<br />Panel. A (NEW)
<br />Design Selection: Voltage: 120/208 Wye Minimum A.I.C. Rating: 35K
<br />Mains: 200 A Phases: 3 Location: ELEC 103
<br />Type: MCB Wires: 4 Served From: UTILITY
<br />Mounting: Surface Modifications:
<br />Trip
<br />Trip
<br />Note
<br />Amps
<br />Poles
<br />Description
<br />Wire
<br />Neut
<br />Gnd
<br />Cond
<br />No.
<br />A
<br />B
<br />C
<br />No.
<br />Cond
<br />Grid
<br />Neut
<br />Wire
<br />Description
<br />Poles
<br />Amps
<br />Note
<br />20 A
<br />1
<br />Receptacle
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />1
<br />1.1 kVA
<br />0.7 kVA
<br />m
<br />2
<br />1/2"
<br />#12
<br />#12
<br />#12
<br />Receptacle
<br />1
<br />20 A
<br />20 A
<br />1
<br />Receptacle
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />3
<br />1.1 kVA
<br />0.7 kVA
<br />x
<br />4
<br />1/2"
<br />#12
<br />#12
<br />#12
<br />Receptacle
<br />1
<br />20 A
<br />20 A
<br />1
<br />Receptacle
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />5
<br />1.1 kVA
<br />0.2 kVA
<br />6
<br />1/2"
<br />#12
<br />#12
<br />#12
<br />Receptacle
<br />1
<br />20 A
<br />20 A
<br />1
<br />Receptacle
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />7
<br />0.9 kVA
<br />0.7 kVA
<br />e.20
<br />8
<br />1/2"
<br />#12
<br />#12
<br />#12
<br />Receptacle
<br />1
<br />20 A
<br />A
<br />1
<br />Receptacle
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />9
<br />0.7 kVA
<br />0.7 kVA
<br />,,.
<br />10
<br />1/2"
<br />#12
<br />#12
<br />#12
<br />Receptacle
<br />1
<br />20 A
<br />20 A
<br />1
<br />Receptacle
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />11
<br />0.7 kVA
<br />0.2 kVA
<br />12
<br />1/2"
<br />#12
<br />#12
<br />#12
<br />Receptacle
<br />1
<br />20 A
<br />20 A
<br />1
<br />Receptacle
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />13
<br />0.2 kVA
<br />0.3 kVA
<br />„ ;°
<br />14
<br />1/2"
<br />#12
<br />#12
<br />#12
<br />Lighting
<br />1
<br />20 A
<br />20 A
<br />1
<br />Lighting
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />15
<br />1.0 kVA
<br />0.4 kVA
<br />16
<br />1/2'
<br />#12
<br />#12
<br />#12
<br />Phone Recept
<br />1
<br />20 A
<br />20 A
<br />1
<br />Store Sign
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />17
<br />0.5 kVA
<br />0.4 kVA
<br />18
<br />1/2"
<br />#12
<br />#12
<br />#12
<br />Roof Recept
<br />1
<br />20 A
<br />20 A
<br />1
<br />Lighting
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />19
<br />0.5 kVA
<br />2.9 kVA,_
<br />,"
<br />20
<br />20 A
<br />1
<br />Lighting
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />21
<br />°; .' %
<br />0.4 kVA
<br />2.9 kVA
<br />-
<br />, , ,
<br />22
<br />1 1/4"
<br />#8
<br />#3
<br />#3
<br />RTU-1
<br />3
<br />80 A
<br />20 A
<br />1
<br />AC-1/CU-1
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />23
<br />0.9 kVA
<br />2.9 kVA
<br />24
<br />20 A
<br />1
<br />Hand Dryer
<br />#12
<br />#12
<br />#12
<br />1/2"
<br />25
<br />1.7 kVA
<br />1.5 kVA
<br />26
<br />1/2"
<br />#12
<br />#12
<br />#12
<br />Elec Water Heater
<br />2
<br />20 A
<br />-
<br />20 A
<br />1
<br />Spare
<br />--
<br />-
<br />-
<br />-
<br />27
<br />0.0 kVA
<br />1.5 kVA
<br />28
<br />-
<br />20 A
<br />1
<br />Spare
<br />-
<br />-
<br />-
<br />-
<br />29
<br />0.0 kVA
<br />0.0 kVA
<br />30
<br />-
<br />-
<br />-
<br />-
<br />Spare
<br />1
<br />20 A
<br />-
<br />-
<br />20 A
<br />1
<br />Spare
<br />-
<br />-
<br />-
<br />-
<br />31
<br />0.0 kVA
<br />0.0 kVA
<br />732
<br />-
<br />-
<br />-
<br />-
<br />Spare
<br />1
<br />20 A
<br />-
<br />-
<br />20 A
<br />1
<br />Spare
<br />-
<br />-
<br />-
<br />-
<br />33
<br />0.0 kVA
<br />0.0 kVA
<br />34
<br />-
<br />-
<br />-
<br />-
<br />Spare
<br />1
<br />20 A
<br />-
<br />-
<br />20 A
<br />1
<br />Spare
<br />-
<br />-
<br />-
<br />-
<br />35
<br />0.0 kVA
<br />0.0 kVA
<br />36
<br />-
<br />-
<br />-
<br />-
<br />Spare
<br />1
<br />20 A
<br />-
<br />-
<br />20 A
<br />1
<br />Spare
<br />-
<br />-
<br />-
<br />--
<br />37
<br />0.0 kVA
<br />0.0 kVA
<br />38
<br />-
<br />-
<br />-
<br />-
<br />Spare
<br />1
<br />20 A
<br />-
<br />-
<br />20 A
<br />1
<br />Spare
<br />-
<br />--
<br />-
<br />--
<br />39
<br />0.0 kVA
<br />0.0 kVA
<br />a>' h
<br />40
<br />-
<br />-
<br />-
<br />-
<br />Spare
<br />1
<br />20 A
<br />-
<br />-
<br />20 A
<br />1
<br />Spare
<br />-
<br />-
<br />-
<br />-
<br />41
<br />0.0 kVA
<br />0.0 kVA
<br />42
<br />-
<br />-
<br />-
<br />-
<br />Spare
<br />1
<br />20 A
<br />-
<br />Total
<br />10.5 kVA
<br />9.3
<br />kVA
<br />6.8
<br />kVA
<br />Load Classification
<br />Connected Load
<br />Demand Factor
<br />Demand Load
<br />Load Summary
<br />HVAC
<br />12.62 kVA
<br />100.00%
<br />12.62 kVA
<br />Total Connected Load:
<br />26.6 kVA
<br />Lighting
<br />2.60 kVA
<br />125.00%
<br />3.25 kVA
<br />Receptacle
<br />11.42 kVA
<br />93.78%
<br />10.71 kVA
<br />Estimated Demand Load:
<br />26.6 kVA
<br />Notes:
<br />1. All breakers indicated as "Spare" shall be in the "OPEN" (OFF) position.
<br />2. Contractor shall field verify the required AIC rating of the panel breakers and modify as required.
<br />Total Estimated Demand Current:174 A
<br />ELECTRICAL SPECIFICATIONS
<br />SECTION 16000
<br />3.2 GROUNDING
<br />2.5 LIGHTING FIXTURES
<br />1. Service equipment, conduit systems, supports, cabinets, equipment,
<br />PART 1 GENERAL
<br />A. Provide all new lighting fixtures complete with lamps, ballasts, reflectors,
<br />transformers, fixtures, the grounded circuit conductor, etc., shall be
<br />plaster frames, louvers, stem hangers, etc., and as described on the drawings.
<br />properly grounded in accordance with the latest issue of the National
<br />1.1 CODES AND REQUIREMENTS
<br />Electrical Code. Provide all bonding jumpers and wire, grounding
<br />A. All electrical work shall comply with the requirements of the applicable
<br />B. All ballasts shall be internally protected by use of two internal,
<br />bushings, damps, etc., as required for complete grounding. Route
<br />edition of the National Electrical Code, Local Building Code and as
<br />temperature -sensitive, non -resetting protectors, equal to G.E. Watt -Miser,
<br />ground conductors to provide the shortest and most direct path to
<br />specified herein whichever is more strict
<br />Class "P"
<br />the ground electrode system. Ground connections shall have dean
<br />contact surfaces, tinned and sweated while bolting. Install all ground
<br />B. The contractor shall comply with the requirements of the General
<br />C. Exit and emergency lights shall conform with local code requirements.
<br />conductors in conduit. Make readily accessible connections to a
<br />continuous, metallic, underground cold water piping system at the
<br />Conditions, Supplemental General Conditions of the project specifications,
<br />point where it enters the building. If this is not practical, connect to
<br />all Contract Documents, and any base building specifications and building
<br />D. Mount all outlets at position and height to dear ducts, etc.
<br />a cold water pipe and provide a meter jumper. Make connections to
<br />aiteria included in this project.
<br />the water pipe that grounds the conduit enclosing the conductor as
<br />E. Acrylic lenses shall be 100% virgin materials and 0.125 inch thick;
<br />well as the conductor. Bond the service equipment to building steel,
<br />C. Visit the premises before submitting bid as no extras will be allowed for lack
<br />minimum unpenetrated thickness shall be 0.035 inch.
<br />concrete encased electrodes, underground metal water piping, driven
<br />of knowledge of existing conditions.
<br />electrode, and all other available grounding electrodes per NEC article
<br />2.6 BRANCH CIRCUIT PANELBOARDS
<br />250.
<br />D. Drawings are diagrammatic in nature. Take ail dimensions from Architectural
<br />A. Provide dead -front, circuit breaker type panels, with the size and number
<br />drawings, certified equipment drawings, and from the structure itself before
<br />of branches indicated. Breakers shall be thermal magnetic type
<br />fabricating any work.
<br />employing quick -make and quick -break mechanisms for manual operation
<br />3.3 PANELBOARDS
<br />as well as automatic operation. Automatic tripping shall be indicated by the
<br />1. Install panelboards with the top of the trim six -feet, three -inches
<br />E. The drawings indicate the location, type and sizes of various utilities within the
<br />breaker handle assuming a distinctive position from the manual "on" and "off'.
<br />(6-Y) from the finished floor.
<br />site where known. Any relocation or remodeling required must be approved
<br />Multiple breakers shall have a common trip. Tie handles will not be permitted.
<br />by the Architect before proceeding. Investigate all utilities such as electric and
<br />2. Field check all panelboard loading and reconnect circuits as
<br />telephone and make arrangements with the proper authority to pay for any
<br />B. Panelboards having branch circuit breaker sizes 15 to 100 amperes shall be:
<br />required to provide balanced phase and line loads.
<br />charges associated with connecting those utilities. Pay for all permits, fees,
<br />1. General Electric "AQ" for operation on 120/208V. systems.
<br />inspections etc.
<br />2. General Electric "AE" for operation on 277/480V. systems.
<br />3.4 MECHANICAL EQUIPMENT WIRING AND CONNECTIONS
<br />1. Mechanical equipment motors and controls furnished with
<br />F. Good workmanship and appearance are considered equal to proper operation.
<br />C. Panelboards may contain two (2) subfeed breakers having a rating in excess
<br />mechanical equipment.
<br />of 100 amperes, but less than 225 amperes.
<br />G. Provide all core drilling, channeling, cutting, patching, trenching and backfill as
<br />2. Provide feeder circuits to mechanical equipment and make
<br />required for installation of electrical equipment. Seal holes, fireproofing where
<br />D. Panelboards having more than two (2) branch circuit breakers rated in
<br />all connections.
<br />necessary, and refinish all repair work to original condition where damaged by
<br />excess of 100 amperes shall be General Electric "Spectra" series.
<br />electrical work.
<br />3. Provide safety switches and/or thermal overload swatches as
<br />E. All spaces shall be fully equipped.
<br />required.
<br />H. Make provisions for safe delivery and secure storage of all materials.
<br />F. Panelboards shall have a grounding lug for the equipment grounding system.
<br />4. Provide all power (line voltage) wiring for mechanical equipment
<br />I. Provide the Architect with a complete set of plans and specifications corrected
<br />and make all connections except for temperature control
<br />to as -built conditions at the completion of the job.
<br />G. Circuit breakers shall have a minimum interrupting capacity as follows:
<br />equipment, which will be wired by mechanical contractor.
<br />1.2 WARRANTY
<br />120/208 volts: 22,000 amperes.
<br />5. Furnish, set in place, and wire, except as indicated, all heating,
<br />The electrical contractor shall provide for the owner a one-year (from the date of final
<br />In addition, upstream fuses shall be selected to provide a series rating
<br />ventilating, air conditioning, plumbing, fire protection, motors and
<br />acceptance) warranty of all electrical equipment and systems provided under this contract
<br />of 100,000 amperes with downstream circuit breakers.
<br />controls in accordance with the following schedule. Carefully
<br />except for incandescent or fluorescent lamps. All defective equipment or materials which
<br />coordinate with work performed under the Mechanical Division
<br />appear during the warranty period shall be replaced or repaired by the electrical contractor
<br />H. Panelboards shall be a minimum twenty inches (20") wide (box).
<br />of these specifications.
<br />in a timely fashion.
<br />I. All buses shall be copper.
<br />6. Heater units in all motor starters shall be sized for approximately e
<br />one hundred fifteen percent (115%) of full load motor current.
<br />J. The above panelboard designations are General Electric; however provide
<br />Check and coordinate all thermal protective devices with the
<br />PART 2 PRODUCTS
<br />any of the following equipment: Cutler Hammer, General Electric,
<br />equipment they protect.
<br />Siemens, or Square D.
<br />2.1 EQUIPMENT
<br />a) Provide for each motor, one-half (1/2) horsepower and below,
<br />A. The contractor shall provide all equipment and accessories necessary whether
<br />a horsepower rated disconnect switch and thermal overload
<br />specifically stated or not to make the required electrical systems complete and
<br />2.7 SAFETY AND DISCONNECT SWITCHES
<br />protection unless integrally provided with the motor. Thermal
<br />operational.
<br />Provide enclosed, fusible or non -fusible safety switches. where
<br />overload switches for single phase motors shall be Allen-Bradley
<br />specified. Safety switches shall bear the UL
<br />indicated and herein speci
<br />Bulletin 600 or acceptable. Size heater units for approximately
<br />B. All equipment provided shall be new except as otherwise stated on the drawings.
<br />label and each enclosure shall be the NEMA type suitable for the
<br />one- hundred fifteen percent (115%) of full load motor current.
<br />All equipment provided shall be U.L. listed when such standards exist for the type
<br />surrounding area and conditions. Switches shall be minimum heavy
<br />of equipment furnished and acceptable for installation by the Local Building Authority.
<br />duty, horsepower rated, and shall have quick -make and quick -break
<br />b) Miscellaneous Equipment: Where outlets are indicated for
<br />mechanisms. Switches used on motor circuits shall have adequate
<br />miscellaneous equipment requiring electric power or control,
<br />2.2 CONDUCTORS
<br />horsepower ratings for the motors served.
<br />provide wire, conduit, etc., and make all connections, unless
<br />A. Minimum size #12 AWG except for control circuits which may be #14 or signal
<br />otherwise indicated. Refer to the Mechanical Specifications and
<br />circuits which shall be as indicated. All conductors shall be copper. Increase
<br />1. Safety switches employed as motor disconnect devices for two (2)
<br />Plans covering sprinkler systems, motor interlocks, switching, etc.
<br />conductor size as necessary to limit branch circuit voltage drop to 3% and feeder
<br />or more loads shall be of the fusible type for rejection type fuses.
<br />Provide wiring, conduit, outlets and provide final electrical
<br />voltage drop to 2%.
<br />connections to all equipment.
<br />2. Heavy duty industrial type safety switches shall be used
<br />B. Splices for #8 and smaller conductors - wire or wing nuts.
<br />and shall be horsepower rated with quick -make, quick -break
<br />3.7 TELEPHONE SYSTEM
<br />mechanisms and interlocked covers.
<br />A. Provide conduits and outlets as indicated. Provide #14 AWG
<br />C. Feeders and other wiring No. 4 AWG and larger, type THWN.
<br />3. Switches shall be as manufactured by Cutler -Hammer, General
<br />pull wire for all empty conduit
<br />D. Other wiring No. 6 and smaller, type THWN.
<br />Electric, Square-D, or Siemens, and all
<br />switches provided shall be by the same manufacturer.
<br />B. Outlets shall consist of 4" square box with bushed opening in
<br />plate. Plates shall match finish of other plates.
<br />E. Wiring in high temperature areas shall be rated 105°C and be a type accepted
<br />by local code.
<br />PART 3 EXECUTION
<br />3.8 SPECIAL SYSTEMS
<br />1. Provide all special systems as specified on the drawings
<br />F. Color Coding: Wiring for control systems to be installed in conjunction with
<br />3.1 CONDUIT/RACEWAYS
<br />including all required accessories to make the system complete
<br />mechanical and miscellaneous equipment shall be color coded in accordance
<br />A. All conductors shall be enclosed by conduit sized in accordance with
<br />and operational. All special systems shall be installed and
<br />with the wiring diagrams furnished with the equipment Branch circuit wiring,
<br />the National Electrical Code. Minimum 3/4" except for
<br />connected in accordance with the manufacturer's specifications.
<br />including circuits to motors, and all feeders shall be coded by line or phase as
<br />factory furnished lighting fixture flexible conduit may be 3/8". Follow the
<br />Provide instructional demonstration for the owner prior to final
<br />follows:
<br />following schedule unless otherwise specified in the drawings.
<br />acceptance.
<br />1. Rigid metal conduit (RMC) and intermediate metal conduit (IMC)
<br />Wire No. 2 AWG and smaller shall be factory color coded. Wire No.1 AWG
<br />shall be utilized for above and below grade applications in accordance
<br />3.9 SEISMIC RESTRAINTS
<br />and larger may be color coded by field painting or color taping of sic inch (T)
<br />with articles 344 AND 342 of the National Electrical Code. All couplings
<br />1. Provide seismic restraints for all electrical equipment and system
<br />length of exposed ends.
<br />shall be threaded.
<br />components as required by local codes.
<br />120/208 Volts
<br />2. Rigid nonmetallic conduit (PVC) Schedule 40 shall be permitted
<br />A = Black
<br />for below grade or concrete cast in place applications above grade.
<br />END OF SECTION
<br />B = Red
<br />All elbow transitions to above grade or stub -out of floor slab shall be
<br />C = Blue
<br />asphalt coated rigid conduit. Provide equipment grounding conductor
<br />Neutral = White
<br />for all runs of rigid nonmetallic conduit.
<br />Ground = Green
<br />Switch Travelers = Pink
<br />3. Electrical metallic tubing (EMT) shall be utilized for all dry, above grade
<br />or above floor applications in accordance with article 358 of the National
<br />2.3 OUTLETS
<br />Electrical Code. Couplings shall be steel compression type made up
<br />A. 4" square or octagonal, zinc coated sheet steel boxes.
<br />wrench -tight.
<br />B. Provide 3/8" no -bolt fixture studs.
<br />4. Flexible metal conduit shall be utilized for all connections to vibrating
<br />equipment such as motors (minimum of 2'-0" - maximum of 6-0"),
<br />C. Provide covers set to come flush with finish walls.
<br />connection to lay -in type light fixtures or in remodel areas specifically
<br />noted for "fishing" in existing walls or non -accessible ceilings.
<br />D. Utility or sectional switch boxes only where permitted.
<br />5. Surface metallic raceways shall be used only in areas specifically
<br />2.4 DEVICES
<br />noted and of size and type specified on the drawings.
<br />A. All devices colors shall be white.
<br />1. Specification grade receptacles, equal to Hubbell 5362 NEMA 5-20R.
<br />6. Metal -Clad Cable (MC) may be utilized for all dry, concealed, above grade
<br />2. A.C. quiet operating type switches equal to Hubbell, rated 20A, 277V.
<br />applications only within tenant space and not crossing any fire or rated
<br />B. Device plates shall be nylon, color to match devices.
<br />barriers. Install cable in accordance with article 330 of the National
<br />C. Mount devices in accordance with the following schedule except where
<br />Electrical Code.
<br />otherwise noted on the drawings:
<br />B. All exposed conduit (including conduit installed in ceiling plenums)
<br />1. Convenience Receptacles - Long Axis Vertical IV' A.F.F.*
<br />shall be routed parallel or perpendicular with the building walls.
<br />2. Light Switches - Latch Side of Door 4V A.F.F.
<br />Support conduit as required by the National Electrical Code.
<br />3. Telephone Outlets VT A.F.F.*
<br />* Except in areas with counters, baseboard heaters or in areas of
<br />block or bride construction.
<br />C. Provide expansion type fittings for all conduits which cross
<br />expansion joints.
<br />www.brph.com Copyright © 2014
<br />Architects, Engineers, Inc.
<br />2727 Paces Ferry Road I Bldg 1 1 Suite 1800
<br />Atlanta I Georgia 1 30339
<br />770-933-9242 1 770-933-9246 f
<br />Offices in Melbourne, Orlando, West Palm
<br />Beach, Atlanta, Charleston, Seattle
<br />These plans are protected by Federal Copyright
<br />protection. Unauthorized use may result in an
<br />infringement action.
<br />ISSUE FOR PERMIT AND CONSTRUCTION
<br />REVISION
<br />-
<br />M
<br />O
<br />c
<br />J
<br />w
<br />J
<br />T
<br />r
<br />In
<br />M
<br />J
<br />I
<br />J
<br />J
<br />-
<br />N1
<br />Z
<br />-
<br />w
<br />,�x�
<br />W
<br />o/
<br />�
<br />0-
<br />w
<br />N
<br />•
<br />�
<br />J
<br />a
<br />c�
<br />Uw^
<br />r
<br />ARCH/ENGR OF RECORD
<br />JOHN D. ADDISON
<br />FL PE #59239
<br />DESIGNED BY
<br />JAH
<br />DRAWN BY
<br />JAH
<br />CHECKED BY
<br />JDA
<br />PROJECT NUMBER
<br />C06898.057.01
<br />DATE
<br />08/13/14
<br />TITLE
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />DRAWING NO.
<br />E400
<br />1
<br />N
<br />K
<br />4 5 6
<br />'_'�---