Laserfiche WebLink
ISSUED FOR: REVIEW <br />11.01.2021 <br />m I <br />ELECTRICAL SPECIFICATIONS AND INSTRUCTIONS FOR INSTALLATION WORK <br />1.0 GENERAL <br />1.1 BIDDERS QUALIFICATIONS AND INSTRUCTIONS: <br />1.1.1 QUALIFICATIONS: <br />THE BIDDERS SHALL BE QUALIFIED, EXPERIENCED, AND LICENSED ELECTRICAL CONTRACTORS. THEY <br />MUST BE FAMILIAR WITH ALL FEDERAL, STATE, AND LOCAL LAWS, ORDINANCES, RULES, AND <br />REGULATIONS THAT MAY, IN ANY MANNER, AFFECT THE TASK. <br />1.1.2 BIDDING INSTRUCTIONS: <br />BEFORE SUBMITTING THE BID, THE BIDDERS MUST REVIEW THE TENANT INFORMATION AND CRITERIA <br />MANUAL, SPECIFICATIONS, PLANS, DRAWINGS, AND ALL OTHER CONDITIONS AND REQUIREMENTS THAT <br />MAY, IN ANY MANNER AFFECT THE WORK UNDER CONTRACT. THEY MUST VISIT THE SITE OF THE <br />PROPOSED PROJECT TO FAMILIARIZE THEMSELVES WITH THE LOCAL CONDITIONS, FIRE RATING <br />REQUIREMENTS, AND THE NATURE OF THE PROJECT. THE PRICING SHALL BE BASED ON THESE <br />SPECIFICATIONS AND THE MATERIALS SHOWN ON THE DRAWINGS. SUBMISSION OF THE BIDS SHALL BE <br />CONSIDERED AS THE EVIDENCE THAT THE BIDDER IS FAMILIARIZED TO ALL THE FACETS OF THE <br />SPECIFIED PROJECT. CONTRACTOR SHALL USE APPLICABLE SECTIONS OF THIS SPEC. <br />1.1.3 EXCEPTIONS: <br />ANY EXCEPTIONS, OMISSIONS, DISCREPANCIES, AND DOUBTS REGARDING PLANS, DRAWINGS, AND <br />SPECIFICATIONS, IF ANY, SHALL BE COMMUNICATED PROMPTLY IN WRITING TO THE ARCHITECT OR TO <br />THE ENGINEER FOR THEIR REVIEW AND RESPONSE BACK BEFORE THE BID SUBMISSION DATE. NO ORAL <br />COMMUNICATION REGARDING THE EXCEPTIONS OR CHANGES SHALL BE ACCEPTED. BIDDERS SHALL BE <br />NOTIFIED OF ANY CHANGES, IF MADE, DUE TO THE ACCEPTANCE OF EXCEPTIONS BEFORE THE BID <br />SUBMITTAL DATE. <br />1.1.4 MATERIAL TAKE OFF: <br />ALL MATERIAL TAKE OFFS, OTHER THAN THE EXISTING DEVICES, SHALL BE MADE USING THE LIGHT & <br />POWER WIRING AND CONDUIT DRAWINGS AND THEIR ASSOCIATED REFERENCES INCLUDING THE <br />SPECIFICATIONS OF THIS PROJECT ON THIS DRAWING. ALL LIGHTING MATERIALS INCLUDING <br />TRANSFORMER, PANELS, FIXTURES, SWITCHES, RECEPTACLES, WIRES AND RACEWAYS, ETC. SHALL BE <br />PURCHASED BY THE CONTRACTORS PER SECTION NO. 2, UNLESS NOTED OTHERWISE. <br />1.1.5 BID PRICE: <br />THE BID PRICE SHALL INCLUDE LABOR AND MATERIAL COSTS, NECESSARY INSURANCE COSTS AND <br />PERMITS FEES AS REQUIRED TO INSTALL THE COMPLETE ELECTRICAL SYSTEM IN COMPLIANCE WITH THE <br />DESIGN REQUIREMENTS OF THIS PROJECT. <br />1.1.6 SUCCESSFUL BIDDER: <br />THE SUCCESSFUL BIDDER WILL BE REFERENCED AS THE CONTRACTOR FROM THIS POINT ONWARDS <br />THROUGHOUT THE REST OF THE SPECIFICATION. <br />1.2 THE ELECTRICAL CONTRACTOR REQUIREMENTS AND INSTRUCTIONS: <br />1.2.1 THE CONTRACTOR SHALL USE EXPERIENCED AND SKILLED PERSONS TO PERFORM ALL THE ELECTRICAL <br />INSTALLATION WORK UNDER THE CONSTANT SUPERVISION OF LICENSED ELECTRICIANS AND/OR <br />LICENSED JOURNEYMAN ELECTRICIANS. <br />1.2.2 THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED PERMITS, PAYING ALL FEES, <br />AND PROVIDING ALL NECESSARY INSPECTIONS INCIDENTAL TO THE ELECTRICAL PORTION OF THE <br />WORK. <br />1.2.3 THE CONTRACTOR SHALL BE RESPONSIBLE FOR CARRYING NECESSARY INSURANCE AS REQUIRED BY <br />LAW TO PROTECT EMPLOYEES, OTHER PERSONS, EQUIPMENT, AND MATERIAL. <br />1.2.4 THE INSTALLATION WORK SHALL COMPLY WITH ALL APPLICABLE STATE, COUNTY, AND LOCAL BUILDING <br />CODES. APPLICABLE CODES, AS A MINIMUM, WILL INCLUDE THE LATEST EDITION OF THE FOLLOWING. <br />THESE WILL BE CONSIDERED PART OF THE SPECIFICATION OF THIS PROJECT. <br />A) BUILDING CODE OF THE APPLICABLE CITY AND COUNTY. <br />B) NATIONAL ELECTRIC CODE NFPA 70, 2017 <br />C) LIFE SAFETY CODE NFPA 101, 2018 <br />D) S.B.C.C.I. LATEST EDITION. <br />1.2.5 IN CASE OF SUBSTITUTIONS THE CONTRACTOR SHALL PROVIDE A WRITTEN REQUEST TO THE <br />ARCHITECT FOR HIS REVIEW . THE CONTRACTOR SHALL IDENTIFY CLEARLY THE DIFFERENCE BETWEEN <br />THE SPECIFIED ITEMS AND THE SUBSTITUTE ITEMS, INCLUDING THE ECONOMIC IMPACT ON THE <br />PROJECT. THE SUBSTITUTE ITEM SHALL NOT BE ORDERED OR USED UNLESS APPROVED BY THE <br />ARCHITECT AND/OR BY THE OWNER IN WRITING. <br />1.2.6 THE CONTRACTOR SHALL SUBMIT FIVE SETS OF SHOP DRAWINGS FOR SPECIFIED PRODUCTS AT ONE <br />TIME WITHIN THIRTY (30) DAYS FROM THE OFFICIAL NOTICE TO PROCEED. <br />SHOP DRAWING SUBMITTAL SHALL BE MADE FOR THE FOLLOWING MATERIALS AND SYSTEMS: <br />A. LIGHTING FIXTURES, DIMMERS, LAMPS, AND SAFETY SWITCHES. <br />B. TRANSFORMERS, SWITCH BOARDS, DISTRIBUTION PANELS, DISCONNECTS, AND WIREWAYS IF <br />PURCHASED NEW. <br />C. METER CENTERS, CIRCUIT BREAKERS, FUSES, MOTOR STARTERS IF PURCHASED FOR THIS PROJECT. <br />D. TIME CLOCK AND OTHER DEVICES. E) SCHEMATIC DIAGRAMS FOR THE ABOVE ITEMS. <br />1.2.7 THE CONTRACTOR SHALL PROVIDE FOLLOWING DOCUMENTS BEFORE THE CLOSING OF THE PROJECT <br />AND PRIOR TO THE FINAL PAYMENT: <br />A. ONE YEAR WRITTEN WARRANTY FOR ANY DEFECT IN WORKMANSHIP, MATERIAL, AND EQUIPMENT. <br />B. TWO SETS OF MANUFACTURER'S OPERATIONAL AND MAINTENANCE MANUALS IF APPLICABLE. <br />C. MANUFACTURER'S WARRANTIES AND WARRANTY CERTIFICATES. <br />D. TWO SETS OF REPRODUCIBLE OR RED MARKED UP PRINTS OF "AS -BUILT" DRAWINGS, ONE FOR THE <br />ARCHITECT AND ONE FOR THE OWNER OF THE PROJECT. <br />1.2.8 THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE THE NECESSARY TEMPORARY ELECTRICAL <br />POWER, AT HIS EXPENSE, AS REQUIRED BY HIS TRADE AND BY THE GENERAL CONTRACTOR. <br />1.2.9 THE CONTRACTOR SHALL MAKE SURE ON A DAILY BASIS THAT ALL UNNECESSARY MATERIAL AND TRASH <br />CONTRIBUTED BY HIS TRADE ARE REMOVED. <br />1.2.10 THE CONTRACTOR SHALL CONCEALED ALL THE CONDUIT IN THE FINISHED AREAS. <br />2.0 PRODUCTS: <br />2.1 GENERAL: <br />THE ELECTRICAL CONTRACTOR SHALL PURCHASE AND USE ALL "NEW" MATERIAL AS SPECIFIED AND <br />SHOWN ON THE ELECTRICAL PLAN OF THIS PROJECT. ALL THE MATERIAL SHALL BE FREE FROM DEFECTS <br />AND SHALL CARRY A "UL" LABEL. <br />2.2 CONDUCTORS: <br />T CONDUCTORS HALL BE UNCOATED COPPER OF 98% CONDUCTIVITY 6 VOLT DAL <br />ALL INSULATED UCTO S S O 00 O C, U <br />RATED, TYPE THHN/THWN AS NECESSARY TO MEET THE DESIGN REQUIREMENTS AND THE APPLICABLE <br />CODES. THW (FOR # 4 AWG AND LARGER) AND THERMO PLASTIC WIRES RATED FOR 75 DEGREES <br />CENTIGRADE OPERATIONS IN WET AND DRY LOCATIONS AND 90 DEGREES CENTIGRADE WITHIN ELECTRIC <br />DISCHARGE LIGHTING EQUIPMENT MAY BE USED. CONDUCTORS NUMBER # 10 AWG AND LOWER SHALL BE <br />SOLID COPPER AND #8 AWG AND ABOVE SHALL BE STRANDED COPPER. THE MINIMUM SIZE OF WIRE <br />SHALL BE # 12 AWG FOR 20 AMP BREAKER, # 10 AWG FOR 30 AMP BREAKER, # 8 AWG FOR 40 AMP <br />BREAKER. <br />2.3 CABLE: <br />SIGNAL CABLES, IF USED, SHALL BE COPPER AND SHALL MEET ALL UL AND N.E.C. CODE REQUIREMENTS. <br />METAL CLAD (TYPE MC), ARMORED (TYPE AC) AND NOW METALLIC (NM) CABLES SHALL NOT BE USED. ALL <br />CABLE ASSEMBLIES SHALL CONTAIN COPPER GROUND CONDUCTOR. <br />2.4 CONDUITS: <br />THE CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT) AND HOT DIPPED GALVANIZED STANDARD <br />STEEL AS MANUFACTURED BY WHEATLAND TUBE COMPANY OR EQUIVALENT. <br />2.5 OUTLET BOXES AND FITTINGS: <br />OUTLET BOXES, FITTING CLAMPS AND HANGERS ETC. SHALL BE GALVANIZED STEEL, RUST RESISTANT AND <br />COMPATIBLE WITH THE RACEWAY. OUTLET BOXES FOR FIXTURES, SWITCHES, AND RECEPTACLES SHALL <br />HAVE SMOOTH ROUND EDGES AND SHALL BE WITH COVER PLATES. BOXES SHALL BE "STEEL CITY" OR <br />EQUIVALENT. FITTINGS FOR EMT CONDUITS SHALL BE COMPRESSION TYPE. NO SET SCREW WILL BE USED. <br />UNUSED HOLES SHALL BE COVERED WITH APPROVED INSERT CAPS. <br />2.6 SWITCHES AND DIMMERS: <br />SWITCHES AND DIMMERS SHALL BE TOTALLY ENCLOSED, RATED AT 120/277 VOLTS AC, 20 AMPS, 2000 <br />WATTS WITH GRAY TOGGLE AND DEVICE PLATE. THESE SHALL BE QUIET OPERATION, COMMERCIAL GRADE <br />AS MANUFACTURED BY LEVITON, LUTRON OR EQUIVALENT. PLATES SHALL MATCH THE SWITCHES. FURNISH <br />IN GANGS AS NECESSARY. <br />2.7 RECEPTACLES: <br />RECEPTACLE SHALL BE COMMERCIAL GRADE, 125 VOLTS AC, AND 20 AMPERE RATING WITH GROUNDED <br />POLE AND TWO CIRCUIT OPTION, AS MANUFACTURED BY LEVITON OR EQUIVALENT. PLATES SHALL MATCH <br />THE RECEPTACLES. FURNISH IN GANGS AS NECESSARY. <br />2.8 DEVICE PLATES: <br />PROVIDE DEVICE PLATE FOR EACH AND EVERY OUTLET BOX. FURNISH IN GANGS AS NECESSARY. PLATES <br />AND SCREWS SHALL BE GRAY UNLESS THE OWNER PREFERS SOME OTHER COLOR, AND SHALL BE OF THE <br />SAME MANUFACTURER AS OF THE DEVICES. <br />2.9 BALLASTS: <br />BALLASTS FOR FLUORESCENT FIXTURES SHALL BE RAPID START, SYLVANIA ELECTRONIC ENERGY SAVING, <br />HIGH POWER FACTOR AND SHALL BE CLASS "P," CBM, TITLE 24 CERTIFIED WITH INTERNAL THERMAL <br />PROTECTOR WITH AUTOMATIC RESET AND CLASS "A" SOUND RATING NOISE LEVELS LESS THAN 30 dB <br />MAXIMUM. BALLASTS SHALL BE MANUFACTURED BY SYLVANIA AS SHOWN ON THE LIGHTING SCHEDULE OR <br />EQUAL EQUAL AND SHALL SHALL BE GUARANTEED AT LEAST FOR FIVE (5) YEARS OF OPERATION AFTER <br />THE ACCEPTANCE. THE BALLAST MODEL NUMBER SHALL BE "2 OR 4 LAMP PSX-SYL Xtreme AS REQUIRED". <br />2.10 LAMPS: <br />LAMPS SHALL BE MANUFACTURED BY SYLVANIA MODEL # SYL "F028/841XP/SS/ECO OR EQUIVALENT. ALL <br />LAMPS SHALL BE GUARANTEED FOR AT- LEAST 4 YEARS OF OPERATION AFTER THE ACCEPTANCE. <br />2.11 LIGHTING DEVICES: <br />ALL LIGHTING FIXTURES, EMERGENCY & EXIT LIGHTS SHALL BE AS LISTED ON THE LIGHT FIXTURE <br />SCHEDULE; HOWEVER BEFORE PURCHASING ANY LIGHT FIXTURES, SUBMIT FIXTURE. CUT SHEETS FOR THE <br />ARCHITECT AND THE OWNER'S APPROVAL. <br />2.12 TIME CLOCK OR TIME SWITCH: <br />TIME CLOCK SHALL BE ELECTRO- MECHANICAL 24 HOURS SEVEN DAYS TYPE WITH RESERVE POWER AND <br />CONTACTS RATED 40 A. 4 PST AND N.E.M.A. TYPE 1 OR 3R ENCLOSURE. IT SHALL BE SELF POWERED BY A <br />SELF STARTING SYNCHRONOUS MOTOR WITH MINIMUM 16 HR SPRING DRIVEN RESERVE POWER AND A <br />DAY OMITTING DEVICE. TIME CLOCK SHALL BE PARAGON 7007-0, TORK "W" SERIES, OR APPROVED EQUAL. <br />2.13 GUARANTEE: <br />ALL ELECTRICAL EQUIPMENT, MATERIAL AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF <br />ONE (1) YEAR FROM THE DATE OF ACCEPTANCE. <br />3.0 INSTALLATION INSTRUCTIONS: <br />3.1 GENERAL: <br />THE PLAN LOCATION OF LIGHTING FIXTURES, JUNCTION BOXES, CONVENIENCE OUTLETS, AND PANEL <br />BOARDS ARE APPROXIMATE UNLESS DIMENSIONED AND ARE TO BE ADJUSTED BY THE CONTRACTOR AS <br />REQUIRED IN THE AREAS WHERE CEILING GRID AND OTHER OBSTRUCTIONS DETERMINE FIXTURE <br />LOCATIONS. THE CONTRACTOR SHALL COORDINATE WITH OTHER ARCHITECTURAL, MECHANICAL AND <br />OTHER SYSTEMS TO AVOID INTERFERENCE. ALL CUTTING AND CONSEQUENT REPAIRS IN CONJUNCTION <br />WITH THE WORK SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. BEAMS OR OTHER STRUCTURAL <br />COMPONENT SHALL NOT BE CUT WITHOUT THE KNOWLEDGE AND WRITTEN CONSENT OF THE ARCHITECT. <br />3.2 THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MATERIALS, LABOR, TRANSPORTATION, RIGGING & <br />HOISTING, TOOLS, AND STORAGE, ETC, FOR ALL WORK INDICATED AND REQUIRED FOR COMPLETE <br />INSTALLATION. <br />3.3 THE ELECTRICAL WORK SHALL BE EXECUTED IN ACCORDANCE WITH ALL APPLICABLE CODES AND SHALL <br />INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING. WORKMANSHIP SHALL BE THE HIGHEST <br />QUALITY AS ESTABLISHED BY TRADE STANDARD. <br />3.4 THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING NECESSARY PERMITS AND COMMUNICATIONS <br />WITH THE LOCAL BUILDING DEPARTMENT AND INSPECTION PERSONNEL TO REVIEW CONTRACT <br />DOCUMENTS PRIOR TO INSTALLATION. <br />3.5 OWNER WILL NOT BE HELD RESPONSIBLE FOR FIELD CHANGES THAT ARISE FROM CONTRACTOR'S ERROR <br />OR OMISSION OF MATERIALS OR WORKMANSHIP IN WORK PERFORMANCE. <br />3.6 THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL UTILITIES PLACEMENT, AS <br />IDENTIFIED ON THE RISER DIAGRAM, AND LOCATION OF THE ELECTRICAL SERVICE EQUIPMENT. THE <br />PAY ALL NECESSARY CHARGES ASSOCIATED WITH INSTALLATION OF ALL UTILITIES <br />CONTRACTOR SHALLA S O <br />TO THE POWER COMPANY PRIOR TO THE CONSTRUCTION. A LETTER SHALL BE PROVIDED FROM THE POWER <br />COMPANY THAT ALL THE CHARGES HAVE BEEN PAID IN FULL. <br />3.7 NECESSARY AND OBVIOUSLY REQUIRED, ELECTRICAL ITEMS THAT ARE NOT SHOWN ON THE DRAWINGS, <br />SHALL NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITIES TO INSTALL A COMPLETE AND SAFE <br />ELECTRICAL SYSTEM. <br />3.8 THE ELECTRICAL CONTRACTOR SHALL FOLLOW THE SAME COLOR CODE IDENTIFICATION FOR EACH PHASE <br />THROUGHOUT THE SYSTEM FROM SERVICE SWITCH OR TRANSFORMER THROUGH ALL BRANCH CIRCUITS. <br />3.9 ALL SLAB OR ROOF PENETRATIONS SHALL BE MADE WITH APPROVED FIRE RATED SMOKE BARRIER <br />FITTINGS. PROVIDE ACCESSORIES (PITCH POCKETS, SLEEVES, ETC.) AS REQUIRED. <br />3.10 JUNCTION BOXES FOR NEON SIGN LIGHTS, SWITCHES, LIGHTING FIXTURES, RECEPTACLES AND FOR <br />PULLING WIRES SHALL BE AS APPROXIMATE AS SHOWN ON THE PLANS BUT EXACT LOCATIONS SHALL BE <br />GOVERNED BY THE ARCHITECTURAL PLANS. <br />3.11 ALL OUTLET BOXES SHALL HAVE SQUARE CUT CORNERS. AIR SPACE GREATER THAN 1/8" AROUND OUTLET <br />BOXES, AND ADJACENT DRYWALL WILL NOT BE PERMITTED. THE CONTRACTOR SHALL COORDINATE WITH <br />DRYWALL INSTALLER PRIOR TO INSTALLATION. CAULK AROUND BOXES TO ELIMINATE STEEL OUTLET. <br />3.12 LIGHTING SWITCHES AND CONVENIENCE RECEPTACLES SHALL BE FLUSH MOUNTED IN SECTIONAL SWITCH <br />BOXES WITH MATCHING COVER PLATES UNLESS NOTED OTHERWISE. <br />3.13 THE MOUNTING ARRANGEMENT OF EACH FIXTURE WILL BE DETERMINED BY THE CONTRACTOR EXCEPT <br />WHERE THE MANUFACTURER HAS GIVEN SPECIFIC MOUNTING INSTRUCTIONS. <br />3.14 THE CONTRACTOR SHALL FURNISH AND INSTALL ALL LUMINARIES, DEVICES, AND EQUIPMENT AS <br />SPECIFIED AND SHOWN ON THE PLAN DIAGRAMS. PROVIDE ALL CABLES, CONDUCTORS, CONDUITS, AND <br />CONNECTIONS AS REQUIRED TO PROVIDE COMPLETE AND OPERATIONAL ELECTRICAL AND MECHANICAL <br />SYSTEMS. ALL CONDUITS SHALL BE RUN CONCEALED IN FINISHED AREAS. <br />3.15 INDIVIDUAL BREAKERS WILL SUPPLY ELECTRICAL POWER TO INDIVIDUAL SIGN OR NEON LIGHT CIRCUITS. <br />NEON TRANSFORMER EQUIPMENT IS TO BE CONCEALED ABOVE ADJACENT COLUMN ENCLOSURE OR TO BE <br />INSTALLED AS SHOWN ON ARCHITECTURAL DRAWINGS. <br />3.16 ALL JOINTS IN CONDUIT AND RACEWAY SHALL BE MADE TIGHT AND BENDS SHALL BE MADE OVER LONG <br />RADIUS WHERE ENTERING A CABINET AND JUNCTION BOX. THE CONTRACTOR SHALL SUPPORT ALL <br />CONDUIT AND RACEWAYS SECURELY FROM JOISTS AND/OR BEAMS (TIE WIRES ARE NOT ACCEPTABLE). THE <br />CONTRACTOR SHALL VERIFY ALL RACEWAY SIZES IN ACCORDANCE WITH THE N.E.C. CODE. NO CONDUIT <br />SHALL CARRY MORE THAN THREE (3) CURRENT CARRYING CONDUCTORS. NOTE: ALL JOB CUT THREADS <br />SHALL BE COATED WITH RUST RESISTANT ZINC CHROMATE FOR THIN WALL EMT. <br />3.17 LIGHTING CONDUITS SHALL BE SUPPORTED AT EVERY 8 FEET. <br />3.18 MOUNTING HEIGHT OF LIGHTING EQUIPMENT, UNLESS NOTED OTHERWISE ON ARCHITECTURAL PLANS <br />SHALL BE APPROXIMATELY AS FOLLOWS: <br />A. LIGHTING SWITCHES CENTERLINE 4 FEET ABOVE A.F.F <br />B. CONVENIENCE OUTLETS CENTERLINE 1 FEET, 6 INCHES A.F.F <br />C. LIGHTING & POWER PANELS TOP 6 FEET, 6 INCHES ABOVE A.F.F <br />D. EMERGENCY LIGHT FIXTURES W ABOVE A.F.F TO BOTTOM OF THE UNIT. <br />3.19 ELECTRICAL RACEWAYS AND SHALL BE SIZED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE (N.E.C.), <br />ARTICLE 250. ALL BRANCH CIRCUITS SHALL HAVE A SEPARATE GREEN INSULATED GROUND WIRE IN EACH <br />CONDUIT RUN. ISOLATED GROUND CONDUCTORS SHALL BE ROUTED TO THOSE CIRCUITS WHICH NEED <br />ISOLATED GROUND SPECIALLY FOR COMPUTERS AND CASH REGISTERS. <br />3.20 THE CONTRACTOR SHALL PROVIDE LIGHTNING PROTECTION VOLTAGE SURGE PROTECTOR FOR ALL <br />SERVICE PHASE CONDUCTORS TO GROUND (IF IT IS NOT ALREADY THERE IN CASE OF RENOVATIONS). <br />DEVICE SHALL BE APT TE 400 OR APPROVED EQUIVALENT. <br />3.21 LUMINARIES SHALL BE AS SPECIFIED IN THE "LIGHTING FIXTURE SCHEDULE". ALL RECESSED AND LAY -IN <br />FIXTURES SHALL BE SUPPORTED FROM THE FOUR CORNERS WITH SUPPORTS CAPABLE OF CARRYING TWICE <br />THE WEIGHT OF THE FIXTURE. ALL SUPPORTS SHALL BE ATTACHED TO THE JOISTS AND/OR BEAMS, NO <br />LIGHTING FIXTURE SHALL BE INSTALLED WITHIN 2 FEET OF ANY SPRINKLER HEAD. <br />3.22 THE CONTRACTOR SHALL INSTALL ALL TELEPHONE JACKS AND WIRING FROM THE MAIN TELEPHONE <br />TERMINAL BOARD TO THE FINAL TELEPHONE OUTLETS. WIRING SHALL BE INSTALLED IN A MINIMUM 1/2 <br />INCH CONDUIT. <br />3.23 THE CONTRACTOR SHALL COORDINATE WITH THE FIRE PROTECTION CONTRACTOR AND SHALL MAKE ALL <br />NECESSARY CONNECTIONS BETWEEN DUCT SMOKE DETECTORS AND HVAC UNITS. <br />3.24 ALL JUNCTION BOXES SHALL BE ACCESSIBLE FROM BELOW. OTHERWISE, CONTRACTOR SHALL PROVIDE <br />ACCESS PANEL AT ALL JUNCTION BOX LOCATIONS AND SMOKE DETECTORS. <br />3.25 IF NOT ALREADY EXISTING, THE CONTRACTOR SHALL FURNISH ALL THE NECESSARY DISCONNECT <br />SWITCHES, RELAY BOXES, AND CONTROL BOXES AS REQUIRED AND RECOMMENDED BY THE HVAC <br />MANUFACTURER FOR THE HVAC UNIT AND WATER HEATER. THE ELECTRICAL CONTRACTOR SHALL <br />COORDINATE WITH THE MECHANICAL CONTRACTOR AND MAKE ALL NECESSARY CONNECTIONS TO MAKE <br />THE HVAC SYSTEM FUNCTIONAL. <br />3.26 A PLASTIC COVERED TYPE WRITTEN IDENTIFICATION CARD FOR ALL MAIN AND BRANCH CIRCUITS <br />INCLUDING SPARES SHALL BE POSTED AT THE INSIDE OF THE PANEL DOOR. <br />3.27 LOCK -ON DEVICES ON PANEL CIRCUIT BREAKERS FOR NIGHT, EXIT AND EMERGENCY LIGHTING CIRCUITS <br />SHALL BE PROVIDED AND THE SHALL BE GIVEN TO THE OWNER. <br />3.28 LOW VOLTAGE WIRING LOCATED ABOVE THE CEILING SHALL BE PLENUM RATED OR INSTALLED IN METAL <br />CONDUIT. <br />4.0 TRANSFORMER AND PANEL BOARD SPECIFICATIONS : <br />THIS SECTION SHALL APPLY TO THE NEW TRANSFORMER, PANEL BOARDS, CIRCUIT BREAKERS, PANEL <br />BOXES & TRIMS, DISCONNECT SWITCHES, AND FUSES. <br />4.1 PANEL BOARDS: <br />PANEL BOARDS SHALL BE GENERAL PURPOSE N.E.M.A. TYPE 1 EN R TYPE R O 3 ENCLOSUR <br />ES SUITABLE FOR <br />SPECIFIED INDOOR OR OUT DOOR LOCATIONS AND AND FLUSH OR SURFACE MOUNTING APPLICATIONS AS <br />INDICATED ON THE PANEL SCHEDULE. PANEL BOARDS AND THE INTERNAL COMPONENTS SHALL BE RATED <br />TO PERFORM THEIR FUNCTIONS CONTINUOUSLY AT 400C AMBIENT AND 50% RELATIVE HUMIDITY. BUSSES, <br />TERMINALS, AND LUGS SHALL BE RATED AND CAPABLE TO FUNCTION CONTINUOUSLY AT 75 DEGREES <br />CENTIGRADE. PANEL BOARDS SHALL BE AS MANUFACTURED BY WESTINGHOUSE ELECTRIC CORP., <br />GENERAL ELECTRIC, SQUARE 'D', CHALLENGER, OR APPROVED EQUAL. <br />A NAMEPLATE LISTING PANEL NUMBER, TYPE, MANUFACTURER'S NAME, NUMBER OF PROTECTIVE AND <br />SWITCHING DEVICES, VOLTAGE, CURRENT, PHASE AND AIC RATINGS SHALL BE PROVIDED. <br />BRANCH CIRCUITS SHALL BE ARRANGED USING DOUBLE ROW CONSTRUCTION. ALL INTERIORS SHALL BE <br />COMPLETELY FACTORY ASSEMBLED WITH SWITCHING AND PROTECTIVE DEVICES, WIRE CONNECTORS, ETC. <br />ALL WIRE CONNECTORS, EXCEPT SCREW TERMINALS, SHALL BE OF THE ANTI -TURN SOLDERLESS TYPE AND <br />ALL SHALL BE SUITABLE FOR COPPER WIRE OF THE SIZES INDICATED ON DRAWINGS OR IN THE PANEL <br />SCHEDULES AND CONTINUOUSLY FUNCTIONING AT 75 DEGREE CENTIGRADE. <br />ALL BREAKERS, SIZED AS SHOWN ON PANEL SCHEDULE, SHALL BE BOLT -ON BREAKERS. <br />INTERIORS SHALL BE SO DESIGNED THAT SWITCHING AND PROTECTIVE DEVICES CAN BE REPLACED <br />WITHOUT DISTURBING ADJACENT UNITS AND WITHOUT REMOVING THE MAIN BUS CONNECTORS AND <br />SHALL BE SO DESIGNED THAT CIRCUITS MAY BE CHANGED WITHOUT MACHINING, DRILLING, OR TAPPING. <br />BUS BARS FOR THE MAINS SHALL BE OF COPPER AND SIZED IN ACCORDANCE WITH UNDERWRITERS' <br />LABORATORIES STANDARDS. UNLESS NOTED OTHERWISE, FULL SIZE NEUTRAL BARS SHALL BE INCLUDED. <br />BUS BAR TAPS FOR PANELS WITH SINGLE POLE BRANCHES SHALL BE ARRANGED FOR SEQUENCE PHASING <br />OF THE BRANCH CIRCUIT DEVICES. <br />THE SHORT CIRCUIT RATING OF THE ASSEMBLED PANEL BOARD SHALL BE IN ACCORDANCE WITH UL. INC. <br />STANDARDS AND THEIR TEST VERIFICATION. <br />PHASE BUSSING SHALL BE FULL HEIGHT WITHOUT REDUCTION. CROSS AND CENTER CONNECTORS SHALL <br />BE COPPER. <br />NEUTRAL AND GROUND BUSSING SHALL HAVE SUITABLE LUGS FOR OUTGOING FEEDERS REQUIRING A <br />NEUTRAL AND GROUND CONNECTIONS. <br />SPACES FOR FUTURE SWITCHING AND PROTECTIVE DEVICES ON LIGHTING AND APPLIANCE DISTRIBUTION <br />PANELS SHALL BE BUSSED FOR THE MAXIMUM DEVICE THAT CAN BE FITTED INTO THEM. <br />PROVIDE BLANK FILLER PLATES IN THE EMPTY SPACES. <br />4.2 CIRCUIT BREAKER: <br />THE CIRCUIT BREAKERS ARE TO BE INDUSTRIAL MOLDED CASE BOLT ON TYPE, STANDARD THERMAL, <br />MAGNETIC, WITH TRIP FREE MECHANISM, THREE POSITION <br />HANDLES INDICATING "ON" "OFF" AND "TRIPPED" CONDITION. <br />EACH POLE SHALL PROVIDE INVERSE TIME DELAY AND INSTANTANEOUS CIRCUIT PROTECTION. THE <br />BREAKER RATING AND CONFIGURATION SHALL BE AS INDICATED ON THE PANEL BOARD SCHEDULE. ALL <br />MULTI POLE BREAKERS SHALL HAVE AN INTERNAL COMMON TRIP. <br />ALL BREAKER LUGS SHALL BE SUITABLE TO WITHSTAND 75 DEGREE CENTIGRADE WITHOUT <br />MALFUNCTIONING. <br />4.3 PANEL TRIM: <br />HINGED DOORS IN PANEL TRIMS SHALL COVER ALL SWITCHING DEVICE HANDLES AND SHALL CONFORM TO <br />THE FOLLOWING REQUIREMENTS: <br />1. DOORS SHALL NOT UNCOVER ANY LIVE PARTS WHILE MAKING SWITCHING DEVICE HANDLES <br />ACCESSIBLE. <br />2. DOORS SHALL HAVE FLUSH -TYPE CYLINDER LOCK AND CATCH, EXCEPT THAT DOORS OVER 48" IN <br />HEIGHT SHALL HAVE AUXILIARY FASTENERS AT TOP AND BOTTOM OF DOOR IN ADDITION TO FLUSH <br />-TYPE CYLINDER LOCK AND CATCH. DOOR HINGES SHALL BE CONCEALED. ALL LOCKS SHALL BE KEYED <br />ALIKE. DIRECTORY FRAME AND CARD HAVING A TRANSPARENT COVER SHALL BE FURNISHED ON EACH <br />DOOR. <br />THE TRIMS SHALL BE FABRICATED FROM CODE GAUGE SHEET STEEL. ALL EXTERIOR AND INTERIOR STEEL <br />SURFACES OF THE PANEL BOARDS SHALL BE PROPERLY CLEANED PRIMED AND PAINTED IN ACCORDANCE <br />WITH THE MANUFACTURER'S STANDARD SPECIFICATIONS AND COLOR. <br />TRIMS FOR FLUSH MOUNT PANELS SHALL OVERLAP THE BOX BY AT LEAST 3/4" ALL AROUND. SURFACE <br />MOUNT PANELS TRIMS SHALL HAVE THE SAME WIDTH AND HEIGHT AS OF THE BOX. TRIMS SHALL BE <br />MOUNTABLE BY A SCREW DRIVER WITHOUT THE NEED FOR SPECIAL TOOLS. <br />4.4 PANEL BOXES: <br />BOXES SHALL BE MADE FROM UNPAINTED GALVANIZED CODE GAUGE STEEL HAVING MULTIPLE KNOCKOUTS <br />ON THE TOP AND THE BOTTOM EXCEPT WHERE NOTED OTHERWISE. BOXES SHALL BE OF SUFFICIENT SIZE <br />TO PROVIDE A MINIMUM GUTTER SPACE OF 4" ON ALL SIDES. <br />WHERE FEEDER CABLES SUPPLYING THE MAINS OF A PANEL ARE CARRIED THROUGH ITS BOX TO SUPPLY <br />OTHER ELECTRICAL EQUIPMENT, THE BOX SHALL BE SO SIZED AS TO INCLUDE THIS WIRING SPACE. THIS <br />WIRING SPACE SHALL BE IN ADDITION TO <br />THE MINIMUM GUTTER SPACE SPECIFIED ABOVE AND THE LIMITING WIDTH MAY BE INCREASED <br />ACCORDINGLY. AT LEAST FOUR (4) INTERIOR MOUNTING STUDS SHALL BE PROVIDED. <br />ALL UNUSED HOLES IN THE BOXES SHALL BE PLUGGED WITH APPROVED INSERT CAPS. BOXES SHALL BE <br />"STEEL CITY" OR EQUAL. <br />4.5 DISCONNECT SWITCHES: <br />THE CONTRACTOR SHALL INSTALL N.E.M.A. TYPE 1 DISC. SWITCHES FOR INDOOR AND N.E.M.A. TYPE 3R <br />DISC. SWITCHES FOR OUT DOOR APPLICATIONS. ALL DISCONNECT SWITCHES FOR SERVICE CONDUCTOR <br />ENTRANCES SHALL BE RATED AT LEAST 100K AIC. DISCONNECT SWITCHES FOR MOTOR CIRCUIT AND FIXED <br />LOAD (SUCH AS HVAC EQUIPMENT, AND WATER HEATER ETC.) CIRCUITS SHALL BE FUSIBLE OR NON <br />FUSIBLE AS SHOWN ON THE DRAWINGS OR REQUIRED BY THE MANUFACTURER. <br />4.6 FUSE: <br />THE CONTRACTOR SHALL USE DUAL ELEMENT, TIME DELAY CURRENT LIMITING, 100,000 AMP AIC RATED, <br />CLASS RK-1 FUSES WHEN PROTECTING PANEL BOARDS AND TRANSFORMERS AND 100,000 AMP AIC RATED <br />CLASS RK-5 FUSES WHEN PROTECTING MOTORS UNLESS NOTED OTHERWISE OR REQUIRED DIFFERENTLY <br />BY THE MANUFACTURER. ALL FUSES IN ANY DISC.. SW SHALL BE OF THE SAME MANUFACTURER AND SHALL <br />BE MANUFACTURED BY BUSSMANN, GOULD SHAWMUT OR EQUIVALENT. <br />BEFORE PERMITTING OR START OF CONSTRUCTION: <br />1. TENANT TO ACQUIRE LANDLORD WRITTEN APPROVAL OF ALL PROPOSED ALTERATIONS. <br />2. CONTRACTOR TO VERIFY ALL EXISTING DIMENSIONS AND ELEVATIONS. <br />3. CONTRACTOR TO COORDINATE ROUGH WINDOW/ DOOR OPENINGS SIZE W/ MFR SPECS <br />Q <br />� I <br />o o� T <br />itW>-(n-OZ0 <br />E- <br />C\2 <br />It <br />O <br />Lo <br />Q <br />Co <br />co <br />H <br />QQ <br />04 O <br />� <br />E <br />z <br />a <br />a <br />O <br />W <br />x <br />N <br />W <br />> <br />a <br />a <br />W <br />� <br />ZZp <br />CJ > <br />z <br />O <br />Lo <br />r-I <br />L <br />Z <br />WU <br />3 <br />WU <br />3 <br />W <br />v <br />v <br />W <br />a <br />a <br />ii5 <br />GCE <br />MAZEN A <br />Z <br />O <br />a <br />U_ <br />LL <br />U <br />L LJ <br />CL <br />U) <br />J <br />Q <br />U_ <br />L.L <br />U <br />LLJ <br />_I <br />W <br />Lo �jj <br />t` O <br />d' U <br />C') <br />I <br />00 <br />to <br />c <br />I � <br />I` <br />C\2O <br />�' a <br />w <br />O <br />z <br />O <br />CO <br />a <br />w <br />U <br />U <br />cd <br />F, <br />ILI <br />U <br />E- <br />U <br />a <br />N <br />E- <br />S.: <br />O <br />L� <br />e� <br />a O <br />W <br />t` <br />d co <br />JOB. NO. 21040 <br />COA. NO.29116 <br />►RIE, PE. <br />E3.0 <br />i ■ <br />