FLUOR STRIP <br />D-48 DOUBLE 48" FLUOR STRIP <br />24 24"CLG MNT WRAPPED FLUOR LIGHT <br />48 48"CLG MNT WRAPPED FLUOR LIGHT <br />5;:24:R 24" VANITY LIGHTING <br />57,,-F 36 :7,uP 36" VANITY LIGHTING <br />48 48" VANITY LIGHTING <br />EXHAUST FAN/LIGHT <br />(+i EXHAUST FAN <br />DOUBLE FLOOD LIGHT W/ COVERS AND <br />150W PAR 38 FL <br />® INTERCOM SPEAKER AT 5'-0" ABV FINISH FLOOR <br />CEILING MNT SPEAKER <br />M CHIMES (DELETE W/ INTERCOM) <br />= MASTER STATION <br />_0&J ELEC PANEL <br />FYI VACUM OUTLET AT 12" <br />CEILING RETURN AIR <br />A/C REGISTER <br />TT THERMOSTAT <br />119 SECURITY PAD <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR LOCATION PURPOSES. <br />i <br />V) N LO <br />'0 q U <br />N C 0 <br />4 <br />W E L t O <br />�Do 2g <br />�= °ter �Q <br />LU QN <br />^` <br />W L Oo ECO <br />CL (D <br />(D <br />❑Lj w0Uj H <br />~W <br />E-Q � _j wgezw z <br />02 <Qco _jo <br />Q Q <br />V <br />U_=¢w0o° <br />DOLLaz�O0F OQZ <br />Q ¢ <br />�I-- <br />— <br />C3w�Oozo=oomzz <br />nW7wwn x¢ <br />U <br />_ <br />CL <br />WOZ <br />ZOW <br />Ow ❑ <br />~OY¢Q¢ <br />o ❑ 0Q<x <br />ca. <br />00 <br />LLa o �w <br />O <br />z N <br />O W <br />_I'_ <br />L-0 ti <br />�I-MO <br />Q M Lo <br />wILL <br />ti <br />z <br />< W Lq <br />�IYM <br />00 <br />Z V <br />z <br />W <br />W <br />O <br />J O <br />Wj <br />'IT <br />� <br />Virtual <br />evi <br />wl <br />si'st, <br />Idc <br />", <br />�A,23 <br />Plans <br />Review <br />om <br />le'te <br />an <br />a'pf <br />ed <br />for compliance <br />w <br />th 0 <br />e 20 <br />20 F <br />It 7 <br />h Edition <br />by <br />Debra <br />nn <br />Kla <br />1 <br />r,P <br />240 <br />I <br />M <br />N <br />ON <br />N <br />co <br />LO <br />O <br />O <br />N <br />O <br />O <br />O <br />O <br />C) <br />o <br />O <br />'t <br />N <br />N <br />o <br />' <br />M <br />N <br />o <br />Z <br />O <br />w <br />o <br />N <br />LO <br />LO <br />% <br />o <br />O <br />N <br />;n <br />0 <br />4 <br />o <br />LO <br />I <br />I <br />' <br />CT <br />�^ <br />�- <br />zZ <br />vJ <br />Qz <br />w <br />O <br />W <br />0O00O <br />V / <br />-�+ <br />O <br />U <br />() <br />Lo <br />O <br />Z)zj <br />ow- <br />O I— <br />z <br />a�a <br />�— <br />< <br />= <br />wz¢ <br />~~tw <br />F- <br />T� <br />zOcn <br />W <br /><�� <br />Q <br />O <br />ZWO <br />® <br />V <br />az� <br />z <br />�z <br />z <br />�� <br />pU <br />oll <br />W <br />� <br />z <br />z <br />z <br />z <br />w <br />W <br />J <br />O <br />N <br />O <br />LAST PLOT DATE <br />N <br />June 19, 2023 <br />z <br />4-1 <br />0 <br />J <br />ELECTRICAL PLAN <br />