ELECTRICAL NOTES: <br />1. GFCI'S ARE TO BE INSTALLED IN THE FOLLOWING <br />LOCATIONS AS SPECIFIED PER NFPA 70 (NEC) 2017 <br />A) BATHROOMS <br />B) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT <br />HAVE A FLOOR LOCATED AT OR BELOW GRADE LEVEL <br />NOT INTENDED AS HABITABLE ROOMS AND LIMITED TO <br />STORAGE AREAS, WORK AREAS, AND AREAS OF <br />SIMILAR USE. <br />C) CRAWL SPACES AT OR BELOW GRADE. <br />D) KITCHENS - WHERE THE RECEPTACLES ARE <br />INSTALLED TO SERVE THE COUNTERTOP SURFACES. <br />E) LAUNDRY, UTILITY, AND WET BAR SINKS - WHERE <br />THE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OF <br />THE OUTSIDE EDGE OF THE SINK. <br />2. ARCH FAULT OUTLETS ARE REQUIRED PER NFPA 70 <br />(NEC) 2017, INCLUDING ARTICLES 210 AND 400. <br />3. ANY CONFLICTS BETWEEN LOCATION OF <br />MECHANICAL FIXTURES ON PLANS AND THE ABILITY TO <br />LOCATE THEM IN THE FIELD MUST BE REPORTED TO THE <br />ARCHITECT PRIOR TO INSTALLATION. <br />4. RECEPTACLE OUTLETS IN GARAGE MUST BE <br />SERVED BY SEPARATE BRANCH CIRCUIT THAT DOES NOT <br />SUPPLY OTHER OUTLETS. <br />5. CM MUST BE AT LEAST T FROM BATH DOOR AND AT <br />LEAST 6' FROM KITCHEN RANGE/OVEN. <br />NOTES: <br />UNLESS OTHERWISE NOTED <br />1. ELECTRICAL OUTLET HEIGHTS AS MEASURED FROM FINISHED <br />FLOOR TO CENTERED LINE OF THE BOX TO BE: 12" AFF <br />(GENERAL) <br />KITCHEN <br />44" AFF <br />BATHROOM <br />39" AFF <br />LAUNDRY ROOM <br />36" AFF <br />EXTERIOR WATERPROOF <br />12" AFF <br />GARAGE GENERAL PURPOSE <br />42" AFF <br />RANGE <br />2" AFF <br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE <br />POSSIBLE. <br />3. ELECTRICAL SWITCHES TO BE AT 42" CENTERLINE ABOVE <br />FINISHED FLOOR <br />4. ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY. <br />ALL WORK SHALL. BE DONE IN STRICT ACCORDANCE WITH THE <br />NATIONAL ELECTRIC CODE, LATEST EDITION, BY A LICENSED <br />ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE FOR <br />THE INSTALLATION & SIZING OF ALL ELECTRICAL, WIRING & <br />ACCESSORIES. <br />5. SMOKE DETECTORS SHALL BE INSTALLED AS DIRECTED BY <br />THE 2016 NFPA 72 NATIONAL FIRE ALARM CODE. <br />6. ALL ELECTRICAL IN THE LIVING ROOMS, DINING ROOMS, <br />SUNROOMS, FAMILY ROOMS, DENS, LIBRARIES, SLEEPING ROOMS, <br />PARLORS AND SIMILAR ROOMS OR AREAS SHALL BE ON AN A.F.C.I. <br />PROTECT CIRCUIT PER NFPA 70 (NEC) 2017. <br />7. IN ALL AREA SPECIFIED IN NFPA 70 (NEC) 2017 210.52, ALL 125 <br />VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED <br />TAMPER -RESISTANT RECEPTACLES. <br />SECOND FLOOR ELECTRICAL PLAN (ELEVATION A&B' <br />1 /4" = 1'-0" <br />ELECTRICAL DETAIL: <br />INTERCOM <br />SPEAKER <br />ALIGNED W/ <br />EDGE OF <br />SWITCH <br />r <br />SWITCH ° <br />4 1/2" <br />DOORJAMB DUPLEX <br />OUTLET ri <br />TRIM o <br />0 <br />BASE <br />NOTE: <br />ALL DIMENSIONS ARE FROM ROUGH FRAMING <br />SMOKE DETECTOR LOCATION: <br />WALL <br />o Z <br />S <br />SMOKE DETECTOR <br />MIN. <br />ELECTRICAL LEGEND: <br />NOTE: ALL HEIGHTS ABOVE FINISH FLOOR <br />& 110V DUPLEX OUTLET AT 12" <br />110V DUPLEX OUTLET AT 39" <br />NOTE: ALL <br />RECEPTACLES <br />110V DUPLEX OUTLET AT 43" <br />ABOVE <br />COUNTERS <br />110V DUPLEX OUTLET AT 45" <br />SHALL BE <br />SPLIT 110V DUPLEX OUTLET <br />MOUNTED <br />HORIZONTAL <br />AT 12" - TOP PLUG IS HOT <br />110V QUAD OUTLET AT 12" <br />WEATHERPROOF GFCI OUTLET AT 12" <br />220V OUTLET AT 30" <br />110V DUPLEX FLOOR OUTLET <br />OUTLET - VERIFY W/MANUF. SPECS <br />FOR LOCATION & TYPE <br />TELEPHONE OUTLET AT 12" OR AS NOTED <br />TELEVISION OUTLET AT 12" -WIRE FOR <br />CABLE & SATELLITE <br />QSTRUCTURED WIRE OUTLET <br />�- SWITCH AT 36" <br />3 WAY SWITCH AT 36" <br />4 WAY SWITCH AT 36" <br />-0 PUSH BUTTON FOR GARAGE DOOR OPENER <br />-fl DIMMER SWITCH AT 36" <br />--� FLUSH -BUTTON DOORBELL <br />} CLG MNT LT FIXTURE <br />CLG MNT PREWIRE - FIXTURE BY OWNER <br />--- SURFACE MNT FIXTURE <br />{- WALL MNT FIXTURE <br />NOTE: <br />C TUB/SHOWER ND OPALEX - ALTERNATE <br />CANS MAY BE <br />C 50W PAR30 NFL 6" WHITE BAFFLE USEDIF <br />APPROVED BY <br />C 50W MR16 4" LOW VOLTAGE OWNER <br />C 50W PAR20 NFL 4" MINI ROUND RECESS <br />�� 50W PAR20 NFL 6" RD REGRESSED BAFFLE EYEBALL <br />{ CLG FAN PREWIRE AND SWITCH <br />COMBINATION CARBON MONOIXED DETECTOR/ <br />cs SMOKE DETECTOR <br />C SMOKE DETECTOR <br />CU-18= UNDER CABINET 18" <br />=S-18= SINGLE 18" FLUOR STRIP <br />=U-24= UNDER CABINET 24" <br />=S-24= <br />SINGLE 24" FLUOR STRIP <br />=D-24= <br />DOUBLE 24" FLUOR STRIP <br />- U-36 = <br />UNDER CABINET 36" <br />- S-36 - <br />SINGLE 36" FLUOR STRIP <br />- D-36 = <br />DOUBLE 36" FLUOR STRIP <br />S-48 — <br />SINGLE 48" FLUOR STRIP <br />c D-48 — <br />DOUBLE 48" FLUOR STRIP <br />24 24"CLG MNT WRAPPED FLUOR LIGHT <br />48 48"CLG MNT WRAPPED FLUOR LIGHT <br />97r24:;9 24" VANITY LIGHTING <br />9;-= 36 ;;R 36" VANITY LIGHTING <br />48 48" VANITY LIGHTING <br />EXHAUST FAN/LIGHT <br />0 EXHAUST FAN <br />DOUBLE FLOOD LIGHT W/ COVERS AND <br />150W PAR 38 FL <br />® INTERCOM SPEAKER AT 5'-0" ABV FINISH FLOOR <br />CEILING MNT SPEAKER <br />M CHIMES (DELETE W/ INTERCOM) <br />=F MASTER STATION <br />ELEC PANEL <br />21 VACUM OUTLET AT 12" <br />WAI CEILING RETURN AIR <br />E3 A/C REGISTER <br />OT THERMOSTAT <br />On SECURITY PAD <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR LOCATION PURPOSES. <br />I <br />to N <br />� <br />W L N U <br />r') � y <br />N <br />M y� <br />V M U P <br />Eo <br />20. 2 O <br />} 0 <br />•SIN^`` w 0- ., c <br />L00 <br />7W <br />V a <br />LLI <br />U' W <br />w <br />�� w w2�0_0 <br />H < x J x Z W z <br />X::) _j 0 0 <br />Q F-- <br />�wU0'0 <br />QJ 0 <br />(Jco §2z0x00Mzz <br />J _ <br />00 <br />Z <br />cn�w�01WW Of0¢< <br />LU <br />� <br />'< <br />ILLoof <br />40w02� 4 26i320 <br />0-Z) o¢Q� <br />wQ O F.-w <br />O <br />O <br />Z N <br />OW <br />n ti <br />0 - M O <br />I- <br />Q U) M to <br />U) - <br />ti <br />I—�0—_M <br />00 <br />Lz 0- <br />Z U H <br />W <br />W <br />J O <br />O <br />Mj <br />It <br />U!02111 <br />Virtual Re <br />iew <br />AsIsi <br />0 <br />c.1 <br />Plans Review <br />cc <br />npleted <br />nd <br />ppr <br />ved <br />r compliance witl <br />the <br />202 <br />F8 <br />7th <br />gi1i <br />n <br />by Debra <br />A <br />ine <br />K14h <br />PX2 <br />00 <br />N <br />N <br />N <br />N <br />N <br />N <br />O <br />N <br />r <br />O <br />N <br />O <br />N <br />NO <br />O <br />N <br />O <br />N <br />O <br />N <br />O <br />- <br />N <br />O <br />® <br />O <br />� <br />o <br />N <br />0 <br />N <br />o <br />' <br />I <br />Z <br />O <br />NU—) <br />W <br />o <br />0 <br />0 <br />0 <br />0 <br />0 <br />l <br />Nt <br />__ <br />N <br />M <br />V <br />In <br />co <br />i <br />Cr <br />M� <br />Z~ <br />zz <br />W <br />OQw <br />W <br />O <br />000 <br />U <br />U � <br />Z)z5; <br />O <br />OF- 0 <br />Q <br />Z <br />aZa <br />� <br />I— <br />WWQ <br />= <br />mew <br />r*4 <br />I- <br />N <br />Zoo <br />■ <br />W <br />CL <br />U) <br />0 <br />ZWO <br />O <br />z <br />V <br />LL <br />gzLL <br />°- z <br />OU <br />MMO <br />W <br />z <br />� <br />z <br />z <br />z <br />w <br />W <br />J <br />rl- <br />0 <br />LAST PLOT DATE <br />. <br />May 8, 2023 <br />4-1 <br />O <br />2ND FLOOR <br />_I <br />ELECTRICAL PLAN <br />A&B <br />