DEMO KEY NOTES DEMOLITION NOTES <br />Key Value Keynote Text <br />26 00 01 EXISTING WAWCEILING MOUNTED CONVENIENCE 1. THIS DRAWING INDICATES AREAS THAT ARE BEING AFFECTED BY THE DEMOLITION. <br />RECEPTACLE(S), FIRE ALARM DEVICES, LIGHTING SWITCHES DASHED LINES SHOW EXISTING EQUIPMENT TO BE REMOVED AND SOLID LINES SHOW <br />ETC., IN THE STOCK ROOM SHALL BE DISCONNECTED AND EXISTING EQUIPMENT TO REMAIN. ELECTRICAL CONTRACTOR SHALL REMOVE ALL <br />REMOVED. PULL OUT AND REMOVE CONDUCTORS TO NEXT ELECTRICAL EQUIPMENT AFFECTED BY THE DEMOLITION AND WILL KEEP REMAINING <br />UPSTREAM JUNCTION BOX WHERE EXISTING SPLICED WAS EQUIPMENT CONNECTED, POWERED TO THE EXISTING CIRCUITS AS REQUIRED. <br />PERFORMED OR CIRCUIT BREAKER LOCATED IN THE <br />ELECTRICAL PANELBOARD IF DEDICATED. 2. THIS DRAWING SHOWS A REPRESENTATIVE SAMPLE OF DEMOLITION WORK THAT IS TO <br />26 00 02 ALL EXISTING LIGHTING FIXTURES WITHIN LAB CORP AREA TAKE PLACE. NOTE THAT EVERY DEVICE, LIGHTING FIXTURE, CONDUIT ETC. REQUIRED TO <br />SHALL BE REMOVED. ALL CONDUIT AND WIRE NOT RE -USED BE DEMOLISHED IS NOT NECESSARILY INDICATED ON THIS PLAN. THE CONTRACTOR <br />SHALL BE REMOVED BACK TO THE SOURCE. SEE 21E111 FOR SHALL VISIT THE JOB SITE TO FAMILIARIZE HIMSELF WITH THE EXTENT OF EXISTING <br />NEW LIGHTING LAYOUT. WORK TO BE DEMOLISHED. <br />3. ALL PROPOSED DEMOLITION WORK SHALL BE THOROUGHLY COORDINATED WITH ALL <br />OTHER TRADES. <br />4. CONFIRM WITH THE MANUFACTURERS OF EXISTING EQUIPMENT THAT IS TO BE REVISED <br />OR EXTENDED. <br />5. WHERE EXISTING ELECTRICAL WORK PREVENTS PROPER CONSTRUCTION OF NEW WORK <br />AS INDICATED, REMOVE, REROUTE, RELOCATE, OR IN OTHER WAYS ALTER EXISTING <br />WORK IN ORDER TO ACCOMMODATE. <br />6. WHERE EXISTING CONDUIT, WIRE, SUPPORTS, HANGERS AND OTHER ELECTRICAL WORK <br />MUST BE REMOVED AS A RESULT OF THE ALTERATIONS, THEY SHALL BE COMPLETELY <br />REMOVED, BACK TO THE FIRST OUTLET WHICH IS LEFT UNAFFECTED BY THE REVISION. <br />CONDUIT WHICH IS BURIED IN CONCRETE OR OTHERWISE INACCESSIBLY POSITIONED <br />MAY BE ABANDONED. IN SUCH CASES, WIRE SHALL BE PULLED OUT OF THE CONDUIT AND <br />THE CONDUIT ITSELF PLUGGED AT EACH END. <br />7. EXISTING ELECTRICAL MATERIALS AND EQUIPMENT, INCLUDING LIGHTING FIXTURES, <br />SWITCHES, RECEPTACLES, SIGNAL LIGHTS, SPEAKERS, INTERCOM EQUIPMENT, <br />CONTROLS, CONDUIT OUTLETS, FITTINGS, AND OTHER DEVICES WHICH ARE REMOVED AS <br />A RESULT OF THE ALTERATIONS SHALL REMAIN THE PROPERTY OF THE OWNER AND <br />--- j SHALL BE STORED ON THE SITE AS DIRECTED, OR REUSED WHERE INDICATED. <br />- ___ _ __ ___.___ 8. EXAMINE THE CONDITION OF SUCH MATERIALS AND EQUIPMENT TO MAKE A PRIOR <br />DETERMINATION OF WHETHER IT IS SUITABLE FOR REUSE. PRESENT FINDINGS <br />PERIODICALLY EXAMINE THE CONDITION OF SUCH MATERIALS AND EQUIPMENT TO MAKE <br />:.r A PRIOR DETERMINATION OF WHETHER IT IS SUITABLE FOR REUSE. PRESENT FINDINGS <br />PERIODICALLY TO THE ENGINEER WHO WILL IN TURN MAKE THE FINAL DECISION <br />REGARDING REUSABILITY. ALL WIRE AND CABLE FOR REUSED AND RELOCATED <br />EQUIPMENT SHALL BE NEW. <br /><26 00 01> 9. IN ORDER TO COORDINATE THE WORK OF THE MECHANICAL AND ELECTRICAL TRADES, <br /><26 00 02> �� REMOVE EXISTING ELECTRICAL WORK IN AND ABOVE CEILING OF THESE AREAS (AS <br />\\\\\ <br />REQUIRED), AFTER WHICH INSTALL NEW WORK AND REINSTALL EXISTING WORK TO <br />�\ REMAIN, AS SHOWN ON THE DRAWINGS. EXISTING LIGHTING FIXTURES, CLOCKS, <br />SPEAKERS, SIGNALS, AND OTHER EQUIPMENT SHALL BE REUSED ONLY WHERE <br />\ f INDICATED. IF FIXTURES MUST BE UTILIZED IN AREAS WITH NEW CEILING TILE, MAKE <br />\\\\\ ARRANGEMENTS FOR CUTTING NEW TILE TO ACCOMMODATE FIXTURES. <br />10. SOME EXCEPTIONS MAY ARISE WHEREIN EQUIPMENT, EITHER IN ALTERED AREAS OR <br />, _ OTHER AREA, MUST BE KEPT IN SERVICE, REQUIRING THAT FEEDERS, SIGNAL <br />\ \\\\\\ CONDUCTORS, CONDUITS, BOXES, ETC. SERVING SAME ALSO BE KEPT IN SERVICE. IN <br />SUCH CASES, THOSE ELECTRICAL FEEDERS, SIGNAL CONDUCTORS, CONDUITS, ETC. <br />\>>. SHALL BE REROUTED AND RECONNECTED BEFORE PRESENT WORK IS REMOVED. IF THIS <br />.. IS NOT POSSIBLE, TEMPORARY WIRING SHALL BE PROVIDED TO ALLOW FOR <br />INSTALLATION OF MECHANICAL WORK, AFTER WHICH NEW WORK SHALL BE INSTALLED <br />AND TEMPORARY WIRING REMOVED. <br />11. REMOVE OR REROUTE ALL ELECTRICAL FEEDERS, RISERS, BRANCH CIRCUITS AND <br />I OTHER WIRING AS REQUIRED BY THE ALTERATIONS. WIRING EXTENDING THROUGH <br />REMODELED AREAS BUT SERVING LOADS WHICH MUST REMAIN SHALL BE REROUTED AS <br />REQUIRED AND RECONNECTED TO THOSE LOADS. <br />12. ANY ELECTRICAL EQUIPMENT THAT IS TAGGED TO BE DISPOSED OF SHALL BE DONE PER <br />APPROVED METHOD ACCORDING TO LOCAL AUTHORITY. <br />13. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS, FEEDERS AND BRANCH <br />CIRCUITS PASSING THROUGH RENOVATED AREA AND SERVING UNDISTURBED AREAS. <br />14. ANY PORTION OF THE EXISTING CONDUIT SYSTEM THAT IS TO BE REUSED FOR THE NEW <br />INSTALLATION SHALL BE CHECKED TO ENSURE THAT THE CONDUIT IS CLEAN, FREE OF <br />CORROSION, FREE OF DAMAGE AND ADEQUATELY SUPPORTED. <br />15. DISCONNECT AND REMOVE ALL ELECTRICAL EQUIPMENT, DEVICES AND CONDUITS IN <br />WALLS, FLOORS AND CEILING SCHEDULED FOR DEMOLITION. <br />16, ALL EXPOSED CONDUITS THAT ARE ABANDONED SHALL BE REMOVED. ALL CONDUITS <br /><26 00 01> �� i` — 'i THAT ARE ABANDONED IN THE SLABS SHALL HAVE WIRING REMOVED AND STUBS SHALL <br /><26 00 02> \ \\\\\\ III f BE PLUGGED FLUSH WITH FLOOR OR CEILING SLABS. <br />17. REMOVE ALL ABANDONED HANGERS, SUPPORTS, ETC. FOR ELECTRICAL ITEMS. <br />18. EXISTING ELECTRICAL SYSTEM IS DESCRIBED BASED ON SURVEYS OF EXISTING <br />\\\\\ CONDITIONS THAT ARE VISIBLE DURING THE DESIGN PHASE. CONTRACTOR SHALL <br />�\ CONFIRM ALL SERVICES PRIOR TO PROCEEDING WITH DEMOLITION. <br />19. PATCH ALL HOLES IN SLABS, WALLS AND CEILING WHERE ELECTRICAL DEVICES AND/OR <br />CONDUIT ARE REMOVED. IF THE REMOVAL OF CONDUIT, BOXES, EQUIPMENT, ETC. <br />`\\\~ COMPROMISES THE FIRE RATING OF THESE ITEMS, THE CONTRACTOR SHALL SEAL <br />OPENINGS WITH CODE APPROVED FIRE STOPPING MATERIAL. <br />20. WHERE FEEDERS OR BRANCH CIRCUITS ARE DISCONNECTED AND REMOVED FROM <br />_ ._:.: _ \`•\�\� EXISTING PANEL BOARDS, CONTRACTOR SHALL MARK THE AFFECTED BREAKERS IN <br />THOSE PANEL BOARDS AS "SPARE". <br />6J. UV <br />s <br />21. CONTRACTOR IS TO PERFORM DEMOLITION WORK IN A NEAT, SKILLFUL, AND CAREFUL <br />MANNER SO AS NOT TO DAMAGE OR DEFACE EXISTING CONSTRUCTION THAT IS TO <br />REMAIN. <br />22. VERIFY THAT REMOVAL OF DEVICES IN RENOVATED AREA DOES NOT AFFECT DEVICES IN <br />EXISTING ELECTRICAL FLOOR PLAN OTHER AREAS THAT MAY BE FED FROM THE CIRCUIT BEING DISCONNECTED. <br />1 /4" = T-0" <br />23. ELECTRICAL CONTRACTOR SHALL REMOVE EXISTING FIRE ALARM SYSTEM. HOWEVER, <br />EXISTING FIRE ALARM SYSTEM SHALL BE MAINTAINED AND IN OPERATION UNTIL NEW <br />FIRE ALARM SYSTEM IS IN OPERATION AND APPROVED BY THE AUTHORITY HAVING <br />JURISDICTION. <br />ERT <br />RM <br />RL <br />LEGEND <br />EXISTING TO REMAIN <br />EXISTING TO BE REMOVED <br />EXISTING TO BE REMOVED AND RELOCATED <br />AREA OF WORK <br />u <br />n .. <br />�� <br />�■ <br />■� <br />ii ii <br />ii <br />.. <br />ii ii <br />.. .. <br />■ ii <br />ii <br />it <br />i■ <br />U <br />■i <br />.. u <br />ii <br />ii ii <br />■ ii <br />it <br />li <br />j. <br />■i <br />n i <br />c <br />_rn uj <br />m o <br />O <br />Li <br />a Lo <br />Cc Cc O <br />CC <br />C o- <br />E- <br />O <br />N <br />000 <br />`.'o <br />`4 NY 1NFp'��4 <br />,..N...«,,,w� <br />,•'��C' ppm1.��pym�: <br />N0.8NMM(,n nun r�'oi <br />Ti Ia y ed Akj 1;11 'I'll <br />o U ­ 11 <br />9 nwnc <br />',,, iftpunl'0,`, <br />0 <br />O <br />5 °? <br />M <br />�ULoL <br />Lo Lo <br />U) CD y <br />C U N a0 <br />cc N O <br />cc LL 0_ d <br />cc m <br />@ =rodeo <br />NCnF- LL <br />ti <br />e4 <br />co <br />(V <br />0 <br />rC> <br />04 <br />Lo <br />�Y <br />N <br />Z <br />U <br />to <br />m <br />cp W <br />CM <br />ai <br />o <br />_j Z6 <br />c <br />J_ <br />y <br />N c� <br />c0 <br />03 65 <br />a <br />L <br />0 <br />LL <br />05 <br />U 3 <br />F_ <br />Z <br />d <br />Z <br />O <br />H <br />J <br />0 <br />2 <br />w <br />J <br />Q <br />U_ <br />H <br />w <br />J <br />w <br />Iq <br />0 <br />CD <br />Lo <br />w <br />w <br />0 <br />H <br />z <br />O <br />E_ <br />a <br />U <br />U) <br />Z <br />0 <br />0 <br />W <br />w <br />w <br />O <br />z <br />Ln <br />N <br />Lo <br />cM <br />c'M <br />C/)� <br />z <br />W v <br />Lu q� <br />rn� -co <br />V <br />J <br />Qo <br />M <br />0 <br />00 <br />N <br />Q <br />N <br />c'1 <br />� <br />of <br />O0 <br />m <br />0 <br />N <br />w <br />rn <br />Z <br />Y <br />o <br />= <br />❑ N <br />Q� <br />1 <br />it <br />2 <br />w <br />LLl <br />Q <br />w !Y <br />Wm <br />Ui <br />❑ <br />: <br />❑ <br />itQ <br />KEY PLAN <br />E-1 00 <br />COPYRIGHT © 2018 WALGREEN CO. <br />