ELECTRICAL SPECIFICATIONS
<br />1. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS,
<br />EQUIPMENT, ACCESS PANELS, CONTROL SYSTEMS, DEVICES, PERMITS
<br />AND SERVICES NECESSARY FOR FURNISHING AND INSTALLING OF A
<br />COMPLETE SERVICEABLE ELECTRICAL SYSTEM.
<br />2. ALL ELECTRICAL SYSTEMS ARE TO BE INSTALLED IN
<br />ACCORDANCE WITH THE 2014 EDITION OF THE NATIONAL
<br />ELECTRICAL CODE, ALL APPLICABLE SECTIONS OF THE NFPA
<br />STANDARDS, THE LOCAL BUILDING CODE, PLANS AND
<br />SPECIFICATIONS.
<br />3. ALL MATERIALS SHALL BE NEW (UNLESS OTHERWISE INDICATED)
<br />AND ANY DAMAGED EQUIPMENT SHALL BE REPLACED.
<br />4. CONTRACTOR WILL WARRANTY ALL MATERIALS AND WORKMANSHIP
<br />FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN (1) ONE YEAR
<br />FROM THE DATE OF ACCEPTANCE. CORRECTION OF ANY DEFECTS
<br />SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL
<br />INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE
<br />INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY.
<br />5. PROVIDE SUBMITTALS IN PDF FORMAT FOR REVIEW BY
<br />ARCH/ENGR PRIOR TO PURCHASING ANY EQUIPMENT OR MATERIALS.
<br />SUBMITTALS SHALL INCLUDE ALL ITEMS AND MATERIALS SUPPLIED BY
<br />CONTRACTOR. SUBMITTALS SHALL HAVE A SUMMARY SHEET SHOWING
<br />ALL SCHEDULED INFORMATION. ANY EQUIPMENT OR MATERIALS
<br />INSTALLED WITHOUT REVIEWED SUBMITTALS SHALL BE REMOVED AND
<br />REINSTALL AT ARCH/ENGR DISCRETION WITH NO ADDITIONAL
<br />COMPENSATION TO CONTRACTOR.
<br />6. PROVIDE 2 SETS OF MAINTENANCE AND OPERATION MANUALS ON
<br />ALL ELECTRICAL EQUIPMENT OR SYSTEMS.
<br />7. DRAWINGS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED.
<br />REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT
<br />LOCATION OF ALL EQUIPMENT. ELECTRICAL CONTRACTOR SHALL
<br />FURNISH AND INSTALL ALL ITEMS REQUIRED FOR A COMPLETE AND
<br />ACCEPTABLE WORKING INSTALLATION.
<br />8. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL SERVICE
<br />REQUIREMENTS WITH POWER COMPANY PRIOR TO INSTALLING ANY
<br />EQUIPMENT. COORDINATION SHALL INCLUDE BUT NOT BE LIMITED
<br />TO, POWER CO. TRANSFORMER LOCATION, TRANSFORMER A. I . C.
<br />RATING, POWER METER TYPES, METER DISCONNECT REQUIRMENTS, AND
<br />EQUIPMENT INSTALLATION HEIGHT REQUIREMENTS.
<br />9. MINIMUM WIRE SIZE SHALL BE #12 AWG IN 1/2" CONDUIT,
<br />UNLESS OTHERWISE NOTED. ALL CONDUCTORS SHALL BE COPPER WITH
<br />THWN OR THHN INSULATION. SEPARATE WIRE AND CONDUIT SYSTEM
<br />MAY BE SUBSTITUTED WITH FACTORY FABRICATED ASSEMBLY OF
<br />INSULATED CONDUCTORS IN A FLEXIBLE METALLIC ENCLOSURE WHERE
<br />PERMITTED BY LOCAL CODES.
<br />10. ALL MATERIAL SHALL BE NEW AND BEAR THE UNDERWRITES
<br />LABEL (U. L. ) WHERE APPLICABLE.
<br />11. THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND
<br />EFFECTIVELY GROUNDED AS REQUIRED IN ARTICLE 250 OF THE
<br />NATIONAL ELECTRICAL CODE.
<br />12. THE ELECTRICAL, TELEPHONE, AND CABLE TELEVISION
<br />INSTALLATIONS SHALL MEET ALL REQUIREMENTS BY THE LOCAL
<br />UTILITY COMPANIES.
<br />13. ALL DISCONNECT SWITCHES SHALL BE RATED FOR 100,000
<br />A.I.C. UNLESS OTHERWISE NOTED. ALL FUSES SHALL BE RATED FOR
<br />200,000 A. I . C. AND SHALL BE CURRENT LIMITING.
<br />14. ALL ELECTRICAL SWITCHGEAR SHALL BE BY SQUARE D, GE, OR
<br />SIEMENS. SUBSTITUTES MUST BE APPROVED BY THE ENGINEER.
<br />15. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS.
<br />PLASTIC BOXES MAY BE USED IN LIEU OF THE STEEL BOX WHERE
<br />PERMITTED BY LOCAL CODES. IN DAMP OR WET LOCATIONS BOXES
<br />SHALL BE MADE FROM CAST ALLOY WITH THREADED HUBS. SPECIAL
<br />ENCLOSURES ARE REQUIRED FOR OTHER CLASSIFIED AREAS. USE
<br />"3M" MPP+ PUTTY PADS PER THEIR LISTING FOR ALL OUTLET BOXES
<br />IN 1 AND 2 HOUR RATED GYPSUM BOARD WALL ASSEMBLIES.
<br />16. MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC WITH
<br />OVERLOAD RELAYS IN EACH HOT LEG. IT SHALL BE THE ELECTRICAL
<br />CONTRACTOR TO PROVIDE ALL STARTERS WHERE REQUIRED.
<br />17. FURNISH AND INSTALL DISCONNECT SWITCHES, OVER CURRENT
<br />PROTECTION, AND WIRING FOR THE AIR CONDITIONING SYSTEM AS
<br />PER MANUFACTURER RECOMMENDATIONS. CONTROLS ARE TO BE
<br />SUPPLIED BY THE AIR CONDITIONING CONTRACTOR AND CONNECTED BY
<br />THE ELECTRICAL CONTRACTOR.
<br />18. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL
<br />CONTRACOR IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETE
<br />SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY THE ENGINEER
<br />OR ARCHITECT.
<br />ELECTRICAL LEGEND
<br />LIGHTING TROFFER - LETTER INDICATES TYPE
<br />®
<br />EMERGENCY TROFFER - LETTER INDICATES TYPE
<br />Do
<br />DOWN LIGHTING FIXTURE - LETTER INDICATES TYPE
<br />Do
<br />EMERGENCY DOWN LIGHTING FIXTURE - LETTER INDICATES TYPE
<br />X 0
<br />EMERGENCY EXIT LIGHT - LETTER INDICATES TYPE
<br />X/EM
<br />COMBINATION EMERGENCY EXIT LIGHT AND EMERGENCY LIGHTING
<br />UNIT- LETTER INDICATES TYPE
<br />EM I=�
<br />EMERGENCY LIGHTING UNIT - LETTER INDICATES TYPE
<br />$
<br />SINGLE POLE TOGGLE SWITCH - MOUNT 48" AFF U.O.N.
<br />$3
<br />THREE WAY SWITCH - MOUNT 48" AFF U. 0. N.
<br />$4
<br />FOUR WAY SWITCH - MOUNTED 48" AFF U. 0. N.
<br />$a
<br />SINGLE POLE SWITCH - MOUNTED 48" AFF U. 0. N.
<br />LOWER CASE LETTER INDICATES CONTROL AREA
<br />INCANDESCENT DIMMER SWITCH - MOUNTED 48"AFF U.O.N.
<br />WATTAGE AS REQUIRED BY CIRCUIT CAPACITY
<br />WALL MOUNTED OCCUPANCY SENSOR
<br />®
<br />PROVIDE WITH LIGHTING PACKAGE TO MATCH LIGHT TYPES
<br />MOUNT 48" AFF U. 0. N.
<br />®
<br />CEILING MOUNTED OCCUPANCY SENSOR
<br />PROVIDE WITH LIGHTING PACKAGE TO MATCH LIGHT TYPES
<br />WALL MOUNTED OCCUPANCY SENSOR WITH DIMMER
<br />®
<br />PROVIDE WITH LIGHTING PACKAGE TO MATCH LIGHT TYPES
<br />MOUNT 48" AFF U. 0. N.
<br />0=
<br />DUPLEX RECEPTACLE - MOUNTED 18" AFF U.O.N.
<br />@=
<br />DUPLEX RECEPTACLE - MOUNTED 5" A.C.B. U.O.N.
<br />Q=
<br />SWITCHED DUPLEX RECEPTACLE - MOUNTED 18"AFF U.O.N.
<br />SWITCHED DUPLEX RECEPTACLE - MOUNTED 6" A. C. B. U.O.N.
<br />DOUBLE DUPLEX RECEPTACLE - MOUNTED 18" AFF U.O.N.
<br />DOUBLE DUPLEX RECEPTACLE - MOUNTED 6" A.C.B. U. 0. N.
<br />DUPLEX RECEPTACLE - MOUNTED FLUSH TO CEILING
<br />DUPLEX RECEPTACLE - IN FLOOR BOX WITH COVER,
<br />COVER TO BE FLUSH WITH FINISHED FLOOR
<br />a
<br />DOUBLE DUPLEX RECEPTACLE - IN FLOOR BOX WITH COVER,
<br />COVER TO BE FLUSH WITH FINISHED FLOOR
<br />®
<br />SPECIAL PURPOSE OUTLET OR EQUIPMENT CONNECTION
<br />COMMUNICATIONS RACEWAY - MOUNTED 18" AFF U.O.N.
<br />d
<br />PROVIDE 2 GANG BOX WITH ONE GANG RING
<br />STUB 3/4" CONDUIT 6" ABOVE CEILING U.O.N.
<br />COMMUNICATIONS RACEWAY - MOUNTED 6" A.C.B. U.O.N.
<br />A
<br />PROVIDE 2 GANG BOX WITH ONE GANG RING
<br />STUB 3/4" CONDUIT 6" ABOVE CEILING U.O.N.
<br />COMMUNICATIONS RACEWAY - IN FLOOR BOX WITH COVER
<br />Q
<br />COVER TO BE FLUSH WITH FINISHED FLOOR
<br />STUB 3/4" CONDUIT 6" ABOVE CEILING U. O. N.
<br />�Q
<br />FIRE ALARM HORN AND STROBE, "34" INDICATES REQUIRED
<br />34
<br />EFFECTIVE INTENSITY (cd), IF NOT INDICATED OUTPUT IS "15"
<br />FIRE ALARM STROBE ONLY
<br />E]
<br />FIRE ALARM PULL STATION
<br />0
<br />JUNCTION BOX, MOUNT FLUSH TO FINISHED SURFACE U.O.N.
<br />MOTOR
<br />LEI
<br />DISCONNECT SWITCH
<br />0
<br />ELECTRICAL PANEL
<br />TBB
<br />TELEPHONE BACKBOARD W/#6 CU GND U.O.N. ( SIZE AS NOTED)
<br />®
<br />KEYED NOTE (SEE LIST)
<br />SOLID LINE INDICATES EQUIPMENT ON COMMON BRANCH CIRCUIT
<br />AND/OR CONTROLLED BY COMMON SWITCH. EACH CIRCUIT SHALL
<br />CONSIST OF A PHASE CONDUCTOR, NEUTRAL AND GROUND
<br />CONDUCTOR. CONTRACTOR SHALL PROVIDE NECESSARY SWITCH
<br />LEGS IN CONDUIT TO ATTAIN SWITCHING ARRANGEMENTS
<br />INDICATED ON PLANS. CONTRACTOR MAY COMBINE CIRCUITS
<br />INTO COMMON HOMERUN(S) CONSISTING OF A COMMON
<br />NEUTRAL AND GROUND CONDUCTOR AND THREE PHASE
<br />CONDUCTORS (A, B, AND C PHASE) .
<br />DOTTED LINE INDICATES EQUIPMENT ON COMMON BRANCH CIRCUIT
<br />BUT NOT CONTROLLED BY SAME SWITCH OR OTHER SIMILAR DEVICE.
<br />THE FOLLOWING ABBREVIATIONS INDICATES:
<br />E EXISTING
<br />R RELOCATE
<br />RE/CKT REUSE EXISTING CIRCUIT
<br />C. L. CENTER LINE
<br />U. 0. N. UNLESS OTHERWISE NOTED
<br />G OR GFI GROUND FAULT INTERRUPTER
<br />WP WEATHERPROOF
<br />IG ISOLATED GROUND
<br />NL NIGHT LIGHT
<br />C/T CURRENT TRANSFORMER
<br />AFF ABOVE FINISHED FLOOR
<br />AFG ABOVE FINISHED GRADE
<br />A. C. B. ABOVE COUNTER BACKSPLASH
<br />BFG BELOW FINISHED GRADE
<br />N. T. S. NOT TO SCALE
<br />N. I. C. NOT IN CONTRACT
<br />U RECEPTACLE WITH (1) USB-A AND (1) USB-C
<br />OUTLET/CHARGER.
<br />NOTE: ALL MOUNTING HEIGHTS INDICATED ARE
<br />TO THE CENTERLINE OF THE DEVICE U.O.N.
<br />LIGHTING FIXTURE SCHEDULE
<br />MARK
<br />LAMP DATA
<br />DESCRIPTION
<br />FIXTURE MODEL NUMBER
<br />MOUNT
<br />VOLT
<br />NOTES
<br />QTY
<br />TYPE
<br />MANUFACTURER
<br />CATALOG NUMBER1
<br />A
<br />INC
<br />20W 24L
<br />2X2 LED T-BAR
<br />LITHONIA
<br />CPANL 2X2 35K DIM
<br />RECESSED
<br />277
<br />AEN
<br />INC
<br />20W 24L
<br />2X2 LED T-BAR W/BATT-NL
<br />LITHONIA
<br />CPANL 2X2 35K DIM PS1055CP
<br />RECESSED
<br />277
<br />2,3
<br />BES
<br />INC
<br />20W 24L
<br />2X2 LED T-BAR W/BATT
<br />LITHONIA
<br />CPANL 2X2 35K DIM PS1055CP
<br />RECESSED
<br />277
<br />2,5
<br />B
<br />INC
<br />32W 40L
<br />2X4 LED T-BAR
<br />LITHONIA
<br />CPANL 2X4 35K DIM
<br />RECESSED
<br />277
<br />BEN
<br />INC
<br />32W 40L
<br />2X4 LED T-BAR W/BATT-NL
<br />LITHONIA
<br />CPANL 2X4 35K DIM PS1055CP
<br />RECESSED
<br />277
<br />2.3
<br />BES
<br />INC
<br />32W 40L
<br />2X4 LED T-BAR W/BATT
<br />LITHONIA
<br />CPANL 2X4 35K DIM PS1055CP
<br />RECESSED
<br />277
<br />2,5
<br />C
<br />1
<br />IOW/FT LED
<br />12" COVE LIGHT
<br />TROV
<br />L35I12-10-277V
<br />SURFACE
<br />277
<br />D
<br />1
<br />16.3W LED
<br />6" LED DOWNLIGHT-IC
<br />JUNO
<br />K22LEDG4-14LM-35K
<br />RECESSED
<br />277
<br />7
<br />DEN
<br />1
<br />16.3W LED
<br />6" LED DOWNLIGHT-IC WITH BATT
<br />JUNO
<br />K22LEDG4-14LM-35K-EM
<br />RECESSED
<br />277
<br />2,3,7
<br />E
<br />EXISTING FIXTURE
<br />EXISTING
<br />277
<br />6
<br />S
<br />1
<br />14.7W LED
<br />6" LED SHOWER DOWNLIGHT
<br />GOTHAM
<br />EV06SH-35-15DFF-SOL-EZ1
<br />RECESSED
<br />277
<br />7.8
<br />X
<br />INC
<br />INC
<br />UNIVERSAL LED EMERGENCY EXIT
<br />LITHONIA
<br />LQMSW3REL
<br />UNIVERSAL
<br />277
<br />2.3
<br />EM
<br />INC
<br />INC
<br />EMERGENCY BATTERY UNIT
<br />LITHONIA
<br />6ELM2
<br />UNIVERSAL
<br />277
<br />2,3,4
<br />LIGHTING FIXTURE NOTES:
<br />1. GENERAL SCHEDULE NOTES (APPLIES TO ALL FIXTURES):
<br />A) CONTRACTOR SHALL COORDINATE FIXTURE MOUNTING WITH ARCHITECTURAL REFLECTED CEILING PLAN(S)
<br />AND SHALL PROVIDE FIXTURE MOUNTING AS REQUIRED TO MATCH CEILING TYPE.
<br />B) ALL FIXTURES BALLAST SHALL BE HIGH POWER FACTOR TYPE.
<br />C) ALL FLUORESCENT BALLAST SHALL BE ENERGY SAVING TYPE.
<br />D) ALL ELECTRICAL FIXTURES MUST BE INDEPENDENTLY SUPPORTED OF CEILING GRID. LIGHT FIXTURES WEIGHTING
<br />LESS THAN 10 POUNDS SHALL HAVE AT LEAST ONE 12 GAGE HANGER WIRE CONNECTED FROM THE FIXTURE TO THE
<br />STRUCTURE ABOVE. LIGHTS WEIGHTING MORE THAN 10 POUNDS SHALL HAVE AT LEAST TWO 12 GAGE WIRES ATTACHED
<br />AT OPPOSING CORNERS OF THE LIGHT FIXTURE.
<br />E) CONTRACTOR SHALL PROVIDE AND INSTALL LIGHTING FIXTURE DISCONNECT MEANS IN ACCORDANCE WITH NEC-410.73(G).
<br />DISCONNECTING MEANS SHALL BE PROVIDED IN INDOOR LOCATIONS, OTHER THAN DWELLINGS AND ASSOCIATED
<br />ACCESSORY STRUCTURES, FOR FLUORESCENT LUMINARIES (FIXTURES) THAT UTILIZE DOUBLE ENDED LAMPS AND
<br />CONTAIN BALLAST(S) THAT CAN BE SERVICED IN PLACE OR BALLASTED LUMINARIES THAT ARE SUPPLIED FROM
<br />MULTIWIRE BRANCH CIRCUITS AND CONTAIN BALLAST(S) THAT CAN BE SERVICED IN PLACE SHALL HAVE A
<br />DISCONNECTING MEANS EITHER INTERNAL OR EXTERNAL TO EACH LUMINAIRE (FIXTURE), TO DISCONNECT
<br />SIMULTANEOUSLY FROM THE SOURCE OF SUPPLY ALL CONDUCTORS OF THE BALLAST, INCLUDING THE GROUNDED
<br />CONDUCTOR IF ANY. THE LINE SIDE TERMINALS OF THE DISCONNECTING MEANS SHALL BE GUARDED. THE
<br />DISCONNECTING MEANS SHALL BE LOCATED SO AS TO BE ACCESSIBLE TO QUALIFIED PERSONS BEFORE
<br />SERVICING OR MAINTAINING THE BALLAST.
<br />F) PROVIDE SUBMITTALS ON ALL FIXTURES. ANY FIXTURE INSTALLED WITHOUT SUBMITTAL APPROVAL
<br />IS SUBJECT TO BEING REPLACED WITH NO ADDITIONAL COMPENSATION TO CONTRACTOR.
<br />G) CONTRACTOR SHALL VERIFY EXISTING CEILING RATING PRIOR TO ORDERING ANY FIXTURES.
<br />REPORT ANY DISCREPANCIES TO ARCHITECT AND ENGINEER.
<br />2. FIXTURES TO BE PROVIDED WITH INTEGRAL EMERGENCY BATTERY BACK-UP.
<br />3. FIXTURES SHALL BE CONNECTED TO CONSTANT NORMAL ROOM LIGHTING BRANCH CIRCUIT OF AREA SERVED
<br />(i.e. LOAD SIDE OF BREAKER, LINE SIDE OF ANY SWITCHING/CONTROLLING DEVICES).
<br />4. FIXTURE TO BE WALL MOUNTED 7'-6" AFF TO TOP.
<br />5. FIXTURES TO BE PROVIDED WITH INTEGRAL EMERGENCY BATTERY BACK-UP. THE EMERGENCY BALLAST SHALL BE
<br />CONNECTED TO CONSTANT NORMAL ROOM LIGHTING BRANCH CIRCUIT OF AREA SERVED (i.e, LOAD SIDE OF BREAKER,
<br />LINE SIDE OF ANY SWITCHING/CONTROLLING DEVICES). THE LIGHT FIXTURE IS TO BE COMPLETELY SWITCHED AND
<br />THE EMERGENCY BALLAST OPERATES ONLY IN THE EVENT OF A BRANCH CIRCUIT POWER FAILURE.
<br />6. EXISTING FIXTURE TO BE CLEANED, RELAMPED, NEW BALLAST, AND NEW BATTERY AS REQUIRED FOR A COMPLETE OPERATING
<br />SYSTEM.
<br />7. IC RATED.
<br />8. UL RATED FOR WET LOCATIONS.
<br />L F 0 VISUAL SIGNAL DEVICE
<br />----- i
<br />NEW DEVICES NE HORN AND STROBE
<br />DUCT SMOKE DETECTOR, NOTIFIER
<br />EXISTING DEVICES FACP1 FIRE ALARM CONTROL PANEL
<br />EXISTING SMOKE DETECTOR, NOTIFIER
<br />F.A.C.P
<br />PULL STATION
<br />EXISL- d -J ING
<br />BUILDING TDEVICES FS FLOW SWITCH
<br />FIRE ALARM SYSTEM SHALL BE INSTALLED Q TAMPER SWITCH
<br />PER ALL LOCAL CODES.
<br />F.A.C.P-FI E ALARM CONTROL PANEL, FIRE BELL
<br />ADDRESSIBLE).
<br />NOTE: F. A. C. P. SHALL HAVE FAAP ANNUNCIATOR PANEL
<br />BATTERY BACKUP.
<br />FIRE ALARM RISER
<br />NTS
<br />FIRE ALARM SYSTEM REQUIREMENTS
<br />CONTRACTOR SHALL PROVIDE AND INSTALL NEW FIRE ALARM DEVICES AS SHOWN
<br />AND SHALL CONNECT ALL DEVICES TO THE EXISTING FIRE ALARM SYSTEM AS
<br />REQUIRED FOR A COMPLETE AND OPERABLE SYSTEM. CONTRACTOR SHALL PROVIDE
<br />A COMPLETE AND OPERABLE FIRE ALARM SYSTEM AS REQUIRED BY GOVERNING
<br />STATE, NFPA AND LOCAL CODES. COMPLETE FIRE ALARM SYSTEM SHALL BE
<br />INSTALLED IN ACCORDANCE WITH THE LATEST GOVERNING EDITIONS OF NFPA 72
<br />AND 101 AND THE FLORIDA BUILDING CODE. CONTRACTOR SHALL INCLUDE IN HIS
<br />BID ALL WORK NECESSARY TO PREPARE COMPLETE INSTALLATION DRAWINGS
<br />SIGNED AND SEALED BY A REGISTERED PROFESSIONAL ENGINEER AS NEEDED
<br />FOR BUILDING PERMIT AS REQUIRED BY THE LOCAL AUTHORITIES HAVING
<br />JURISDICTION. CONTRACTOR SHALL COORDINATE ALL WORK NECESSARY FOR
<br />EQUIPMENT BEING PROVIDED. CONTRACTOR SHALL BE RESPONSIBLE FOR
<br />COMPLETE AND OPERABLE SYSTEM.
<br />941 Lake Baldwin
<br />Orlando, FL 32814
<br />1
<br />®`®®®d®IIIIIIIIJO®o
<br />Co
<br />L
<br />•.
<br />:2 r
<br />coUJ
<br />O;
<br />Q
<br />a
<br />°F %
<br />J 9111P10®®®`0
<br />U
<br />O
<br />am
<br />O
<br />V7
<br />n M
<br />UM
<br />o
<br />Zo
<br />ao•
<br />oi�
<br />0
<br />w
<br />�
<br />C
<br />r� 1&
<br />U M�Z
<br />a
<br />Z_j��
<br />o
<br />W
<br />5
<br />W IL owc
<br />W DATE: 07/31 /20
<br />o 4 6 PROJECT: 20027NO037
<br />Z N�g DRAWN: DG
<br />W g o CHECKED: RS
<br />W �
<br />Z M=g
<br />V LJJ
<br />3mOO
<br />NOTES, LEGEND,
<br />-N%%O*,j AND LIGHT SCHEDULE
<br />
|