Laserfiche WebLink
THESE RECOMMENDATIONS ARE BASED: ON NFPA-99 STANDARDS FOR MEDICAL GAS <br />SYSTEMS. LOCAL BUILDING AND FIRE CODES MAY SUPERSEDE NFPA-99. IMPORTANT: <br />VERIFY LOCAL REQUIREMENTS BEFORE BEGINNING CONSTRUCTION. <br />SIGNAGE REQUIRED ON DOOR - <br />CAUTION <br />.MEDICAL GASES <br />NO SMOKING OR OPEN FLAME <br />ROOM MAY HAVE INSUFFICIENT OXYGEN <br />OPEN DOOR AND ALLOW ROOM TO VENTILATE BEFORE ENTERING <br />PIPING (SEE MFR. SPECS) <br />LOW VOLTAGE: CONTROL <br />I HR. FIRE RATED WIRES: TO D-34 <br />ROOM <br />MANIFOLD INSTALLED BY <br />1 HR. FIRE RATED CONTRACTOR <br />DOOR WITH LOCK <br />,--CYLINDER CAPTOR INSTALLED <br />BY CONTRACTOR, <br />---CYLINDERS BY DOCTOR <br />N20, 02 C t <br />NOT TO SCALE <br />REQUIRES VENTING TO BUILDING <br />EXTERIOR PER NFPA-99 STANDARDS <br />PROVIDED BY HENRY SCHEIN DENTALAND <br />INSTALLED BY CONTRACTOR <br />LINDER CLOS T <br />4 CYLINDERS <br />LOW VOLTAGE WIRE TO <br />MANIFOLD SYSTEM WIRE BY <br />HENRY SCHEIN DENTAL <br />TO A I I 5V OUTLET IN <br />CEILING SPACE 1.5 A <br />CUTOUT <br />DIMENSIONS <br />MOUNTING FRAME <br />PROVIDED BY HENRY SCHEIN DENTAL AND <br />INSTALLED BY CONTRACTOR. <br />N2, 2 ALAR1 PANEL <br />NOT TO SCALE <br />115 VAC RECEPTACLE <br />VtATSrREMMFT5 IN' <br />CYLINDER ROOM <br />(PERMITTED IN LEVEL 11 <br />FACILITY) <br />LATOR (TYP.) <br />TO OUTLETS <br />(IF ZONE VALVES ARE <br />NOT REQUIRED) <br />O.D. i'O.D. <br />02 <br />SYSTEA <br />�o 0 MANIF <br />N20 N20 02 <br />2 X 10 BLOCKING <br />FLUSH WITH STUDS, <br />4U'A.F.F. TO <br />CENTER LINE. - <br />NOT TO SCALE <br />-THE ELECTRICIAN SHALL EXTEND L/V <br />CABLE, PROVIDED WITH THE EQUIPMENT, <br />FROM THE MANIFOLD TO THE ZONE <br />VALVE, (IF REQUIRED.). <br />CYLINDER ROOM <br />LEVEL I I I FACILITY <br />WITH LESS THAN 2000 CU. Fr. GAS (INCLUDING STORAGE, <br />EXCLUDING NITROGEN). <br />99 <br />i- O.D. 02 - <br />k'O.D. N20 <br />CYLINDER <br />RESTRAINTS <br />FROM <br />MANIFOLD <br />THE ELECTRICIAN SHALL EXTEND L /V <br />CABLE, PROVIDED WITH THE EQUIPMENT <br />FROM THE MANIFOLD TO THE ALARM <br />STATION. <br />MANUAL ZONE VALVES _'N <br />(VERIFY THAT ZONE VALVES <br />ARE TO BE USED,) REQUIRED <br />WHEN THE CYLINDERS ARE <br />REMOTELY LOCATED OR <br />SERVICE MORE THAN ONE <br />FACILITY. VERIFY GAS <br />DIRECTION. TO <br />A` O.D. N20 OUTLETS <br />�'O, D. 02 -CAI I <br />=2016 <br />115 VAC SERVICE MAY BE <br />REQUIRED FOR THE ALARM <br />STATION (VERIFY), <br />ALARM. STATION <br />WALL MODEL IS ILLUSTRATED <br />A DESK MODEL 15 OPTIONAL <br />(REQUIRED BY NFPA 99). <br />Z:3-la . <br />= cr 758" A.F.F. <br />GENERAL REQUIREMENTS <br />1.),STRICT ACCORDANCE WITH THE NFPA 991 IS REQUIRED. <br />2.1 IF THE CYLINDER ROOM IS REMOTELY LOCATED IT MUST BE LOCKED. <br />3.) THE CYLINDER ROOM SHALL BE VENTILATED WITH NO LESS THAN 72 SQ IN <br />TOTAL FREE AREA WHEN NO OTHER VENTING IS POSSIBLE. <br />4.) USE TYPE K OR L PRE CLEANED, DEGREASED, CAPPED COPPER PIPING ONLY. <br />3/-W'O.D, FOR N20 AND 1/2"FOR 02. <br />5.) USE SILVER SOLDER OR SIMILAR BRAZING ALLOY. SOLDER SHALL HAVE A <br />MELTING TEMPERATURE Of 1000 DEGREES F. <br />6.) PRIOR TO SHEET ROCK, STATIC PRESSURE TEST THE PIPING SYSTEM USING DRY <br />,NITROGEN AT 150 PS.L FOR 24 HOURS. <br />7.) EACH LINE SHALL BE INDIVIDUALLY TESTED TO ENSURE THE PIPING DID NOT GET <br />CROSSED. CONNECT THE N20 / 02 CYLINDERS AND SET THE PRESSURE <br />ACCORDING TO INSTRUCTIONS. CHECK ONLY ONE GAS AT A TIME. <br />8.) LABELING SHALL APPEAR ON THE PIPING AT 20 FT, (MAX) INTERVALS AND AT <br />LEAST ONCE IN EACH TREATMENT ROOM. <br />9.) THIS ILLUSTRATION IS FOR THE GENERAL LAYOUT ONLY. EXACT EQUIPMENT <br />REQUIREMENTS SHALL BE AS DIRECTED AT SITE. <br />10.) PROVIDE A I HOUR FIRE -RATED DO <br />a' O.D. N20 I'O.D. 02 <br />SEE MAN UFACTURER'SS.PECS FOR INSTALLATION <br />� 1,4 —IL , Nj-,� r —,%LLC_ l' <br />Rpfl_'lL"4 fOS t_0tA-rL_&A <br />OUTLET STATION <br />RECESSED MODEL <br />�2 <br />ILLUSTRATED. <br />Lu z <br />'m 0 <br />REDUCE TO VACUUM <br />,00 <br />OUTLET (IF REQ'D) <br />Lu <br />VACUUM TRUNK LINE <br />0 <br />(IF REQ'D) <br />FINISHED FLOOR <br />ISSUE <br />DATE <br />REVIEW <br />02/22/11 <br />PERMIT <br />02123AI <br />REV. <br />REV. <br />REV. <br />Rr=v. <br />1r M VOUM4% MIM, trans, LeTAILS NO <br />sPECIFIGATM MV WWLTIS ARE THE SOLE <br />PROPHiT I M FRAZE VMRK NO. AV %OU NOT BE <br />lar ==, PM42M OR COPIED FOR OTHM <br />MX507% IN WOLE OR FMr MMM 7w HRMM <br />WOW OF FRANC FRAZE, ARCHIMT, ALA. <br />ALL M&M ARE FM5MVW Vf TW ARCHITECT N <br />ACWWANCE NTH UA C*vtRr*ff AND WENT LAN5. <br />MOONED IROMROMTON NLL DE MaMW TO <br />IM MI MW OF M LAK <br />O <br />11 <br />Tv <br />W�QQ <br />O <br />�4 <br />U���N <br />PRD_fr:55I0NAL SEAL <br />40, <br />: <br />O� <br />bo <br />Ic E <br />SHEET Tl= <br />PLUMSINCHDETAILS <br />