ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FTF <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />)4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />i O <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />e <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />® D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />i a <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />® 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />JQ <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />0 <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I I <br />I I <br />_ I I <br />I I <br />LAV <br />3" VTR <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />OPT. <br />LAV <br />_—'na F fiLR <br />LOAD CALCULATIONS <br />UNIT -A 1532 (1532) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1533 S.F. <br />4599 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10599 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />SUBTOTAL: 23060 <br />TOTAL: 33659 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9464 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31768 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />Optional Overhead Service <br />Same As Underground <br />150 Or 200 Amp Service <br />METER MA)N <br />0-200 AMP <br />3R <br />Power Co. Feed <br />200A <br />Indoor Panel <br />Center <br />NEMA1 <br />200 AMP <br />Cable <br />#4 Solid COPPER Ground <br />II <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Risbr Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />O <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. <br />/ \ <br />FAN/LIGHT <br />WP <br />GFI <br />irn <br />r,----- I--- <br />1 <br />DINING <br />KITCHEN <br />GFI <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM <br />^\ /i^TROUGH-IN\ <br />FOR OPT. ` <br />FAN/LIGHT 1 <br />/ I <br />I <br />1 / <br />FOYER '�_ <br />I I <br />I <br />I DB <br />ENtRY WPa- <br />LIGHT AS aO GFI® <br />PER SPECS <br />DB&GFI TO _----1 <br />BE ALIGNED <br />VERTICALLY <br />1 <br />I�I , <br />I <br />I <br />I <br />C.M <br />1 UPSTAIRS C <br />GFI <br />@ 44" <br />\ <br />LW.H. <br />A.F.F. <br />\ O <br />I \ <br />1 <br />I <br />+� I GARAGE <br />I I <br />\ GARAGE <br />LIGHT AS <br />PER SPECS <br />GARAGE <br />DOOR <br />GFI <br />--------------- <br />I <br />I � <br />LU <br />I <br />I <br />I <br />0< <br />Fa <br />I <br />I <br />Q <br />90 <br />I <br />I <br />I <br />DLU <br />I <br />I <br />COACH LIGHTS <br />OR PREWIRE AS <br />PER SPECS <br />DISCONNECT <br />1ST ELECTRICAL -UNIT-A 1532 <br />SCALE: Y"=V-0" <br />DEDICATED RECEPTACLE <br />FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />2ND ELECTRICAL - UNIT -A 1532 <br />SCALE: Y4'=T-0" <br />M <br />N <br />O <br />N <br />�.. <br />o <br />A ,-o <br />r� <br />Q <br />c� <br />— m K <br />N C L._ d <br />�o <br />1n O i0 <br />3 c a' <br />W <br />� ac <br />E C <br />d <br />Cc 3 M <br />U <br />O <br />E <br />a � <br />N <br />0 <br />N <br />N <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential <br />7th Edition. Engineer's signature and seal is only for <br />the structural <br />engineering portions of the drawing pages beadng <br />Engineer's <br />signature and seal. <br />W <br />Q <br />v E <br />8 <br />N O <br />O <br />N 00 <br />0, rn <br />2s LL <br />Q <br />C J Z LL W <br />J LL u_ 5 a <br />o <br />W <br />L p <br />7 M r_ <br />r°CID <br />IL <br />0 <br />In N 2 Q - <br />Z <br />N <br />O U U <br />W <br />❑ ❑ <br />ca R <br />Z N M <br />z � � <br />Z � � <br />U) <br />Q Q <br />J — <br />N <br />.1T <br />.20. <br />Q)l <br />�Z <br />C7 <br />LL <br />C/3 <br />p <br />'�• <br />V <br />O <br />l!1 <br />w g <br />c N <br />w t$ <br />i <br />c) <br />Q Y <br />• <br />sr <br />o <br />QD <br />C <br />M <br />N< <br />0 <br />Z <br />J <br />LL <br />E C <br />C) <br />w z <br />� <br />v <br />Z <br />na <br />N V <br />�0 <br />X ti <br />Up <br />4UVq <br />O � <br />E <br />p <br />3 <br />Z <br />O <br />N <br />as <br />mf <br /><W <br />ZC: <br />N � <br />�b <br />f� <br />rn <br />a <br />Z a <br />aZ <br />W <br />o <br />w <br />�o <br />O <br />a� <br />0 O <br />0 <br />> r. <br />N <br />rn <br />N <br />� <br />� <br />H <br />� <br />O <br />T <br />� <br />N <br />a <br />cI <br />LO <br />60 <br />M <br />N <br />r— <br />00 <br />U <br />04 <br />00 <br />v <br />cLO <br />�-- <br />O <br />+-� <br />. <br />N <br />L O <br />00 O <br />OT <br />VJ <br />Q O <br />00 <br />CD <br />N <br />TL— <br />ai <br />m <br />� I <br />Z <br />Z <br />:3�! <br />E O <br />�i N <br />m r <br />m <br />m <br />E <br />o ui <br />c <br />n <br />U _j <br />Q p <br />JOB <br />NO: 22-12493-12498 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />r <br />